| 2006-03-17 00:00:00 | ************ UNSAT 2ND REVIEW ********* |
| | |
| | 1)NOTE: PLEASE KNOW, THERE ARE MANY |
| | ELECTRICAL COMMENTS BASED ON SERVICES AS |
| | SHOWN, HOWEVER MANY OF THOSE DO NOT |
| | APPLY AS THE SERVICES AS SHOWN ARE NOT |
| | PERMITTED. PLEASE SEE 230.2, ONLY ONE |
| | ELECTRICAL SERIVCE WILL BE PERMITTED. |
| | ALL MAINS ARE TO BE GROUPED PER 230.72. |
| | PLEASE SEE PTHER COMMENTS AS THEY WILL |
| | HAVE AN AFFECT ONE RISER AND NEW |
| | SERVICE. |
| | |
| | 2)NOTE: PLEASE SEE RISER AS SHOWN SHOWS |
| | 200A OCP FEEDING 125A PANEL. |
| | 240.4, 215.5 ETC. |
| | |
| | 3)NOTE: PLEASE SEE MISSING EQUIPMENT |
| | GROUNDING CONDUCTORS ON ALL CONDUITS ON |
| | RISER. |
| | |
| | 4)NOTE: PLEASE SHOW ALL SERVICE AND |
| | PANEL LOCATIONS ON PLANS. |
| | 215.5 |
| | |
| | 5)NOTE: PLEASE KNOW, A HOUSE PANEL WILL |
| | BE REQUIRED FOR ANY COMMON AREA BRANCH |
| | CIRCUITS. PLEASE KNOW, THE EGRESS |
| | LIGHTING ON UPPER FOYER AND STAIRS MAY |
| | NOT BE FED FROM ANY ONE UNIT. |
| | 210.25 |
| | PLEASE ALSO SEE COMMENTS WITH RESPECT TO |
| | THE EGRESS LIGHTING AND CONTROL. |
| | |
| | 6)NOTE: PLEASE SEE LS101-7.8,7.9, |
| | NFPA-70 210.70, EGRESS LIGHTING IS |
| | REQUIRED AND THE METHOD OF CONTROL CAN |
| | BE DECIDED BY THE DESIGNER. PLEASE KNOW |
| | HOWEVER , IS USING SWITCHES, THERE MUST |
| | ALSO BE 3-WAY SWITCHING AT LOWER LEVEL. |
| | PLEASE ALSO SEE 7.9.2.2, 7.8.1.3 WHICH |
| | REQUIRES 10FT CANDLES MIN DURING NORMAL |
| | OPERATION AND 1 FT CANDLE UNDER |
| | EMERGENCY. A BATTERY BACK UP LT OF SOME |
| | SORT(S0 WILL BE REQUIRED TO SUPPLY THE |
| | MIN OF 1 FT CANDLE UNDER AN EMERGENCY |
| | CONDITION. |
| | |
| | 7)NOTE: PLEASE SEE 424.3B FOR MININUM |
| | OCP FOR ALL AHU'S. PLEASE SEE 2-POLE 20A |
| | OCP FOR 10KW LOAD? |
| | PLEASE SEE 50A OCP FOR 10KW ETC, NONE OF |
| | THESE MEET ABOVE CODE. |
| | |
| | 8)NOTE: PLEASE SEE THE "WALL UNIT" AS |
| | SHOWN AND ALSO VERIFY OCP AND UNIT. |
| | |
| | 9)NOTE: PLEASE PROVIDE ENERGY |
| | CALCUALTIONS PER 2004 FBCCHAPTER 13. |
| | |
| | 10)NOTE: PLEAS PROVIDE SPEC FOR WATER |
| | HEATERS BEING SHOWN OUTSIDE IN OPEN AIR. |
| | THESE UNIT MUST BERATED FOR WET |
| | LOCATIONS, OR OUTDOOR WP ENCLOUSURES |
| | SHALL BE SHOWN AND DETAILED. |
| | 110.3, 215.5 |
| | |
| | 11)NOTE: PLEASE SEE SD'S SHALL BE |
| | INSTALLED PER NFPA-72 11.8.3.5, NO SD |
| | CAN BE WITH-IN 20' OF THE COOKING |
| | APPLIANCE UNLESS MEETING THE EXCEPTIONS |
| | AS SET-FORTH. PLEASE PROVIDE NOTES FOR |
| | TYOE OF SD(S) BEING INSTALLED PER |
| | EXCEPTIONS. |
| | |
| | 12)NOTE: PLEASE SEE THAT PLANS SHALL |
| | INDICATE THE CURRENT CODES FOR THIS |
| | DESIGN. PLEASE KNOW, WE ARE UNDER THE |
| | 2002 NFPA-70, 2002 NFPA-72, 2003 |
| | NFPA-101, 2004 FBC. PLANS TO INDICATE |
| | THESE AT A MIN. |
| | |
| | 13)NOTE: PLEASE SEE 2002 NEC 210.12 FOR |
| | MIN ARC FAULT PROTECTION REQUIRED FOR |
| | ALL CIRCUITING TO SLEEPING ROOMS. |
| | RECEPTS, LTS, FANS SD'S ETC. |
| | |
| | 14)NOTE: PLEASE INDICATE ALL CIRCUITING |
| | ON PLANS AND CORRELATE WITH THE |
| | SUBMITTED PANEL SCHEDULES. |
| | 215.5 |
| | |
| | 15)NOTE: PLEASE SEE MISSING DEDICATE |
| | BATH CIRCUITS PER 210.52D, 210.11C3, |
| | SHALL BE 20A AND #12. |
| | |
| | 16)NOTE: COULD NOT LOCATE ANY MAIN |
| | LAUNDRY FACILITIES , PLEASE SEE |
| | 210.11C2,210.52F, 220.16 ETC. |
| | PLEASE ALSO SEE MIN FACILITIES REQUIRED |
| | UNDER THE PLUMB AND MECHANICAL CODE. |
| | |
| | 17)NOTE: PLEASE SEE FHAR 24 CFR 100.205 |
| | FOR ALL DEVICE HEIGHTS AND DEVICE |
| | LOCATIONS. THESE ARE TO BE NOTED ON |
| | PLANS. |
| | |
| | 18)NOTE: PLEASE SEE 210.52B1 FOR CIRCUIT |
| | REQUIRED IN DINING AREAS AND THE LIKE, |
| | THESE SHALL BE ON ONE OR MORE OF THE |
| | SMALL APPLIANCE CIRCUITS. |
| | |
| | 19)NOTE: PLEASE SEE 210.8A FOR GFI |
| | LOCATIONS. (BATHRMS) EXISTING OR NEW). |
| | |
| | 20)NOTE: PLEASE SEE FBC FOR EXSITING |
| | BUILDING AND REQUIREMENTS FOR BRINGING |
| | ALL UP TO CODE WIHT THE SCOPE OF WORK |
| | BEING PERMFORMED. PLEASE SEE THAT THE |
| | LEVEL OF ALTERATION SAHLL BE STATED. |
| | |
| | 21)NOTE: PLEASE SEE LOAD CALCS FOR UNIT |
| | "B" WHICH SHOWS NO A/C LOAD IN LOAD |
| | CALCUALTIONS, YET PANEL SCHEDULE SHOWS |
| | 10KW OF LOAD?? |
| | 215.5,424.4,240.4,310.16, ETC. |
| | |
| | 22)NOTE: PLEASE SEE 250.110, 250.122, |
| | 250.24, 250.66 FOR SIZING OF GROUNDING |
| | ELECTRODE CONDUCTOR AND EQUIPMENT GRNDS. |
| | |
| | 23)NOTE: PLEASE SEE PLANS CONTAINING |
| | TITLE BLOCKS AND WORK COVERED IN THE |
| | REQUIREMENTS OF FS 481.229 ARE REQUIRED |
| | TO BE SIGNED , DATED AND SEALED BYB THE |
| | REGISTERED ARCHITECT AS LISTED. PLEASE |
| | SEE 481.221, FAC 61G1-16.003, .004 |
| | |
| | 24) NOTE: PLEASE SEE AHU, SHOWS TWO |
| | DISCONECTS FOR ONE UNIT?? PLEASE VERIFY |
| | AS THIS IS NOT COMMON AND NO CONDUCTOR, |
| | DISC SIZE INFORMATION WAS SUPPLIED OR |
| | SHOWN. PLEASE ALSO SEE 240.21 AS THESE |
| | ARE BEING SHOWN AS "TAPPED" CONDUCTORS?? |
| | PLEASE KNOW, THIS SHOULD INDICATE ONE |
| | DISCONNECT PER 440.11. |
| | 31.16,240.4 ETC. |
| | |
| | 25)NOTE: PLEASE SEE NO MECHANICAL PLANS |
| | WERE SUBMITTED IN ORDER TO VERIFY AND |
| | CORRELATE THE EQUIPEMNT, CALCULATIONS |
| | ETC. |
| | PLEASE SEE FBC 106.3.5.1.1 WHICH |
| | DICTATES THE MIN PLANS REQUIRED FOR PLAN |
| | REVIEW OF COMMERCIAL BUILDINGS. |
| | |
| | 26)NOTE: PLEASE SEE THE NOC SUBMITTED |
| | HSA SINCE EXPIRED PER FS 713.13(2). IF |
| | WORK HAS NOT COMMENCED WITHIN 90 DAYS OF |
| | RECORDING NOC, THE NOC SHALL BECOME |
| | VOID. |
| | |
| | ** PLEASE SEE ANY COMMENTS FROM OTHER |
| | TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | ** PLEASE SUBMIT THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |