Plan Review Details - Permit 05110838
Plan Review Stops For Permit 05110838
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-01-13 Cont ID  
Sent By amorse Date 2006-01-13 Time 08:41 Rev Time 0.50
Received By amorse Date 2006-01-13 Time 08:41 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-12-21 Cont ID  
Sent By amorse Date 2005-12-21 Time 14:53 Rev Time 1.00
Received By amorse Date 2005-12-21 Time 14:53 Sent To PC
Notes
2005-12-21 00:00:00 
  
 DENIED
  
 1) NEW NOA UNDER LIMITATION (1) EXCLUDES
 THE USE OF RATIONAL ANALYSIS TO
 DETERMINE ENHANCED FASTENING.
  
 NOTE: USING THE SIMPLIFIED METHOD IN THE
 2004 FBC TABLE 1609.6B 140 MPH EXPOSURE
 B. A 12/12 SLOPE WITH 10 SQ FT EFFECTIVE
 AREA HAS A WIND LOAD OF -41.2 WHICH THE
 NOA EXCEEDS BUT THE MEAN ROOF HEIGHT IS
 38 FT AND THE LOAD MUST BE ADJUSTED BY A
 FACTOR OF 1.05 = -43.26 WHICH NOW
 EXCEEDS THE NOA.
 CAN YOUR ENGINEER MEET THIS CRITERIA, IF
 NOT THIS PRODUCT WILL NOT BE ACCEPTED
  
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-11-22 Cont ID  
Sent By amorse Date 2005-11-22 Time 14:07 Rev Time 0.50
Received By amorse Date 2005-11-22 Time 14:07 Sent To PC
Notes
2005-11-22 00:00:00DENIED
  
 1) CONTRACTOR MUST SUBMIT 2 SIGNED AND
 SEALED COPIES OF ENHANCED FASTENING,
 REPAIR ENGINEERING
  
 2) THE STATEWIDE PRODUCT APPROVAL FOR
 THIS PRODUCT IS PENDING AND THE PERMIT
 CANNOT BE ISSUED WITHOUT IT
  
 NOTE: FL. ADMIN CODE RULE 9B-72 (IN
 EFFECT SINCE OCT. 1, 2003) REQUIRES THAT
 PRODUCTS HAVE STATEWIDE,LOCAL OR
 SITE-SPECIFIC PRODUCT APPROVAL.
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 (561)805-6716