Plan Review Details - Permit 05120096
| Plan Review Stops For Permit 05120096 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2006-01-27 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2006-01-27 |
Time |
07:51 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2006-01-27 |
Time |
07:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2006-01-06 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2006-01-06 |
Time |
12:57 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2006-01-06 |
Time |
12:57 |
Sent To |
|
|
| Notes |
| 2006-01-06 00:00:00 | DENIED | | | | | | 1) THE NOA THAT IS PART OF THE STATE | | | PRODUCT APPROVAL FOR THE POLYGLASS | | | MODIFIED ROOF SYSTEM LISTS A MAXIMUM | | | DESIGN PRESSURE OF -45 PSF FOR THE | | | APPROVED ASSEMBLY THAT WAS SUBMITTED. | | | THE NOA FOR THIS SYSTEM SPECIFIES | | | GENERAL LIMITATION #9, WHICH DOES NOT | | | ALLOW THE PRESSURE TO BE INCREASED BY | | | ENHANCED FASTENING. THEREFORE, THE | | | ENGINEERING DOES NOT WORK FOR THIS | | | PRODUCT. PLEASE SEE NOA THAT WAS | | | SUBMITTED. | | | | | | 2) THE ENGINEERING IS MIXING CRITERIA | | | FROM TWO NOAS AND DIFFERENT ASSEMBLIES. | | | | | | 3)A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-12-30 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2005-12-30 |
Time |
08:39 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2005-12-30 |
Time |
08:39 |
Sent To |
|
|
| Notes |
| 2005-12-30 00:00:00 | DENIED | | | | | | 1) THE NOA THAT WAS SUBMITTED FOR THE | | | POLYGLASS MODIFIED SYSTEM HAS BEEN | | | REVISED BY NOA 03-0130.08. SEE UPDATED | | | INFORMATION ON STATE PRODUCT APPROVAL | | | WEBSITE AT WWW.FLORIDABUILDING.ORG. | | | | | | 2) ENGINEERING IS BASED ON THE OLD NOA. | | | | | | 3) THE ENGINEERING SUBMITTED DOES NOT | | | CORRESPOND WITH THE ASSEMBLY INDICATED | | | IN THE NOA THAT WAS SUBMITTED. THE NOA | | | IS FOR A NON-INSULATED WOOD DECK WITH | | | -45 PSF DESIGN PRESSURE AND DOES NOT | | | ALLOW ENHANCED FASTENING. ENGINEERING IS | | | FOR INSULATED DECK WITH -60 PSF AND | | | ALLOWS ENHANCED FASTENING. | | | | | | 4) THE MAX PRESSURE IN THE APPLICATION | | | FORM FOR THE METAL ROOF IS FOR STEEL | | | DECKS. SEE NOA. | | | | | | 5) PROVIDE TWO COPIES OF THE FL PRODUCT | | | APPROVAL COVER SHEETS. | | | | | | 6)A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|
|
| Review Stop |
B1 |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2006-01-27 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2006-01-27 |
Time |
09:57 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2006-01-27 |
Time |
09:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B1 |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-12-02 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-12-02 |
Time |
11:33 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2005-12-02 |
Time |
11:32 |
Sent To |
|
|
| Notes |
| 2005-12-02 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2004 | | | | | | 1.)FLORIDA STATE OR LOCAL PRODUCT | | | APPROVAL REQUIRED IN ADDITION TO THE | | | NOAS PROVIDED, FAC9B72. | | | WWW.FLORIDABUILDING.ORG | | | | | | 2.)THE APPLICATION STATES THAT THERE | | | WILL BE A NEW SELF ADHERING FLAT ROOF. | | | THE NOA REQUIRES A MECHANICALLY FASTENED | | | BASE SHEET.ADDRESS. | | | | | | 3.)TWO DIFFERENT ASSEMBLIES WERE | | | SUBMITTED FOR THE POLYGLASS PRODUCT, | | | NEITHER OF WHICH IS COMPLIANT FOR THE | | | DESIGN PRESSURE OF A MINIMUM OF -89 FOR | | | ZONE 3 IN EXPOSURE B.BOTH REFER TO | | | PRODUCT LIMITATION #9.SUBMIT ONLY THE | | | ASSEMBLY YOU ARE INSTALLING. | | | | | | | | | | | | |
|
|
|