| Plan Review Stops For Permit 05110803 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2006-06-06 |
|
|
Cont ID |
|
| Sent By |
lursu |
Date |
2006-06-06 |
Time |
09:04 |
Rev Time |
0.00 |
| Received By |
lursu |
Date |
2006-06-06 |
Time |
09:04 |
Sent To |
|
|
| Notes |
| 2006-06-06 00:00:00 | PERMIT ATTACHED TO EXT #0001 ,2475 | | | MERCER AVE FOR THE BLDG 2( THREE STORY | | | OFFICE).IT WILL BE THE RESPONSIBILITY OF | | | THE DEVELOPER TO ASSIGN THE INTERIOR | | | UNITS NUMBERS. | | | BASED ON THE ADDRESSING GUIDE EACH | | | STRUCTURE SHALL BE ASSIGNED A NUMBER ( | | | SITE ADDRESS) . |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2007-10-25 |
|
|
Cont ID |
|
| Sent By |
amorse |
Date |
2007-10-25 |
Time |
17:27 |
Rev Time |
0.00 |
| Received By |
amorse |
Date |
2007-10-25 |
Time |
17:27 |
Sent To |
PC |
|
| Notes |
| 2007-10-25 17:29:02 | | | | | | | BULDING REVISION OK,COVER SHEET AND SHEETS A-4 AND | | | A-6 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2007-01-31 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-01-31 |
Time |
14:25 |
Rev Time |
3.33 |
| Received By |
jwitmer |
Date |
2007-01-30 |
Time |
15:44 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2006-10-20 |
|
|
Cont ID |
|
| Sent By |
amorse |
Date |
2006-10-20 |
Time |
06:49 |
Rev Time |
0.00 |
| Received By |
amorse |
Date |
2006-10-20 |
Time |
06:49 |
Sent To |
PC |
|
| Notes |
| 2006-10-20 06:50:24 | | | | | | | DENIED | | | | | | 1) FIXED WINDOWS APPEAR TO BE SEPERATE LITES IF SO | | | MULLIONS ARE REQUIRED AND PRODUCT APPROVALS SHALL BE | | | SUBMITTED | | | | | | 2) THE STATE COVER FL#5259 FOR THE POLYSTICK | | | UNDERLAYMENT IS NOT THE CORRECT COVER FOR THE | | | MIAMI-DADE NOA PLEASE SUBMIT CORRECT COVER (FL#986-R1) | | | | | | 3) THE STATE COVER FL#2795 FOR THE FIXED WINDOWS ARE | | | FOR THE 2001 CODE CYCLE, YALE OGRON DOES NOT YET HAVE | | | STATE APPROVAL FOR THIS PRODUCT SO A LOCAL PRODUT | | | APPROVAL WAS GIVEN FOR THE MIAMI-DADE NOA. THE SAME | | | APPLIES TO THE SMITH MOUNTAIN ENTRANCE DOOR & TRANSOM | | | NOA'S | | | | | | 4) PROVIDE THE UL LISTING/SYSTEM USED TO MEET THE ONE | | | HOUR RATING FOR THE CEILING AND ATTIC ACCESS PANELS. | | | DRAWINGS ONLY SHOW ONE LAYER 5/8" TYPE X WHICH IS A 40 | | | MINUTE RATING | | | | | | 5) PROVIDE ENERGY CALC'S PER 13-101.1.6 FBC USING | | | METHOD B AS PER CONVERSATION WITH PATTY KRAUSS (MECH | | | PLAN REVEIW) AND SHOW COMPLIANCE ON THE CONSTRUCTION | | | DOCUMENTS | | | | | | 6) PER ELEVATOR SHOP DRAWINGS PROVIDE MINIMUM ONE HR | | | RATED DOOR TO THE MACHINE ROOM COMPLETE WITH CLOSER AND | | | LOCK | | | | | | 7) PROVIDE HARDWARE SCHEDULE WITH HARDWARE THAT MEETS | | | THE ACCESSABILITY REQUIREMENTS PER 11-4.13.8 THROUGH | | | 11-4.13.11 | | | | | | 8) PROVIDE SHORING PLANS FOR BEAMS (OTHER THAN TAHT | | | ALREADY SUPPLIED FOR EPICORE) | | | | | | 9) ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME, | | | ADDRESS, AND LICENCE NUMBER ON EACH SHEET THAT BEARS | | | THEIR SEAL PER | | | 61G15-23.002(2) FAC GUARD RAIL DETAIL IS MISSING | | | ENGINEERS NAME AND PE LICENCE NUMBER | | | | | | 10) FIRE SPRINKLERAND EPICORE FRAMING LAYOUT PLANS DO | | | NOT CARRY AN ORIGINAL "SIGNATURE" AS REQUIRED BY | | | 61G15-23.002(2) FAC AND THE FLORIDA BOARD OF | | | PROFESSIONAL ENGINEERS | | | | | | 11) THE ENGINEER SEAL ON THE TRUSS LAYOUT PLANS AND | | | INDEX SHEETS DOES NOT MEET THE REQUIREMENTS OF | | | 61G15-23.001 FAC, 471.025 FS AND THE FBPE THAT THE | | | WORDING ON THE SEAL SHALL CHANGE FROM CERTIFICATE TO | | | LICENCE | | | | | | 12) THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS | | | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS | | | AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST | | | EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC | | | (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES | | | PER 108.3 FBC* PLEASE SEE THAT THE VALUE HAS BEEN | | | INCREASED AND FEES ARE DUE | | | | | | 13) A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT IS REQUIRED PRIOR TO | | | A PERMIT BEING ISSUED | | | | | | 14) NOTE: AN ELEVATION CERTIFICATE WILL BE REQUIRED | | | PRIOR TO THE ISSUANCE OF A CO | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-03-03 |
|
|
Cont ID |
|
| Sent By |
amorse |
Date |
2006-03-03 |
Time |
12:26 |
Rev Time |
0.00 |
| Received By |
amorse |
Date |
2006-03-03 |
Time |
12:26 |
Sent To |
PC |
|
| Notes |
| 2006-03-03 00:00:00 | | | | | | | | | | | | | DENIED | | | | | | 1) SUBMIT PRODUCT APPROVALS, | | | THOSE PRODUCTS WHICH ARE REGULATED BY | | | DCA RULE 9B-72 SHALL BE REVIEWED AND | | | APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR | | | JURISDICTIONAL APPROVAL PER 106.3.3 FBC* | | | | | | 2) SUBMIT SITE PLAN, | | | DRAWINGS SHALL SHOW THE LOCATION OF ALL | | | WORK, INCLUDING THE PROPOSED BUILDING(S) | | | OR STRUCTURE(S), AND ALL EXISTING | | | MAN-MADE IMPROVEMENTS AND EVERY EXISTING | | | SURVEY, OR OTHER SPECIAL SURVEY, | | | PREPARED BY A QUALIFIED SURVEYOR. PER | | | 106.3.4 FBC* | | | | | | 3) SUBMIT SOIL REPORT PER 1802.2.1 FBC | | | AND 106.3.5.1.1 FBC* | | | | | | 4) DRAWINGS SHALL SPECIFY CONSTRUCTION | | | TYPE WITH AREA AND HEIGHT MODIFICATIONS | | | USED TO MEET CODE | | | | | | 5) AN AUTOMATIC FIRE SPRINKLER SYSTEM | | | SHALL BE INSTALLED PER 903.2.10 FBC, | | | PROVIDE DRAWINGS | | | | | | 6) PROVIDE ENERGY CALCULATIONS AND | | | COMPLIANCE WITH 13-101.1.6 AND | | | 13-103.1.1.1 FBC | | | | | | 7) SUBMIT ENGINEERED TRUSS DRAWINGS PER | | | 2303.4.1 AND ENGINEERING NOTE 1 OF TRUSS | | | DESIGN CRITERIA ON S/4 | | | | | | 8) S/4 HAS REFERENCE TO STANDING SEAM | | | METAL ROOF AND A/3 HAS CONCRETE ROOF | | | TILE, CLARIFY | | | | | | 9) GUARDS ON A/3 AND A/5 DO NOT MATCH | | | | | | 10) SIGN AND AWNINGS SHALL BE SUBMITTED | | | UNDER SEPERATE PERMITS | | | | | | 11) DRAWINGS MISSING SITE,PARKING,ETC, | | | TO REVIEW FOR ACCESSABILITY, COMPLY WITH | | | REQUIREMENTS OF CHAPTER 11 FBC | | | | | | 12) DRAWINGS MISSING REQUIRED FOR REVIEW | | | OF EGRESS, COMPLY WITH REQUIREMENTS OF | | | CHAPTER 10 FBC | | | | | | 13) BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO | | | PALM BEACH COUNTY. THE ACTUAL PERMIT SET | | | OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 14) PROVIDE STAIR SHOP DRAWINGS FOR | | | COMPLIANCE, ATTACHMENT, ETC. | | | | | | 15) PROVIDE COMPLIANCE OF GUARDS WITH | | | 1607.7 FBC | | | | | | 16) UPON SUBMITTAL OF THESE REQUIREMENTS | | | FURTHER COMMENTS MAY BE GENERATED | | | | | | NOTE: FBC = FLORIDA BUILDING CODE 2004 | | | FBC* = WEST PALM BEACH | | | ADMINISTATIVE AMMENDMENTS TO FBC | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2007-10-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-10-07 |
Time |
09:48 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-10-07 |
Time |
09:48 |
Sent To |
PC |
|
| Notes |
| 2007-10-07 09:49:19 | REV FOR PARKING LOT | | | LIGHTING/POLES/FIXTURES/CIRCUITING. | | | OK, STAMPED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2007-09-20 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-09-20 |
Time |
12:18 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-09-20 |
Time |
11:38 |
Sent To |
FIRE |
|
| Notes |
| 2007-09-20 12:19:07 | ** REDLINED LETTER AS IT STATES THE 2005 NEC, WHEN | | | PROJECT IS ACTUALLY PERMITTED UNDER THE 2002 NEC. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2006-12-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-12-29 |
Time |
17:40 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-12-29 |
Time |
16:31 |
Sent To |
|
|
| Notes |
| 2006-12-29 17:17:07 | ** PROVISO ** | | | | | | NOTES REDLINED, AND NOTES FOR INFORMATION **** | | | | | | PLANS ARE TO BE REVISED FOR NOTES #1 AND #2 BELOW | | | ALONG WITH ANY OTHER REVISIONS BEFORE ROUGH. | | | | | | | | | *** 1) ELECTRICAL ROOMS, EQUIPMENT ROOMS, PIT AREA AND | | | ROOMS OF THE LIKE SHALL CONTAIN AUTOMATIC MEANS FOR | | | LIGHTING TO TURN OFF AS REQUIRED PER FBC | | | 13-415.1.ABC.1.1, .1.2, AND .1.3 | | | THIS WAS NOT ON ORIGINAL REVIEW , AS THIS WAS NOT KNOWN | | | TO THIS OFFICE. | | | ** AS INFORMATION FOR FUTURE BUILD OUTS, ALL SHALL | | | COMPLY COMPLETELY WITH THE NEW REQUIREMENTS UNDER THE | | | NEW 2004 FBC CHAPTER 13. | | | | | | ** 2) PLEASE SEE THE MINIMUM LEVELS FOR HORN/STROBES | | | SHALL MEET 2004 FBC 11-4.28.2, .3(4). | | | 75 MIN CANDELAS ON STROBES AND 15DB MIN FOR HORNS. THIS | | | COMMENT WAS NOT MADE ON ANY PREVIOUS ELECTRICAL REVIEWS | | | AS IT HAS NOW ONLY BECOME ONE OF THE ITEMS ELECTRICAL | | | PLAN REVIEW WILL BE REQUIRED TO REVIEW FOR. | | | | | | 3) PLEASE SEE THE TRUSS PLANS SUBMITTED STILL DO NOT | | | CONTAIN AN ORIGINAL SIGNATURE, THEY ARE IN FACT COLOR | | | PHOTO-COPIES. SEE BUILDING REVIEW NOTES OR BE SURE TO | | | SUBMIT/CHANGE THESE DOCUMENTS OUT BEFORE BUILDING | | | REVIEW COMMENCES | | | IF THERE ARE ANY QUESTIONS ON THIS OR WHEN AN | | | APPOINTMENT TO DO SO CAN BE SET UP, PLEASE CALL. | | | | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESIATE IN | | | CONTACTING THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2006-09-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-09-21 |
Time |
19:17 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-09-21 |
Time |
15:53 |
Sent To |
|
|
| Notes |
| 2006-09-21 00:00:00 | ***** UNSAT 2ND REVIEW ***** | | | | | | BLGD "B". | | | | | | ** PLEASE SEE THE FOLLOWING COMMENTS, | | | SOME OF WHICH ARE BEING NOTEDBY THIS | | | REVIEWER AS A "HEADS-UP". THESE ITEMS | | | ARE REQUIRED FOR COMPLIANCE FOR THE | | | ENTIRE PROJECT. | | | PLEASE SEE MANY ARE NOT FOR THE | | | ELECTRICAL REVIEW. | | | PLEASE SEE SOME ITEMS WHICH ARE REQUIRED | | | FOR ELECTRICAL . | | | PLEASE SEE ONLY ONE COMMENT FROM | | | PREVIOUS ELECTRICAL REVIEW STILL STANDS | | | AND SOME NEW COMMENTS BASED ON PLANS | | | SUBMITTED. | | | | | | | | | 1) NOTE: PLEASE SEE MISSING FOOTER STEEL | | | REQUIRED TO BE PART OF THE GROUNDING | | | ELECTRODE SYSTEM. 250.50 | | | PLEASE SEE CWP, GRND RODS AND BLDG STEEL | | | IS BEING SHOWN, ONLY MISSING FOOTER | | | STEEL. | | | | | | 2) NOTE: PLEASE SEE FA SHEETS SUBMITTED | | | SEPARATELY FROM SETS WHICH ARE NOT | | | SIGNED , DATED OR SEALED BY THE ENGINEER | | | OF RECORD. PLEASE ALSO SEE SHEETS | | | WITHOUT TITLE BLOCKS. | | | PLEASE SEE FBC 106.1 FOR MINIMUM | | | REQUIRMENTS FOR PLANS/DRAWINGS TO BE | | | SUBMITTED. (SCALE/CLARITY ETC) | | | FS 471.025 | | | | | | 3) NOTE: PLEASE SEE ALL FIRE SPRINKLER | | | PLANS WHICH CONTAIN A "RUBBER STAMP" FOR | | | THE ENGINEER OF RECORD. PLEASE KNOW, | | | THIS HAS BEEN NOTED ON OTHER PROJECTS | | | FOR THE SAME ENGINEER THAT A "RUBBER | | | STAMP" FOR THE REQUIRED ORIGINAL | | | SIGNATURE IS NOT ACCEPTABLE UNDER FAC | | | 61G15-23.002, FLORIDA STATUES 471.025. | | | PLEASE ALSO SEE THE SEAL FOR SAID | | | ENGINEER IS ALSO NO LONGER VALID AS THE | | | SEAL HAS EXPIRED PER RULING IN THEFAC | | | 61G15-23.001. THE RULING PASSED IN FEB | | | "04"WHICH REQUIRED THE WORDING OF | | | "CERTIFICATE" TO CHANGE TO "LICENSE" FOR | | | ALL ENGINEERS. PLEASE KNOW THE STATE | | | FBPE'S HAD ANEXTENSIONGRANTED FOR | | | ALMOST TWO YEARS TO GIVE ALL ENGINEERS | | | TIME TO OBTAIN THEIR NEW SEALS. THIS | | | EXTENED DATE WAS TO DEC 31ST, 2005. | | | PLEASE KNOW AS THIS HAS BEEN STATED ON | | | PREVIOUS PROJECTS AND PLANS ARE STILL | | | COMING IN WITH A "RUBBER STAMP" FROM | | | THIS DESIGN PROFESSIOAL, ONE SET OF EACH | | | PLAN FOR EACH SET AND EACHBUILDING IS | | | NOW BEING RETAINED BY THIS OFFICE FOR | | | FILE. PLEASE KNOW THIS MAY BE TURNED | | | OVER TO THE FLORIDA BOARD OF | | | PROFESSIONAL ENGINEERS FOR REVIEW AND | | | STATE'S LEGAL COUNSEL TO THE BOARD. | | | | | | 4) NOTE: PLEASE SEE TRUSS PLANS. PLEASE | | | SEE BUILDING REVIEW COMMENTS. | | | A)PLEASE SEE THE FAC 61G15-23.001. THE | | | RULING PASSED IN FEB "04" REQUIRED THE | | | WORDING OF "CERTIFICATE" TO CHANGE TO | | | "LICENSE" FOR ALL ENGINEERS. PLEASE KNOW | | | THE STATE FBPE'S HAD ANEXTENSION TO | | | DEC 31ST, 2005. PLEASE OBTAIN NEW SEAL. | | | B) PLEASE ALSO SEE THAT THESE SHEETS | | | ALSO DO NOT CONTAIN AN ORIGINAL | | | SIGNATURE AS REQUIRED UNDER FS 471.025, | | | FAC 61G15-23.002. | | | THESE MAY ALSO BE RETAINED. | | | | | | 5) NOTE: PLEASE SEE SETS OF PLANS FOR | | | THE "EPICORE FRAMING PLAN". PLEASE SEE | | | THESE CONTAIN A RAISED SEAL OVER | | | SIGNATURES WHICH ARENOT ORIGINAL AND | | | ARE "PHOTO-COPIES" OF THE ENGINEER'S | | | SIGNATURE WHICH IS REQUIRED TO BE | | | ORIGINAL. | | | PLEASE KNOW THESE ALSO MAY BE RETAINED | | | AS ALL SETS FOR BOTH BLDG'S ARE THE SAME | | | AS NOTED. | | | | | | 6) NOTE: PLEASE SEE SURVEY'S , PLEASE | | | SEE THESE ALSO CONTAIN A RAISED SEAL | | | OVER A "COPIED" SIGNATURE WHICH IS NOT | | | PERMITTED UNDER FAC 61G17 AND FS | | | 472.025. | | | PLEASE BE SURE THESE ARE SIGNED WITH | | | ORIGINAL SIGNATURE. | | | | | | ** PLEASE SEE THE COMMENTS FOR THE | | | ELECTRICAL ENGINEERING FIRM ARE MINOR | | | EXCEPT FOR THE FA SHEETS. | | | | | | ** PLEASE KNOW, THE SIGNING, DATING AND | | | SEALING OF ALL DOCUMENTS IS MOST | | | IMPORTANT!! | | | | | | ** IMPORTANT** | | | | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | PLEASE SEE COMPLETE SETS WITH ALL | | | ARCHITECTURAL PLANS WERE NOT MADE INTO | | | THE SETS SUBMITTED. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-12-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-12-25 |
Time |
11:06 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2005-12-25 |
Time |
10:55 |
Sent To |
|
|
| Notes |
| 2005-12-25 00:00:00 | IN ELEC FOR REVIEW | | | *** UNSAT *** | | | | | | 1)NOTE: PLEASE BE SURE PLANS, A-SHEETS | | | ETC REFERENCE THE CURRENT CODES IN | | | EFFECT AND APPLIED UNDER. | | | (2004 FBC , 2002 NFPA-72, 2003 NFPA-101, | | | 2002 NFPA-70 | | | | | | 2)NOTE: PLEASE SSE FIRE REVIEW COMMENTS | | | WHICH MAY HAVE A DIRECT AFFETC ON | | | ELECTRICAL PLANS. | | | | | | 3)NOTE: PLEASE SEE NFPA-101 7.8 , 7.9 | | | WHICH REQUIRES STAIRWAYS TO HAVE A MIN | | | OF 10FT CANDLES DURING NORMAL POWER AND | | | 1FT CANDLE UNDER EM POWER/BATTERY BACK | | | UP. | | | PLEASE PROVIDE PHOTOMETRICS FOR THIS. | | | MAY BE A BRIEF DETAIL FOR THE MIN NEEDED | | | TO PUBLIC RIGHT OF WAY. | | | | | | 4)NOTE: PLEASE SEE 250.50 WHICH ALSO | | | REQUIRES THE FOOTER STEEL TO BE PART OF | | | THE GROUNDING ELECTRODE SYSTEM. PLEASE | | | ADD. | | | PLEASE INCLUDE. | | | | | | 5)NOTE: PLEASE CORRLELATE RISER WITH | | | HOUSE PANEL. PLEASE SEE RISER INDICATES | | | PANEL "H" AS 225A MCB , HOWEVER PANEL | | | INDICATES BEING MLO? | | | | | | 6)NOTE: | | | | | | 7)NOTE: PLEASE CLARIFY THE EQUIPMENT | | | GROUNDING CONDUCTOR FROM MAIN TO HOSE | | | PANEL. | | | 250.110,250.24, 250.122 | | | | | | ** PLEASE REMOVE ANY OLD/VOIDED SHEETS | | | FROM SETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO COMPLETE SETS FOR REVIEW AND | | | STAMPING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVEIW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
P |
Date |
2006-10-27 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2006-10-27 |
Time |
11:39 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2006-10-27 |
Time |
11:31 |
Sent To |
|
|
| Notes |
| 2006-10-27 11:39:45 | I TALKED TO PAUL BURI OF SIMMON & WHITE THAT HE WILL | | | REMOVE THE WORD SECTION E-E FROM SHEET 4 OF 10 CIVIL | | | DRAWINGS WHEN ARCHITECH RESUBMIT WITH EVERYBODY'S | | | COMMENTS. ALL OTHER ENG COMMENTS ARE TAKEN CARE. | | | THEREFORE, IT IS APPROVED BY ENG.RASIK CHOKSHI | | | 805-6723 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
F |
Date |
2006-09-22 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2006-09-22 |
Time |
10:46 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2006-09-22 |
Time |
10:22 |
Sent To |
|
|
| Notes |
| 2006-09-22 00:00:00 | FAILED FOR FOLLOWING REASONS: | | | | | | 1. SHEET 4 0F 10,WHERE IS SEC E-E | | | DETAILS.PLEASE SHOW ALL CONTROL | | | STRUCTURES, & DETAILS, | | | ELEVATIONS,BLEEDER ELE ETC., | | | 2. PLEASE WRIRE NOTES THAT MEET | | | STANDARDS OF CITY OF WPB FOR | | | SIDEWALK,DRIVEWAY, PARKING,ADA,& ALSO | | | SHOW DUMPSTER ENCLOSURE DETAILS. | | | 3. PLEASE SHOW ALL CATCH BASINS IN THE | | | SURROUNDING SITE, TO MAKE SURE THAT YOUR | | | SITE INCLUDING NEIGHBOURS DO NOT GET | | | FLOODED. | | | 4. PLEASE SHOW CENTERLINE OF THE ROAD | | | ELE.,SIDEWALK ELE.,PARKING LOT ELE, & | | | FIRST FLOOR ELE., ALL THESE MUST MEET | | | FLORIDA BUILD. CODES. | | | | | | PLEASE RESPOND EACH ITEM TO EXPEDITE | | | YOUR PERMIT. | | | | | | RASIK CHOKSHI 805-6723 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2006-01-20 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2006-01-20 |
Time |
14:13 |
Rev Time |
0.50 |
| Received By |
mamini |
Date |
2006-01-20 |
Time |
14:12 |
Sent To |
|
|
| Notes |
| 2006-01-20 00:00:00 | FAILED: | | | | | | 1. PLEASE PROVIDE CIVIL/SITE PLANS FOR | | | OURE REVIEW AND APPROVAL, SUBMITAL | | | SHOULD INCLUDE STORM WATER CALCULATION, | | | POLLUTION PREVENTION PLANS.NOTE THAT | | | CIVIL PLANS ALSO SHOULD BE SUBMITTED TO | | | THE PUBLIC UTILITIES AND ENGINEERING FOR | | | ALL THE CONNECTION TO THE CITY SERVICES, | | | WATER, SEWER, BACKFLOWS AND METER'S | | | LOCATIONS, ATT; MANNY GONZALEZ 494-1086. | | | | | | IF ANY QUESTION PLEASE CONTACT 805-6723 | | | MOHAMMAD R. AMINI |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2007-10-25 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-10-25 |
Time |
17:14 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-10-25 |
Time |
17:12 |
Sent To |
|
|
| Notes |
| 2007-10-25 17:13:53 | *****APPROVED (REVISION)***** | | | | | | | | | REVISED COVER SHEET,A-4, AND A-6 WERE REVIEWED;NO | | | FIRE-STAMP NEEDED. | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2007-10-03 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-10-03 |
Time |
11:28 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-10-03 |
Time |
10:59 |
Sent To |
|
|
| Notes |
| 2007-10-03 11:28:35 | *****APPROVED***** | | | | | | | | | REVISED PLAN SHEET E-1B AND NEWLY ADDED SHEET FAB-1 | | | WERE STAMPED, INITIALED, AND DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2007-01-31 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-01-31 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-01-31 |
Time |
14:16 |
Sent To |
|
|
| Notes |
| 2007-01-31 14:19:48 | *****APPROVED***** | | | | | | | | | SHEETS A-3, E-1B, AND FS-1 WERE STAMPED, INITIALED, AND | | | DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2006-10-17 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2006-10-17 |
Time |
16:57 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2006-10-17 |
Time |
16:57 |
Sent To |
|
|
| Notes |
| 2006-10-17 17:27:01 | *****APPROVED***** | | | | | | | | | **RESPONSES TO PREVIOUS FIRE PLAN REVIEW COMMENTS | | | (12/23/2005) ACCEPTABLE AS FOLLOWS: | | | | | | 01.)PLEASE NOTE THAT AS PER WEST PALM BEACH CODE, THE | | | NUMERICAL ADDRESS ON THE BUILDING SHALL BE NO LESS THAN | | | 6" IN HEIGHT ANDNO LESS THAN 1" IN WIDTH.IF A | | | MONUMENT SIGN/MARQUEE IS ERECTED, THE ADDRESS OR A | | | RANGE OF ADDRESSES ARE REQUIRED. | | | | | | 02.)OK;SEE ELECTRICAL PLAN REVIEW NOTE #3;TO BE | | | CORRECTED WHEN THE FIRE SPRINKLER PERMIT AND PLANS ARE | | | SUBMITTED. | | | | | | 03.)OK | | | | | | 04.)SO NOTED. | | | | | | 05.)SEE NOTE #2. | | | | | | 06.)OK | | | | | | 07.)OK;SEE ELECTRICAL PLAN REVIEW NOTE #2;TO BE | | | CORRECTED WHEN THE FIRE ALARM PERMIT AND PLANS ARE | | | SUBMITTED. | | | | | | 08.)OK | | | | | | 09.)OK | | | | | | 10.)OK | | | | | | 11.)OK | | | | | | 12.)OK | | | | | | 13.)SO NOTED. | | | | | | 14.)OK | | | | | | 15.)SO NOTED. | | | | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2005-12-23 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2005-12-23 |
Time |
09:47 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2005-12-23 |
Time |
09:28 |
Sent To |
|
|
| Notes |
| 2005-12-23 00:00:00 | 1. BUILDING ADDRESS REQUIRED. A MINIMUM | | | OF AT LEAST 6" HIGH NUMBERS ARE | | | REQUIRED. | | | | | | 2. BUILDING WILL BE REQUIRED TO BE FIRE | | | SPRINKLER PROTECTED IN ACCORDANCE WITH | | | FS 553.895 (2) | | | | | | 3. COULD NOT LOCATE ANY EXISTING OR NEW | | | FIRE HYDRANTS. | | | | | | 4. A KNOX-BOX WILL BE REQUIRED FOR THE | | | BUILDING. | | | | | | 5. NO FIRE SPRINKLER DRAWINGS PROVIDED | | | WITH PLANS. | | | | | | 6. SEPERATE PLANS AND PERMITS REQUIRED | | | FOR FIRE SPRINKLER SYSTEM. | | | | | | 7. SEPERATE PLANS AND PERMITS REQUIRED | | | FOR FIRE ALARM SYSTEM. FIRE ALARM SYSTEM | | | SHALL BE MONITORED BY A UL LISTED | | | CENTRAL STATION APPROVED FOR CENTRAL | | | STATION SERVICE. | | | | | | 8. PLEASE PROVIDE PRESCRIPTVE STRENGTH | | | REQUIREMENTS FOR ALL HANDRAILS AND | | | GUARDRAILS. DETAILS LOCATED ON PAGE A-6. | | | | | | 9. MORE DETAILS REQUIRED ON AWNINGS. | | | FLAME RETARDANCY WILL BE REQUIRED. | | | | | | 10. TENANT IMPROVEMENTS SHALL HAVE | | | EMERGENCY LIGHTING AND ILLUMINATED EXIT | | | SIGNS. | | | | | | 11. PLEASE ILLUSTRATE PORTABLE FIRE | | | EXTINGUISHER LOCATIONS. | | | | | | 12. RENOVATION, CONSTRUCTION, AND | | | DEMOLITION SHALL COMPLY WITH NFPA 241. | | | | | | 13. SUITABLE ROADS ARE TO BE PROVIDED | | | DURING CONSTRUCTION. | | | | | | 14. THE FIRE DEPARTMENT SPRINKLER | | | CONNECTION SHALL BE LOCATED NO FARTHER | | | THAN 150 FEET FROM A FIRE HYDRANT. | | | | | | 15. KNOX-BOX LOCKING CAPS SHALL BE | | | PROVIDED ON THE FIRE DEPARTMENT | | | CONNECTION. | | | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | | OFFICER | | | 804-4709 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2007-12-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-12-19 |
Time |
16:09 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-12-19 |
Time |
16:09 |
Sent To |
Z |
|
| Notes |
| 2007-12-19 16:11:06 | TO "Z" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2007-10-05 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-10-05 |
Time |
11:15 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-10-05 |
Time |
11:15 |
Sent To |
E |
|
| Notes |
| 2007-10-05 11:16:00 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2007-09-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-09-14 |
Time |
09:39 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-09-14 |
Time |
09:39 |
Sent To |
E |
|
| Notes |
| 2007-09-14 09:40:13 | TO "DPALMER" DESK/REV--OK TO HAND-ROUTE PER ROBERT | | | BROWN. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2007-09-10 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-09-10 |
Time |
09:01 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-09-10 |
Time |
09:01 |
Sent To |
|
|
| Notes |
| 2007-10-01 09:19:14 | TO "COMM" BD#6 | | 2007-09-10 09:01:45 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-09-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-09-06 |
Time |
14:44 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-09-06 |
Time |
14:44 |
Sent To |
M |
|
| Notes |
| 2007-09-06 14:45:23 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-12-07 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-12-07 |
Time |
15:33 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-12-07 |
Time |
15:33 |
Sent To |
|
|
| Notes |
| 2006-12-27 09:52:29 | TO "COMM" BD#4/PLANS ON RACK--2 BOXES | | 2006-12-07 15:33:50 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-09-07 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-09-07 |
Time |
15:00 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-09-07 |
Time |
15:00 |
Sent To |
|
|
| Notes |
| 2006-09-15 00:00:00 | TO "COMM" BD#5/PLANS ON RACK/2 BOXES | | 2006-09-07 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-03-03 |
|
|
Cont ID |
|
| Sent By |
amorse |
Date |
2006-03-03 |
Time |
12:27 |
Rev Time |
0.00 |
| Received By |
amorse |
Date |
2005-11-28 |
Time |
10:59 |
Sent To |
|
|
| Notes |
| 2005-12-06 00:00:00 | TO "COMM" BD#56 | | 2005-11-28 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2007-12-27 |
Time |
|
Rev Time |
0.00 |
| Received By |
rkussner |
Date |
2007-12-27 |
Time |
14:34 |
Sent To |
|
|
| Notes |
| 2007-12-27 14:36:35 | 12/27/07- SENT TO CHRAK 12/27/07 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2007-09-14 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-09-14 |
Time |
17:51 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-09-14 |
Time |
17:51 |
Sent To |
PC |
|
| Notes |
| 2007-09-14 17:51:42 | LETTER FOR CHANGE, GRILL AND DUCT SIZE |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2006-10-12 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-10-12 |
Time |
12:15 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-10-12 |
Time |
12:15 |
Sent To |
|
|
| Notes |
| 2006-10-12 12:16:50 | ***************SHELLONLY*************** | | | BUILDING B: | | | | | | RESPONSE TO COMMENTS FROM REVIEW DATED 2-2-06: | | | | | | COMMENT 1:REPONSE INDICATES PER OUR CONVERSATION | | | METHOD A ENERGY CALCULATIONS WILL BE SUBMITTED WITH | | | SPEPARATE BUILD OUT PERMIT.PER 2004 FBC CHAPTER 13 | | | SUB-CHAPTER 13-101.1.1, NEW CONSTRUCTION COMEERCIAL | | | BUILDINGS SHALL COMPLY WITH SUBCHAPTER 13-4.METHOD B, | | | BUILDING, ENVELOPE TRADE-OFF METHOD IS REQUIRED FOR | | | SHELL BUILDINGS.THE METHOD A WILL BE REQUIRED FOR THE | | | BUILD-OUT PERMIT.THIS WAS ALSO A COMMENT BY THE | | | BUILDING PLANS EXAMINER. | | | | | | PLAN SHEET M-1B | | | SCOPE OF MECHANICAL WORK TO BE DONE UNDER THE SHELL | | | PERMIT IS AS FOLLOWS: | | | 1.DUCTLESS SPLIT UNIT TO THE ELEVATOR EQUIPMENT ROOM | | | 2.OUTDOOR INTAKES & EXHAUST LOUVERS, EXTENDING 12" | | | INTO BUILDING & CAPPED OF FUTURE. | | | | | | PLEASE NOTE, PVC REFRIGERANT RISER SHALL NOT BE A PASS | | | THROUGH ANY FUTURE PLENUMS. | | | | | | COMMENT 2 & 3 WERE ADDRESSED. | | | | | | ***NEW COMMENT**** | | | ADDITIONAL MECHANICAL PERMIT REQUIRED FOR THE BUILDOUT | | | PLAN SHEET M-1B INDICATES CONDENSING UNITS,PLEASE | | | NOTE CLEARANCES SHALL BE NO LESS THAN MANUFACTURER'S | | | RECOMMENDATIONS AND SUFFICIENT TO ALLOW INSPECTIONS, | | | SERVICE REPAIR OR REPLACEMENT PER 2004 FMC 306.1. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2006-02-02 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-02-02 |
Time |
09:24 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-02-02 |
Time |
08:32 |
Sent To |
|
|
| Notes |
| 2006-02-02 00:00:00 | DENIED:BUILDING B | | | 1.PERMIT APPLICATION INDICATES SHELL | | | ONLY. | | | | | | 2.THE MECHANICAL PLANS INDICATE | | | INSTALLATION OF THE CONDENSATE DRAIN | | | LINES. THE MECHANICAL NOTE #2, WASTE & | | | VENT PIPING SHALL BE PVC & DWV.FOR | | | FUTURE BUILDOUT - NO COMBUSTIBLES | | | ALLOWED IN THE RETURN AIR PLENUM PER | | | 2004 FMC 602.2.1. | | | | | | 3.PLAN SHEET M-1 & M-2, PLANS INDICATE | | | SLEEVES FOR FRESH AIR INTAKE & EXHAUST | | | AIR.PLEASE PROVIDE THE DISTANCE | | | BETWEEN THE TOP OF THE CONDENSING UNIT | | | TO THE FRESH AIR INTAKE.THE CONDENSING | | | UNIT WILL BE OMITTING HOT AIR WHICH | | | SHALL NOT BE RECIRCULATED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2006-09-23 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-09-23 |
Time |
10:40 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-09-23 |
Time |
10:40 |
Sent To |
|
|
| Notes |
| 2006-09-23 00:00:00 | RE-SUB |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2006-02-25 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-02-25 |
Time |
11:23 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-02-25 |
Time |
11:23 |
Sent To |
|
|
| Notes |
| 2006-02-25 00:00:00 | PLUMBING PLAN REVIEW EXAMINER | | | PAUL SCHMITZ 561-805-6692 | | | [email protected] | | | FBC PLUMBING 2004 | | | FBC FUEL GAS 2004 | | | AMENDMENTS TO THE FLORIDA BUILDING CODE | | | CH 1, ADMINISTRATION, 2004 EDITION ( | | | ATFBC) FBC BUILDING 2004, CH 11 | | | DENIED | | | 1)PLEASE SEE ANY POSSIBLE COMMENTS FROM | | | OTHER TRADES WHICH MAY AFFECT PLUMBING | | | PLANS.ENGINEERING,MECHANICAL,ZONING, | | | ELECTRICAL, BUIDING. | | | 2) SHT M-1 REFERENCES BUILDING "A" | | | PLEASE REFERENCEBUILDING "B" AS | | | INDICATED ON PERMIT APPLICATION. | | | 3)SHT M-3 RISER S-1, SEC 903.4 EVERY | | | VENT STACK SHALL CONNECT TO THE BASE OF | | | THE DRAINAGE STACK. | | | 4)106.3.5 MINIMUM PLAN REVIEW CRITERIA | | | FOR BUILDINGS. THE EXAMINATION OF THE | | | DOCUMENTS BY THE BUILDING OFFICIAL SHALL | | | INCLUDE THE FOLLOWING MINIMUM CRITERIA | | | AND DOCUMENTS: A FLOOR PLAN; SITE PLAN; | | | FOUNDATION PLAN; FLOOR/ROOF FRAMING PLAN | | | OR TRUSS LAYOUT; AND ALL EXTERIOR | | | ELEVATIONS: | | | PROVIDE SEPERATE SHEETS FOR PLUMBING | | | AND,MECHANICAL. | | | 5)WHEN RESUBMITTING PLANS PLEASE | | | INDICATE THE REVISION & REMOVE & REPLACE | | | ANY PAGES AS NECESSARY. | | | A TRANSMITTAL LETTER LISTING THE | | | ORIGINAL REVIEW COMMENT NUMBER, WITH A | | | DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | 6) PLEASE COMPLETELY REMOVE ANY | | | OLD/VOIDED SHEETS FROM SETS AND ONLY | | | INSERT NEW REVISED SHEETS INTO COMPLETE | | | SETS FOR REVIEW AND STAMPING. | | | | | | END OF COMMENTS, QUESTIONS 561-805-6692 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2007-01-07 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2007-01-07 |
Time |
21:10 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2007-01-07 |
Time |
21:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2006-10-02 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2006-10-02 |
Time |
19:36 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2006-10-02 |
Time |
19:36 |
Sent To |
|
|
| Notes |
| 2006-10-02 00:00:00 | 10/02/06 ***FAILED*** | | | | | | 1) LOCATION OF A/C UNITS ON THE | | | ELECTRICAL PLANS CONFLICTS WITH THE | | | INSTALLATION OF LANDSCAPING.A/C UNITS | | | SHALL BE SHOWN ON THE SITE AND LANDSCAPE | | | PLANS AND SHALL BE ADJUSTED ACCORDINGLY | | | TO ACCOMMODATE SUCH INSTALLATIONS. | | | ADDITIONALLY, ENSURE THAT THE MECHANICAL | | | EQUIPMENT DOES NOT ENCROACH MORE THAN 3 | | | FEET INTO A REQUIRED SETBACK. | | | | | | 2) THE SITE PLAN INDICATES 45,000 GROSS | | | SQUARE FEET OF BUILDING WHILE THE ARCH. | | | PLANS INDICATE 58,998 GROSS SQUARE FEET. | | | PLANS SHALL BE CONSISTENT AND THE | | | PARKING, LANDSCAPING, PERVIOUS, | | | IMPERVIOUS, ETC. SHALL BE ADJUSTED | | | ACCORDINGLY. | | | | | | 3) A NOTE SHALL BE PROVIDED ON THE SITE | | | AND LANDSCAPE PLANS THAT THE MONUMENT | | | WILL BE UNDER A SEPARATE PERMIT. | | | | | | QUESTIONS/COMMENTS, CONTACT JOHN ROACH, | | | SENIOR PLANNER, AT (561) 822-1435. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2006-02-16 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2006-02-16 |
Time |
09:42 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2006-02-16 |
Time |
09:42 |
Sent To |
|
|
| Notes |
| 2006-02-16 00:00:00 | 2/16/06 ***FAILED*** | | | | | | 1) NO SITE PLAN OR LANDSCAPE PLAN WAS | | | PROVIDED.ADDITIONALLY COMMENTS MAY | | | ARISE UPON SUBMISSION OF SUCH PLANS. | | | | | | QUESTIONS/COMMENTS, CONTACT JOHN ROACH, | | | PLANNER AT (561) 822-1435. |
|
|