Plan Review Details - Permit 05120081
Plan Review Stops For Permit 05120081
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-04-18 Cont ID  
Sent By alange Date 2006-04-18 Time 14:13 Rev Time 1.50
Received By alange Date 2006-04-18 Time 14:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-04-07 Cont ID  
Sent By alange Date 2006-04-07 Time 10:48 Rev Time 1.50
Received By alange Date 2006-04-07 Time 10:48 Sent To  
Notes
2006-04-07 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
  
 3. ALL PLANS SUBMITTED AFTER OCTOBER, 1,
 2004 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE.
 REMOVE OLD A-1 AND INSERT NEW WITH ALL
 REQUIRED DESIGN PARAMETERS.
  
 6.PRODUCT APPROVALS REQUIRED FOR
 LINTELS.
  
 7.ALL PRODUCT APPROVALS SUBMITTED
 SHALL HAVE THE FOLLOWING STATE PRODUCT
 APPROVAL ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 10.INCLUDE ON PLANS A DOOR AND WINDOW
 SCHEDULE.
  
 11.SHOW WINDOW BUCK DETAIL HAVING BUCK
 OFFER FULL SUPPORT OF THE FRAME.
 R-613.6.2SQUARE EDGED BUCK, NOT
 BEVELED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-01-23 Cont ID  
Sent By alange Date 2006-01-23 Time 11:10 Rev Time 3.00
Received By alange Date 2006-01-23 Time 09:39 Sent To  
Notes
2006-01-23 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3. ALL PLANS SUBMITTED AFTER OCTOBER, 1,
 2004 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE.
  
 4.ENERGY CALCS SHALL BE TO THE 2004
 FBC.
  
 5.SUBMIT SPECS FOR FIREPLACE.
  
 6.PRODUCT APPROVALS REQUIRED FOR
 LINTELS, STRAPS AND TIE-DOWNS.
  
 7.ALL PRODUCT APPROVALS SUBMITTED
 SHALL HAVE THE FOLLOWING STATE PRODUCT
 APPROVAL ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 8.SUBMIT SPECS FOR BBQ AND HOOD.
  
 9. W P B ADMINISTRTIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 10.INCLUDE ON PLANS A DOOR AND WINDOW
 SCHEDULE.
  
 11.SHOW WINDOW BUCK DETAIL HAVING BUCK
 OFFER FULL SUPPORT OF THE FRAME.
 R-613.6.2
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-04-21 Cont ID  
Sent By dpalmer Date 2007-04-21 Time 15:47 Rev Time 0.00
Received By dpalmer Date 2007-04-21 Time 15:36 Sent To PC
Notes
2007-04-21 15:47:31REV FOR FINAL.

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2007-04-16 Cont ID  
Sent By dpalmer Date 2007-04-16 Time 16:32 Rev Time 0.00
Received By dpalmer Date 2007-04-16 Time 15:59 Sent To PC
Notes
2007-04-16 16:33:22** UNSAT **
  
 1) NOTE: PLEASE SEE THERE IS NOW A PANEL BEING ADDED
 FOR POOL EQUIPMENT; HOWEVER THE PANEL IS NOT ON RISER
 AND NOT SHOWN PLANS FOR LOCATION.
 PLEASE ALSO SEE THAT THE PANEL SCHEDULE SEEMS TO ONLY
 SHOW ON SIDE OF THE PANEL. PLEASE LABEL CIRCUITS AS
 DONE ON PANELS A1 AND B.
 215.5, 408.4 ETC
 FBC106.3.5.4
  
 2) NOTE: PLEASE SEE NEW PANEL SCHEDULE FOR METER/MAIN
 WHICH INDICATES 2/0'S FOR THE SUB PANELS A1 AND B, YET
 THE RISER SHOWS #1'S. IF THE CONDUCTORS ARE INDEED
 2/0'S THEN THE CONDUIT SIZE AS SHOWN IS NOT LARGE
 ENOUGH.
 PLEASE ADJUST AND CORRELATE PLANS.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-11-13 Cont ID  
Sent By dpalmer Date 2006-11-13 Time 12:34 Rev Time 0.00
Received By dpalmer Date 2006-11-13 Time 12:25 Sent To PC
Notes
2006-11-13 12:34:35REV ADDRESSED PREVIOUS COMMENTS.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-09-17 Cont ID  
Sent By dpalmer Date 2006-09-17 Time 11:48 Rev Time 0.00
Received By dpalmer Date 2006-09-17 Time 11:36 Sent To PC
Notes
2006-09-17 00:00:00** UNSAT **
  
 ** PLEASE SEE NOTES BELOW WERE GIVEN ON
 4/3/06 WHICH STILL ARE NEED OF
 ADDRESSING.
  
 ** NEW NOTES
  
 1) NOTE: PLEASE CLARIFY IF THE DINING RM
 IS ON ONE OR "MORE" OF THE SMALL
 APPLIANCE CIRCUITS. PLEASE SEE IF THE
 DINING ROOM IS ON ITS OWN SMALL APPL
 DINING CIRCUIT, PLEASE REVISE PANEL
 SCHEDULE AND LOAD CALCULATIONS PER
 210.52B1,210.11C1,220.16
  
 2) NOTE: PLEASE SEE PLANS SHOW A
 GENERATOR WHICH IS NOT ON RISER AND
 THERE IS CURRENTLY NO RECORD OF A PERMIT
 BEING PULLED TO INSTALL A GENERATOR.
 PLEASE REMOVE. OR NOTE "FUTURE". PLEASE
 KNOW, THE LOCATION OF THE GEN IS
 REQUIRED TO BE 5' FROM BUILDING AND ANY
 SURROUNDIGN STRUCTURES/WALLS/FENCES OR
 PER MANUFACTURES SPEC MIN.
  
 3) NOTE: PLEASE SEE LIVING ROM/ BEDRM #3
 FOR WALL SPACES RECEPT SPACING PER
 210.52.
 6' OF DOOR AND MORE THAN 2' OF WALL
 SPACE.
  
  
 ** PREVIOUS REVIEW NOTES WHICH WERE
 GIVEN AS A "PROVISO".
 PLEASE SEE ALL THE CIRCUITS BEING SHOWN
 AS #12 WITH 15A BREAKERS?
  
  
  
 *** PREVIOUS REVIEW REDLINED NOTES.
  
 *** NOTES REDLINED **
  
 PLEASE SEE MANY 15A CIRCUITS SHOWN WITH
 #12 AWG, THIS IS OK, HOWEVER IF SHOWN
 THIS IS WHAT WILL BE REQUIRED TO BE
 INSTALLED.
  
 PLEASE SEE POOL LTS SHOWN ON 20A CIRCUIT
 W/ #14 AWG. PLEASE SEE 240.4,310.16, MAY
 ONLY BE 15A OCP OR ADJUST AWG TO #12.
  
 PLEASE SEE ALL DISCONNECT'S SHOWN ON
 RISER DIAGRAM WHICH DO NOT INDICATE WHAT
 THEY ARE FEEDING. THESE ARE TO BE
 IDENTIFIED.
  
 PLEASE SUBMIT THE ABOVE CORRECTIONS,
 ALONG WITH ANY OTHER REVISIONS "BEFORE
 ROUGH ELECTRICAL INSPECTION".
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE IN CONTRACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-04-03 Cont ID  
Sent By dpalmer Date 2006-04-03 Time 07:48 Rev Time 0.00
Received By dpalmer Date 2006-04-03 Time 06:52 Sent To M
Notes
2006-04-03 00:00:00*** NOTES REDLINED **
  
 PLEASE SEE MANY 15A CIRCUITS SHOWN WITH
 #12 AWG, THIS IS OK, HOWEVER IF SHOWN
 THIS IS WHAT WILL BE REQUIRED TO BE
 INSTALLED.
  
 PLEASE SEE POOL LTS SHOWN ON 20A CIRCUIT
 W/ #14 AWG. PLEASE SEE 240.4,310.16, MAY
 ONLY BE 15A OCP OR ADJUST AWG TO #12.
  
 PLEASE SEE ALL DISCONNECT'S SHOWN ON
 RISER DIAGRAM WHICH DO NOT INDICATE WHAT
 THEY ARE FEEDING. THESE ARE TO BE
 IDENTIFIED.
  
 PLEASE SUBMIT THE ABOVE CORRECTIONS,
 ALONG WITH ANY OTHER REVISIONS "BEFORE
 ROUGH ELECTRICAL INSPECTION".
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE IN CONTRACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-12-23 Cont ID  
Sent By dpalmer Date 2005-12-23 Time 13:36 Rev Time 0.00
Received By dpalmer Date 2005-12-23 Time 11:05 Sent To M
Notes
2005-12-23 00:00:00**** UNSAT ****
  
 1)NOTE: PLEASE SEE FS 481.221 WHICH
 REQUIRES THE PLANS TO BE SIGNED,DATED
 AND SAEALED BY SAID ARCHITECT,
 (E-SHEETS NOT DONE)
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 PLEASE SEE IT IS NOTED THAT THE AIC
 RATING IS ALREADY SHOWN FOR THE SUB
 PANELS, JUST NEEDST O BE SHOWN FOR MAIN.
  
 3)NOTE: PLEASE SHOW METER MAIN COMBO ON
 PLANS ALSO, AS PLANS SHOWS A METER AND A
 SEPARATE MAIN DISC.
  
 4)NOTE: PLEASE SEE LOCATIONS ON PLANS
 FOR MANY MISSING RECEPTS REQUIRED PER
 210.52
 6' OF DOORS, ETC
 PLEASE ALSO SEE WAHT APPEAR TO BE A
 "SHIFT" ON THE PLANS FOR ONE OF THE
 BEDRMS.
  
 5)NOTE: PLEASE INCLUDE ALL ROOM/AREA
 DESIGNATIONS ON PLANS.
  
 6)NOTE: PLEASE BE SURE TO MOVE ALL SD'S
 INTO BEDROOM AREAS,AS SD'S ARE REQUIRED
 TO BE WITHIN 12" OF THE HIGHEST POINT OF
 A FLAT CEILING.
 NFPA-72 11.8.3.5
  
 7)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
 PLEASE BE SURE TO CORRELATE THE 60+
 FIXTURES ON PLANS WITH THE LOAD AND
 SCHEDULE.
  
 8)NOTE: PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE, AS ONLY AFCI PROTECTION IS
 SHOWN FOR RECEPTS.
 2002 NEC 210.12, REQUIRES ALL ELECTRICAL
 OUTLETS IN BEDRMS TO HAVE ARC FAULT
 PROTECTION. SD'S, LTS, FANS, RECEPTS
 ETC.
  
 9)NOTE: PLEASE SEE 250.66 FOR MIN SIZING
 FOR GEC. PLEASE SEE A #2 IS SHOWN TO
 CWP, HOWEVER A #4 IS ALSO SHOWN. PLEASE
 SEE THE REQUIRED CONTINUOUS GEC SHALL BE
 #2 MIN.
  
 10)NOTE: PLEASE SEE LAUNDRY RM? , PLEASE
 SEE WHAT APPEARS TO BE ONLY A RECEPT FOR
 THE WASHER OR DRYER, AS BOTH ARE NOT
 SHOWN.
 215.5
  
 11)NOTE: PLEASE SEE MIN CLEARENCE
 REQUIRED PER 110.26 FOR CU DISCONNECTS.
  
 ** PLEASE BE SURE TO REMOVE ALL
 OLD/VOIDED SHEETS AND ONLU INERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 PLEASE ONLY SUBMIT ONE COPY OF ANY
 OLD/VOIDED SHEETS FOR REFERENCE.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2007-04-23 Cont ID  
Sent By adarroug Date 2007-04-23 Time 16:38 Rev Time 0.00
Received By adarroug Date 2007-04-23 Time 16:38 Sent To P
Notes
2007-04-23 16:41:11TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-04-19 Cont ID  
Sent By adarroug Date 2007-04-19 Time 11:21 Rev Time 0.00
Received By adarroug Date 2007-04-19 Time 11:21 Sent To E
Notes
2007-04-19 11:21:19TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-04-16 Cont ID  
Sent By adarroug Date 2007-04-16 Time 09:59 Rev Time 0.00
Received By adarroug Date 2007-04-16 Time 09:59 Sent To E
Notes
2007-04-16 09:59:21TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-11-08 Cont ID  
Sent By adarroug Date 2006-11-08 Time 13:20 Rev Time 0.00
Received By adarroug Date 2006-11-08 Time 13:20 Sent To E
Notes
2006-11-08 13:20:23TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-09-12 Cont ID  
Sent By adarroug Date 2006-09-12 Time 09:07 Rev Time 0.00
Received By adarroug Date 2006-09-12 Time 09:07 Sent To P
Notes
2006-09-12 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-09-12 Cont ID  
Sent By adarroug Date 2006-09-12 Time 09:05 Rev Time 0.00
Received By adarroug Date 2006-09-12 Time 09:05 Sent To M
Notes
2006-09-12 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-06-19 Cont ID  
Sent By adarroug Date 2006-06-19 Time 15:44 Rev Time 0.00
Received By adarroug Date 2006-06-19 Time 15:44 Sent To P
Notes
2006-06-19 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-04-13 Cont ID  
Sent By adarroug Date 2006-04-13 Time 11:13 Rev Time 0.00
Received By adarroug Date 2006-04-13 Time 11:13 Sent To B
Notes
2006-04-13 00:00:00TO "ALANGE" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-03-31 Cont ID  
Sent By adarroug Date 2006-03-31 Time 15:14 Rev Time 0.00
Received By adarroug Date 2006-03-31 Time 15:14 Sent To E
Notes
2006-03-31 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-12-23 Cont ID  
Sent By adarroug Date 2005-12-23 Time 09:14 Rev Time 0.00
Received By adarroug Date 2005-12-23 Time 09:14 Sent To E
Notes
2005-12-23 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-01-23 Cont ID  
Sent By alange Date 2006-01-23 Time 11:11 Rev Time 0.00
Received By alange Date 2005-12-07 Time 10:30 Sent To  
Notes
2005-12-07 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-09-12 Cont ID  
Sent By tgordon Date 2006-09-12 Time 16:16 Rev Time 0.30
Received By tgordon Date 2006-09-12 Time 16:16 Sent To  
Notes
2006-09-12 00:00:00REVISION TO MECH. PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-04-03 Cont ID  
Sent By tgordon Date 2006-04-03 Time 08:50 Rev Time 0.30
Received By tgordon Date 2006-04-03 Time 08:50 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-12-27 Cont ID  
Sent By dpalmer Date 2005-12-23 Time 14:08 Rev Time 0.45
Received By tgordon Date 2005-12-27 Time 16:24 Sent To P
Notes
2005-12-27 00:00:00*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE ON
 FORM 600A-04 (2004) PER FBC 13-600.3.A .
  
 2) ENERGY CALCULATIONS NEED TO BE SIGNED
 BY OWNER/AGENT.
  
 3) MECHANICAL PLANS MUST BEAR THE NAME
 AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN, PER FBC 104.2.1 .
  
 4) NEED TO SUPPLY COMBUSTION AIR FOR GAS
 WATER HEATER IN GARAGE, PER 2004 FBC/R
 M1701.1, (DID NOT FIND ON ARCHITECTS
 PLANS).
  
 5) NEED DETAILED MANUFACTURE'S
 SPECIFICATION'S AND INSTALLATION
 INSTRUCTIONS FOR FIRE PLACE.
  
 6) NEED COMBUSTION AIR CAL,S. FOR FIRE
 PLACE.
  
 7) GRILL IN COVERED PORCH REQUIRES AN
 APPROVED EXHAUST HOOD, PER FBC/R M1504.1
  
 8) T-STAT #1 NOT SHOWING ON PLANS.
  
 9) RETURN AIR DUCT AND GRILL TO LIBRARY
 NOT SIZED.
  
 10) RETURN AIR GRILL FOR AHU #2 APPEARS
 TO BE TO SMALL FOR A FIVE TON UNIT.
  
 11) THE GENERATOR WILL REQUIRE A SEPARET
 PERMIT.
  
 12) NEED TO FILE A NOTICE OF
 COMMENCEMENT, PER F.S. 713.13 .
  
 13) NEED TO UP DATE WORKERS COMP. INSUR.
 INFO.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  
  
  
 .
  
  
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-09-15 Cont ID  
Sent By mperson Date 2006-09-15 Time 11:07 Rev Time 0.33
Received By mperson Date 2006-09-15 Time 11:07 Sent To PC
Notes
2006-09-15 00:00:00REVISION: AS BUILT SANITARY ISOMETRIC
 RISER DIAGRAM.

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-06-26 Cont ID  
Sent By mperson Date 2006-06-26 Time 15:41 Rev Time 0.45
Received By mperson Date 2006-06-26 Time 15:41 Sent To PC
Notes
2006-06-26 00:00:00******REVISION DENIED******
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLAN REVIEW FOR THE PLUMBING
 REVISION:
  
 1.PER FBC-2004, CHAPTER 1,SECTION
 106.3.5.4 RESIDENTIAL (ONE AND TWO
 FAMILY) SUBMIT A PLUMBING SANITARY
 ISOMETRIC RISER DIAGRAM CLEARLY
 INDICATING ALL FIXTURES, WASTE, VENTS,
 TRAPS WITH SIZES, AND CLEANOUT
 LOCATIONS. PLEASE SEE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
 2.PLEASE SEE THE CORRECTED DRAWING IN
 RED INK INDICATING ALL CLEANOUTS ON THE
 SANITARY ISOMETRIC RISER DIAGRAM PER THE
 FOLLOWING.
 (A) 708.3.4 BASE OF STACK. A CLEANOUT
 SHALL BE PROVIDED AT THE BASE OF EACH
 WASTE OR SOIL STACK
 (B) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM) PLEASE
 NOTE THE WASHING MACHINE CLEANOUT SIZE
 AS 3".
 (C) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS. PLEASE NOTE
 THE WASHING MACHINE CLEANOUT LOCATION AS
 48" ABOVE FINNISH FLOOR.
 3. PLEASE INDICATE ON THE SANITARY RISER
 DIAGRAM THE AUTOMATIC AIR VENTS (SV) AND
 THE SIZE AND "VENT THROUGH ROOF" (VTR)
 LOCATIONS PER THE CORRECTED DRAWING IN
 RED INK.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-04-03 Cont ID  
Sent By jleech Date 2006-04-03 Time 10:25 Rev Time 0.00
Received By jleech Date 2006-04-03 Time 10:25 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-12-28 Cont ID  
Sent By jleech Date 2005-12-28 Time 15:11 Rev Time 0.50
Received By jleech Date 2005-12-28 Time 15:11 Sent To B
Notes
2005-12-28 00:00:00DENIED;
 1.W/M DRAIN TO BE BELOW L.T. AND A C.O.
 REQUIRED AT 48" AFF.
 2.BIDET MISSING FROM MASTER BATHROOM.
 3.SHOWER MISSING FROM CABANA BATH.
 SEE RISER DIAGRAM ON SET OF PLANS
 MARKED IN RED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status P Date 2005-12-21 Cont ID  
Sent By mmclean Date 2005-12-21 Time 16:36 Rev Time 0.00
Received By mmclean Date 2005-12-21 Time 16:36 Sent To I
Notes
2005-12-21 00:00:00MUST PULL A SEPERATE PERMIT FOR
 POOL/SPA/DECK