| Plan Review Stops For Permit 05120142 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2006-01-05 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-01-05 |
Time |
10:53 |
Rev Time |
0.33 |
| Received By |
alange |
Date |
2006-01-05 |
Time |
10:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2006-02-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-02-22 |
Time |
14:52 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-02-22 |
Time |
14:52 |
Sent To |
PC |
|
| Notes |
| 2006-02-22 00:00:00 | REDLINED: | | | | | | NO EQUIPMENT GRNDS FROM METER TO FIRST | | | MEANS OF DISC. | | | 250.6,250.24 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2006-02-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-02-10 |
Time |
17:06 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-02-10 |
Time |
17:02 |
Sent To |
PC |
|
| Notes |
| 2006-02-10 00:00:00 | ******** UNSAT *********** | | | | | | | | | 1)NOTE: PLEASE SEE NEW RISER IS NOW | | | SHOWING A 200A DISCONNECT, DOES THIS | | | CONTAIN OCP AS REQUIRED? | | | PLEASE ALSO SEE THIS NEW 200A DISCONNECT | | | AS IT IS FEEDING A 150A PANEL WITH 150A | | | FEEDERS? | | | PLEASE VEIRFY IF THIS 200A DISCONNET | | | CONTAINS EITHER 150A BRKR, OR 150A FUSES | | | ETC.? | | | PLEASE ALSOSEE NEW ATS WITH 200A OCP IS | | | ALSO SHOWN FEEDING A 150A PANEL AND | | | FEEDERS WITH 200A OCP. | | | 240.4,310.16,240, 230.70 215.5 | | | | | | 2)NOTE: PLEASE PROVIDE AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT PER 110.9, | | | 215.5 | | | | | | 3)NOTE: PLEASE PROVIDE AND SUBMIT LOAD | | | CALCULATIONS. PLEASE SEE RISER MENTIONS, | | | LOAD IS @ 125A'S, HOWEVER GENERATOR IS | | | ONLY RATED @ 112A'S PER NG 27KW RATING. | | | PLEASE KNOW, DERATING MAY BE TAKEN FOR | | | NORMAL GEHN/LTS RECEPTS ETC, HOWEVER | | | 100% SHALL BE FIGURED FOR CONNECTED | | | MOTOR, A/C, AND A/C HEAT LOADS UNLESS | | | SOME MEANS OF LOAD SHEDDING IS PROVIDED. | | | 220,702.5,215.5 | | | | | | 4)NOTE: PLEASE SEE EXISTING SERVICE | | | SEEMED TO INDICATE A 300A | | | SERVICE,HOWEVER AS SHOWN, RISER HAS NOW | | | INCREASED THIS TO 400A'S? HAS METER | | | CHANGED? WHAT SIZE IS METER? | | | PLEASE ALSO VERIFY EXISTING GROUNDING | | | ELECTRODE SYSTEM AND SIZE OF EXIST. | | | IF SERVICE DOES INCREASE THEN GEC SHALL | | | BE REQUIRED TO BE INCREASED BASED ON | | | TABLE FROM 250.66 | | | | | | 5)NOTE: PLEASE SEE NOC RECORDED HAS | | | SINCE EXPIRED AND WILL BE REQUIRED TO BE | | | RE-RECORDED AS REQUIRED UNDER | | | FS713.13(2). WORK HAS NOT COMMENCED | | | WITHIN 90 DAYS OF RECORDING , THE NOC | | | SHALL BECOME VOID. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-12-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-12-28 |
Time |
17:19 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2005-12-28 |
Time |
17:19 |
Sent To |
M |
|
| Notes |
| 2005-12-28 00:00:00 | ********** UNSAT ************* | | | | | | | | | 1)NOTE: PLEASE SUBMIT COMPLETE PLANS FOR | | | REVIEW MEETING MIN 2002 NEC CODE | | | COMPLIANCE. | | | PLEASE SEE RISER SUBMITTED DOES NOT | | | INLCUDE, CONDUCTORS, CONDUIT SIZES, | | | GROUNDING, LOAD CALCULATIONS ETC ETC. | | | 215.5,225.31-225.39, 230.72, 250.50, | | | 250.30, 702.5 ,,,,, | | | | | | 2)NOTE: PLEASE SEE PLANS SHALL BE OF | | | DRAFTSMAN QUALITY PER FBC ADMINISTRATIVE | | | SECTION 106.1.3 | | | | | | 3)NOTE: PLEASE SEE VALUATION IS BASED ON | | | ALL LABOR AND MATERIALS, EVEN IF ANY | | | EQUIPMENT IS OWNER SUPPLIED. | | | 108.3 | | | | | | 4)NOTE: PLEASE SUBMIT A LAYOUT OF HOUSE | | | FOR LOCATION OF GEN, MAINS(S), GEN, | | | PANELS ETC. | | | SEE OTHER REVIEWER(S) COMMENTS WITH | | | RESPECT TO MIN DISTANCE TO BE SHOWN FROM | | | VENTED OPENINGS, WINDOWS ETC IN | | | DWELLING. | | | | | | PLEASE KNOW, A COMPLETE REVIEW FOR CODE | | | COMPLIANCE CAN NOT BE DONE AT THIS TIME. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2006-01-04 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-01-04 |
Time |
07:51 |
Rev Time |
0.25 |
| Received By |
jleech |
Date |
2006-01-04 |
Time |
07:51 |
Sent To |
B |
|
| Notes |
| 2006-01-04 00:00:00 | GAS PERMIT REQUIRED. GAS CONTRACTOR TO | | | PROVIDE DRAWINGS WITH PERMIT APPICATION. | | | FINAL GAS INSPECTION REQUIRED BEFORE | | | GEN. FINAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2006-02-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-02-16 |
Time |
11:47 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-02-16 |
Time |
11:47 |
Sent To |
E |
|
| Notes |
| 2006-02-16 00:00:00 | TO "DPALMER" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-02-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-02-02 |
Time |
17:38 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-02-02 |
Time |
17:38 |
Sent To |
E |
|
| Notes |
| 2006-02-02 00:00:00 | TO "DPALMER" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-12-22 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-12-22 |
Time |
16:47 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-12-22 |
Time |
16:47 |
Sent To |
E |
|
| Notes |
| 2005-12-22 00:00:00 | TO "GEN-RES" BOX "E" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-01-05 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-01-05 |
Time |
10:53 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2005-12-10 |
Time |
13:04 |
Sent To |
|
|
| Notes |
| 2005-12-10 00:00:00 | TO "Z" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2005-12-29 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2005-12-29 |
Time |
15:35 |
Rev Time |
0.15 |
| Received By |
tgordon |
Date |
2005-12-29 |
Time |
15:35 |
Sent To |
G |
|
| Notes |
| 2005-12-29 00:00:00 | *** PROVISO *** | | | 1) GENERATOR EXHUST MUST BE TEN FEET | | | AWAY FROM ANY BUILDING OPENINGS | | | (WINDOWS, DOORS, ROOF & EAVE VENTS), AND | | | TEN FEET AWAY FROM ADJECENT BUILDING | | | OPENS. PER 2004 FBC/M 401.5.1 . | | | 2) NEED DETAILED MANUFACTURE'S | | | SPECIFICATION'S AND INSTALLATION | | | INSTRUCTIONS ON JOB SITE FOR | | | INSPECTIONS. | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2005-12-22 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-12-22 |
Time |
14:51 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-12-22 |
Time |
14:51 |
Sent To |
I |
|
| Notes |
| 2005-12-22 00:00:00 | PROVISO: GENERATOR MUST SIT BACK 25FT | | | WITHIN THE FIRST 25FT FRONT SETBACK & | | | CAN ONLY ENCROACH 4FT INTO A SETBACK. |
|
|