| 2005-12-20 00:00:00 | DENIED |
| | REFERENCE: FBC-2004 424.2 SWIMMING POOLS |
| | |
| | 1) FBC-2004 SEC 424.2.6.1 ENGINEERING |
| | DESIGN, CONSTRUCTION AND WORKMANSHIP. |
| | ANSI/NSPI-5. (ADD TO NOTES) |
| | 2) FBC-2004 424.2.7.2 PUMPS AND |
| | EQUIPMENT SHALL BE MOUNTED ON A |
| | SUBSTANTIAL BASE IN A MANNER THAT WILL |
| | ELIMINATE STRAIN ON PIPING.SLAB SHALL |
| | BE A NOMINAL 4" THICK. (DETAIL) |
| | 3) FBC-2004 SEC 424.2.9 WATER SUPPLY, |
| | LOCAL ORD.#2853-95, BACKFLOW REQUIRED ON |
| | WATER SERVICE. (ADD TO NOTES) |
| | 4) FBC-2004 424.2.12.1 PRESSURE TESTS. |
| | PER MANUFACTURE RECOMMENDATIONS, NO AIR |
| | TEST SHALL BE APPROVED FOR PVC PIPE AND |
| | FITTINGS. (ADD TO NOTES) |
| | 5) FBC-2004 SEC 424.2.13.2 JOINTS AND |
| | CONNECTIONS, FBC PLMG SEC 605.21 PURPLE |
| | PRIMER REQUIRED ON PVC PIPING. (ADD TO |
| | NOTES) |
| | 6) FBC-2004 SEC 424.2.14.2 WATER |
| | RETENTION PROVIDE A POSITIVE MEANS OF |
| | RETAINING WATER IN THE HEATER WHEN PUMP |
| | IS SHUT OFF.(MANUFACTURE CUT SHEETS |
| | SUBMITTAL) |
| | 7) CITY OF WEST PALM BEACH ADD. TO |
| | FBC-2004 SEC 106.1.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS.CONSTRUCTION |
| | DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN |
| | DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT |
| | LAWS, ORDINANCES, RULES AND REGULATIONS, |
| | AS DETERMINED BY THE BUILDING OFFICIAL. |
| | |