Plan Review Details - Permit 05120142
Plan Review Stops For Permit 05120142
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-01-05 Cont ID  
Sent By alange Date 2006-01-05 Time 10:53 Rev Time 0.33
Received By alange Date 2006-01-05 Time 10:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-02-22 Cont ID  
Sent By dpalmer Date 2006-02-22 Time 14:52 Rev Time 0.00
Received By dpalmer Date 2006-02-22 Time 14:52 Sent To PC
Notes
2006-02-22 00:00:00REDLINED:
  
 NO EQUIPMENT GRNDS FROM METER TO FIRST
 MEANS OF DISC.
 250.6,250.24

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-02-10 Cont ID  
Sent By dpalmer Date 2006-02-10 Time 17:06 Rev Time 0.00
Received By dpalmer Date 2006-02-10 Time 17:02 Sent To PC
Notes
2006-02-10 00:00:00******** UNSAT ***********
  
  
 1)NOTE: PLEASE SEE NEW RISER IS NOW
 SHOWING A 200A DISCONNECT, DOES THIS
 CONTAIN OCP AS REQUIRED?
 PLEASE ALSO SEE THIS NEW 200A DISCONNECT
 AS IT IS FEEDING A 150A PANEL WITH 150A
 FEEDERS?
 PLEASE VEIRFY IF THIS 200A DISCONNET
 CONTAINS EITHER 150A BRKR, OR 150A FUSES
 ETC.?
 PLEASE ALSOSEE NEW ATS WITH 200A OCP IS
 ALSO SHOWN FEEDING A 150A PANEL AND
 FEEDERS WITH 200A OCP.
 240.4,310.16,240, 230.70 215.5
  
 2)NOTE: PLEASE PROVIDE AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT PER 110.9,
 215.5
  
 3)NOTE: PLEASE PROVIDE AND SUBMIT LOAD
 CALCULATIONS. PLEASE SEE RISER MENTIONS,
 LOAD IS @ 125A'S, HOWEVER GENERATOR IS
 ONLY RATED @ 112A'S PER NG 27KW RATING.
 PLEASE KNOW, DERATING MAY BE TAKEN FOR
 NORMAL GEHN/LTS RECEPTS ETC, HOWEVER
 100% SHALL BE FIGURED FOR CONNECTED
 MOTOR, A/C, AND A/C HEAT LOADS UNLESS
 SOME MEANS OF LOAD SHEDDING IS PROVIDED.
 220,702.5,215.5
  
 4)NOTE: PLEASE SEE EXISTING SERVICE
 SEEMED TO INDICATE A 300A
 SERVICE,HOWEVER AS SHOWN, RISER HAS NOW
 INCREASED THIS TO 400A'S? HAS METER
 CHANGED? WHAT SIZE IS METER?
 PLEASE ALSO VERIFY EXISTING GROUNDING
 ELECTRODE SYSTEM AND SIZE OF EXIST.
 IF SERVICE DOES INCREASE THEN GEC SHALL
 BE REQUIRED TO BE INCREASED BASED ON
 TABLE FROM 250.66
  
 5)NOTE: PLEASE SEE NOC RECORDED HAS
 SINCE EXPIRED AND WILL BE REQUIRED TO BE
 RE-RECORDED AS REQUIRED UNDER
 FS713.13(2). WORK HAS NOT COMMENCED
 WITHIN 90 DAYS OF RECORDING , THE NOC
 SHALL BECOME VOID.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-12-28 Cont ID  
Sent By dpalmer Date 2005-12-28 Time 17:19 Rev Time 0.00
Received By dpalmer Date 2005-12-28 Time 17:19 Sent To M
Notes
2005-12-28 00:00:00********** UNSAT *************
  
  
 1)NOTE: PLEASE SUBMIT COMPLETE PLANS FOR
 REVIEW MEETING MIN 2002 NEC CODE
 COMPLIANCE.
 PLEASE SEE RISER SUBMITTED DOES NOT
 INLCUDE, CONDUCTORS, CONDUIT SIZES,
 GROUNDING, LOAD CALCULATIONS ETC ETC.
 215.5,225.31-225.39, 230.72, 250.50,
 250.30, 702.5 ,,,,,
  
 2)NOTE: PLEASE SEE PLANS SHALL BE OF
 DRAFTSMAN QUALITY PER FBC ADMINISTRATIVE
 SECTION 106.1.3
  
 3)NOTE: PLEASE SEE VALUATION IS BASED ON
 ALL LABOR AND MATERIALS, EVEN IF ANY
 EQUIPMENT IS OWNER SUPPLIED.
 108.3
  
 4)NOTE: PLEASE SUBMIT A LAYOUT OF HOUSE
 FOR LOCATION OF GEN, MAINS(S), GEN,
 PANELS ETC.
 SEE OTHER REVIEWER(S) COMMENTS WITH
 RESPECT TO MIN DISTANCE TO BE SHOWN FROM
 VENTED OPENINGS, WINDOWS ETC IN
 DWELLING.
  
 PLEASE KNOW, A COMPLETE REVIEW FOR CODE
 COMPLIANCE CAN NOT BE DONE AT THIS TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-01-04 Cont ID  
Sent By jleech Date 2006-01-04 Time 07:51 Rev Time 0.25
Received By jleech Date 2006-01-04 Time 07:51 Sent To B
Notes
2006-01-04 00:00:00GAS PERMIT REQUIRED. GAS CONTRACTOR TO
 PROVIDE DRAWINGS WITH PERMIT APPICATION.
 FINAL GAS INSPECTION REQUIRED BEFORE
 GEN. FINAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-02-16 Cont ID  
Sent By adarroug Date 2006-02-16 Time 11:47 Rev Time 0.00
Received By adarroug Date 2006-02-16 Time 11:47 Sent To E
Notes
2006-02-16 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-02-02 Cont ID  
Sent By adarroug Date 2006-02-02 Time 17:38 Rev Time 0.00
Received By adarroug Date 2006-02-02 Time 17:38 Sent To E
Notes
2006-02-02 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-12-22 Cont ID  
Sent By adarroug Date 2005-12-22 Time 16:47 Rev Time 0.00
Received By adarroug Date 2005-12-22 Time 16:47 Sent To E
Notes
2005-12-22 00:00:00TO "GEN-RES" BOX "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-01-05 Cont ID  
Sent By alange Date 2006-01-05 Time 10:53 Rev Time 0.00
Received By alange Date 2005-12-10 Time 13:04 Sent To  
Notes
2005-12-10 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-12-29 Cont ID  
Sent By tgordon Date 2005-12-29 Time 15:35 Rev Time 0.15
Received By tgordon Date 2005-12-29 Time 15:35 Sent To G
Notes
2005-12-29 00:00:00*** PROVISO ***
 1) GENERATOR EXHUST MUST BE TEN FEET
 AWAY FROM ANY BUILDING OPENINGS
 (WINDOWS, DOORS, ROOF & EAVE VENTS), AND
 TEN FEET AWAY FROM ADJECENT BUILDING
 OPENS. PER 2004 FBC/M 401.5.1 .
 2) NEED DETAILED MANUFACTURE'S
 SPECIFICATION'S AND INSTALLATION
 INSTRUCTIONS ON JOB SITE FOR
 INSPECTIONS.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2005-12-22 Cont ID  
Sent By mmclean Date 2005-12-22 Time 14:51 Rev Time 0.00
Received By mmclean Date 2005-12-22 Time 14:51 Sent To I
Notes
2005-12-22 00:00:00PROVISO: GENERATOR MUST SIT BACK 25FT
 WITHIN THE FIRST 25FT FRONT SETBACK &
 CAN ONLY ENCROACH 4FT INTO A SETBACK.