Plan Review Details - Permit 05111031
Plan Review Stops For Permit 05111031
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-02-16 Cont ID  
Sent By jwitmer Date 2006-02-16 Time 07:38 Rev Time 0.77
Received By jwitmer Date 2006-02-15 Time 16:18 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-12-07 Cont ID  
Sent By jwitmer Date 2005-12-01 Time 10:47 Rev Time 0.77
Received By jwitmer Date 2005-12-01 Time 10:47 Sent To  
Notes
2005-12-01 00:00:00BUILDING PLAN REVIEW
 PERMIT:05111031
 ADD: 2480 PRESIDENTIAL WAY # 1401
 CONT:WILDES BUILDERS
 TEL: (561)833-2023
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 1) PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 2) PLANS SHALL ALSO HAVE THE DATE
 PLANS WERE SIGNED & SEALED.
  
 3) TYPE I/ TYPE II BUILD/ COMBUSTIBLES
 603.1 ALLOWABLE MATERIALS.
 COMBUSTIBLE MATERIALS SHALL BE PERMITTED
 IN BUILDINGS OF TYPE I OR II
 CONSTRUCTION IN THE FOLLOWING
 APPLICATIONS AND IN ACCORDANCE WITH
 SECTIONS 603.1.1 THROUGH 603.1.3 :
 1. FIRE-RETARDANT-TREATED WOOD SHALL BE
 PERMITTED IN:
 1.1. NONBEARING PARTITIONS WHERE THE
 REQUIRED FIRE-RESISTANCE RATING IS 2
 HOURS OR LESS.
 1.2. NONBEARING EXTERIOR WALLS WHERE NO
 FIRE RATING IS REQUIRED.
  
 4)A) THE USE AND OCCUPANCY, IN
 ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3 .
 4B) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6 .
 4C)THE DESIGN OCCUPANT LOAD.
 4D) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 4E) ANY SPECIAL STIPULATIONS AND
 CONDITIONS OF THE BUILDING PERMIT.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2006-02-08 Cont ID  
Sent By jleahy Date 2006-02-07 Time 16:48 Rev Time 0.45
Received By jleahy Date 2006-02-07 Time 16:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2006-01-12 Cont ID  
Sent By jleahy Date 2006-01-12 Time 10:49 Rev Time 0.30
Received By jleahy Date 2006-01-12 Time 10:49 Sent To  
Notes
2006-01-12 00:00:00WORK IS COMPLETE AND HAS BEEN INSPECTED
  
 PERMIT HAS BEEN FINALED.JL

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2006-01-12 Cont ID  
Sent By jleahy Date 2005-12-13 Time 09:49 Rev Time 0.45
Received By jleahy Date 2005-12-02 Time 10:08 Sent To  
Notes
2005-12-02 00:00:00NEED PANEL SCHEDULE,SHOW TYPE OF PANEL
  
 NOTES ON PLAN SAY CONTRACTOR REPLACED
 ALL WIRING IN UNIT PLEASE SHOW ALL WORK
 DONE ON PLANS.
  
 IF ALL WIRING WAS REPLACED THEN GFI AND
 ARC FAULTS ARE REQUIRED.
  
 PLEASE SHOW ALL WORK.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-02-10 Cont ID  
Sent By mwennerg Date 2006-02-10 Time 14:13 Rev Time 0.00
Received By mwennerg Date 2006-02-10 Time 14:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-12-02 Cont ID  
Sent By mwennerg Date 2005-12-02 Time 14:50 Rev Time 0.00
Received By mwennerg Date 2005-12-02 Time 14:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-02-03 Cont ID  
Sent By adarroug Date 2006-02-03 Time 16:11 Rev Time 0.00
Received By adarroug Date 2006-02-03 Time 16:11 Sent To  
Notes
2006-02-03 00:00:00TO "BOB"#13

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-12-02 Cont ID  
Sent By mwennerg Date 2005-12-02 Time 14:52 Rev Time 0.00
Received By mwennerg Date 2005-11-30 Time 13:19 Sent To  
Notes
2005-11-30 00:00:00TO "BOB"#3

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-02-11 Cont ID  
Sent By pschmitz Date 2006-02-11 Time 09:34 Rev Time 0.00
Received By pschmitz Date 2006-02-11 Time 09:28 Sent To  
Notes
2006-02-11 00:00:00 
 PLUMBING PLAN REVIEW EXAMINER
 PAUL SCHMITZ 561-805-6692
 [email protected]
 FBC PLUMBING 2004
 FBC FUEL GAS 2004
 FBC 2004 BUILDING CH 11
 1) SHT EP-1
 PLUMBING ISOMETRIC REMOVED FROM NEW
 SHEETS.
 SEC 105 PERMITS REQUIRED
 SEPERATE PLUMBING PERMIT REQUIRED.
 END OF COMMENTS, QUESTIONS 561-805-6692

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-11-30 Cont ID  
Sent By jleech Date 2005-11-30 Time 13:52 Rev Time 0.50
Received By jleech Date 2005-11-30 Time 13:52 Sent To  
Notes
***NONE***