Plan Review Details - Permit 05120123
Plan Review Stops For Permit 05120123
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-12-27 Cont ID  
Sent By adarroug Date 2005-12-27 Time 15:12 Rev Time 0.00
Received By adarroug Date 2005-12-27 Time 15:12 Sent To M
Notes
2005-12-27 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-12-10 Cont ID  
Sent By adarroug Date 2005-12-10 Time 11:03 Rev Time 0.00
Received By adarroug Date 2005-12-10 Time 11:03 Sent To MEDGAS
Notes
2005-12-10 00:00:00TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-12-28 Cont ID  
Sent By tgordon Date 2005-12-28 Time 08:42 Rev Time 0.20
Received By tgordon Date 2005-12-28 Time 08:42 Sent To  
Notes
2005-12-28 00:00:00REQUIREMENTS FROM LAST REVIEW HAVE BEEN
 ADDRESSED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-12-12 Cont ID  
Sent By tgordon Date 2005-12-12 Time 09:47 Rev Time 0.30
Received By tgordon Date 2005-12-12 Time 09:46 Sent To  
Notes
2005-12-12 00:00:00*** DENIED ***
 1) NEED TO SUBMIT MANUAL J CALCULATIONS.
 2) SHOW SENSIBLE BTU'S ON PLANS ALSO.
 3) SHOW AHU'S TOTAL CFM'S ON PLANS.
 4) EXPLAIN WHERE CONDENSATE DRAIN IS
 DISCHARGING TO.
 5) SHOW WHERE SECONDARY DRAIN LINE GOES
 TO, OR IF A FLOAT SWITCH IS BEING USED.
 6) RETURN AIR GRILLS AND SUPPLY AIR
 GRILLS NEED TO BE SIZED.
 7) RETURN AIR DUCTS IN OFFICE 6,7,AND 8
 ARE NOT SIZED.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.