Plan Review Details - Permit 05111159
Plan Review Stops For Permit 05111159
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-09-19 Cont ID  
Sent By jwitmer Date 2006-09-19 Time 14:54 Rev Time 1.22
Received By jwitmer Date 2006-09-19 Time 14:54 Sent To  
Notes
2006-09-19 00:00:00PERMIT: 05111159
 ADD: 1600 OKEECHOBEE RD
 CONT: THORTON & THORTON INC
 TEL: (321)229-3406
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 4TH REVIEW/ 3RD FAILURE
 ACTION: DENIED
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) SHEETS SD-3 & SD-4 81/2X11 HAVE
 COPIES OF A SIGNATURE NOT THE ORIGINAL
 SIGNATURE! SEE 481.221.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-05-31 Cont ID  
Sent By jwitmer Date 2006-05-31 Time 13:33 Rev Time 2.22
Received By jwitmer Date 2006-05-31 Time 13:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-04-06 Cont ID  
Sent By jwitmer Date 2006-04-06 Time 09:27 Rev Time 2.22
Received By jwitmer Date 2006-04-06 Time 09:10 Sent To  
Notes
2006-04-06 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05111159
 ADD: 1600 OKEECHOBEE RD
 CONT: THORTON & THORTON INC
 TEL: (321)229-3406
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2A) COMPLIED
 2B) COMPLIED
 2C) COMPLIED
 2D) COMPLIED
 2E)FROM PREVIOUS REVIEW, IF AN AUTOMATIC
 SPRINKLER SYSTEM ISPROVIDED, WHETHER
 THE SPRINKLER SYSTEM IS REQUIRED. IF THE
 FIRE SPRINKLER IS PROVIDED OR REQUIRED
 BY CODE THEN THE FIRE SPRINKLER PLANS
 SHALL BE INCLUDED IN THE BUILDING PERMIT
 PACKAGE BEFORE ISSUANCE OF THIS PERMIT.
 NOTE FIRE SPRINKLER PERMIT AND FIRE
 SPRINKLER PLANS ARE REQUIRED SEPERATELY.
 2F) COMPLIED AT THIS TIME.
  
 3)FROM THE PREVIOUS REVIEW, 3) PROVIDE A
 CURRENT SURVEY OF THE BUILDING,(2004
 FBC) 106.1.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE & EXTENT OF THE WORK
 PROPOSED & SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND REVELENT LAWS, ORDINANCES, AND RULES
 AND REGULATIONS AS DETERMINED BY THE
 BUILDING OFFICIAL.
  
 4)FROM THE PREVIOUS REVIEW, NOT
 ADDRESSED IN RESPONCE SHEET.
 IT APPEARS THAT THE SO CALLED MEZANINE
 NO LONGER MEETS THE DEFINITION SINCE THE
 AREA BELOW THE MEZANINE CAN'T BE FIGURED
 INTO THE CLEAR FLOOR AREA.
  
 505.2 AREA LIMITATION.
 THE AGGREGATE AREA OF A MEZZANINE OR
 MEZZANINES WITHIN A ROOM SHALL NOT
 EXCEED ONE-THIRD OF THE AREA OF THAT
 ROOM OR SPACE IN WHICH THEY ARE LOCATED.
 THE ENCLOSED PORTIONS OF ROOMS SHALL NOT
 BE INCLUDED IN A DETERMINATION OF THE
 SIZE OF THE ROOM IN WHICH THE MEZZANINE
 IS LOCATED. IN DETERMINING THE ALLOWABLE
 MEZZANINE AREA, THE AREA OF THE
 MEZZANINE SHALL NOT BE INCLUDED IN THE
 AREA OF THE ROOM.
  
 5) COMPLIED
  
 6) COMPLIED
  
 7A) FROM THE PREVIOUS REVIEW,
 7) PROVIDE EGRESS PATHWAYS FOR THE
 WAREHOUSE AREAS,116 & 117. THE PLAN
 SHOWS A EGRESS AISLE IN 116 TO A EXIT
 AND BACK INTO THE OFFICE OCCUPANCY. NOTE
 THE OCCUPANTS OF THE OFFICE SHOULD NOT
 BE TAKEN INTO THE WAREHOUSE STORAGE
 OCCUPANCY AS PART OF AN EGRESS UNLESS IT
 IS IN A RATED CORRIDOR! THE EXIT
 LIGHTINTHE OFFICE AREA THATLEADS INTO
 THE STORAGE AREA SHOULD BE REMOVED
 UNLESS A RATED CORRIDOR.
 1032.4.1
 IN GROUP S1 STORAGE, OCCUPANCIES COMMON
 PATH OF TRAVEL SHALL NOT EXCEED 50 FEET
 (15 M).
 EXCEPTION: COMMON PATHS OF TRAVEL SHALL
 NOT EXCEED 100 FEET (30 M) IN BUILDINGS
 PROTECTED BY AN APPROVED AUTOMATIC
 SPRINKLER SYSTEM.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-02-08 Cont ID  
Sent By jwitmer Date 2006-02-08 Time 07:22 Rev Time 2.22
Received By jwitmer Date 2006-02-08 Time 07:22 Sent To  
Notes
2006-02-08 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05111159
 ADD: 1600 OKEECHOBEE RD
 CONT: THORTON & THORTON INC
 TEL: (321)229-3406
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) 110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 3) PROVIDE ACURRENT SURVEY OF THE
 BUILDING,(2004 FBC) 106.1.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE & EXTENT OF THE WORK
 PROPOSED & SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND REVELENT LAWS, ORDINANCES, AND RULES
 AND REGULATIONS AS DETERMINED BY THE
 BUILDING OFFICIAL.
  
 4) IT APPEARS THAT THE SO CALLED
 MEZANINE NO LONGER MEETS THE DEFINITION
 SINCE THE AREA BELOW THE MEZANINE CAN'T
 BE FIGURED INTO THE CLEAR FLOOR AREA.
  
 505.2 AREA LIMITATION.
 THE AGGREGATE AREA OF A MEZZANINE OR
 MEZZANINES WITHIN A ROOM SHALL NOT
 EXCEED ONE-THIRD OF THE AREA OF THAT
 ROOM OR SPACE IN WHICH THEY ARE LOCATED.
 THE ENCLOSED PORTIONS OF ROOMS SHALL NOT
 BE INCLUDED IN A DETERMINATION OF THE
 SIZE OF THE ROOM IN WHICH THE MEZZANINE
 IS LOCATED. IN DETERMINING THE ALLOWABLE
 MEZZANINE AREA, THE AREA OF THE
 MEZZANINE SHALL NOT BE INCLUDED IN THE
 AREA OF THE ROOM.
 THE PLANS DO NOT INDICATE WHAT TYPE
 OF OCCUPANCY THE ROOM WILL BE AT THE
 HEAD OF THE STAIRS, MAY REQUIRE A SECOND
 MEANS OF EGRESS, ( ENCLOSED STAIR)?
  
 5) PLANS DO NOT PROVIDE WHAT TYPE OF
 MATERIAL WILL BE STORED IN WAREHOUSE
 116 OR 117? THIS MAY REQUIRE EITHER A 1
 HR RATED WALL BETWEEN OFFICE AND
 WAREHOUSE ONCE DECLARE WHAT TYPE OF
 MATERIALS ARE TO BE STORED?S1 VS S2?
  
 6) PLANS ALSO INDICATE BATTERY CHARGER
 AND GUARDRAIL? EXPLAIN THE USAGE, AND
 AMOUNT OF BATTERIES?
  
 7) PROVIDE EGRESS PATHWAYS FOR THE
 WAREHOUSE AREAS, E1.1 DOES NOT INDICATE
 EXIT LIGHTS IN WAREHOUSE AREA.1016.1.1
 ILLUMINATION OF MEANS OF EGRESS SHALL BE
 PROVIDED IN ACCORDANCE WITH THIS SECTION
 FOR EVERY BUILDING AND STRUCTURE.FOR
 THE PURPOSES OF THIS REQUIREMENT, EXIT
 ACCESS SHALL INCLUDE ONLY DESIGNATED
 STAIRS, AISLES, CORRIDORS, RAMPS,
 ESCALATORS AND PASSAGEWAYS LEADING TO AN
 EXIT.FOR THE PURPOSES OF THIS
 REQUIREMENT, EXIT DISCHARGE SHALL
 INCLUDE ONLY DESIGNATED STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCALATORS,WALKWAYS
 AND EXIT PASSAGEWAYS LEADING TO A PUBLIC
 WAY.
  
 8) SHEET E4.1 MISSING SEAL ON ONE SET OF
 PLANS.PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2006-10-17 Cont ID  
Sent By dpalmer Date 2006-10-17 Time 18:57 Rev Time 0.00
Received By dpalmer Date 2006-10-17 Time 18:51 Sent To  
Notes
2006-10-17 18:58:42REV FOR LAYOUT OF RECEPTS, AND CORRECTED ELECTRICAL
 SERVICE EQUIPMENT LAYOUT.

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2006-09-24 Cont ID  
Sent By dpalmer Date 2006-09-24 Time 09:28 Rev Time 0.00
Received By dpalmer Date 2006-09-24 Time 09:15 Sent To PC
Notes
2006-09-24 00:00:00*** STILL NEED TO REVISE E1.1 TO
 CORRELATE WITH THE REVISED ELECTRICAL
 RISER DIAGRAM.
 THIS RISER OK.

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2006-09-10 Cont ID  
Sent By dpalmer Date 2006-09-10 Time 12:33 Rev Time 0.00
Received By dpalmer Date 2006-09-10 Time 12:28 Sent To  
Notes
2006-09-10 00:00:00**** UNSAT ***
  
 1) NOTE: PLEASE SEE REVISED PLANS AS
 NOTED AND REQUESTED BEFORE ANY ROUGH
 ELECTRICAL INSPECTIONS HAS NOT BEEN
 SUBMITTED TO DATE. INSPECTIONS, HAVE
 BEEN DONE HOWEVER INSPECTION DATED 9/8
 FAILED AS NOT READY AND TO SEE NOTES
 REDLINED ON PLANS HAS NOT BEEN ADDRESS.
 PLEASE SEE THE ELECTRICAL PERMIT HAS
 BEEN PLACED ON "HOLD".
  
 2) NOTE: PLEASE SEE THE FOLLOWING IS NOT
 FOR ELECTRICAL PLANS SUBMITTED.
 PLEASE SEE 8 1/2X 11'S SUBMITTED AND
 ATTACHED TO PLANS SUBMITTED CONTAIN
 RAISED SEALS OVER PHOTO-COPIED SIGNATURE
 FOR ARCHITECT WHICH IS REQUIRED TO BE AN
 ORIGINAL SIGNATURE.
 FS 481.221.
 PLEASE KNOW, A RAISED SEAL OVER A
 PHOTO-COPIED SIGNATURE DOES NOT MAKE
 THIS ORIGINAL AND DOCUMNETS ARE NOT
 VALID.
  
 PLEASE SUBMITE REVISED ELECTRICAL PLANS
 AS STATED ON "PROVISO/REDLINED NOTES" ON
 PLANS.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-07-03 Cont ID  
Sent By dpalmer Date 2006-07-03 Time 16:44 Rev Time 0.00
Received By dpalmer Date 2006-07-03 Time 16:24 Sent To PC
Notes
2006-07-03 00:00:00NEED TO REVISE LAYOUT OF PANELS AND
 IDENTIFICATION ON E 1.1 BEFORE ROUGH.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-06-21 Cont ID  
Sent By dpalmer Date 2006-06-21 Time 15:58 Rev Time 0.00
Received By dpalmer Date 2006-06-21 Time 11:56 Sent To PC
Notes
2006-06-21 00:00:00********* UNSAT ***********
  
 1) NOTE: PLEASE SEE PANELS AS SHOWN ON
 PLANS E1.1 DO NOT CORRELATE WITH RISER
 AND PANEL SCHEDULES.
 PLEASE SEE TWO PANEL "A"'S SHOWN, 1-400A
 AND 1-200A. PLEASE SEE PANEL "B" WHICH
 IS SHOWN AS 600A'S ON PLANS AND 200A'S
  
 2) NOTE: PLEASE SEE RISER DIAGRAM
 INDICATES TWO MDP'S AND ONE OF THE
 SCHEDULES INDICATES MDB. IS THIS ONE OF
 THE MDP'S?
 PLEASE ALSO SEE THE 2ND MDP WHICH IS
 400A RATEDSEEMS TO BE FED FROM MDP
 ONE, WHICH IS 600A'S AND DOES NOT
 INDICATE ANY OCP FEEDING THE MDP-2??
 PLEASE VERIFY IF THIS IS A FEED THUR
 LUGS , TAPPED CONDUCTOS ETC.
 PLEASE KNOW, IF TAPPED ? THEN PLEASE SEE
 240.21. PLEASE KNOW, AS SHOWN IS SEEMS
 THE MDP-2 WOULD REQUIRE AND MCB TO LIMIT
 THE LOAD AND FOR PROTECTION OF WHAT IS
 NOW SHOWN AS A MLO MDP.
 PLEASE SEE NO CONDUCTORS ARE BEING
 INDICATED FOR THE EXISTING MDP ETC.
 UNABLE TO VERIFY AT THIS TIME.
 PLEASE SEE 230.70,230.2,230.71,230.72,
 240.4,310.16,240.21 ETC.
 215.5
  
 3) NOTE: PLEASE CLARIFY THE DIFFERENCE
 IN E2.1 AND 2.2.
  
  
 ** PLEASE BE SURE TO REVMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-06-01 Cont ID  
Sent By dpalmer Date 2006-06-01 Time 15:12 Rev Time 0.00
Received By dpalmer Date 2006-06-01 Time 13:46 Sent To  
Notes
2006-06-01 00:00:00************ UNSAT 3RD REVIEW *********
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW AND SOME NEW NOTES DUE TO PLANS
 SUBMITTED.
  
  
 1) NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 PER NEC 2002 220. PLEASE SEE BOTH
 PREVIOUS REVIEWS REQUESTED THIS.
 220.3,220.10,220.11,220.13,215.3,230.42
 ETC.
 ALL NEW LOADS SHALL BE SHOWN BEING ADDED
 TO EXISITNG LOADS.
 PLANS ONLY MENTIONS "PROJECTED" NEW
 LOADS??
  
 2) NOTE: PLEASE INDICATE AND SHOW ALL
 ROOM AND AREA DESIGNATIONS ON PLANS.
 IE: OFFICE, BATHRMS, CLOSETS, STORAGE
 AREAS, ETC ETC.
  
 3) NOTE: PLEASE SHOW THE LOCATION OF THE
 PANELS AND SERVICE EQUIPMENT ON PLANS.
 PLEASE SEE RESPONSE MENTIONS THIS IS NOW
 SHOWN ON REVISED PLANS, ONLY PANELS "C"
 AND "D" WERE LOCATED AT WHAT APPEARS TO
 BE UNDER STAIRS?
 215.5
  
 4) NOTE: PLEASE SEE RISER HAS NOW BEEN
 REVISED ONCE AGAIN NOW SHOWING A PANEL
 "D" WHICH WAS NOT ON EITHER OF THE FIRST
 TWO REVIEWS?
 PLEASE SEE FIRST SET OF PLANS SHOWED
 ONLY A PANEL "A" AND "B", THEN A PANEL
 "C" WAS ADDED AND NOW A 4TH PANEL WAS
 ADDED.
 PLANS ALSO INDICATE A MAIN DIST PANEL,
 YET NO INFORMATION WAS SUBMITTED FOR
 THIS.
 PLEASE VERIFY ALL WHICH IS EXISTING AND
 WHICH IS NEW.
 PLEASE SEE RISER CONTAINS A VERY SMALL
 NOTE WHICH MENTIONS ALL IS EXISTING, YET
 PANELS DO NOT CONTAIN ANY CHECK OR MARK
 LOCATED IN THE PANEL DISCRIPTION
 INDICATING NEW OR EXISTING?
 PLEASE SEE RISER STILL NOT INDICATE SIZE
 OF SERVICE WHICH LOADS ARE ONOR BEING
 ADDED TO.
 215.5
  
 5) NOTE: PLEASE COMPLETE CIRCUITING ON
 PLANS.
 SEE WAREHOUSE AREA. LTS ARE SHOWN,
 HOWEVER NO CONTROLS ETC.
 215.5
  
 6) NOTE: PLEASE SEE THE PREVIOUS REVIEWS
 WITH RESPECT TO THE CIRCUITING OF EM AND
 EXT LTS.
 PLEASE SEE THE RESPONSE LTR MENTIONS
 CIRCUITING MEETS 700.12E , HOWEVER
 PLEASE SEE ALL EM/EXT LTS SHALL BE
 CIRCUITED TO THE SAME BRANCH CIRCUIT FOR
 LIGHTING IN ANY ONE AREA. (IF LTS IN
 THAT ARE GO OUT, THE EMERGENCY LIGHTING
 WILL COME ON.
 PLEASE CORRELATE AND ADJUST ALL
 CIRCUITING ON PLANS AND PANEL SCHEDULES.
  
 7) NOTE: PLEASE SEE FBC CHAPTER 13 WAS
 NOTED IN PREVIOUS REVIEW AND RESPONSE
 MENTIONS THIS WILL BE UNDER SEPARATE
 PERMIT/WORK?
 PLEASE KNOW,ALL THIS INFORMATION IS
 REQUIRED AT THIS TIME FOR REVIEW OF CODE
 COMPLIANCE.
 THIS SCOPE OF WORK ON PLAN AS SHOWN
 REQUIRES THIS INFORMATION AT THIS TIME.
 PLEASE PROVIDE VOLTAGE DROP WORST CASE
 PER 13-413.1ABC.1,
 PLEASE SEE 13-415.1.ABC.1.1, .2, .3.
 SCHEDULING, OVERIDES, ETC TO BE SHOWN.
  
 8) NOTE: PLEASE CLARIFY THE LOW VOLTGE
 SHOWN ON PREVIOUS TWO SETS OF PLANS
 SUBMITTED WERE NOT SUBMITTED WITH NEW
 PLANS?? IF THE LV IS NOT GOING TO BE
 INCLUDED, THEN ANY LV WILL BE REQUIRED
 TO BE UNDER SEPARATE PERMIT, PLANS AND
 FEES.
 THIS IS ONLY NOTED.
  
 9) NOTE: PLEASE SEE PREVIOUS NOTES GAVE
 A NOTICE TO FLORIDA STATUES 553.80(2)(B)
 WITH RESPECT TO THE DESIGN PROFESSIONALS
 AND REPEAT COMMENTS FOR CODE COMPLIANCE.
 PLEASE KNOW, DUE TO ONE OR MORE OF THE
 COMMENTS BEING THE SAME FOR THE THIRD
 REVIEW, A 4X PLAN REVIEW FEE WAS ADDED
 AS REQUIRED BY THE FS.
 PLEASE KNOW, A FEEOF $3600.00 WAS ADDED
 FOR THE PLAN REVIEW PORTION.
 THIS FEE IS BASED ON 30% OF THE BASE
 PERMIT FEE TIMES FOUR. THIS FEE IS
 REQUIRED TO BE PAID BEFORE SUBMITTING
 PLANS FOR FOURTH REVIEW.
 ** PLEASE KNOW, ONE COPY OF ALL THREE
 SETS OF PLANS ARE NOW BEING RETAINED BY
 THIS OFFICE FOR POSSIBLE REVIEW BY THE
 STATE OF FLORIDA BOARD OF ARCHITECTS AND
 LEGAL COUNSEL TO THE BOARD.
 ** PLEASE KNOW, IT IS RECOMMENDED A
 MEETING BE SET UP TO GO OVER PLANS AND
 COMMENTS TO HELP ALLEAVIATE ANY SUCH
 ADDITIONAL FEESAND ANY FURTHER DELAYS
 IN THE PROJECT START DATE.
 PLEASE SEE COPY THE THE FS IS ATTACHED
 ONCE AGAIN.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW AND PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE TO GO OVER
 COMMENTS OR QUESTIONS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-03-23 Cont ID  
Sent By dpalmer Date 2006-03-23 Time 08:27 Rev Time 0.00
Received By dpalmer Date 2006-03-22 Time 20:16 Sent To  
Notes
2006-03-23 00:00:00*** UNSAT 2ND REVIEW ***
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW AND NEW NOTES FOR INFORMATION
 ADDED TO PLANS.
 FIRST SET OF NOTES BELOW ARE TAKEN
 DIRECTLY FROM FIRST REVIEW.
  
 ************* UNSAT **************
  
 1)NOTE: OK
  
 2)NOTE:OK/ NO, HSEE NEW NOTES FOR
 CIRCUIT. PLEASE ALSO SEE ROOM AND AREA
 DESIGNATIONS WERENOT REVISED.
  
 3)NOTE: NO, PLEASE SHOW ALL PANEL
 LOCATIONS. NEED TO VERIFY 11.26,240.24,
 407.7 ETC
  
 **PRE REVIEW **
 PLEASE SEE LEGEND NOTES SHOWS
 METER AND PANELS, HOWEVER THESE COULD
 NOT BE LCOATE DON PLANS. PLEASE SHOW
 PANEL LOCATIONS. PLEASE BE SURE TO SEE
 110.26, 240.24.
 215.5
  
 4)NOTE: NO, PLEASE SEE THE LOADS WHICH
 WERE SUBMITTED SEEM ONLY TO BE FOR NEW
 LOADS ADDED AND LENDS NO INFORMATION FOR
 EXISTING LOADS THIS LOAD IS ADDED TO AND
 THE SIZE OF EXISTING SERVICE AS BEING
 NOTED.
 NEED TO VERIFY CAPACITY ETC.
 PLEASE ALSO VERIFY ALL CONTINOUS LOADS(
 LIGHTING) AT 125%.
  
 ** PRE-REVIEW**
 PLEASE SUBMIT LOAD CALCULATIONS
 FOR SAID PANELS.
 ARE THEY FED FROM OTHER PANELS? OR IS
 THE TWO PANELS SUBMITTED THE ONLY PANELS
 FROM SERVICE?
 PLEASE SEE THE ONLY ITEMS SHOWN ON PANEL
 SCHEDULES ARE LTS AND RECEPTS?
 ARE OTHER LOADS, A/C ETC ON OTHER
 PANELS?
 PLEASE BE SURE TO SEE 220.10, 220.3,
 220.11, 220.13, ETC
 PLEASE ALSO SHOW ALL CONTINUOUS LOADS
 @125%. LIGHTING/LARGEST MOTOR. ETC
  
 6)NOTE:OK.
  
 7)NOTE:NO, COULD NOT LOCATE AS
 RESPONSE LTR MENTIONS THESE ARE ADDED.
  
 ** PRE REVIEW **
 PLEASE SEE NO RECEPTS ARE SHOWN
 IN BATH RM(S) OR KITCHEN/LUNCH ROOM?
 PLEASE VERIFY.
 PLEASE SEE 2002 NEC 210.8B, 210.8B3
 WHICH REQUIRES ALL 15- AND 20-AMPERE,
 125-VOLT RECEPTACLES IN NONDWELLING-TYPE
 KITCHENS TO BE GFCI PROTECTED. THIS
 REQUIREMENT APPLIES TO EACH AND EVERY
 15- AND 20-AMPERE, 125-VOLT KITCHEN
 RECEPTACLE, WHETHER OR NOT THE
 RECEPTACLE SERVES COUNTERTOP APPLIANCES.
  
 8)NOTE:NO, PLEASE SEE RESPONSE LTR
 MENTIONS THE TITLE BLOCKS WERE REVISED,
 HOWEVER THE "PRINTED NAME AND PRINTED
 LICENSE NUMBER " OF ARCHITECT COULD NOT
 BE LOCATED ON SAID TITLE BLOCKS AS
 REQUIRED.
  
 ** PRE- REVIEW **
 PLEASE SEE FAC 61G1-16.004 WHICH
 ALSO REQUIRES THE PRINTED NAME AND
 LICENSE # OF SAID ARCHITECT.
 PLEASE KNOW THIS IS REQUIRED OF ALL
 TRADES AND FOR ALL SHEETS WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
 9)NOTE: OK.
  
 10)NOTE:NO, PLEASE SEE THIS PROJECT IS
 ON "OKEECHOBEE RD AND PLANS NEED TO
 REFLECT THIS.OLD OKEECHOBEE IS NOT
 ACCURATE. IT IS KNOWN TO THIS OFFICE
 THAT PBCPA OFFICE INDICATES THIS AS "OLD
 " AND THE STREET SIGNS EVEN INDICATE
 THIS.
 PLEASE SEE BLDG REVIEW.
  
 ** PRE- NOTES**
 PLEASE SEE PERMIT APPLICATION
 AND PLANS BOTH MENTIONS "OLD"
 OKEECHOBEE.
 PLEASE KNOW AND PLEASE SEE PALM BEACH
 COUNTY PROPERY APPRAISER'S RECORDS AND
 CITY OF WEST PALM BEACH RECORDS FOR THIS
 PCN NUMBER IS FOR "OKEECHOBEE RD".
 PLEASE ADJUST PLANS ETC.
  
 NEW NOTES**
  
 1) NOTE: PLEASE SEE CIRCUITING IS NOW
 SHOWN, HOWEVER PLEASE SEE 700.12E WHICH
 REQUIRES ALL EM/EXT LTS TO BE CIRCUITED
 TO THE LOCAL BRANCH CIRCUIT IN THE AREA
 IN WHICH THESE ARE LOCATED.
  
 2)NOTE: PLEASE SEE FBC 2004, CHAPTER 13,
  
 PLEASE PROVIDE WORST CASE VDPER
 13-413.1ABC.1
 PLEASE PROVIDE ALL AUTOMATED SYSTEM(S)
 INFORMATION AS REQUIRED PER
 13-415.1.ABC.1 AND .2
 PLEASE SUBMIT SCHEDULING, OVERRIDES,
 OCCUPANCY SENSOR INFORMATION AND TYOE OF
 SYSTEM TO BE INSTALLED.
 CIRCUITING WAS NOT SHOWN ON PREVIOUS
 PLANS.
  
 3) NOTE: PLEASE SEE FS 553.80(2)(B) WITH
 RESPECT TO DESIGN PROFESSIONAL AND
 REPEAT COMMENTS FOR CODE COMPLIANCE.
 THIS IS ONLY A NOTICE.
  
  
 ** PLEASE SEE ANY OTHER POSSIBLE
 COMMENTS FROM OTHER REVIEWER(S) WHICH
 MAY AFFECT ELECTRICAL PLANS.
  
  
 ***************************************
 ** PLEASE DO NOT ATTACHED THE OLD SETS
 TO THE NEW SETS. ONLY ONE OLD SET SHOULD
 BE SUBMITTED AND THIS SET SHOULD BE
 SEPARATE.
 *************************************
  
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE SUBMIT ONE SET OF ANY OLD/VOIDED
 REMOVED SHEETS FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
2006-03-22 00:00:00IN ELEC FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-12-24 Cont ID  
Sent By dpalmer Date 2005-12-24 Time 12:11 Rev Time 0.00
Received By dpalmer Date 2005-12-24 Time 11:32 Sent To  
Notes
2005-12-24 00:00:00************* UNSAT **************
  
 1)NOTE: PLEASE SEE FIRE REVIEW NOTES,
 PLEASE SEE AS OF JAN 1ST, 2005 WE ARE
 CURRENTLY UNDER THE 2003 LS-101
  
 2)NOTE: PLEASE SHOW ALL CIRCUTING ON
 PLANS AND CORRELATE WITH THE PANEL
 SCHEDULES SUBMITTED.
 PLEASE KNOW, EACH CIRCUIT SHALL BE
 IDENTIFIED FOR EACH PANEL. A,B ETC.
 ROOM AND AREA DESIGANTIONS SHALL ALSO BE
 PLACED ON PLANS, WHICH WILL CORRELATE
 WITH THE CIRCUITING ON PANEL SCHEDULE.
 PANEL SCHEDULE SHOULD NOTE BATHRM
 CIRCUIT# X. ETC.
 215.5
  
 3)NOTE: PLEASE SEE LEGEND NOTES SHOWS
 METER AND PANELS, HOWEVER THESE COULD
 NOT BE LCOATE DON PLANS. PLEASE SHOW
 PANEL LOCATIONS. PLEASE BE SURE TO SEE
 110.26, 240.24.
 215.5
  
 4)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 FOR SAID PANELS.
 ARE THEY FED FROM OTHER PANELS? OR IS
 THE TWO PANELS SUBMITTED THE ONLY PANELS
 FROM SERVICE?
 PLEASE SEE THE ONLY ITEMS SHOWN ON PANEL
 SCHEDULES ARE LTS AND RECEPTS?
 ARE OTHER LOADS, A/C ETC ON OTHER
 PANELS?
 PLEASE BE SURE TO SEE 220.10, 220.3,
 220.11, 220.13, ETC
 PLEASE ALSO SHOW ALL CONTINUOUS LOADS
 @125%. LIGHTING/LARGEST MOTOR. ETC
  
 6)NOTE: PLEASE INDICATE NEW OR EXSITING
 SIGN CIRCUIT REQUIRED PER 600.5 AT FRONT
 DOOR LOCATION.
  
 7)NOTE: PLEASE SEE NO RECEPTS ARE SHOWN
 IN BATH RM(S) OR KITCHEN/LUNCH ROOM?
 PLEASE VERIFY.
 PLEASE SEE 2002 NEC 210.8B, 210.8B3
 WHICH REQUIRES ALL 15- AND 20-AMPERE,
 125-VOLT RECEPTACLES IN NONDWELLING-TYPE
 KITCHENS TO BE GFCI PROTECTED. THIS
 REQUIREMENT APPLIES TO EACH AND EVERY
 15- AND 20-AMPERE, 125-VOLT KITCHEN
 RECEPTACLE, WHETHER OR NOT THE
 RECEPTACLE SERVES COUNTERTOP APPLIANCES.
  
 8)NOTE: PLEASE SEE FAC 61G1-16.004 WHICH
 ALSO REQUIRES THE PRINTED NAME AND
 LICENSE # OF SAID ARCHITECT.
 PLEASE KNOW THIS IS REQUIRED OF ALL
 TRADES AND FOR ALL SHEETS WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
 9)NOTE: PLEASE SEE SHEET 4 OF 5 IN ONE
 SETIS NOT SEALED BY SAID ARCHITECT.
 FS 481.221
  
 10)NOTE: PLEASE SEE PERMIT APPLICATION
 AND PLANS BOTH MENTIONS "OLD"
 OKEECHOBEE.
 PLEASE KNOW AND PLEASE SEE PALM BEACH
 COUNTY PROPERY APPRAISER'S RECORDS AND
 CITY OF WEST PALM BEACH RECORDS FOR THIS
 PCN NUMBER IS FOR "OKEECHOBEE RD".
 PLEASE ADJUST PLANS ETC.
  
  
 ** PLEASE SEE ANY OTHER POSSIBLE
 COMMENTS FROM OTHER REVIEWER(S) WHICH
 MAY AFFECT ELECTRICAL PLANS.
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE SUBMIT ONE SET OF ANY OLD/VOIDED
 REMOVED SHEETS FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-06-06 Cont ID  
Sent By mwennerg Date 2006-06-06 Time 15:54 Rev Time 0.00
Received By mwennerg Date 2006-06-06 Time 15:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-04-06 Cont ID  
Sent By mwennerg Date 2006-04-06 Time 15:07 Rev Time 0.00
Received By mwennerg Date 2006-04-06 Time 15:07 Sent To  
Notes
2006-04-06 00:00:00******DENIED******
  
 1) EXITS AND EMERGENCY LIGHTING ARE
 ILLUSTRATED DIFFERENTLY ON EACH SHEET.
 PLEASE CORRULATE, AND CLEARLY IDENTIFY
 LOCATIONS. ARE THERE ENOUGH EXITS IN
 WAREHOUSE AREAS? SHT A-5 WAS INDICATED
 FOR REFERENCE, HOWEVER THAT SHEET HAS
 BEEN VOIDED. SHT E-1.1 DOES NOT SHOW ANY
 EMERGENCY LIGHTING IN AREA 116.
  
 2) DETAILS FOR STORAGE RACKS ARE
 REQUIRED FOR REVIEW PRIOR TO APPROVAL OF
 DRAWINGS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLANS REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-12-21 Cont ID  
Sent By mcarsill Date 2005-12-21 Time 10:37 Rev Time 0.00
Received By mcarsill Date 2005-12-21 Time 10:11 Sent To  
Notes
2005-12-21 00:00:001. WRONG LIFE SAFETY CODE REFERENCED.
 SHOULD READ 2003 EDITION NOT 2001
 EDITION.
  
 2. ALL DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 3. DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY.
  
 4. ALL EXITS ARE TO REMIAN CLEAR AND
 UNOBSTRUCTED.
  
 5. GASOLINE POWERED EQUIPMENT SHOULD NOT
 BE USED INDOORS DUE TO THE RISK OF
 CARBON MONIXIDE BUILD-UP.
  
 6. SEPERATE PLANS AND PERMITS REQUIRED
 FOR ANY FIRE SPRINKLER SYSTEM
 MODIFICATION.
  
 7. PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATIONS FOR WALLS AND CEILINGS.
  
 8. SECURITY PLAN APPEARS TO BE ABSENT OF
 DEVICES THAT ARE REFLECTED IN THE KEY ON
 PAGE E3.1.
  
 9. PLEASE ILLUSTRATE EXIT SIGNS AND
 EMERGENCY LIGHTING IN WAREHOUSE AREA
 116, AND 117.
  
 10. SEPERATE PLANS AND PERMITS REQUIRED
 FOR ANY FIRE ALARM SYSTEM REMODELING.
  
 11. PLEASE PROVIDE MORE DETAILS ON
 BATTERY CHARGER EQUIPMENT CONTAINED IN
 WAREHOUSE 116.
  
 12. PLEASE PROVIDE DETAILS ON STORAGE
 RACKS ILLUSTRATED WITHIN THE PLANS.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-10-03 Cont ID  
Sent By adarroug Date 2006-10-03 Time 14:16 Rev Time 0.00
Received By adarroug Date 2006-10-03 Time 14:16 Sent To  
Notes
2006-10-17 13:31:58TO "COMM" BD#9
2006-10-03 00:00:00WAITING FOR "COMM" BD-REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-09-19 Cont ID  
Sent By adarroug Date 2006-09-19 Time 14:04 Rev Time 0.00
Received By adarroug Date 2006-09-19 Time 14:04 Sent To E
Notes
2006-09-19 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-08-25 Cont ID  
Sent By adarroug Date 2006-08-25 Time 08:43 Rev Time 0.00
Received By adarroug Date 2006-08-25 Time 08:43 Sent To  
Notes
2006-08-25 00:00:00WAITING FOR "COMM" BD-REV
 TO "COMM" BD#34

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-07-03 Cont ID  
Sent By adarroug Date 2006-07-03 Time 15:55 Rev Time 0.00
Received By adarroug Date 2006-07-03 Time 15:55 Sent To E
Notes
2006-07-03 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-06-20 Cont ID  
Sent By adarroug Date 2006-06-20 Time 15:02 Rev Time 0.00
Received By adarroug Date 2006-06-20 Time 15:02 Sent To E
Notes
2006-06-20 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-05-15 Cont ID  
Sent By adarroug Date 2006-05-15 Time 08:47 Rev Time 0.00
Received By adarroug Date 2006-05-15 Time 08:47 Sent To  
Notes
2006-05-31 00:00:00TO "COMM" BD#9
2006-05-15 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-02-28 Cont ID  
Sent By adarroug Date 2006-02-28 Time 15:58 Rev Time 0.00
Received By adarroug Date 2006-02-28 Time 15:58 Sent To  
Notes
2006-03-21 00:00:00TO COMM BOARD #34
2006-02-28 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-02-18 Cont ID  
Sent By pschmitz Date 2006-02-18 Time 13:44 Rev Time 0.00
Received By pschmitz Date 2005-12-02 Time 08:26 Sent To  
Notes
2006-02-18 00:00:00ENTERED "N" PES
2005-12-20 00:00:00TO "COMM" BD#31
2005-12-02 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2006-06-01 Cont ID  
Sent By pkrauss Date 2006-06-01 Time 07:18 Rev Time 0.00
Received By pkrauss Date 2006-06-01 Time 07:17 Sent To  
Notes
2006-06-01 00:00:00NO MECHANICAL PLANS OR CONTRACTOR
 INDICATED WITH PERMIT APPLICATION.
 PLEASE PROVIDE PLANS WITH MECHANICAL
 PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-04-12 Cont ID  
Sent By hmoser Date 2006-04-12 Time 15:23 Rev Time 0.00
Received By hmoser Date 2006-04-12 Time 15:23 Sent To  
Notes
2006-04-12 00:00:00NO MECHANICAL PLANS 4/12/06 HM.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-01-23 Cont ID  
Sent By pkrauss Date 2006-01-23 Time 11:13 Rev Time 0.00
Received By pkrauss Date 2006-01-23 Time 11:09 Sent To  
Notes
2006-01-23 00:00:00MECHANICAL PLANS OR CONTRACTOR WERE
 SUBMITTED WITH THE BUILDING PERMIT
 APPLICATION.PLEASE PROVIDE PLANS WITH
 MECHANICAL PERMIT APPLICATION.PLEASE
 INDICATE EXISTING, NEW OR RELOCATED
 WORK.PLEASE NOTE, FIRE DAMPERS ARE
 REQUIRED WHEN PENETRATING RATED
 PARTITIONS OR WALLS.PLEASE INDICATE
 LOCATION OF NEW OR EXISTING FIRE
 DAMPERS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 4 Status F Date 2006-09-12 Cont ID  
Sent By kstevens Date 2006-09-12 Time 11:56 Rev Time 0.00
Received By kstevens Date 2006-09-12 Time 11:56 Sent To  
Notes
2006-09-12 00:00:00DENIED
 REFERENCE: FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. PLUMBING REVISION DENIED. THE PLANS
 SHALL HAVE AN ORIGINAL SIGNATURE. THE
 SIGNATURES ARE PHOTO COPIES. THE TITLE
 BLOCK SHALL HAVE A SPACE FOR THE PRINTED
 NAME OPF THE PERSON SEALING THE
 DOCUMENT. FAC 61G1-16.004(5)(6) AND FS
 481.2055.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-06-02 Cont ID  
Sent By pschmitz Date 2006-06-02 Time 14:01 Rev Time 0.00
Received By pschmitz Date 2006-06-02 Time 14:01 Sent To  
Notes
2006-06-02 00:00:00SEE PROVISO: SHT'S P-1,P-2
 F/S FOR I/D WASTE.
 NO WATER COOLER D/F REQUIRED

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-04-19 Cont ID  
Sent By pschmitz Date 2006-04-19 Time 09:28 Rev Time 0.00
Received By pschmitz Date 2006-04-19 Time 09:28 Sent To M
Notes
2006-04-19 00:00:00PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE,
  
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
 UNSAT
 1)SHT CS, PREVIOUS NOTES NOT ADDRESSED.
 URINAL,EYE WASH AND BREAK ROOM SINKS NOT
 SHOWN ON BUILDING DATA FIXTURE COUNT.
  
 2)SHT A-2 SHOW LOCATION OF DRINKING
 FOUNTAIN.
 3) SHT A-4 DETAILS CORELATE DETAILS FOR
 THE LUNCH ROOM SINK AND COFFEE COUNTER
 SINK.
 4) SHT A-2 11-4.24 SINKS.NO DOORS ON
 CABINETS, SHOW CLEAR FLOOR SPACE.
 11-4.24.1 GENERAL.
 SINKS REQUIRED TO BE ACCESSIBLE BY
 SECTION 11-4.1 SHALL COMPLY WITH SECTION
 11-4.24.
 11-4.24.4 DEPTH.
 EACH SINK SHALL BE A MAXIMUM OF 6?
 INCHES (165 MM) DEEP.
 11-4.24.5 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE AT LEAST 30 INCHES
 BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE
 PROVIDED IN FRONT OF A SINK TO ALLOW
 FORWARD APPROACH. THE CLEAR FLOOR SPACE
 SHALL BE ON AN ACCESSIBLE ROUTE AND
 SHALL EXTEND A MAXIMUM OF 19 INCHES (485
 MM) UNDERNEATH THE SINK (SEE FIGURE
 11-32).
 11-4.24.7 FAUCETS.
 FAUCETS SHALL COMPLY WITH SECTION
 11-4.27.4. LEVER-OPERATED, PUSH-TYPE,
 TOUCH-TYPE, OR ELECTRONICALLY CONTROLLED
 MECHANISMS ARE ACCEPTABLE DESIGNS.
 5) SHT A-2 VENDING MACHINE.PROVIDE
 INFORMATION ON INDIRECT WASTE FOR
 VENDING MACHINES.
 6) SHT P-1 CORELATE PLUMBING FIXTURE
 SCHEDULE WITH FIXTURE LAYOUT.
 7) SHT P-1,2SHOW ACCESIBLELOCATION
 OF WATER HEATER.
 607.3 THERMAL EXPANSION CONTROL.
 A MEANS OF CONTROLLING INCREASED
 PRESSURE CAUSED BY THERMAL EXPANSION
 SHALL BE PROVIDED WHERE REQUIRED IN
 ACCORDANCE WITH SECTIONS 607.3.1 AND
 607.3.2.
 607.3.1 PRESSURE-REDUCING VALVE.
 FOR WATER SERVICE SYSTEM SIZES UP TO AND
 INCLUDING 2 INCHES (51 MM), A DEVICE FOR
 CONTROLLING PRESSURE SHALL BE INSTALLED
 WHERE, BECAUSE OF THERMAL EXPANSION, THE
 PRESSURE ON THE DOWNSTREAM SIDE OF A
 PRESSURE-REDUCING VALVE EXCEEDS THE
 PRESSURE-REDUCING VALVE SETTING.
 607.3.2 BACKFLOW PREVENTION DEVICE OR
 CHECK VALVE.
 WHERE A BACKFLOW PREVENTION DEVICE,
 CHECK VALVE OR OTHER DEVICE IS INSTALLED
 ON A WATER SUPPLY SYSTEM UTILIZING
 STORAGE WATER HEATING EQUIPMENT SUCH
 THAT THERMAL EXPANSION CAUSES AN
 INCREASE IN PRESSURE, A DEVICE FOR
 CONTROLLING PRESSURE SHALL BE INSTALLED.
 8)SHT P-2 WATER RISER
 SECTION 606 INSTALLATION OF THE BUILDING
 WATER DISTRIBUTION SYSTEM
 606.1 LOCATION OF FULL-OPEN VALVES.
 FULL-OPEN VALVES SHALL BE INSTALLED IN
 THE FOLLOWING LOCATIONS:
 1. ON THE BUILDING WATER SERVICE PIPE
 FROM THE PUBLIC WATER SUPPLY NEAR THE
 CURB.
 2. ON THE WATER DISTRIBUTION SUPPLY PIPE
 AT THE ENTRANCE INTO THE STRUCTURE.
 3. ON THE BASE OF EVERY WATER RISER PIPE
 IN OCCUPANCIES OTHER THAN
 MULTIPLE-FAMILY RESIDENTIAL OCCUPANCIES
 THAT ARE TWO STORIES OR LESS IN HEIGHT
 AND IN ONE- AND TWO-FAMILY RESIDENTIAL
 OCCUPANCIES.
 4. ON THE TOP OF EVERY WATER DOWN-FEED
 PIPE IN OCCUPANCIES OTHER THAN ONE- AND
 TWO-FAMILY RESIDENTIAL OCCUPANCIES.
 9) SHT P-2 WATER HAMMER ARRESTORS SHOWN
 AT TOP OF RISER IS NOT PER THE
 MANFACTURE INSTALLATION INSTRUCTIONS.
 SHOULD BE AT POINT OF SERVICE, OR
 BETWEEN THE LAST TWO FIXTURES.
 10) SHT P-2 WATER AND SANITARY RISRER IS
 NOT SHOWING ALL OFF THE FIXTURES.I COUNT
 AT LEAST 14 FIXTURES.
 END OF COMMENTS, QUESTIONS 561-805-6692
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-02-18 Cont ID  
Sent By pschmitz Date 2006-02-18 Time 12:15 Rev Time 0.00
Received By pschmitz Date 2006-02-18 Time 12:15 Sent To  
Notes
2006-02-18 00:00:00PLUMBING PLAN REVIEW EXAMINER
 PAUL SCHMITZ 561-805-6692
 [email protected]
 FBC PLUMBING 2004
 FBC FUEL GAS 2004
 AMENDMENTS TO THE FLORIDA BUILDING CODE
 CH 1, ADMINISTRATION, 2004 EDITION
 ( ATFBC)
 FBC BUILDING 2004, CH 11
 DENIED
  
 1)SHT CS BUILDING DATA
 MINIMUM FACILITIES TABLE 403.1
 MIXED USE, NUMBER OF W/C ON PLANS, FOUR.
 FOURREQUIRED.
 REST RM 113, URNIAL IS NOT SHOWN IN
 FIXTURE COUNT.
 LAVATORIES: THREE SHOWN, THREE REQUIRED.
 DRINKING FOUNTAIN: ONE REQUIRED.
 EYE WASH SHOWER: ONE REQUIRED SEC 411.
 SERVICE SINK: NOT SHOWN ON FIXTURE COUNT
 ONE SHOWN IN ROOM 109.
 MERCHANTILE: MEN, WOMEN.1-W/C, 1-LAV.
 1-D/F, 1-S/S.
 STORAGE: MEN, WOMEN, 1-W/C, 1-LAV,
 1- EYE WASH SHOWER, SEC 411
 BUSINESS: MEN,WOMEN 1-W/C,1-LAV.1-D/F.
  
 2) SHT CS SHEET INDEX SHOWS P-1,P-2 NOT
 INCLUDED IN SUBMITTED SET OF PLANS.
  
 3) (ATFBC) SEC 106.3.5.1.3 (3)(4)
 COMMERICAL BUILDINGS, PLUMBING SANITARY
 DRAINAGE, WATER PIPING ISOMETRIC REQ.
 3) SHT A-4 DETAIL B-A-4 DINENSION ON W/C
 OFF WALL IS 18 INCHES.
  
 4) SECTION 11-4
 ACCESSIBLE ELEMENTS AND SPACES:
 SCOPE AND TECHNICAL REQUIREMENTS
 11-4.1 MINIMUM REQUIREMENTS.
 11-4.1.1 APPLICATION.
 (1) GENERAL. THIS CODE ESTABLISHES THE
 MINIMUM STANDARDS FOR THE ACCESSIBILITY
 OF BUILDINGS AND FACILITIES BUILT OR
 ALTERED WITHIN THE STATE.
 (A) ALL AREAS OF NEWLY DESIGNED OR NEWLY
 CONSTRUCTED BUILDINGS AND FACILITIES
 REQUIRED TO BE ACCESSIBLE BY SECTION
 11-4.1.2 AND SECTION 11-4.1.3 AND
 ALTERED PORTIONS OF EXISTING BUILDINGS
 AND FACILITIES REQUIRED TO BE ACCESSIBLE
 BY SECTION 11-4.1.6 SHALL COMPLY WITH
 THIS CODE, SECTION 11-4.1 THROUGH
 SECTION 11-4.35, UNLESS OTHERWISE
 PROVIDED IN THIS SECTION OR AS MODIFIED
 IN A SPECIAL APPLICATION SECTION.
 SHOW ELEVATIONS, DIMIENSIONS, TURNING
 SPACE FOR REQUIRED PLUMBING FIXTURES.
  
  
 END OF COMMENTS, QUESTIONS 561-805-6692
  
  