Plan Review Details - Permit 05120225
Plan Review Stops For Permit 05120225
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-03-02 Cont ID  
Sent By mjacobs Date 2006-03-02 Time 09:13 Rev Time 0.75
Received By mjacobs Date 2006-03-02 Time 08:43 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-01-26 Cont ID  
Sent By mjacobs Date 2006-01-26 Time 10:51 Rev Time 2.00
Received By mjacobs Date 2006-01-26 Time 06:55 Sent To PC
Notes
2006-01-26 00:00:001) TWO COPIES OF EACH DRAWINGS IS
 REQUIRED FOR PLAN REVIEW. ONLY ONE SET
 OF EACH IS IN THE PACKAGE.
  
 2) THE ANCHORING PLAN NEEDS ORIGINAL
 SEAL AND SIGNATURE BY THE ARCHITECT OR
 ENGINEER WHO PREPARE THE DRAWINGS.
 SEE FL STATUUTES CH. 481 AND 471. ALSO
 SEE FBC.106.1
  
 3) I SPOKE WITH JD @ TED'S SHEDS AND HE
 TOLD ME HE WILL BE SENDING YOU THE
 CORRECT INFORMATION IN THE MAIL. WHEN
 YOU RECEIVE THIS INFORMATION SUBMIT TWO
 COPIES OF THE ANCHORING DATAILS AND TWO
 COPIES OF THE SHED DETAILS
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-01-11 Cont ID  
Sent By mjacobs Date 2006-01-11 Time 14:42 Rev Time 0.00
Received By mjacobs Date 2006-01-11 Time 06:58 Sent To E
Notes
2006-01-11 00:00:00 
 1) PLEASE SUBMIT THE COMPLETE FOUNDATION
 SUPPORT AND TIE-DOWN SYSTEM FOR PLAN
 REVIEW.
  
 2) IF THE DESIGN PROFESSIONAL IS AN
 ARCHITECT OR ENGINEER LEGALLY REGISTERED
 UNDER THE LAWS OF THIS STATE REGULATING
 THE PRACTICE OF ARCHITEDTURE AS PROVIDED
 FOR IN CHAPTER 481, FLORIDA STATUTES,
 PART 1, OR ENGINEERING AS PROVIDED FOR
 IN CHAPTER 471, SHALL AFFIX HIS OR HER
 OFFICIAL SEAL, SIGNATURE AND DATE TO
 SAID DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA,
 AS REQUIRED BY FLORIDA STATUTE.
 FBC 106.1
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
 [email protected].

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2006-03-01 Cont ID  
Sent By btrobaug Date 2006-03-01 Time 07:23 Rev Time 0.33
Received By btrobaug Date 2006-03-01 Time 07:00 Sent To B
Notes
2006-03-01 00:00:00 
 NO ELECTRICAL CIRCUITS TO BE INSTALLED
 PER OWNER, SENT TO MYRON./WRT.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-01-23 Cont ID  
Sent By btrobaug Date 2006-01-23 Time 13:32 Rev Time 0.25
Received By btrobaug Date 2006-01-23 Time 13:01 Sent To B
Notes
2006-01-23 00:00:00 
 THE COMMENTS FROM THE PRIOR REVIEW HAVE
 NOT BEEN ADDRESSED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-01-12 Cont ID  
Sent By btrobaug Date 2006-01-12 Time 15:07 Rev Time 0.33
Received By btrobaug Date 2006-01-12 Time 15:01 Sent To PC
Notes
2006-01-12 00:00:00 
 IF INSTALLING ELECTRICAL DEVICES IN THE
 SHED SHOW HOW FED, DISCONNECTED PER
 225.31 AND GROUNDED PER 250.32. ALSO AN
 ELECTRICAL PERMIT IS REQUIRED IF NO
 ELECTRIC IS TO BE INSTALLED PLEASE
 INDICATE SAME ON PLAN.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-02-25 Cont ID  
Sent By adarroug Date 2006-02-25 Time 12:49 Rev Time 0.00
Received By adarroug Date 2006-02-25 Time 12:49 Sent To E
Notes
2006-02-25 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-01-22 Cont ID  
Sent By adarroug Date 2006-01-22 Time 12:34 Rev Time 0.00
Received By adarroug Date 2006-01-22 Time 12:34 Sent To E
Notes
2006-01-22 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-12-27 Cont ID  
Sent By adarroug Date 2005-12-27 Time 10:52 Rev Time 0.00
Received By adarroug Date 2005-12-27 Time 10:52 Sent To B
Notes
2005-12-27 00:00:00TO "MISC" BOX#2

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-01-11 Time   Rev Time 0.00
Received By adarroug Date 2005-12-10 Time 14:54 Sent To  
Notes
2005-12-10 00:00:00TO "Z" BOX

Review Stop Z ZONING
Rev No 1 Status P Date 2005-12-22 Cont ID  
Sent By mmclean Date 2005-12-22 Time 17:27 Rev Time 0.00
Received By mmclean Date 2005-12-22 Time 17:27 Sent To I
Notes
2005-12-22 00:00:00NOTE: SHED MUST BE A MINIMUM OF 5FT FROM
 PROPERTY LINE.