Plan Review Details - Permit 05120043
Plan Review Stops For Permit 05120043
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-12-15 Cont ID  
Sent By mjacobs Date 2005-12-15 Time 08:39 Rev Time 2.00
Received By mjacobs Date 2005-12-15 Time 07:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-04-11 Cont ID  
Sent By jleahy Date 2006-04-11 Time 07:09 Rev Time 0.00
Received By jleahy Date 2006-04-11 Time 07:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-12-06 Cont ID  
Sent By jleahy Date 2005-12-06 Time 10:52 Rev Time 0.30
Received By jleahy Date 2005-12-06 Time 10:51 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-12-15 Cont ID  
Sent By mwennerg Date 2005-12-15 Time 14:26 Rev Time 0.00
Received By mwennerg Date 2005-12-15 Time 14:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-04-10 Cont ID  
Sent By adarroug Date 2006-04-10 Time 14:36 Rev Time 0.00
Received By adarroug Date 2006-04-10 Time 14:36 Sent To  
Notes
2006-04-10 00:00:00TO "BOB"#9

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-12-15 Cont ID  
Sent By mwennerg Date 2005-12-15 Time 14:30 Rev Time 0.00
Received By mwennerg Date 2005-12-02 Time 14:28 Sent To  
Notes
2005-12-05 00:00:00TO "BOB"#9
2005-12-02 00:00:00WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-04-11 Cont ID  
Sent By tgordon Date 2006-04-11 Time 10:52 Rev Time 0.45
Received By tgordon Date 2006-04-11 Time 10:52 Sent To  
Notes
2006-04-11 00:00:00*** PROVISO ***
  
 1) AS PER 2004 FBC(M) 602.2.1, MATERIALS
 EXPOSED WITHIN PLENUMS SHALL BE NON -
 COMBUSTIBLE OR SHALL HAVE A FLAME SPREAD
 INDEX OF NOT MORE THAN 25 AND SMOKE -
 DEVELOPED INDEX OF NOT MORE THAN 50 WHEN
 TESTED IN ACCORDANCE WITH ASTM E 84.
  
 2) PROVIDE RETURN AIR OPENINGS IN FIRE
 WALLS.
  
 3) AS PER 2004 FBC(M) 607.5.1 FIRE
 WALLS.
 DUCTS AND AIR TRANSFER OPENINGS
 PERMITTED IN FIRE WALLS IN ACCORDANCE
 WITH SECTION 705.11 OF THE FLORIDA
 BUILDING CODE, BUILDING SHALL BE
 PROTECTED WITH APPROVED FIRE DAMPERS
 INSTALLED IN ACCORDANCE WITH THEIR
 LISTING.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-12-15 Cont ID  
Sent By tgordon Date 2005-12-15 Time 10:55 Rev Time 0.30
Received By tgordon Date 2005-12-15 Time 10:55 Sent To FIRE
Notes
2005-12-15 00:00:00*** PROVISO ***
  
 1) AS PER 2004 FBC(M) 602.2.1, MATERIALS
 EXPOSED WITHIN PLENUMS SHALL BE NON -
 COMBUSTIBLE OR SHALL HAVE A FLAME SPREAD
 INDEX OF NOT MORE THAN 25 AND SMOKE -
 DEVELOPED INDEX OF NOT MORE THAN 50 WHEN
 TESTED IN ACCORDANCE WITH ASTM E 84.
  
 2) PROVIDE RETURN AIR OPENINGS IN FIRE
 WALLS.
  
 3) AS PER 2004 FBC(M) 607.5.1 FIRE
 WALLS.
 DUCTS AND AIR TRANSFER OPENINGS
 PERMITTED IN FIRE WALLS IN ACCORDANCE
 WITH SECTION 705.11 OF THE FLORIDA
 BUILDING CODE, BUILDING SHALL BE
 PROTECTED WITH APPROVED FIRE DAMPERS
 INSTALLED IN ACCORDANCE WITH THEIR
 LISTING.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729.
  
  
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-12-13 Cont ID  
Sent By jleech Date 2005-12-13 Time 07:30 Rev Time 0.00
Received By jleech Date 2005-12-13 Time 07:30 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy