| Plan Review Stops For Permit 05120057 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2006-02-07 |
|
|
Cont ID |
|
| Sent By |
kconrad |
Date |
2006-02-07 |
Time |
11:06 |
Rev Time |
0.00 |
| Received By |
kconrad |
Date |
2006-02-06 |
Time |
18:58 |
Sent To |
|
|
| Notes |
| 2006-02-07 00:00:00 | 1)SHEET A-1 INDICATES FLOOR PLAN FOR | | | BARNIES:SHOULD REFLECT SALES OFFICES. | | | | | | 2)CONSTRUCTION SHALL COMPLY WITH THE | | | 2004 FLORIDA BUILDING CODE/EXISTING | | | BUILDING CODE/LEVEL 2 ALTERATIONS. | | | | | | 3)INTERIOR FINISHES SHALL COMPLY WITH | | | FBC SECTION/TABLE 803.5-C AND SHALL MEET | | | THE CLASS C FLAMESPREAD CRITERIA.ALL | | | CARPETING SHALL COMPLY WITH THE RADIANT | | | FLUX REQUIREMENTS. | | | | | | B)THE SUSPENDED ACOUSTICAL CEILING | | | SHALL BE INSTALLED IN ACCORDANCE WITH | | | THE PROVISIONS OF ASTM635/636. | | | | | | 4)MEANS OF EGRESS SHALL COMPLY WITH FBC | | | SECTION 812. | | | | | | 5)ACCESSIBILITY SHALL COMPLY WITH | | | CHAPTER 11 OF THE FLORIDA BUILDING CODE. | | | | | | | | | | | | ANY EXISTING WALL/CEILING PENETRATION | | | ARE REQUIRED TO BE FIRE-STOPPED TO | | | MAINTAIN THE APPLICABLE RATING OF THE | | | ASSEMBLY.SEE EXISTING BUILDING CODE | | | SECTION 812.3.1. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2006-02-06 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2006-02-06 |
Time |
15:56 |
Rev Time |
0.30 |
| Received By |
jleahy |
Date |
2006-02-06 |
Time |
15:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2006-02-03 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2006-02-03 |
Time |
10:35 |
Rev Time |
0.30 |
| Received By |
jleahy |
Date |
2006-02-03 |
Time |
10:35 |
Sent To |
|
|
| Notes |
| 2006-02-03 00:00:00 | NEED PANEL SCHEDULES BEFORE FINAL. | | | | | | ALSO NEED SUITE NUMBER. | | | | | | JAKE LEAHY |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-12-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-12-27 |
Time |
20:21 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2005-12-27 |
Time |
20:17 |
Sent To |
|
|
| Notes |
| 2005-12-27 00:00:00 | ****** UNSAT ****** | | | | | | 1)NOTE: PLEASE PLACE A NOTE ON PLANS | | | WHICH STATES A MIN OF 1FT CANDLE SHALL | | | BE MEASURED AT ALL WALKING SURFACES FOR | | | MEANS OF EGRESS PER LS 101 7.9.2.1 | | | | | | 2)NOTE: PLEASE SEE NO PANEL SCHEDULE(S) | | | WERE SUBMITTED TO CORRELATE WITH NEW | | | CIRCUITING PLACED ON PLANS. | | | 215.5 | | | PLEASE SUBMIT. | | | | | | 3)NOTE: PLEASE SPECIFY SUITE/UNIT # ON | | | PLANS AND ON PERMIT APPLICATION | | | SUBMITTED. | | | | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS FROM | | | SETS AND ONLY INSERT NEW REVISED SHEETS | | | INTO COMPLETE SETS FOR REVIEW AND | | | STAMPING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2006-02-03 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-02-03 |
Time |
14:12 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-02-03 |
Time |
14:12 |
Sent To |
|
|
| Notes |
| 2006-02-03 00:00:00 | ******PASSED****** | | | | | | 1) PLEASE NOTE THAT DRAWINGS INDICATE | | | THAT FIRE SPRINKLER HEAD RELOCATIONS ARE | | | TO OCCUR, HOWEVER A MEETING HELD ON | | | 2/3/06 REVEALED THAT NO SUCH WORK WILL | | | COMMENCE. NO WORK ON FIRE PROTECTION | | | SYSTEM IS ALLOWED WITHOUT SEPARATE SHOP | | | DRAWINGS AND PERMIT. | | | | | | | | | MIKE WENNERGREN, CAPTAIN | | | WPBFR (561) 805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2005-12-30 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-12-30 |
Time |
14:43 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-12-30 |
Time |
14:43 |
Sent To |
|
|
| Notes |
| 2005-12-30 00:00:00 | ******DENIED****** | | | | | | 1) SHT E101 ILLUSTRATES A SINGLE MARKED | | | EXIT. THE CRITERIA IN ACCORDANCE WITH | | | NFPA 101, 2003 EDITION SEC. 38.2.4.3 (1) | | | HAS NOT BEEN MET, RENDERING THIS | | | ARRANGEMENT UNACCEPTABLE. | | | | | | 2) SEPARATE SHOP DRAWINGS AND PERMITS | | | REQUIRED FOR FIRE SPRINKLER AND FIRE | | | ALARM REMODEL. | | | | | | 3) PLEASE INDICATE THE INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILING IN | | | TERMS OF CLASS A,B, OR C. | | | | | | 4) 2A-10B,C RATED FIRE EXTINGUISHERS | | | SHALL BE MOUNTED AT DISTANCE TO SATISFY | | | 75' TRAVEL DISTANCE REQUIREMENT. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-02-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-02-15 |
Time |
17:11 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-02-15 |
Time |
17:11 |
Sent To |
B |
|
| Notes |
| 2006-02-15 00:00:00 | TO "KCONRAD" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-02-06 |
|
|
Cont ID |
|
| Sent By |
ptjomsto |
Date |
2006-02-06 |
Time |
12:17 |
Rev Time |
0.00 |
| Received By |
ptjomsto |
Date |
2006-02-06 |
Time |
12:17 |
Sent To |
|
|
| Notes |
| 2006-02-06 00:00:00 | 1ST RESBUB GIVEN TO DEWEY |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-02-07 |
|
|
Cont ID |
|
| Sent By |
kconrad |
Date |
2006-02-07 |
Time |
11:40 |
Rev Time |
0.00 |
| Received By |
kconrad |
Date |
2005-12-06 |
Time |
09:07 |
Sent To |
|
|
| Notes |
| 2005-12-27 00:00:00 | TO "COMM" BD#22 | | 2005-12-06 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2006-01-30 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2006-01-30 |
Time |
13:32 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2006-01-30 |
Time |
13:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2006-02-07 |
|
|
Cont ID |
|
| Sent By |
kconrad |
Date |
2006-02-07 |
Time |
11:40 |
Rev Time |
0.00 |
| Received By |
kconrad |
Date |
2006-02-07 |
Time |
11:40 |
Sent To |
|
|
| Notes |
|
|