Plan Review Details - Permit 05111033
Plan Review Stops For Permit 05111033
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-05-18 Cont ID  
Sent By lmartine Date 2007-05-18 Time 14:15 Rev Time 0.00
Received By lmartine Date 2007-05-18 Time 14:14 Sent To  
Notes
2007-05-18 14:15:29REVISION TO TO MAKE 3RD FLOOR WINDOWS BIGGER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-10-06 Cont ID  
Sent By alange Date 2006-10-06 Time 08:08 Rev Time 1.50
Received By alange Date 2006-10-06 Time 08:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-09-05 Cont ID  
Sent By alange Date 2006-09-05 Time 08:55 Rev Time 0.75
Received By alange Date 2006-09-05 Time 08:55 Sent To  
Notes
2006-09-05 00:00:00DENIED
  
 NEW COMMENT:
 THE NEW POLYGLASS PRODUCT APPROVAL
 SUMBITTED SHALL HAVE CALCULATIONS FOR
 ENHANCED FASTENING SUBMITTED PER
 LIMITATION NUMBER 7 ON PAGE 45 OF THE
 MIAMI-DADE.
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-08-16 Cont ID  
Sent By alange Date 2006-08-16 Time 13:31 Rev Time 1.25
Received By alange Date 2006-08-16 Time 13:31 Sent To  
Notes
2006-08-16 00:00:00DENIED
 THE FOLLOWING MIAMI-DADE PRODUCTS
 APPROVALS ARE STILL MISSING STATE
 PRODUCT APPROVALS.
 -MONIER LIFETILE
 -CAST-CRETE LINTELS
 -JOHNS MANSVILLE BITUMEN ROOF *ALSO*
 SELECT ASSEMBLY USED ON MIAMI-DADE
 REPORT
 10.ALL PRODUCT APPROVALS SHALL HAVE
 THE FOLLOWING STATE PRODUCT APPROVAL
 ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-07-26 Cont ID  
Sent By alange Date 2006-07-26 Time 08:37 Rev Time 2.00
Received By alange Date 2006-07-26 Time 08:37 Sent To  
Notes
2006-07-26 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.SUBMIT TWO ORIGONAL SINGED AND
 SEALED SURVEYS. FS. 472.025
  
 6.SPECIFY CONSTRUCTION TYPE ON PLANS
 FBC 602
  
 7. SHOW LEVEL OF ALTERATION ON PLANS.
 A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE ORE A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303,304 AND 305 OF THE 2004
 EXISTING BUILDING CODE.
  
 8. ALL PLANS SUBMITTED AFTER OCTOBER, 1,
 2004 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE.
  
 9.SHOW SIZE AND TYPE OF EXISTING
 WINDOW IN BEDROOM NUMBER 3.FBC 2004
 R310
  
 10.ALL PRODUCT APPROVALS SHALL HAVE
 THE FOLLOWING STATE PRODUCT APPROVAL
 ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 11.PRODUCT APPROVALS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-01-06 Cont ID  
Sent By alange Date 2006-01-06 Time 08:24 Rev Time 3.00
Received By alange Date 2006-01-05 Time 14:39 Sent To  
Notes
2006-01-06 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.SUBMIT TWO ORIGONAL SINGED AND
 SEALED SURVEYS. FS. 472.025
  
 3.SUBMIT ENERGY CALCS TO THE 2004 FBC.
  
 4.FOOTINGS SHALL BE DESIGNED AS PER
 THE RECOOMMENDATIONS FROM THE
 GEOTECHNICAL EXPLORATION REPORT.
  
 5.BASED ON ICC BUILDING VALUATION DATA
 THE PERMIT VALUATION HAS BEEN REVISED TO
 $164,256.ADDITIONAL PERMIT FEES ARE
 DUE.SEE ATTTACHED INVOICE.
  
 6.SPECIFY CONSTRUCTION TYPE ON PLANS
 FBC 602
  
 7.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE ORE A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303,304 AND 305 OF THE 2004
 EXISTING BUILDING CODE.
  
 8. ALL PLANS SUBMITTED AFTER OCTOBER, 1,
 2004 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE.
  
 9.SHOW SIZE AND TYPE OF EXISTING
 WINDOW IN BEDROOM NUMBER 3.FBC 2004
 R310
  
 10.SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR ALL EXTERIOR DOORS,
 WINDOWS,LINTELS, ROOFING AND STRAPS AND
 TIE-DOWNS.
 ALL PRODUCT APPROVALS SHALL HAVE THE
 FOLLOWING STATE PRODUCT APPROVAL
 ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 11.PRODUCT APPROVALS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-12-20 Cont ID  
Sent By btrobaug Date 2007-12-20 Time 16:14 Rev Time 0.00
Received By btrobaug Date 2007-12-20 Time 12:54 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-08-16 Cont ID  
Sent By btrobaug Date 2006-08-16 Time 10:40 Rev Time 0.50
Received By btrobaug Date 2006-08-16 Time 10:13 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-07-23 Cont ID  
Sent By dpalmer Date 2006-07-23 Time 11:49 Rev Time 0.00
Received By dpalmer Date 2006-07-23 Time 11:18 Sent To M
Notes
2006-07-23 00:00:00***** UNSAT *****
  
 ** PLEASE KNOW, IT IS UNCLEAR WHERE
 PLANS FROM THE PREVIOUS SUBMITTED SETS
 ARE AS THOSE WERE REVIEWED BY MR. BILL
 TROBAUGH. PLEASE KNOW, THIS REVIEW IS
 BASED ON PLANS SUBMITTED.
  
 1) NOTE: PLEASE SEE 2004 RESIDENTIAL
 CODE R313 AND PLEASE SHOW A LAYOUT FOR
 ALL EXISTING BEDRMS WHICH WILL REQUIER
 ALL SD'S TO BE BROUGHT UP TO THE CURRENT
 CODE PER NFPA-72 11.5.1.1,11.8.3
 PLEASE INDICATE IF THESE ARE GOING TO BE
 NEW OR ARE EXISTING MEETING THE CURRENT
 CODE AND BEING TIED INTO NEW SD'S SHOWN
 ON THESE PLANS.
  
 2) NOTE: PLEASE SEE 210.11C2, 220.16 AS
 THE MIN VA FOR WASHER/LAUNDRY IS NOT
 CORRECT. PLEASE ADJUST.
  
 3) NOTE: PLEASE CORRELATE ALL ELECTRICAL
 HEAT FOR AHU'S WITH MECHANCIAL PLANS.
 PLEASE SEE KW RATINGS DO NOT MATCH. THIS
 WILL AFFECT ELECTRICAL CALCUALATIONS.
 PLEASE ALSO SEE 424.3B FOR MIN OCP
 REQUIRED @125% FOR HEAT STRIPS.
 PLEASE ADJUST CALCULATIONS PER 220.31B.
  
 4) NOTE: PLEASE SEE MANY GEN LIGHTING
 CIRCUITS ARE BEING SHOWN WITH A LOAD OF
 1500 VA ON 15A CIRCUITS, HOWEVER SHOWS
 #12?? PLEASE KNOW, A MAX OF 1440VA IS
 PERMITTED ON A 15A CIRCUIT, UNLESS THESE
 ARE INDEED 20A CIRCUITS AS #12 IS
 TYPICALLY FOR 20A CIRCUITS? PLEASE KNOW,
 IF CIRCUIT IS GOING TO BE 20A, THEN A
 PERMITTED LOAD OF 1920VA IS PERMITTED.
 PLEASE CLARIFY AND COORELATE WHICH ONES.
 240.4,310.16, FBC 106.1.2
  
 5) NOTE: PLEASE CLARIFY THE AMOUNT OF
 SMALL APPLIANCE CIRCUITS BEING SHOWN??
 PLEASE SEE PANEL SCHEDULE SHOWS ONE SM
 APPL AND ONE GFI APPL, ALTHOUGH THERE
 ARE WHAT SEEMS TO BE SMALL APPL CIRCUITS
 ON 3RD FLR ALONG WITH FRIG. PLEASE SEE
 PANEL SCHEDULE ONLY SHOWS ONE FRIG.
 PLEASE SEE 210.11C1,210.52B1,220.16 AS A
 MIN OF 1500VA IS REQUIRED FOR "EACH" OF
 SMALL APPPLIANCE CIRCUITS PROVIDE AND A
 MIN OF TWO ARE REQUIRED IN KITCHEN ON
 FIRST FLR.
 PLEASE ALSO SEE THAT THE DINING RM
 RECEPTS SHALL ALSO BE FIGURED PER ABOVE
 CODES NOTED. PLEASE ADJUST.
  
 6) NOTE: PLEASE SEE THE FOLLOWING CODES
 SHALL BE SPECIFIED ON PLANS.
 NFPA-70 (NEC) 2002 NAD NFPA-72 2002.
 PLEASE KNOW, PLANS ONLY MENTIONS TO
 NEC.
 106.1.2
  
 7) NOTE: PLEASE SEE REDLINED PLANS FOR
 MISSING RECEPT ALONG WALL IN MASTER
 BEDRM.
 210.52
  
 8) NOTE: PLEASE SEE CIRCUITS ON PANEL
 SCHEDULE SHALL BE SPECIFIC TO RMS AND
 AREAS IN WHICH THEY FEED.
 IE: MASTER BEDRM LTS, LIVING RM RECEPTS
 ETC. IT IS KNOWN, THAT CIRCUITS WILL BE
 REVISED DURING THE CONSTRUCTION PROCESS,
 HOWEVER CIRCUITS SHALL BE SPECIFIC AT
 THIS TIME. 408.4.
 PLEASE ALSO BE SURE TO LIST ALL THE
 REQUIRED ARC FAULT PROTECTED CIRCUITS ON
 PANEL SCHEDULE. 210.12B, 408.4
  
 9) NOTE: PLEASEGO OVER CALCULATIONS,
 AS THE LOAD SHOWN AFTER TAKING THE
 DE-RATINGS SHOWS 190A'S. PLEASE KNOW,
 LOADS FOR A/ C ARE NOT SHOWN AS NEEDED
 AND SHOWN ON MECHANICAL PLANS, ALONG
 WITH MIN SM APPL/DINING LOADS ETC.
 PLEASE SEE 90.8 AS THE CODEREQUIRES
 SPACE FOR FUTURE LOADS ETC.
 ** PLEASE KNOW, IF LOAD EXCEEDS ANY
 FURTHER THAN SHOWN A LARGER SERVICE MAY
 BE REQUIRED. PLEASE CHECK CALCULATIONS
 AS SHOWN.
  
 10) NOTE: PLEASE SHOW THE LOCATION OF
 THE 200A DISCONNECT AS SHOWN ON RISER.
 110.26,240.24
  
 11) NOTE: PLEASE SEE MISSING LT REQUIRED
 FOR AHU(S) ON FIRST FLR PER 210.70.
 PLEASE SEE 3RD FLR AHU MISSING RECEPT IN
 ATTIC AS LT IS SHOWN. 210.63
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-12-16 Cont ID  
Sent By btrobaug Date 2005-12-16 Time 09:14 Rev Time 0.50
Received By btrobaug Date 2005-12-16 Time 07:41 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2007-12-12 Cont ID  
Sent By adarroug Date 2007-12-12 Time 15:50 Rev Time 0.00
Received By adarroug Date 2007-12-12 Time 15:50 Sent To Z
Notes
2007-12-12 15:50:55TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2007-09-12 Cont ID  
Sent By adarroug Date 2007-09-12 Time 10:34 Rev Time 0.00
Received By adarroug Date 2007-09-12 Time 10:34 Sent To M
Notes
2007-09-12 10:34:43TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-05-17 Cont ID  
Sent By adarroug Date 2007-05-17 Time 15:11 Rev Time 0.00
Received By adarroug Date 2007-05-17 Time 15:11 Sent To B
Notes
2007-05-17 15:11:35TO "LMARTINEZ" DESK/NEW ROOF

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-05-04 Cont ID  
Sent By adarroug Date 2007-05-04 Time 13:36 Rev Time 0.00
Received By adarroug Date 2007-05-04 Time 13:36 Sent To B
Notes
2007-05-04 13:37:00TO "LMARTINEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-09-23 Cont ID  
Sent By adarroug Date 2006-09-23 Time 16:28 Rev Time 0.00
Received By adarroug Date 2006-09-23 Time 16:28 Sent To B
Notes
2006-09-23 00:00:00TO "ALANGE" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-08-31 Cont ID  
Sent By adarroug Date 2006-08-31 Time 16:22 Rev Time 0.00
Received By adarroug Date 2006-08-31 Time 16:22 Sent To B
Notes
2006-08-31 00:00:00TO "ALANGE" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-08-24 Cont ID  
Sent By adarroug Date 2006-08-24 Time 11:28 Rev Time 0.00
Received By adarroug Date 2006-08-24 Time 11:28 Sent To Z
Notes
2006-08-24 00:00:00TO "Z" BOX/RESUB--NEW SHEETS

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-08-11 Cont ID  
Sent By mmiller Date 2006-08-11 Time 14:19 Rev Time 0.00
Received By mmiller Date 2006-08-11 Time 14:19 Sent To E
Notes
2006-08-11 00:00:00SENT TO BT DESK/ RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-07-18 Cont ID  
Sent By adarroug Date 2006-07-18 Time 10:44 Rev Time 0.00
Received By adarroug Date 2006-07-18 Time 10:44 Sent To E
Notes
2006-07-18 00:00:00TO "BTROBAUGH" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-07-07 Cont ID  
Sent By adarroug Date 2006-07-07 Time 16:49 Rev Time 0.00
Received By adarroug Date 2006-07-07 Time 16:49 Sent To Z
Notes
2006-07-07 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-12-10 Cont ID  
Sent By adarroug Date 2005-12-10 Time 09:45 Rev Time 0.00
Received By adarroug Date 2005-12-10 Time 09:45 Sent To E
Notes
2005-12-10 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-01-06 Cont ID  
Sent By alange Date 2006-01-06 Time 08:25 Rev Time 0.00
Received By alange Date 2005-11-30 Time 14:00 Sent To  
Notes
2005-11-30 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 4 Status N Date 2007-12-21 Cont ID  
Sent By tgordon Date 2007-12-21 Time 08:09 Rev Time 0.20
Received By tgordon Date 2007-12-21 Time 08:09 Sent To P
Notes
2007-12-21 08:10:15REVISION TO BUILDING PLANS NOT MECH.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-09-13 Cont ID  
Sent By tgordon Date 2007-09-13 Time 11:09 Rev Time 0.30
Received By tgordon Date 2007-09-13 Time 11:09 Sent To  
Notes
2007-09-13 11:10:35REVISION TO MECH. PLANS AND ENERGY CAL'S.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-07-24 Cont ID  
Sent By tgordon Date 2006-07-24 Time 14:21 Rev Time 0.20
Received By tgordon Date 2006-07-24 Time 14:21 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-12-16 Cont ID  
Sent By tgordon Date 2005-12-16 Time 10:31 Rev Time 0.30
Received By tgordon Date 2005-12-16 Time 10:31 Sent To P
Notes
2005-12-16 00:00:00*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE ON
 FORM 600A-04 (2004) PER FBC 13-600 .
  
 2) AND PLEASE HAVE THE ENERGY CAL'S.
 SIGHED BY THE OWNER OR AGENT.
  
 3) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-12-31 Cont ID  
Sent By jleech Date 2007-12-31 Time 08:25 Rev Time 0.00
Received By jleech Date 2007-12-31 Time 08:25 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-07-25 Cont ID  
Sent By jleech Date 2006-07-25 Time 08:24 Rev Time 0.00
Received By jleech Date 2006-07-25 Time 08:24 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-12-20 Cont ID  
Sent By jleech Date 2005-12-20 Time 10:05 Rev Time 0.50
Received By jleech Date 2005-12-20 Time 10:05 Sent To B
Notes
2005-12-20 00:00:00DENIED;
 1.W/M AND L/T ARE REQUIRED TO DISCHARGE
 DOWN STREAM OF THE FIRST FLOOR BATHROOM
 GROUP. FBC-2004 PLUMBING SEC.909.1.
 2.SINK ON 3RD FLOOR TO DRAIN DOWN STREAN
 OF THE OF THE SECOND FLOOR BATHROOM
 GROUP. SEC.909.1.
 3.DRAIN REQUIRED FOR ICE MACHINE IN
 KITCHEN, IF DRAIN NOT REQUIRED SUBMIT
 MANUFACTURE CUT SHEET.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  

Review Stop Z ZONING
Rev No 4 Status P Date 2007-12-17 Cont ID  
Sent By choops Date 2007-12-17 Time 09:32 Rev Time 0.00
Received By choops Date 2007-12-17 Time 09:32 Sent To E
Notes
2007-12-17 09:34:14***APPROVED - REVISION - ADDED ELECTRICAL OUTLETS AND
 WATER HEATER***
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 3 Status N Date 2006-08-26 Cont ID  
Sent By mmclean Date 2006-08-26 Time 07:13 Rev Time 0.00
Received By mmclean Date 2006-08-26 Time 07:13 Sent To I
Notes
2006-08-26 00:00:00NOTE: THE PERMIT WAS REVIEWD 7/17/06 AND
 APPROVED. SEE ATTACHED SURVEYS.

Review Stop Z ZONING
Rev No 2 Status P Date 2006-07-17 Cont ID  
Sent By mmclean Date 2006-07-17 Time 07:56 Rev Time 0.00
Received By mmclean Date 2006-07-17 Time 07:56 Sent To I
Notes
2006-07-17 00:00:00NOTE: THE SETBACK FOR THE PROPOSED
 ADDITION IS 5FT(WEST) AND 10FT(EAST).THE
 ADDITION WILL SETBACK IN .2" FROM THE
 EXISTING 4.8FT SETBACK (WEST). THE
 PROPOSED A/C UNIT SHALL NOT BE CLOSER
 THAN 1FT FROMSIDE PROPERTY LINE.
  
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2005-12-09 Cont ID  
Sent By mmclean Date 2005-12-09 Time 17:30 Rev Time 0.00
Received By mmclean Date 2005-12-09 Time 17:30 Sent To I
Notes
2005-12-09 00:00:00DENIED,
 1. MUST PROVIDE THE SIDE SETBACKS OF THE
 PROPOSED ADDITION FROM PROPERTY LINE ON
 THE TWO COPY OF CURRENT SURVEYS.
  
 NOTE: SIDE: 5FT MINIMUM, 15FT TOTAL.
  
 NOTE: THE REF. ON 3RD FLOOR MUST BE AN
 U/C REF.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720