| 2005-12-01 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT:05111031 |
| | ADD: 2480 PRESIDENTIAL WAY # 1401 |
| | CONT:WILDES BUILDERS |
| | TEL: (561)833-2023 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | 1) PLANS, SPECIFICATIONS,REPORTS OR |
| | OTHER DOCUMENTS PREPARED BY THE DESIGN |
| | PROFESSIONAL AND BEING FILED FOR PUBLIC |
| | RECORD SHALL HAVE THE SIGNATURE AND |
| | SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| | TO THE DOCUMENT. |
| | FL STATE STAT: 61G15-23.002 ENGINEERS |
| | FL ATATE STAT: 61G16.003 ARCHITECTS |
| | |
| | 2) PLANS SHALL ALSO HAVE THE DATE |
| | PLANS WERE SIGNED & SEALED. |
| | |
| | 3) TYPE I/ TYPE II BUILD/ COMBUSTIBLES |
| | 603.1 ALLOWABLE MATERIALS. |
| | COMBUSTIBLE MATERIALS SHALL BE PERMITTED |
| | IN BUILDINGS OF TYPE I OR II |
| | CONSTRUCTION IN THE FOLLOWING |
| | APPLICATIONS AND IN ACCORDANCE WITH |
| | SECTIONS 603.1.1 THROUGH 603.1.3 : |
| | 1. FIRE-RETARDANT-TREATED WOOD SHALL BE |
| | PERMITTED IN: |
| | 1.1. NONBEARING PARTITIONS WHERE THE |
| | REQUIRED FIRE-RESISTANCE RATING IS 2 |
| | HOURS OR LESS. |
| | 1.2. NONBEARING EXTERIOR WALLS WHERE NO |
| | FIRE RATING IS REQUIRED. |
| | |
| | 4)A) THE USE AND OCCUPANCY, IN |
| | ACCORDANCE |
| | WITH THE PROVISIONS OF CHAPTER 3 . |
| | 4B) THE TYPE OF CONSTRUCTION AS DEFINED |
| | IN CHAPTER 6 . |
| | 4C)THE DESIGN OCCUPANT LOAD. |
| | 4D) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| | PROVIDED, WHETHER THE SPRINKLER SYSTEM |
| | IS REQUIRED. |
| | 4E) ANY SPECIAL STIPULATIONS AND |
| | CONDITIONS OF THE BUILDING PERMIT. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |