Plan Review Details - Permit 05110890
Plan Review Stops For Permit 05110890
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-04-14 Cont ID  
Sent By jwitmer Date 2006-04-14 Time 15:18 Rev Time 1.55
Received By jwitmer Date 2006-04-14 Time 15:18 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-04-06 Cont ID  
Sent By jwitmer Date 2006-04-06 Time 11:09 Rev Time 1.11
Received By jwitmer Date 2006-04-06 Time 10:52 Sent To  
Notes
2006-04-06 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05110890
 ADD: 5400 S DIXIE
 CONT:PLAN REVIEW ONLY
 TEL: (954)816-3351
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) TRUSS TIE DOWNS- MISSING THE FL
 COVERSHEET
  
 B)PRE FABRICATED CANOPIES- NOT COVERED
 UNDER THIS PERMIT- NO INFORMATION
 SUBMITTED FOR ENGINEERED SYSTEM.
 C) METAL ROOF NON-STRUCTURAL SEE
 SUBMITTAL SHEET. FLORIDA COVERSHEET
 SUBMITTED WITH THE WRONG BACK UP
 DOCUMENTATION.
 D) BAHAMA SHUTTERS- DECORATIVE ,NOA NOT
 REQUIRED BUT ENGINEERING IS REQUIRED TO
 ENSURE THIS SHUTTER WILL NOT ITSELF
 BECOME A MISSLE IN A HIGH WIND EVENT.
 THIS SHUTTER IS TO REMAIN FIXED IN THE
 OPEN POSITION, NEVER TESTED FOR WIND,
 PROVIDE ENGINEERING INDICATING SHUTTER
 ATTACHMENT TO THE BUILDING FIXED IN THE
 OPEN POSITION FOR 140 MPH.
  
  
 2) THE PRE FABRICATED CANOPY SHOULD
 HIGHLIGHT WHAT SYSTEM TO BE USED. PLANS
 INDICATE FOOTERS BUT THE COLUMNS BY
 OTHERS, DOES THIS MEAN THAT THE COLUMNS
 WILL BE BOLTED TO THE TOP OF THE FOOTER.
 NO PLANS SUBMITTED CANOPY TO BE
 CONSIDERED A SEPERATE PERMIT.
  
 3)COMPLIED.
  
 4) SEE COMMENT 1D
  
 5)COMPLIED.
 NEW COMMENTS
 6) SUBMITTAL PRECAST LIGHT POLES ARE A
 ENGINEERED SYSTEM, REQUIES SEALED PLANS.
 PLANS, SPECIFICATIONS,REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
  
  
 BUILDING PLAN REVIEW
 PERMIT: 05110890
 ADD: 5400 S DIXIE
 CONT:PLAN REVIEW ONLY
 TEL: (954)816-3351
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
  
 A) TRUSS TIE DOWNS ARE MISSING THE
 FLORIDA COVER SHEET.
  
 B) PRE FABRICATED CANOPIES- TRUE THEY DO
 NOT REQUIRE FL PRODUCT APPROVAL, THEY DO
 REQUIRE ENGINEERED DRAWINGS AND ARE NOT
 COVERED UNDER THIS PERMIT BUT A SEPERATE
 PERMIT.
  
 C) METAL ROOF NON-STRUCTURAL. THE
 FLORIDA COVERSHEET SUBMITTED INDICATES
 THE NOA THAT TIES TO THIS REPORT. A
 DIFFERENT NOA WAS SUBMITTED.
  
 D) BAHAMA SHUTTERS- SEE COMMENT# 4.
  
 2) THE PRE FABRICATED CANOPY SHOULD
 HIGHLIGHT WHAT SYSTEM TO BE USED. PLANS
 INDICATE FOOTERS BUT THE COLUMNS BY
 OTHERS, DOES THIS MEAN THAT THE COLUMNS
 WILL BE BOLTED TO THE TOP OF THE FOOTER?
 THIS WAS THE FIRST SET OF COMMENTS , NO
 ENGINEERING WAS SUBMITTED. A SEPERATE
 PERMIT IS REQUIRED FOR AWNINGS AND
 CANOPIES.
  
 3) COMPLIED.
  
 4) THE BAHAMA STYLE SHUTTERS DO NOT NEED
 STATE APPROVAL BUT THAT THE INSTALLATION
 WILL BE FOR A FIXED OPEN POSITION DURING
 A HIGH WIND EVENT. THIS TYPE OF
 INSTALLATION WILL REQUIRE ENGINEERING
 FOR THE INSTALLATION OF THE BAHAMA
 SHUTTER INSTALLED AS A FIXED SHUTTER IN
 THE OPEN POSITION. MUST MEET THE 140 MPH
 TO NOT BECOME A MISSLE ITSELF.
  
 5)COMPLIED.
  
 NEW COMMENT.
 6) SITE LIGHT POLES ARE AN ENGINEERED
 SYSTEM REQUIRING SEALED PLANS.
 RC ENGINEERING.
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-01-26 Cont ID  
Sent By jwitmer Date 2006-01-26 Time 16:20 Rev Time 1.55
Received By jwitmer Date 2006-01-26 Time 16:20 Sent To  
Notes
2006-01-26 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05110890
 ADD: 5400 S DIXIE
 CONT:PLAN REVIEW ONLY
 TEL: (954)816-3351
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) TRUSS TIE DOWNS
 B) PRE FABRICATED CANOPIES
 C) METAL ROOF NON-STRUCTURAL
 D) BAHAMA SHUTTERS
 THE AEICOR METAL ROOF SUBMITED HAS A
 MAXIMUM DESIGN PRESSURE OF -37.5 WHERE
 AS IN ZONE 3 A -68.1.SEE SYSTEMS
 LIMITATION # 1. ALL RATIONAL ANALYSIS
 COMPUTATION SHALL BE PREPARED, SIGNED,
 SEALED BY A FL REGISTERED PROFESSIONAL
 ENGINEER , REGISTERED ARCHITECT OR
 REGISTERED ROOF CONSULTANT.SEE
 STRUCTURAL PLAN ZONE 3 -121.9 TAKEN AS A
 "C" EXPOSURE.
  
 2) THE PRE FABRICATED CANOPY SHOULD
 HIGHLIGHT WHAT SYSTEM TO BE USED. PLANS
 INDICATE FOOTERS BUT THE COLUMNS BY
 OTHERS, DOES THIS MEAN THAT THE COLUMNS
 WILL BE BOLTED TO THE TOP OF THE FOOTER/
  
 3) NORTH ENTRY, HANDICAPPED ACCESS AISLE
 HAS A BOLLARD DIRECTLY IN THE CENTER OF
 THE WALKWAY FOR EACH ACCESS AISLE.
  
 4) THE BAHAMA STYLE SHUTTERS DO NOT NEED
  
 STATE APPROVAL BUT THAT THE INSTALLATION
 WILL BE FORE A FIXED OPEN POSITION
 DURING A HIGH WIND EVENT.
  
 5)THE SITE PLAN A1.01 DOES NOT INDICATE
 THE LOCATION OF THE CANOPY ON THE SOUTH
 SIDE OF THE BUILDING. A3.01 DETAIL 5 THE
 CANOPY APPEARS TO HAVE A DRIVE THROUGH
 THE WAY THE CURBS ARE DETAILED, WHEREAS
 THE SITE PLAN SHOWS PARKING SPACES,
 PLEASE CLARIFY.
  
 THIS REVIEW WILL CONTINUE 1-30-06

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-06-24 Cont ID  
Sent By dpalmer Date 2006-06-24 Time 10:27 Rev Time 0.00
Received By dpalmer Date 2006-06-24 Time 10:18 Sent To PC
Notes
2006-06-24 00:00:00REV, SHOWS A 1200MAIN FEEDING EXISTING
 MDP.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-06-08 Cont ID  
Sent By dpalmer Date 2006-06-08 Time 18:54 Rev Time 0.00
Received By dpalmer Date 2006-06-08 Time 18:35 Sent To PC
Notes
2006-06-08 00:00:00**** UNSAT ****
  
 1) NOTE: PLEASE CORRELATE PANEL
 SCHEDULES AND RISER SUBMITTED.
 PLEASE SEE THE MDP STILL IS SHOWN
 WITHOUT A MCB AS REQUIRED AND REDLINED
 ON ALL PREVIOUS PLANS.
 PLEASE SEE THE RISER NOW SHOWS WHAT
 APPEARS TO BE A NEW 1200 CB MAIN,
 HOWEVER IS SHOWN AS EXISTING, YET THIS
 WAS NOT SHOWN ON ANY OF THE PREVIOUS
 PLANS AND HAS NOT BEEN REVISED UNDER THE
 MAIN BUILDING PLANS AS OF THIS REVIEW.
 PLEASE ALSO SEE THIS MAIN 1/1 DOES NOT
 INDICATE ANY FEEDERS TO THE MLO MDP.
 215.5, 230.70 ETC
  
 2) NOTE: PLEASE KNOW IT SHALL BE
 CONFIRMED WITH BUILDING REVIEWER, BUT
 THE TRASH COMPACTOR MAY BE REQUIRED TO
 BE UNDER A SEPARATE PERMIT.
 THIS WILL BE CONFIRMED ON 6/13 PLEASE
 KNOW, IF THIS IS THE SITUATION, THEN A
 PERMIT AND PLANS MUST BE ISSUED FIRST.
 PLEASE KNOW IF NOT THEN PLEASE BE SURE
 TO REVISED BASE BUILDING PLANS FOR THE
 ABOVE COMMENTS BEFORE SUBMITTING
 REVISIONS FOR THE SITE PLANS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-03-30 Cont ID  
Sent By dpalmer Date 2006-03-30 Time 09:53 Rev Time 0.00
Received By dpalmer Date 2006-03-30 Time 09:20 Sent To  
Notes
2006-03-30 00:00:00PASSED PENDING, SUBMITTAL OF WIND LOAD
 CALCULATIONS FOR BUIDLING REVIEW AND
 PASSING OF THOSE WIND LOAD CALCUALTIONS.
 THESE MUST BE SIGNED, DATED AND SEALED
 BY A FLORIDA LICENSED PE.
 471.025
  
  
 ** NOTE BELOW ELECTRICAL PANEL PH,
 REMOVED AND INITIALED AS NOTE NO LONGER
 APPLIES.
 NOTE MENTIONED, "EXISITNG PANEL AND NO
 LOAD CHANGE", THIS WAS NOT POSSIBLE AS
 NEW LOADS WERE ADDED FOR SITE LIGHTING
 AND BUILDING LIGHTING FIXTURES.
 LOADS ARE OK.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-12-24 Cont ID  
Sent By dpalmer Date 2005-12-24 Time 13:16 Rev Time 0.00
Received By dpalmer Date 2005-12-24 Time 12:19 Sent To  
Notes
2005-12-24 00:00:00**** UNSAT ****
  
 ** PLEASE KNOW, PLANS HAVE ONLY BEEN
 SUBMITTED FOR "PLAN REVIEW" ONLY AND NOT
 FOR PERMIT.
  
 1)NOTE: PLEASE SUBMIT THE SITE LIGHTING
 POLES/FIXTURES CALCULATIONS AT THIS
 TIME.
 THIS WILL BE REVIEWED BY BLDG REVIEW.
  
 2)NOTE: PLEASE SE BLDG NOTES AS SEALED
 SURVEY IS A PHOTOCPOY THE SURVEYOR'S
 ORIGINAL SIGNATURE. PLEASE SEE FS
 472.025 WHICH REQUIRES AN ORIGINAL
 SIGNATURE.
  
 3)NOTE: PLEASE SEE PANEL "PA", PLEASE BE
 SURE TO CORRELATE WITH MAIN PLANS.
 PLEASE SEE PLANS MENTIONS, NO CHANGES TO
 LOAD, HOWEVER THIS CAN NOT BE POSSIBLE
 AS THESE NEW ELECTRICAL ITEMS DO NOT
 EXIST AT THIS TIME.
 PLEASE SEE NOTES UNDER MAIN PERMIT.
  
 4)NOTE: PLEASE SEE NEW ELECTRICAL
 LIGHTING SHOWN ON A-SHEETS WHICH IS NOT
 ON PLANS. PLEASE ALSO VERIFY WITH PLANS
 UNDER MAIN PERMIT WHICH DO NOT SEEM TO
 SHOW THESE.
 215.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW . IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2006-03-31 Cont ID  
Sent By mamini Date 2006-03-31 Time 15:25 Rev Time 0.50
Received By mamini Date 2006-03-31 Time 15:25 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2006-02-03 Cont ID  
Sent By mamini Date 2006-02-03 Time 13:55 Rev Time 1.00
Received By mamini Date 2006-02-03 Time 13:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-12-21 Cont ID  
Sent By mcarsill Date 2005-12-21 Time 10:05 Rev Time 0.00
Received By mcarsill Date 2005-12-21 Time 09:55 Sent To  
Notes
2005-12-21 00:00:001. BUILDING ADDRESS REQUIRED ON PROPER
 ELEVATION. A MINIMUM OF AT LEAST 6" HIGH
 NUMBERS ARE REQUIRED.
  
 2. EXISTING AUTOMATIC DOOR SHALL MEET
 THE CODE REQUIREMENTS FOR POWERED
 OPERATED DOORS.
  
 3. ALL CONSTRUCTION, RENOVATION, AND
 DEMOLITION SHALL COMPLY WITH NFPA 241.
  
 4. ALL EXITS ARE TO REMAIN CLEAR AND
 UNOBSTRUCTED.
  
 5. WORK IS SUBJECT TO FIELD INSPECTION.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-06-21 Cont ID  
Sent By adarroug Date 2006-06-21 Time 12:43 Rev Time 0.00
Received By adarroug Date 2006-06-21 Time 12:43 Sent To E
Notes
2006-06-21 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-05-26 Cont ID  
Sent By adarroug Date 2006-05-26 Time 15:40 Rev Time 0.00
Received By adarroug Date 2006-05-26 Time 15:40 Sent To B
Notes
2006-05-26 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-05-26 Cont ID  
Sent By adarroug Date 2006-05-26 Time 15:36 Rev Time 0.00
Received By adarroug Date 2006-05-26 Time 15:36 Sent To E
Notes
2006-05-26 00:00:00TO 'E" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-04-13 Cont ID  
Sent By adarroug Date 2006-04-13 Time 16:28 Rev Time 0.00
Received By adarroug Date 2006-04-13 Time 16:28 Sent To B
Notes
2006-04-13 00:00:00TO "JWITMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-03-04 Cont ID  
Sent By adarroug Date 2006-03-04 Time 16:10 Rev Time 0.00
Received By adarroug Date 2006-03-04 Time 16:10 Sent To  
Notes
2006-03-30 00:00:00TO "COMM" BD#53
2006-03-04 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-03-04 Cont ID  
Sent By adarroug Date 2006-02-25 Time 16:09 Rev Time 0.00
Received By adarroug Date 2005-11-29 Time 10:25 Sent To  
Notes
2005-12-13 00:00:00TO "COMM" BD#25
2005-11-29 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-01-31 Cont ID  
Sent By pkrauss Date 2006-01-31 Time 15:45 Rev Time 0.00
Received By pkrauss Date 2006-01-31 Time 15:45 Sent To  
Notes
2006-01-31 00:00:00************PLAN CHECK ONLY***********
  
 NO MECHANICAL PLANS, CONTRACTOR OR SCOPE
 OF WORK INDICATED.PLEASE PROVIDE PLANS
 WITH MECHANICAL PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-03-18 Cont ID  
Sent By pschmitz Date 2006-03-18 Time 06:33 Rev Time 0.00
Received By pschmitz Date 2006-03-18 Time 06:33 Sent To  
Notes
2006-03-18 00:00:00PROVISO:
 BACK FLOW PREVENTER REQUIRED.
 SEPERATE PERMIT BY LICENSED PLUMBER.

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-02-25 Cont ID  
Sent By pschmitz Date 2006-02-25 Time 08:37 Rev Time 0.00
Received By pschmitz Date 2006-02-25 Time 08:34 Sent To  
Notes
2006-02-25 00:00:00PLUMBING PLAN REVIEW EXAMINER
 PAUL SCHMITZ 561-805-6692
 [email protected]
 FBC PLUMBING 2004
 FBC FUEL GAS 2004
 PROVISO
  
 SEPERATE PERMIT FOR INSTALLATION OF BACK
 FLOW PREVENTER.BY LICENSED PLUMBING
 CONTRACTOR.
  
 END OF COMMENTS, QUESTIONS 561-805-6692

Review Stop Z ZONING
Rev No 2 Status P Date 2006-03-15 Cont ID  
Sent By jroach Date 2006-03-15 Time 16:24 Rev Time 0.00
Received By jroach Date 2006-03-15 Time 16:24 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2006-02-01 Cont ID  
Sent By lshapiro Date 2006-02-01 Time 14:12 Rev Time 0.00
Received By lshapiro Date 2006-02-01 Time 15:56 Sent To  
Notes
2006-02-09 00:00:00THE GENERAL COMMERCIAL (GC) ZONING
 DISTRICT REQUIRE A MINIMUM 15-FOOT
 SETBACK FROM RESIDENTIALLY ZONED
 PROPERTY.THE NEW STRUCTURE OVER THE
 DROP OFF AREA IS WITHIN THE REQUIRED
 15-FOOT SETBACK.PLEASE CONTACT ME SO
 THAT WE CAN DISCUSS.
2006-02-01 00:00:00THE FOLLOWING INFORMATION SHALL BE
 PROVIDED ON THE REVISED PLANS.
 1. SHOW THE LOCATION OF UTILITY EASEMENT
 AND ALL UTILITY LINES ON THE PROPERTY
 INCLUDING UNDERGROUND AND OVERHEAD
 FACILITIES ON THE SITE PLAN AND
 LANDSCAPE PLANS.
 2. THE MEDIAN ON THE PLANS ARE NOT
 LOCATED IN THE CORRECT LOCATION.REVISE
 THE SITE AND LANDSCAPE PLANS AND SHOW
 THE LOCATION OF THE MEDIAN.
 3. INGRESS FROM BUNKER RANCH ROAD.
 3.A. THE DRIVEWAY FROM BUNKER RANCH ROAD
 SHALL BE RIGHT OUT ONLY WITHOUT INGRESS
 INTO THE SITE.THE DRIVEWAY AT PUTNAM
 RANCH WILL BE LEFT OUT ONLY, BUT WITH
 INGRESS PERMITTED PREFERABLY FROM
 EASTBOUND PUTNAM RANCH.
 4. LANDSCAPE PLANS
 4A. SHOW ALL EXISTING PLANTS AND TREES
 INCLUDING THE SPECIES AND CALIPER SIZE.
 4B. PROVIDE THE FOLLOWING ADDITIONAL
 INFORMATION ON THE PLANS.
 4B.(1). PROVIDE A TABLE INDICATING THE
 NUMBER OF TREES PROVIDED.ONE SHADE
 TREE IS REQUIRED FOR EACH 1,600 SQUARE
 FEET OF OPEN SPACE AND ONE FLOWERING
 TREE FOR EACH 6,400 SQUARE FEET.THE
 CALCULATIONS MAY INCLUDE THOSE USED FOR
 BUFFERING SCREENING.
 4B. (2) ONE SHRUB SHALL BE PLANTED FOR
 EVERY 500 SQUARE FEET OF OPEN SPACE.
 4C. PROVIDE TREES, SHRUBS, AND HEDGES
 OUTSIDE OF THE UTILITY EASEMENT ALONG
 THE EAST PROPERTY LINE.THE TREES AND
 SHRUBS SHALL BE EVERGREEN AND SHORT
 ENOUGH NOT TO AFFECT THE OVERHEAD LINES.
 4D. PROVIDE THE CORRECT LANDSCAPE
 CALCULATIONS FOR THE FOLLOWING:
 4.D.(1). SHADE OR FLOWERING TREES SHALL
 BE PLANTED EVERY 30 FEET IN THE FIVE
 FOOT LANDSCAPE BUFFER ALONG
 RIGHT-OF-WAY.
 4.D.(2). OFF-STREET PARKING REQUIRES 10
 SQUARE FEET OF LANDSCAPING FOR EACH
 PARKING SPACE.REVISE THE LANDSCAPE
 PLAN AND DEMONSTRATE THE PLAN MEETS THE
 REQUIREMENT.
 4.D.(3).HEDGES SHALL BE PLANTED IN 2-3
 FOOT INTERVALS ALONG THE LANDSCAPE
 BUFFER ADJACENT TO THE EAST PROPERTY
 LINE.
 4.E. SHOW THE WALL ALONG THE EAST SIDE
 OF THE PROPERTY AND SECURITY WALL AND
 GATE ON THE EAST SIDE OF THE BUILDING
 THAT WILL PREVENT STORAGE AND
 CONGREGATION OF PERSONS AFTER HOURS AT
 THE REAR OF THE STRUCTURE (SEE MORE
 DETAILS OF SECURITY WALL/GATE BELOW).
 5. SECURITY WALL
 5.A. PROVIDE A MINIMUM 6 FOOT TALL WALL
 AND PROVIDE THE MATERIALS AND DETAILS ON
 THE SITE PLAN.
 5.B. PROVIDE 3 STRANDS OF BARBED WIRE AT
 THE TOP OF THE WALL AND GATE.THE
 BARBED WIRE SHALL BE MOUNTED VERTICALLY
 OR ANGLED INTERIOR TO THE ENCLOSURE.
 5.C. THE GATE SHALL BE AT LEAST 6 FEET
 HIGH AND SHALL BE TRANSPARENT (I.E.
 CHAIN-LINK) TO ALLOW POLICE TO VIEW
 AREAS BEHIND THE BUILDING DURING
 PATROLS.
 5.D. THE POLICE DEPARTMENT SUGGESTS
 UPGRADING THE SECURITY CAMARA SYSTEM FOR
 THE PARKING LOT AND MOUNT ON THE
 BUILDING TAPING 24 HOURS WITH MONITOR(S)
 IN AN INTERIOR OFFICE.
 6. DUMPSTER ENCLOSURE
 6.A. THE GATE ON THE ENCLOSURE SHALL BE
 AT AN EQUAL HEIGHT OR GREATER THAN THAT
 OF THE COMPACTOR.
 6.B. PROVIDE THE HEIGHT OF THE
 COMPACTOR.
 6.C. PROVIDE THE MINIMUM DIMENSIONS OF
 THE DUMPSTER/COMPACTOR ENCLOSURE ON THE
 SITE AND LANDSCAPE PLAN (SEE ATTACHED
 DIAGRAM).
 6.C.(1).THE MINIMUM AREA INSIDE THE
 ENCLOSURE IS 13 FEET 8 INCHES BY 13 FEET
 8 INCHES.
 6.C.(2). A ONE FOOT CLEARANCE IS
 REQUIRED BETWEEN THE PAD AND WALL
 ENCLOSURES.
 6.C.(3). A 10 FOOT STOP BAR, 1-FOOT 18
 INCHES FROM THE BACK OF THE WALL
 ENCLOSURE IS REQUIRED.
 6.C.(4). THE MINIMUM GATE OPENING WIDTH
 IS 12 FEET 6 INCHES.
 7. WALL ALONG EAST PROPERTY LINE.
 7.A. PROVIDE WALL DETAILS (TEXTURE,
 MATERIALS, CONSTRUCTION).
 7.B. MAKE SURE THE WALL IS NOT IN THE
 UTILITY EASEMENT.