| 2005-12-08 00:00:00 | |
| | 1) THIS ROOF IS MISSING OR NOT IN |
| | COMPLIANCE WITH THE FOLLOW ITEMS: |
| | |
| | _X__ CONTRACTOR DID NOT PROVIDE THE MEAN |
| | ROOF HEIGHT. |
| | |
| | _X__ CONTRACTOR DID NOT INDICATE THE |
| | ROOF PITCH, OR THE DECK TYPE. |
| | |
| | _X__ CONTRACTOR FAILED TO INDICATE WHICH |
| | SYSTEM TO BE USED. THE SYSTEM SELECTED |
| | IS THE MEMBRANE UNDERLAYMENT FOR |
| | MECHANICALLY FASTENED TILE SYSTEM ONLY. |
| | |
| | 2) FBC 1606.2.5.GENERAL LIMITATION |
| | #9 PROHIBITS RATIONAL ANALYSIS OR |
| | EXTRAPOLATION TO ENHANCE THE UPLIFT |
| | PRESSURE AT PERIMETER AND CORNER AREAS |
| | BY REDUCING THE FASTENER SPACING IN |
| | THESE AREAS.EITHER SELECT AN |
| | ALTERNATIVE SYSTEM (OR PRODUCT APPROVAL) |
| | THAT DOES NOT CITE GENERAL LIMITATION |
| | #9.ALTERNATIVELY IF THE SELECTED |
| | SYSTEM DOES CITE GENERAL LIMITATION #9, |
| | IT MUST HAVE A MAXIMUM DESIGN PRESSURE |
| | THAT EXCEEDS THE PRESSURE IN ROOF ZONE 3 |
| | (TYPICALLY -89 PSF FOR MEAN ROOF HEIGHT |
| | OF 30 FEET OR LESS). |
| | |
| | 3) PLEASE SEE THE ROOFING PROCEDURES |
| | POLICY ENCLOSE IN PACKAGE. ALL |
| | INFORMATION IS REQUIRED FOR PLAN REVIEW. |
| | ALSO TWO COPIES OF EACH PRODUCT APPROVAL |
| | IS REQUIRED. ONLY ONE STATE COVER SHEET |
| | WAS SUBMITTED. |
| | |
| | 4) IS THIS A FLAT ROOF OR A PITCH ROOF |
| | PLEASE INDICATE ON THE APPLICATION ALONG |
| | WITH THE OTHER INFORMATION. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | TEL: (561) 805-6726 |
| | FAX: (561) 659-8026 |