Plan Review Details - Permit 05120172
Plan Review Stops For Permit 05120172
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-02-08 Cont ID  
Sent By jwitmer Date 2006-02-08 Time 12:04 Rev Time 0.55
Received By jwitmer Date 2006-02-08 Time 12:04 Sent To  
Notes
2006-02-08 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05120172
 ADD: 2800 N FLAGLER (ROOF)
 CONT: J COMPTON ELEC.
 TEL: (954)219-9011
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
  
 1) PLANS DO NOT INDICATE HOW THE
 GENERATOR WILL RESIST MOMENT OF
 OVERTURNING.106.1.2 ADDITIONAL
 DATA. THE BUILDING OFFICIAL MAY REQUIRE
 DETAILS, COMPUTATIONS, STRESS DIAGRAMS,
 AND OTHER DATA NECESSARY TO DESCRIBE THE
 CONSTRUCTION OR INSTALLATION AND THE
 BASIS OF CALCULATION. ALL DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 REQUIRED BY THE BUILDING OFFICIAL TO BE
 PREPARED BY AN ARCHITECT OR ENGINEER
 SHALL BE AFFIXED WITH THIER OFFICIAL
 SEAL, SIGNATURE AND DATE AS STATE LAW
 REQUIRES.
 1604.4 ANALYSIS.
 LOAD EFFECTS ON STRUCTURAL MEMBERS AND
 THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE
 INTO ACCOUNT EQUILIBRIUM, GENERAL
 STABILITY, GEOMETRIC COMPATIBILITY AND
 BOTH SHORT- AND LONG-TERM MATERIAL
 PROPERTIES.
 MEMBERS THAT TEND TO ACCUMULATE RESIDUAL
 DEFORMATIONS UNDER REPEATED SERVICE
 LOADS SHALL HAVE INCLUDED IN THEIR
 ANALYSIS THE ADDED ECCENTRICITIES
 EXPECTED TO OCCUR DURING THEIR SERVICE
 LIFE.
 ANY SYSTEM OR METHOD OF CONSTRUCTION TO
 BE USED SHALL BE BASED ON A RATIONAL
 ANALYSIS IN ACCORDANCE WITH
 WELL-ESTABLISHED PRINCIPLES OF
 MECHANICS. SUCH ANALYSIS SHALL RESULT IN
 A SYSTEM THAT PROVIDES A COMPLETE LOAD
 PATH CAPABLE OF TRANSFERRING LOADS FROM
 THEIR POINT OF ORIGIN TO THE
 LOAD-RESISTING ELEMENTS.
 THE TOTAL LATERAL FORCE SHALL BE
 DISTRIBUTED TO THE VARIOUS VERTICAL
 ELEMENTS OF THE LATERAL-FORCE-RESISTING
 SYSTEM IN PROPORTION TO THEIR RIGIDITIES
 CONSIDERING THE RIGIDITY OF THE
 HORIZONTAL BRACING SYSTEM OR DIAPHRAGM.
 RIGID ELEMENTS THAT ARE ASSUMED NOT TO
 BE A PART OF THE LATERAL-FORCE-RESISTING
 SYSTEM SHALL BE PERMITTED TO BE
 INCORPORATED INTO BUILDINGS PROVIDED
 THAT THEIR EFFECT ON THE ACTION OF THE
 SYSTEM IS CONSIDERED AND PROVIDED FOR IN
 DESIGN. PROVISIONS SHALL BE MADE FOR THE
 INCREASED FORCES INDUCED ON RESISTING
 ELEMENTS OF THE STRUCTURAL SYSTEM
 RESULTING FROM TORSION DUE TO
 ECCENTRICITY BETWEEN THE CENTER OF
 APPLICATION OF THE LATERAL FORCES AND
 THE CENTER OF RIGIDITY OF THE
 LATERAL-FORCE-RESISTING SYSTEM.
 EVERY STRUCTURE SHALL BE DESIGNED TO
 RESIST THE OVERTURNING EFFECTS CAUSED BY
 THE LATERAL FORCES SPECIFIED IN THIS
 CHAPTER. SEE SECTION 1609 FOR WIND AND
 SECTION 1610 FOR LATERAL SOIL LOADS.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-01-05 Cont ID  
Sent By dpalmer Date 2006-01-05 Time 10:59 Rev Time 0.00
Received By dpalmer Date 2006-01-05 Time 10:59 Sent To I
Notes
2006-01-05 00:00:00********* UNSAT ***********
  
 1)NOTE: PLEASE SUBMIT THE MANUFCATURES
 CUT/SPEC SHEETS FOR THE NEW PROPOSED
 ATS. PLEASE BE SURE A LISITNG FROM A
 NRTL IS SHOWN.
  
 2)NOTE: PLEASE PROVIDE A MEANS OF
 SHUTTING OFF THE FUEL SOURCE FOR GEN AT
 THE GROUND FLR LOCATION OF EXISTING
 MAINS FOR BLDG. THIS MEANS SHOULD BE
 READILY ACCESSIBLE FOR SHUTTING DOWN THE
 FUEL SUPPLY FOR THE GEN, INCLUSIVE OF
 NAT GAS AND LP. 445.18
  
 3)NOTE: PLEASE BE SURE TO SPECIFY IF GEN
 WILL OR WILL NOT BE SEPARATELY DERIVED.
 250.30, ETC
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. PLEASE BE SURE TO SEE ANY OTHER
 POSSIBLE COMMENTS FROM OTHER REVIEWER(S)
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-01-10 Cont ID  
Sent By mwennerg Date 2006-01-10 Time 14:08 Rev Time 0.00
Received By mwennerg Date 2006-01-10 Time 14:07 Sent To  
Notes
2006-01-10 00:00:00******PROVISO******
  
 1) ALL WORK TO COMPLY WITH NFPA 110 AND
 APPLICABLE BUILDING CODES.
  
 2) PLEASE SEE ELECTRICAL COMMENT #1
 REGARDING MANUFACTURER SPEC SHEETS.
  
  
 PLANS WILL BE STAMPED AT TIME OF
 RESUBMITTAL.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLANS REVIEW (561) 805-6722

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-03-04 Cont ID  
Sent By pschmitz Date 2006-03-04 Time 07:11 Rev Time 0.00
Received By pschmitz Date 2006-03-04 Time 07:11 Sent To PC
Notes
2006-03-04 00:00:00PLUMBING PLAN REVIEW EXAMINER
 PAUL SCHMITZ 561-805-6692
 [email protected]
 FBC PLUMBING 2004
 FBC FUEL GAS 2004
 AMENDMENTS TO THE FLORIDA BUILDING CODE
 CH 1, ADMINISTRATION, 2004 EDITION
 DENIED
  
 1) SEE ATTACHED GAS PERMIT APPLICATION
 REQUIRMENTS.
 2) PROVIDE ALL INFORMATION ON EXISTING
 GAS PIPING SYSTEM.
  
 END OF COMMENTS, QUESTIONS 561-805-6692

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-01-09 Cont ID  
Sent By adarroug Date 2005-12-22 Time 14:38 Rev Time 0.00
Received By adarroug Date 2005-12-22 Time 08:54 Sent To  
Notes
2006-01-09 00:00:00TO "COMM" BD#19
2005-12-22 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By adarroug Date 2005-12-10 Time 13:38 Sent To  
Notes
2005-12-10 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-01-13 Cont ID  
Sent By tgordon Date 2006-01-13 Time 14:02 Rev Time 0.25
Received By tgordon Date 2006-01-13 Time 14:02 Sent To G
Notes
2006-01-13 00:00:00*** PROVISO ***
 1)GENERATOR EXHUST MUST BE TEN FEET AWAY
 FROM ANY BUILDING OPENINGS (WINDOWS,
 DOORS, ROOF & EAVE VENTS). PER 2004
 FBC/M 401.5.1 .
 2)NEED DETAILED MANUFACTURE'S
 SPECIFICATION'S AND INSTALLATION
 INSTRUCTIONS ON JOB SITE FOR INSPECTOR.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 1 Status P Date 2005-12-20 Cont ID  
Sent By mmclean Date 2005-12-20 Time 14:32 Rev Time 0.00
Received By mmclean Date 2005-12-20 Time 14:32 Sent To I
Notes
2005-12-20 00:00:00INFORMAL SITE PLAN APPROVED 09/15/05 BY
 ANGELLA JONES-VANN (IRSPR #05-22.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved