Plan Review Details - Permit 05120057
Plan Review Stops For Permit 05120057
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-02-07 Cont ID  
Sent By kconrad Date 2006-02-07 Time 11:06 Rev Time 0.00
Received By kconrad Date 2006-02-06 Time 18:58 Sent To  
Notes
2006-02-07 00:00:001)SHEET A-1 INDICATES FLOOR PLAN FOR
 BARNIES:SHOULD REFLECT SALES OFFICES.
  
 2)CONSTRUCTION SHALL COMPLY WITH THE
 2004 FLORIDA BUILDING CODE/EXISTING
 BUILDING CODE/LEVEL 2 ALTERATIONS.
  
 3)INTERIOR FINISHES SHALL COMPLY WITH
 FBC SECTION/TABLE 803.5-C AND SHALL MEET
 THE CLASS C FLAMESPREAD CRITERIA.ALL
 CARPETING SHALL COMPLY WITH THE RADIANT
 FLUX REQUIREMENTS.
  
 B)THE SUSPENDED ACOUSTICAL CEILING
 SHALL BE INSTALLED IN ACCORDANCE WITH
 THE PROVISIONS OF ASTM635/636.
  
 4)MEANS OF EGRESS SHALL COMPLY WITH FBC
 SECTION 812.
  
 5)ACCESSIBILITY SHALL COMPLY WITH
 CHAPTER 11 OF THE FLORIDA BUILDING CODE.
  
  
  
 ANY EXISTING WALL/CEILING PENETRATION
 ARE REQUIRED TO BE FIRE-STOPPED TO
 MAINTAIN THE APPLICABLE RATING OF THE
 ASSEMBLY.SEE EXISTING BUILDING CODE
 SECTION 812.3.1.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-02-06 Cont ID  
Sent By jleahy Date 2006-02-06 Time 15:56 Rev Time 0.30
Received By jleahy Date 2006-02-06 Time 15:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-02-03 Cont ID  
Sent By jleahy Date 2006-02-03 Time 10:35 Rev Time 0.30
Received By jleahy Date 2006-02-03 Time 10:35 Sent To  
Notes
2006-02-03 00:00:00NEED PANEL SCHEDULES BEFORE FINAL.
  
 ALSO NEED SUITE NUMBER.
  
 JAKE LEAHY

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-12-27 Cont ID  
Sent By dpalmer Date 2005-12-27 Time 20:21 Rev Time 0.00
Received By dpalmer Date 2005-12-27 Time 20:17 Sent To  
Notes
2005-12-27 00:00:00****** UNSAT ******
  
 1)NOTE: PLEASE PLACE A NOTE ON PLANS
 WHICH STATES A MIN OF 1FT CANDLE SHALL
 BE MEASURED AT ALL WALKING SURFACES FOR
 MEANS OF EGRESS PER LS 101 7.9.2.1
  
 2)NOTE: PLEASE SEE NO PANEL SCHEDULE(S)
 WERE SUBMITTED TO CORRELATE WITH NEW
 CIRCUITING PLACED ON PLANS.
 215.5
 PLEASE SUBMIT.
  
 3)NOTE: PLEASE SPECIFY SUITE/UNIT # ON
 PLANS AND ON PERMIT APPLICATION
 SUBMITTED.
  
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS FROM
 SETS AND ONLY INSERT NEW REVISED SHEETS
 INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-02-03 Cont ID  
Sent By mwennerg Date 2006-02-03 Time 14:12 Rev Time 0.00
Received By mwennerg Date 2006-02-03 Time 14:12 Sent To  
Notes
2006-02-03 00:00:00******PASSED******
  
 1) PLEASE NOTE THAT DRAWINGS INDICATE
 THAT FIRE SPRINKLER HEAD RELOCATIONS ARE
 TO OCCUR, HOWEVER A MEETING HELD ON
 2/3/06 REVEALED THAT NO SUCH WORK WILL
 COMMENCE. NO WORK ON FIRE PROTECTION
 SYSTEM IS ALLOWED WITHOUT SEPARATE SHOP
 DRAWINGS AND PERMIT.
  
  
 MIKE WENNERGREN, CAPTAIN
 WPBFR (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-12-30 Cont ID  
Sent By mwennerg Date 2005-12-30 Time 14:43 Rev Time 0.00
Received By mwennerg Date 2005-12-30 Time 14:43 Sent To  
Notes
2005-12-30 00:00:00******DENIED******
  
 1) SHT E101 ILLUSTRATES A SINGLE MARKED
 EXIT. THE CRITERIA IN ACCORDANCE WITH
 NFPA 101, 2003 EDITION SEC. 38.2.4.3 (1)
 HAS NOT BEEN MET, RENDERING THIS
 ARRANGEMENT UNACCEPTABLE.
  
 2) SEPARATE SHOP DRAWINGS AND PERMITS
 REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL.
  
 3) PLEASE INDICATE THE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILING IN
 TERMS OF CLASS A,B, OR C.
  
 4) 2A-10B,C RATED FIRE EXTINGUISHERS
 SHALL BE MOUNTED AT DISTANCE TO SATISFY
 75' TRAVEL DISTANCE REQUIREMENT.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-02-15 Cont ID  
Sent By adarroug Date 2006-02-15 Time 17:11 Rev Time 0.00
Received By adarroug Date 2006-02-15 Time 17:11 Sent To B
Notes
2006-02-15 00:00:00TO "KCONRAD" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-02-06 Cont ID  
Sent By ptjomsto Date 2006-02-06 Time 12:17 Rev Time 0.00
Received By ptjomsto Date 2006-02-06 Time 12:17 Sent To  
Notes
2006-02-06 00:00:001ST RESBUB GIVEN TO DEWEY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-02-07 Cont ID  
Sent By kconrad Date 2006-02-07 Time 11:40 Rev Time 0.00
Received By kconrad Date 2005-12-06 Time 09:07 Sent To  
Notes
2005-12-27 00:00:00TO "COMM" BD#22
2005-12-06 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-01-30 Cont ID  
Sent By hmoser Date 2006-01-30 Time 13:32 Rev Time 0.00
Received By hmoser Date 2006-01-30 Time 13:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-02-07 Cont ID  
Sent By kconrad Date 2006-02-07 Time 11:40 Rev Time 0.00
Received By kconrad Date 2006-02-07 Time 11:40 Sent To  
Notes
***NONE***