Plan Review Details - Permit 05110836
Plan Review Stops For Permit 05110836
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-08-28 Cont ID  
Sent By jwitmer Date 2006-08-28 Time 07:40 Rev Time 0.00
Received By jwitmer Date 2006-08-28 Time 07:40 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-23 Cont ID  
Sent By jwitmer Date 2006-08-23 Time 16:13 Rev Time 2.20
Received By jwitmer Date 2006-08-23 Time 16:13 Sent To PC
Notes
2006-08-23 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05110836
 ADD: 1122 PALM BEACH LAKES
 CONT: POMEROY ELECTRIC, INC.
 TEL: (954)427-0705
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THE WIND LOAD CALCULATIONS INDICATE
 THE DESIGN CRITERIA AS ASCE 7-04. THE
 2004 FBC BUILDING USES ASCE 7-02 SEE
 CHAPTER 35 FOR REFRENCED STANDARDS.
  
 2) SHEET 2OF 7 S1 USES 8/3 WHICH SHOULD
 BE 9/3.
  
 3) SHEET 3OF 7 PAGES 37' POLE, (POLE
 TYPE I) INDICATE SOME TYPE OF TAMPERING
 WITH THE PRINTED NUMBERS. THE PRINTED OR
 TAMPERED NUMBERS REPRESENT A 37' POLE
 INSAND WHERE AS THE DIAGRAM AT LEFT
 INDICATES A 34'-0" OVERALL LENGTH.
 EMBEDMENT IN SAND.106.1.2*
  
 4) WHAT DOES EPA STAND FOR? WHY IS THE
 120 & 150 MPH WIND ZONES ELIMINATED
 WHEREAS THE TYPE II POLE HASA ALL 3
 CATAGORIES FILED IN? AGAIN TAMPERED
 WITH.106.1.2*
  
 5) SHEET POLE TYPE II, 37' EMBEDMENT IN
 ROCKWHY IS THERE A DIFERENCE IN WEIGHT
  
 IF BOTH POLE TYPE 1 & POLE TYPE II BOTH
 ARE 37' LONG, A 280 LB DIFFERENCE?
 106.1.2*
  
 6) THE ES-1 SHEEET DOES NOT INDICATE IF
 THE POLES TO BE USED ARE A 37' TYPE I
 POLE OR A 37' TYPE II POLE? ADDITIONAL
 INFORMATION? 106.1.2*
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-08-14 Cont ID  
Sent By dpalmer Date 2006-08-14 Time 18:01 Rev Time 0.00
Received By dpalmer Date 2006-08-14 Time 17:52 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-12-06 Cont ID  
Sent By dpalmer Date 2005-12-06 Time 09:34 Rev Time 0.00
Received By dpalmer Date 2005-12-06 Time 09:34 Sent To  
Notes
2005-12-06 00:00:00*** UNSAT ***
  
 1)NOTE: PLEASE SEE PERMIT APPLICATION
 HAS COME IN FOR NEW WIRING OF CARWASH,
 YET PLANS ALSO SUBMITTED FOR SITE
 LIGHTING.
 PLEASE SEE THAT ALL PLANS SUBMITTED FOR
 THIS JOB SITE MUST BE DONE BY THE
 ENGINEER OF RECORD.
 PLEASE BE SURE THAT ALL WIND LOADING
 CALCULATIONS ARE SUBMITTED WITH SITE
 LIGHTING.
  
 IF THIS PERMIT APPLICATION IS FOR SITE
 LIGHTING ONLY , PLEASE ADJSUT
 APPLICATION.
 PLEASE SEE THAT BLDG PERMIT NUMBER WHICH
 IS REFERENCED ON APPLICATION HAS NOT YET
 BEEN ISSUED.
 A PERMIT FOR ELECTRICAL WIRING OF BLDG
 CAN NOT BE ISSUED AT THIS TIME.
  
 PLEASE CORRELATE AND ADJUST APPLICATIONS
 FOR INTENDED WORK. IF THERE ARE ANY
 QUESTIONS, PLEASE DO NOT HESITATE ON
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2005-12-06 Time   Rev Time 0.00
Received By adarroug Date 2005-11-28 Time 16:49 Sent To  
Notes
2005-11-28 00:00:00TO "DPALMER" DESK