Plan Review Details - Permit 05110841
Plan Review Stops For Permit 05110841
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-02-07 Cont ID  
Sent By shill Date 2006-02-07 Time 15:44 Rev Time 1.00
Received By shill Date 2006-02-07 Time 15:28 Sent To  
Notes
2006-02-07 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED
  
 2.)SHOW MANEUVERING CLEARANCE FOR THE
 FOLLOWING DOORS, FBC11-4.13.6, FIGURE
 25: EXAM ROOM 1, PUSH SIDE; WAITING ROOM
 PULL SIDE; OFFICE 104 PUSH SIDE
  
 3.)ARE ANY TENANT SEPARATIONS
 AFFECTED?
  
 4.)A1, DEMOLITION NOTES, ITEM 3 REFERS
 TO A RESIDENCE.ADDRESS.
  
 5.)NO EXITING INFORMATION WAS
 PROVIDED.HOW DOES THE CHANGE IN THE
 PLAN AFFECT MEANS OF EGRESS?SHOW
 COMPLIANCE WITH FBC10 ON THE PLAN.
  
 6.)DECLARE GOVERNING CODE.
  
 7.)INDEX REFERS TO A SHEET A3 WHICH IS
 NOT A PART OF THE PLAN SUBMITTED.
 ADDRESS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-01-04 Cont ID  
Sent By dpalmer Date 2006-01-04 Time 15:47 Rev Time 0.00
Received By dpalmer Date 2006-01-04 Time 15:47 Sent To I
Notes
2006-01-04 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE INDICATE THE CIRCUITING
 ON PLANS AND CORRELATE WITH A PANEL
 SCHEDULE TO BE SUBMITTED.
  
 PLEASE SEE 700.12E FOR CIRCUITING OF
 EM/EXT LTS.
 THE BRANCH CIRCUIT FEEDING THE UNIT
 EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
  
 2)NOTE: PLEASE SEE POSSIBLE FIRE REVIEW
 COMMENTS AS THE PLANS APPEAR TO SHOW THE
 SD'S AS 120V HARDWIRED. ARE THESE
 CONNECTED INTO FA SYSTEM OR PANEL?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-01-10 Cont ID  
Sent By mwennerg Date 2006-01-10 Time 13:39 Rev Time 0.00
Received By mwennerg Date 2006-01-10 Time 13:39 Sent To  
Notes
2006-01-10 00:00:00******PROVISO******
  
 1) SEPARATE SHOP DRAWINGS AND PERMITS
 REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL.
  
 2) A SINGLE EXIT IS ACCEPTABLE PROVIDED
 THAT COMPLIANCE WITH NFPA 101, 2003
 EDITION SEC. 38.2.4.3 IS MET.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLANS REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-02-07 Cont ID  
Sent By shill Date 2006-02-07 Time 16:14 Rev Time 0.00
Received By shill Date 2005-12-10 Time 13:40 Sent To  
Notes
2006-01-09 00:00:00TO "COMM" BD#1
2005-12-10 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-01-17 Cont ID  
Sent By hmoser Date 2006-01-17 Time 09:46 Rev Time 0.00
Received By hmoser Date 2006-01-17 Time 09:46 Sent To  
Notes
2006-01-17 00:00:00DEMOLITION ONLEY SUBMITED ON PLANS.PLANS
 FOR MECHANICAL DEMOLITION IS NOT
 REQUIRED.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732