Plan Review Details - Permit 05120096
Plan Review Stops For Permit 05120096
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-01-27 Cont ID  
Sent By rmcdouga Date 2006-01-27 Time 07:51 Rev Time 0.00
Received By rmcdouga Date 2006-01-27 Time 07:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-01-06 Cont ID  
Sent By rmcdouga Date 2006-01-06 Time 12:57 Rev Time 0.00
Received By rmcdouga Date 2006-01-06 Time 12:57 Sent To  
Notes
2006-01-06 00:00:00DENIED
  
 1) THE NOA THAT IS PART OF THE STATE
 PRODUCT APPROVAL FOR THE POLYGLASS
 MODIFIED ROOF SYSTEM LISTS A MAXIMUM
 DESIGN PRESSURE OF -45 PSF FOR THE
 APPROVED ASSEMBLY THAT WAS SUBMITTED.
 THE NOA FOR THIS SYSTEM SPECIFIES
 GENERAL LIMITATION #9, WHICH DOES NOT
 ALLOW THE PRESSURE TO BE INCREASED BY
 ENHANCED FASTENING. THEREFORE, THE
 ENGINEERING DOES NOT WORK FOR THIS
 PRODUCT. PLEASE SEE NOA THAT WAS
 SUBMITTED.
  
 2) THE ENGINEERING IS MIXING CRITERIA
 FROM TWO NOAS AND DIFFERENT ASSEMBLIES.
  
 3)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-12-30 Cont ID  
Sent By rmcdouga Date 2005-12-30 Time 08:39 Rev Time 0.00
Received By rmcdouga Date 2005-12-30 Time 08:39 Sent To  
Notes
2005-12-30 00:00:00DENIED
  
 1) THE NOA THAT WAS SUBMITTED FOR THE
 POLYGLASS MODIFIED SYSTEM HAS BEEN
 REVISED BY NOA 03-0130.08. SEE UPDATED
 INFORMATION ON STATE PRODUCT APPROVAL
 WEBSITE AT WWW.FLORIDABUILDING.ORG.
  
 2) ENGINEERING IS BASED ON THE OLD NOA.
  
 3) THE ENGINEERING SUBMITTED DOES NOT
 CORRESPOND WITH THE ASSEMBLY INDICATED
 IN THE NOA THAT WAS SUBMITTED. THE NOA
 IS FOR A NON-INSULATED WOOD DECK WITH
 -45 PSF DESIGN PRESSURE AND DOES NOT
 ALLOW ENHANCED FASTENING. ENGINEERING IS
 FOR INSULATED DECK WITH -60 PSF AND
 ALLOWS ENHANCED FASTENING.
  
 4) THE MAX PRESSURE IN THE APPLICATION
 FORM FOR THE METAL ROOF IS FOR STEEL
 DECKS. SEE NOA.
  
 5) PROVIDE TWO COPIES OF THE FL PRODUCT
 APPROVAL COVER SHEETS.
  
 6)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-01-27 Cont ID  
Sent By rmcdouga Date 2006-01-27 Time 09:57 Rev Time 0.00
Received By rmcdouga Date 2006-01-27 Time 09:57 Sent To  
Notes
***NONE***

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-12-02 Cont ID  
Sent By shill Date 2005-12-02 Time 11:33 Rev Time 0.00
Received By shill Date 2005-12-02 Time 11:32 Sent To  
Notes
2005-12-02 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2004
  
 1.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED IN ADDITION TO THE
 NOAS PROVIDED, FAC9B72.
 WWW.FLORIDABUILDING.ORG
  
 2.)THE APPLICATION STATES THAT THERE
 WILL BE A NEW SELF ADHERING FLAT ROOF.
 THE NOA REQUIRES A MECHANICALLY FASTENED
 BASE SHEET.ADDRESS.
  
 3.)TWO DIFFERENT ASSEMBLIES WERE
 SUBMITTED FOR THE POLYGLASS PRODUCT,
 NEITHER OF WHICH IS COMPLIANT FOR THE
 DESIGN PRESSURE OF A MINIMUM OF -89 FOR
 ZONE 3 IN EXPOSURE B.BOTH REFER TO
 PRODUCT LIMITATION #9.SUBMIT ONLY THE
 ASSEMBLY YOU ARE INSTALLING.
  
  
  
  