Plan Review Details - Permit 05120031
Plan Review Stops For Permit 05120031
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-05-15 Cont ID  
Sent By alange Date 2006-05-15 Time 15:13 Rev Time 1.66
Received By alange Date 2006-05-15 Time 15:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-04-04 Cont ID  
Sent By alange Date 2006-04-04 Time 10:52 Rev Time 1.25
Received By alange Date 2006-04-04 Time 10:48 Sent To  
Notes
2006-04-04 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 9.ROYAL WALL ENGINEERING SHALL BE
 DESIGNED TO THE 2004 FBC.
  
 ANY QUESTIONS CALL ME
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-01-03 Cont ID  
Sent By alange Date 2006-01-03 Time 08:56 Rev Time 3.50
Received By alange Date 2006-01-03 Time 08:56 Sent To  
Notes
2006-01-03 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.SUBMIT ENERGY CALCS TO THE 2004
 FBC.
  
 4.SUBMIT TWO ORIGONAL SIGNED AND
 SEALED SURVEYS.
  
 5.SUBMIT PRODUCT APPROVALS FOR STRAPS
 AND TIE-DOWNS.
  
 6. ALL PRODUCT APPROVALS SUBMITTED SHALL
 HAVE THE FOLLOWING STATE PRODUCT
 APPROVAL ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 7.BASED ON SBCCI BUILDING VALUATION
 DATA THE PERMIT VALUATION HAS BEEN
 REVISED TO $254,072.
  
 8. R403.1.4 MINIMUM DEPTH .
 ALL EXTERIOR FOOTINGS SHALL BE PLACED AT
 LEAST 12 INCHES BELOW THE UNDISTURBED
 GROUND SURFACE.
  
 9. ROYAL WALL CONSTRUCTION PROCEDURE:
 1. ALL REQUIRED SUBMITTALS FOR SINGLE
 FAMILY STRUCTURES ALONG WITH ENGINEERED
 PLANS, SHOP DRAWINGS INCLUDING
 ENGINEERING CALCULATIONS.
 2. LETTER FROM A LICENSED THRESHOLD
 INSPECTOR STATING THAT AN INSPECTION
 WILL BE MADE AT THE MANUFACTURED SITE OF
 THE JOB SPECIFIC COMPONENTS TO VERIFY
 CONSTRUCTION COMPLIANCE OF THE
 COMPONENTS WITH THE ENGINEERED DESIGN.
  
 DURING CONSTRUCTION SUBMITTALS:
 1. CERTIFICATE OF COMPLIANCE AFFIDAVIT
 FROM THE THRESHOLD INSPECTOR THAT, TO
 THE BEST OF HIS/HER KNOWLEDGE AND
 BELIEF, THE OFF-SITE CONSTRUCTED
 COMPONENTS OUTLINED HEREIN AND INSPECTED
 UNDER HIS/HER AUTHORITY HAVE BEEN
 COMPLETED IN CONFORMANCE WITH THE
 APPROVED PLANS, SHOP DRAWINGS AND
 ENGINEERING.
  
 10.PLEASE DO NOT ATTACHE PRODUCT
 APPROVALS TO PLANS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-05-14 Cont ID  
Sent By dpalmer Date 2006-05-14 Time 08:57 Rev Time 0.00
Received By dpalmer Date 2006-05-14 Time 08:46 Sent To B
Notes
2006-05-14 00:00:00NEW PLANS ADDRESSING PREVIOUS "PROVISO",
 SUBMITTED. PLANS ARE OK AND STAMPED.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-03-23 Cont ID  
Sent By dpalmer Date 2006-03-23 Time 20:20 Rev Time 0.00
Received By dpalmer Date 2006-03-23 Time 20:02 Sent To M
Notes
2006-03-23 00:00:00********** PROVISO ************
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW AND SOME NEW NOTES, DUE TO
 CHANGES IN PLANS.
  
 1) NOTE: PLEASE SEE 424.3B FOR MIN OCP
 FOR AHU #2. SHOWS 10KW HEAT WITH 45A
 OCP. 60A MIN.
  
 2)NOTE: PLEASE SEE AN "EQUIPMENT
 GROUNDING CONDUCTOR" IS NOW BEING SHOWN
 FROM METER TO MAIN CIRCUIT BRKR PANEL.
 THIS PANEL IS FIRST MEANS OF DISCONNECT
 AND THE EQUIP GRND IS ONLY INSTALLED
 AFTER THE FIRST MEANS OF DISCONNECT.
 250.6,250.24B
  
 3) NOTE: PLEASE SEE LOCATION OF GFI ON
 PENINSULAR SHALL BE VERFIED, AS LOCATION
 DOES NOT SEEM TO MEET 210.52C2, (6" OF
 COUNTER OVERHANG).
  
 4)NOTE: PLANS ARE TO REFERENCE THE 2002
 NFPA-70.
  
 **************************************
 PLEASE SEE THIS "PROVISO " IS TO REVISE
 PLANS , ALONG WITH ANY OTHER REVISIONS
 BEFORE ROUGH ELECTRICAL INSPECTION IS
 CALLED IN.
 IF THERE ARE ANY QUESTIONS , PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 PLEASE SEE "PROVISO", IF PLANS COME BACK
 FOR ANY OTHER COMMENTS FROM OTHER
 TRADES, PLEASE BE SURE TO MAKE
 CORRECTIONS TO "PROVISO" AT THAT TIME.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-12-22 Cont ID  
Sent By dpalmer Date 2005-12-22 Time 16:35 Rev Time 0.00
Received By dpalmer Date 2005-12-22 Time 16:26 Sent To M
Notes
2005-12-22 00:00:00**** UNSAT ****
  
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2)NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52. PLEASE SEE REDLINED PLANS FOR
 LOCATIONS/
 PLEASE ALSO VERIFY THE "LOFT" AREA, AS
 IF THE IS CALLED A LOFT/HABITABLE RM,
 THEN TWO ADDITIONAL RECEPTS WOULD BE
 REQUIRED(SEE REDLINES) IF A HALL, THEN
 THIS WOULD BE OK.
  
 3)NOTE: PLEASE PROVIDE ONE ADDITIONAL
 SD AT THIS SAME "LOFT" AREA OUTSIDE
 BEDRMS.
 NFPA-72 11.5.1.1
  
 4)NOTE: PLEASE LIST THE MIN REQUIRED
 DEDICATED BATH(S) CIRCUIT(S) PER
 210.11C3
 PLEASE SEE THIS MUST BE 20A AND #12.
 PLEASE SEE BATH RM BETWEEN BEDRMS 3 AND
 4, WHICH SEEMS TO SHOWS GFI, HOWEVER
 THIS MUST BE WITHIN 3' OF SINK'S EDGE.
 SCALE PUTS THIS CLOSE, PLEASE VERIFY.
  
 5)NOTE: PLEASE MAKE REFERENCE TO THE
 CURRENT NEC (2002) ON PLANS.
  
 6)NOTE: PLEASE CORRLELATE A/C HEAT
 STRIPS ON ELECTRICAL PLANS AND A/C
 SHEETS.
 PLEASE SEE BOTH UNITS SHOW 10KW HEAT ON
 MECHANICAL, HOWEVER ONE IS SHOWN AS 5KW
 ON PANEL SCHEDUL, YET OCP AND AWG IS
 SHOWN FOR 10KW.
  
 7)NOTE: PLEASE VERIFY LOAD CALCS,
 PERCENTAGES AND KVA IS SHOWN, HOWEVER
 THESE DO NOT DETAIL WHAT THEY ARE FROM.
 220.30, 215.5
  
 8) NOTE: PLEASE VERIFY THE RECEPT SHOWN
 ON PENINSULAR, AS NEITHER IS SHOWN AS
 GFI?
 PLEASE VERIFY AS A MIN OF ONE IS
 REQUIRED PER 210.52C3, AND GFI PER
 210.8A6
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 TWO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 ONE SET OF OLD/VOIDED SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-05-23 Cont ID  
Sent By adarroug Date 2006-05-23 Time 11:19 Rev Time 0.00
Received By adarroug Date 2006-05-23 Time 11:19 Sent To M
Notes
2006-05-23 00:00:00TO "M' BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-05-02 Cont ID  
Sent By adarroug Date 2006-05-02 Time 16:56 Rev Time 0.00
Received By adarroug Date 2006-05-02 Time 16:56 Sent To Z
Notes
2006-05-02 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-03-21 Cont ID  
Sent By dpalmer Date 2006-03-21 Time 16:56 Rev Time 0.00
Received By dpalmer Date 2006-03-21 Time 16:56 Sent To E
Notes
2006-03-21 00:00:00TO DP'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-12-22 Cont ID  
Sent By adarroug Date 2005-12-22 Time 09:16 Rev Time 0.00
Received By adarroug Date 2005-12-22 Time 09:16 Sent To E
Notes
2005-12-22 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-01-03 Cont ID  
Sent By alange Date 2006-01-03 Time 09:02 Rev Time 0.00
Received By alange Date 2005-12-05 Time 09:15 Sent To  
Notes
2005-12-05 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-05-23 Cont ID  
Sent By tgordon Date 2006-05-23 Time 14:06 Rev Time 0.45
Received By tgordon Date 2006-05-23 Time 14:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2006-05-10 Cont ID  
Sent By tgordon Date 2006-05-10 Time 15:50 Rev Time 0.30
Received By tgordon Date 2006-05-10 Time 15:50 Sent To E
Notes
2006-05-10 00:00:00*** DENIED ***
 1) AS NOTED IN LAST REVIEW 3-27-06 #2,
 MANUAL J CALCULATIONS FOR SYSTEM TWO
 ARE CALLING FOR 17,566 SENSIBLE BTU'S,
 AND THE MECHANICAL PLANS FOR SYSTEM TWO
 ARE CALLING FOR 26,400 SENSIBLE BTU'S.
 THE PLANS CAN ONLY CALL FOR 20% MORE
 THAN THE MANUAL J CAL'S. PER 2004 FBC
 13-607.1.ABC.1.1, PLEASE CORRECT.
  
 2) MANUAL J CAL'S FOR SYSTEM ONE ARE
 CALLING FOR 13,731 SENSIBLE BTU'S, AND
 THE MECHANICAL PLANS FOR SYSTEM ONEARE
 CALLING FOR 18,000 SENSIBLE BTU'S, AGAIN
 THE PLANS CAN ONLY CALL FOR 20% MORE
 THAN THE MANUAL J CAL'S (THE A/C SYSTEMS
 ON THE PLANS ARE TO LARGE FOR THE HOUSE
 ACCORDING TO YOUR MANUAL J CAL'S) PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-03-27 Cont ID  
Sent By tgordon Date 2006-03-27 Time 09:12 Rev Time 0.45
Received By tgordon Date 2006-03-27 Time 09:12 Sent To P
Notes
2006-03-27 00:00:00*** DENIED ***
 1) ENERGY CALCULATIONS ARE CALLING FOR
 56,000 TOTAL BTU'S, AND THE MECHANICAL
 PLANS ARE CALLING FOR 60,400 TOTAL
 BTU'S. THE PLANS CAN NOT CALL FOR MORE
 TOTAL BTU'S THAN THE ENERGY CAL'S,
 PLEASE CORRECT.
  
 2) MANUAL J CALCULATIONS FOR SYSTEM TWO
 ARE CALLING FOR 17,566 SENSIBLE BTU'S,
 AND THE MECHANICAL PLANS FOR SYSTEM TWO
 ARE CALLING FOR 26,400 SENSIBLE BTU'S.
 THE PLANS CAN ONLY CALL FOR 20% MORE
 THAN THE MANUAL J CAL'S. PER 2004 FBC
 13-607.1.ABC.1.1, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-12-23 Cont ID  
Sent By tgordon Date 2005-12-23 Time 09:42 Rev Time 1.30
Received By tgordon Date 2005-12-23 Time 09:42 Sent To P
Notes
2005-12-23 00:00:00*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE ON
 FORM 600A-04 (2004) PER FBC 13-600.3.A .
  
 2) BOTH AHU'S ARE LABELED AS AHU #2.
  
 3) PLEASE SHOW LOCATION OF EACH A/C
 DRAIN LINE TERMINATION.
  
 4) MASTER SUITE RETURN AIR TRANSFER DUCT
 IS TO SMALL (12" SUPPLY REQUIRES 15"
 RETURN). PLEASE SEE NOTE #5.
  
 5) BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 6) (INFORMATIONAL) PLEASE SEE MANUAL J
 PAGE #3 TO SEE IF A 2 1/2 TON FOR A/C
 UNIT #2 WOULD BE MORE COMPLIANT WITH
 2004 FBC 13-607.1.ABC.1.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-03-30 Cont ID  
Sent By jleech Date 2006-03-30 Time 07:39 Rev Time 0.00
Received By jleech Date 2006-03-30 Time 07:39 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-12-23 Cont ID  
Sent By jleech Date 2005-12-23 Time 12:09 Rev Time 0.75
Received By jleech Date 2005-12-23 Time 12:09 Sent To B
Notes
2005-12-23 00:00:00DENIED;
 1.W/M TO DISCHARGE BELOW L/T, AND A C.O.
 TO BE INSTALLED AT 48" AFF.
 2.W/M BRANCH DRAIN SHALL BE 3" TO TO
 SAN. TEE.
 3.1/2 BATH NOT THE SAME LAY OUT AS FLOOR
 PLAN.
 4.SAOARATE RISERS ARE REQUIRED FOR
 SECOND FLOOR BATHROOMS. CAN NOT RUN INTO
 VENT STACKS FOR FIRST FLOOR FIXTURES.
 5. SHEET A-1 SHOWS 2 L/T'S RISER DIAGRAM
 SHOWS ONE, PLEASE CLARIFY.
 6.SECOND FLOOR BATHROOM #1 RISER DIAGRAM
 SHOWS 2 LAV'S FLOOR PLAN SHOWS ONE.
 PLEASE CLARIFY.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status P Date 2005-12-20 Cont ID  
Sent By mmclean Date 2005-12-20 Time 15:01 Rev Time 0.00
Received By mmclean Date 2005-12-20 Time 15:01 Sent To I
Notes
2006-03-23 00:00:00*** PLEASE SEE "PROVISO", IF PLANS COME
 BACK FOR ANY OTHER COMMENTS, PLEASE
 ADDRESS "PROVISO" COMMENTS AT THAT TIME.