Plan Review Details - Permit 05110790
Plan Review Stops For Permit 05110790
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-06-07 Cont ID  
Sent By jwitmer Date 2006-06-07 Time 10:58 Rev Time 0.55
Received By jwitmer Date 2006-06-07 Time 10:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-05-30 Cont ID  
Sent By jwitmer Date 2006-05-30 Time 07:20 Rev Time 1.11
Received By jwitmer Date 2006-05-30 Time 07:20 Sent To  
Notes
2006-05-30 00:00:00PERMIT: 05110790
 ADD: 871 VILLAGE BLVD
 CONT: 3D CONSTRUCTIO
 TEL: (407)383-9797
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW
 ACTION: DENIED
  
 1) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 2)LAST REVIEW THIS ITEM WAS GIVEN A
 PROVISO, NEW PLANS WERE SUBMITTED AND
 THIS COMMENT WAS NOT TAKEN CARE OF, THIS
 DOOR (#6) WILL REQUIRE 18" ON THE LATCH
 SIDE (PULL)11-4.13.6 MANEUVERING
 CLEARENCES AT DOORS. MINIMUM MANEUVERING
 CLEARENCES AT DOORS THAT ARE NOT
 AUTOMATIC OR POWER-ASSISTED SHALL BE AS
 SHOWN IN FIG. 25. THE FLOOR OR GROUND
 AREA WITH IN THE REQUIRED CLEARENCES
 SHALL BE CLEAR & LEVEL.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-04-06 Cont ID  
Sent By jwitmer Date 2006-04-06 Time 13:20 Rev Time 1.33
Received By jwitmer Date 2006-04-06 Time 13:20 Sent To  
Notes
2006-04-06 00:00:00BUILDING PROVISO: OOR# 6 TO COMPLY WITH:
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-02-07 Cont ID  
Sent By jwitmer Date 2006-02-07 Time 16:30 Rev Time 1.22
Received By jwitmer Date 2006-02-07 Time 16:30 Sent To PC
Notes
2006-02-07 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05110790
 ADD: 871 VILLAGE BLVD
 CONT: 3D CONSTRUCTIO
 TEL: (407)383-9797
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 SIGNATURE NOT TO BE COPIES BUT
 ORIGINAL!!!!!!!!
  
 3) 110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.(2004)
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
  
 4)1609.3 BASIC WIND SPEED.
 THE BASIC WIND SPEED IN MILES PER HOUR,
 FOR THE DEVELOPMENT OF WIND LOADS, SHALL
 BE DETERMINED FROM FIGURE 1609 . BASIC
 WIND SPEED FOR THE SPECIAL WIND REGIONS
 INDICATED, NEAR MOUNTAINOUS TERRAIN AND
 NEAR GORGES SHALL BE IN ACCORDANCE WITH
 LOCAL JURISDICTION REQUIREMENTS. THE
 EXACT LOCATION OF WIND SPEED LINES SHALL
 BE ESTABLISHED BY LOCAL ORDINANCE USING
 RECOGNIZED PHYSICAL LAND MARKS SUCH AS
 MAJOR ROADS, CANALS, RIVERS AND LAKE
 SHORES, WHEREVER POSSIBLE.
 WEST PALM BEACH IS LOCATED IN A 140 MPH
 WIND ZONE 3 SECOND GUST.
  
 5)(2004 FBC) 106.1.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE &
 EXTENT OF THE WORK PROPOSED & SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND REVELENT
 LAWS, ORDINANCES, AND RULES AND
 REGULATIONS AS DETERMINED BY THE
 BUILDING OFFICIAL.
 IT APPEARS THAT ADDITIONAL AIR HANDLERS
  
 ARE BEING INSTALLED ON THE ROOF, A
 LETTERWILL BE REQUIRED FROM AN
 ENGINEER FOR THE ADDITIONAL POINT
 LOADING OF THE BAR JOIST, ALSO WILL ANY
 BAR JOIST BE CUT?
  
 6) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) PREMANUFACTURED A/C ROOF STANDS
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 7)1511.7 ROOF MOUNTED MECHANICAL UNITS
 SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGHT IN ACCORDANCE WITH TABLE 1511.7.
  
 8) 106.3.3* PRODUCT APPROVALS- 2004
 THOSE PRODUCTS THAT ARE RGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 9)FBC 13-103.1.2 BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHETECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 10) MECHANICAL DESIGNER TO SIGN & SEAL
 ENERGY CALC13-103.2 DETAILS, PLANS AND
 SPECIFICATIONS.
 PLANS AND SPECIFICATIONS SHALL BE
 SUBMITTED WITH EACH APPLICATION FOR A
 BUILDING PERMIT. ENERGY CODE
 CALCULATIONS SHALL BE MADE A PART OF THE
 PLANS AND SPECIFICATIONS OF THE
 BUILDING. THE BUILDING OFFICIAL SHALL
 REQUIRE, SUBJECT TO THE EXCEPTIONS IN
 SECTION 481.229, FLORIDA STATUTES , AND
 SECTION 471.003, FLORIDA STATUTES , THAT
 PLANS AND SPECIFICATIONS BE PREPARED BY
 AN ENGINEER OR ARCHITECT LICENSED TO
 PRACTICE IN THE STATE OF FLORIDA. THE
 PLANS AND SPECIFICATIONS, INCLUDING THE
 ENERGY CODE CALCULATIONS, SHALL SHOW, IN
 SUFFICIENT DETAIL, ALL PERTINENT DATA
 AND FEATURES OF THE BUILDING AND THE
 EQUIPMENT AND SYSTEMS AS HEREIN GOVERNED
 INCLUDING, BUT NOT LIMITED TO: DESIGN
 CRITERIA, EXTERIOR ENVELOPE COMPONENT
 MATERIALS, U -VALUES OF THE ENVELOPE
 SYSTEMS, R -VALUES OF INSULATING
 MATERIALS, SIZE AND TYPE OF APPARATUS
 AND EQUIPMENT, EQUIPMENT AND SYSTEMS
 CONTROLS AND OTHER PERTINENT DATA TO
 INDICATE CONFORMANCE WITH THE
 REQUIREMENTS OF THE CODE
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2006-07-22 Cont ID  
Sent By dpalmer Date 2006-07-22 Time 18:24 Rev Time 0.00
Received By dpalmer Date 2006-07-22 Time 18:24 Sent To PC
Notes
2006-07-22 00:00:00LTR FROM ENGINEER TO ALLOW THE USE OF
 MC CABLE.

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2006-06-29 Cont ID  
Sent By dpalmer Date 2006-06-29 Time 14:15 Rev Time 0.00
Received By dpalmer Date 2006-06-29 Time 14:15 Sent To PC
Notes
2006-06-29 00:00:00LIGHTING CONTROL SYSTEM ADDED,
 HOWEVER LOADS ON E-1 AND E-2 STILL DO
 NOT CORRELATE. IF PLANS ARE REVISED FOR
 ANY OTHER ITEMS , PLEASE CORRECT.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-06-16 Cont ID  
Sent By dpalmer Date 2006-06-16 Time 16:33 Rev Time 0.00
Received By dpalmer Date 2006-06-16 Time 15:42 Sent To PC
Notes
2006-06-16 00:00:00*********** PROVISO ************
  
 1) NOTE: PLEASE SEE PLANS DO NOT COMPLY
 WITH FBC 2004 CHAPTER 13,
 13-415.1.ABC.1.1,.1.2, .1.3,
 13-415.1AB, 13-415.1.ABC.1
  
  
 2) NOTE: PLEASE SEE TOTAL LOADS FOR THIS
 SAPCE ON E-1 SHALL CORRELATE WITH E-2.
  
 ***
 PLEASE KNOW, CORRECTED PLANS MUST BE
 SUBMITTED AS A REVISION BEFORE ANY
 INSPECTIONS FOR ANY TRADES ARE DONE.
 IF REVISED PLANS ARE NOT SUBMITTED FOR
 REVIEW, PERMIT STATUS WILL E PLACED INTO
 A "HOLD" STATUS.
  
 PLEASE KNOW A "HOLD WILL BE PLACED IN
 SYSTEM TO NOTE THE HOLD ON INPSECTIONS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2006-06-07 Cont ID  
Sent By dpalmer Date 2006-06-07 Time 21:09 Rev Time 0.00
Received By dpalmer Date 2006-06-07 Time 20:33 Sent To  
Notes
2006-06-07 00:00:00*********** UNSAT 5TH TIME. **********
  
 PLEASE SEE NOTES FROM PREVIOUS REVIEWS.
  
  
 1) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1
 UNDER THE 2004 FBC.
 PLEASE KNOW IT WAS DISCUSSED WITH THE
 ARCHITECT THAT ONE OF TWO SCENERIO'S FOR
 THIS COMPLIANCE NEEDED TO TAKE PLACE ON
 THE PLANS. EITHER MEET THE EXCEPTION AS
 SETFORTH FOR TENANT SPACE IN BUILDING
 WITH PERCENTAGE OR PROVIDE A LIGHTING
 CONTROL SYSTEM OF SOME SORT TO SHUT
 LIGHTING DOWN AS REQUIRED.
 NEITHER ITEMS WERE SHOWN, OR NOTED ON
 PLANS??
 ** PLEASE SEE NEW PANEL SPECS FOR EACH
 OF THE TWO EXISTING PANELS WERE ADDED TO
 PLANS WHICH WAS NOT PART OF ANY OF THE
 PREVIOUS COMMENTS AND IT IS UNCLEAR WHY
 THESE WERE ADDED.?
  
 2)NOTE: PLEASE SEE LOAD SUMMARYS ON E-1
 AND E-2 STILL DO NOT CORRELATE???
 65.1,72.7?? WHICH IS IT? IF GOING BY THE
 LOAD CALCULATIONS AS SHOWN ON PANELS
 WHICH NOW SEEM TO BE CORRECT.
  
  
 CALLED CONTRACTOR WITH THE ASST BUILDING
 OFFICIAL MR ROBERT BROWN AFTER GOING
 OVER COMMENTS AND PLANS. LEFT MESSAGE
 FOR MR. DAVE DAVORE.
  
 PLANS WILL BE ROUTED TO MR LUIS
 MARTINEZ.
  
 PLEASE SUBMIT THE ABOVE INFORMATION AS
 REQUESTED.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-05-14 Cont ID  
Sent By dpalmer Date 2006-05-14 Time 08:37 Rev Time 0.00
Received By dpalmer Date 2006-05-14 Time 08:36 Sent To  
Notes
2006-05-14 00:00:00PLANS SUBMITTED BY E-MAIL.
 REVIEW DONE AS PER ROBERT BROWN AND LUIS
 MARTINEZ.
  
 PLEASE SEE COMMENTS BELOW WHICH WERE
 E-MAILED BACK TO BOTH ARCHITECTS.
  
 1) NOTE: PLEASE SEE "WINDOW " RECEPT BY
 FRONT DOOR IS STILL ON B-23 WITH OTHER
 DINING AREA RECEPTS.
 2)NOTE: PLEASE SEE LIGHTING CONTROL IN
 REQUIRED AS THE "BUILDING" IS OVER 5000
 SQ FT. PLEASE SEE FBC AS THIS OCCUPANCY
 IS IN THE REST OF THE LARGERBUILDING.
 3) NOTE: PLEASE SEE LOADS FOR A/C UNITS
 STILL DO NOT CORRELATE IN PANEL SCHEDULE
 WHICH IN TURN REFLECTS ALL LOADS.
 PLEASE GO VER ALL LOAD CALCULATIONS.
 4) NOTE: PLEASE SEE LOADS IN SUMMARY DO
 NOT CORRELATE WITH LOADS ON RISER SHEET.
 PLEASE SEE NOW, THE MIN AIC RATINGS FOR
 PANELS A AND B HAVE BEEN REMOVED.?
 PLEASE KNOW, I WILL BE OUT OF THE OFFICE
 BY THIS THURS THE 18TH.
 5) NOTE: PLEASE KNOW, THE CHIEF
 ELECTRICAL INSPECTOR HAS VERIFIED THE
 NUMBER OF SERVICE MAINS AT TENANT
 LOCATION AND THIS NEW MAIN SHOULD BE OK.
 PLEASE PROVIDE BOLLARDS AS SHOWN FOR
 PROTECTION OF NEW SERVICE MAIN BEING
 ADDED TO THE END OF BUILDING.
 THESE REVISIONS, NEED TO GO THOUGH THE
 ENGINEER TO BE VERIFIED.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-05-08 Cont ID  
Sent By dpalmer Date 2006-05-08 Time 22:28 Rev Time 0.00
Received By dpalmer Date 2006-05-08 Time 06:50 Sent To  
Notes
2006-05-08 00:00:00***********UNSAT 3RD REVIEW *********
  
 ** PLEASE SEE PLANS CONTAIN NOTES FROM
 PREVIOUS REVIEWS WHICH STILL NEED TO BE
 ADDRESSED ALONG WITH NEW COMMENTS AS
 PLANS HAVE HAD CHANGES ONCE AGAIN.
  
 ** PLEASE ALSO SEE PLANS ARE CONTAIN
 REVISIONS TO MECHANICAL AND BUILDING
 WHICH WILL REQUIRE NEW REVIEWS OF THOSE
 SAID PLANS.
  
 ** PLEASE SEE NOTES BELOW AS NOTES ARE
 TAKEN DIRECTLY FROM PREVIOUS REVIEW.
 PLEASE SEE NEW NOTES AT THE BOTTTOM OF
 REVIEW.
  
 ******** UNSAT 2ND REVIEW *********
  
 PLEASE SEE NOTES FROM PREVIOUS REVIEW
 WHICH ARE STILL NEEDING TO BE ADDRESSED
 AND NEW COMMENTS TO CHNAGES IN PLANS
 FROM PREVIOUS PLANS SUBMITTED.
  
 * PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW AND NEW
 NOTES ARE ADDED TO THE END OF FIRST
 REVIEW NOTES.
  
 ************ UNSAT ************
  
  
 1)NOTE: NOTE #1, NO.SEE NOTES WITH
 RESPECT TO THE FBC CHAPTER 13.
  
 ** PREVIOUS REVIEW **
 NOTE #1 NO, PLEASE SEE PREVIOUS
 NOTE AS PLANS ORIGINALLY CAME IN
 DESIGNED UNDER THE 2001 FBC WHEN THE
 CODE IN EFFECT AT THAT TIME WAS THE
 2004. PLEASE SEE PREVIOUS NOTE MENTIONED
 TO PLEASE MAKE ALL CHANGES IN DESIGN TO
 THE 2004 FBC.
 PLEASE SEE NEW NOTES BELOW.
  
 ** PRE-REVIEW**
 PLEASE SEE PLANS STATE THE 2001
 FBC, HOWEVER AS OF OCT. 1ST, 2005 THE
 CODE HAS CHANGED TO THE 2004 FBC AND ALL
 OTHER RELEVANT CODES.
 PLEASE SEE PERMIT WAS NOT APPLIED FOR
 UNTIL NOV. 21ST, 2005
 PLEASE ADJUST ALL PLANS.
  
 2)NOTE: NOTE #2 OK.
  
 ** PRE-REVIEW**
  
 PLEASE SEE ALL SHEETS IN BOTH SETS ARE
 SEALED PHOTOCOPIES OF SIGNED PLANS.
 PLEASE SEE FS 481.221 AND FAC
 61G1-16.003 WHICH REQUIRE THE PLANS TO
 HAVE AN "ORIGINAL WET SIGNATURE AND
 DATE".
 ** PLEASE KNOW THIS IS REQUIRED FOR ALL
 TRADES AND FOR ALL SHEETS WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
 ONE SET MAY BE RETAINED.
  
 3)NOTE: NOTE #3 OK.
  
 ** PREVIOUS NOTE **
 NOTE #3 OK, HOWEVER SEE NEW
 NOTES FOR HAND DRAWN ITEMS ON SIGNED AND
 SEALED PLANS.
  
 ** PRE-REVIEW**
 PLEASE SEE ELECTRICAL SHEETS
 CONTAIN A TITLE BLOCK FOR AN ENGINEER.
 PLEASE KNOW, IF THIS ENGINEER IS
 RESPONSIBLE FOR DESIGN OR ELECTRICAL
 WORK ON SAID PLANS, THEN PLANS MUST BE
 SIGNED DATED AND SEALED BY SAID
 ENGINEER.
 FS 471.025
 PLEASE ALSO SEE FLORIDA ADMINISTRATIVE
 CODE 61G15-23.002 WHICH REQUIRES THE
 TITLE BLOCK FOR ENGINEER TO BE COMPLETE
 WITH ALL INFORMATION AS SET-FORTH IN THE
 LISTED FAC.
  
 4)NOTE:NOTE #4 OK.
  
 ** PRE-REVIEW**
 PLEASE SEE 600.5 FOR MISSING
 REQUIRED SIGN CIRCUIT.
  
 5)NOTE:NOTE #5 NO, PLEASE SEE A
 CIRCUIT AND LOAD IS BEING ADDED TO PANEL
 "B" CIRCUIT #10. PLEASE SEE RECEPT IS
 STILL NOT BEING SHOWN ABOVE THE WINDOW
 AND HOW LOADS WERE DERIVED FOR THIS CAN
 NOT BE VERIFIED AS NOW ONLY A LOAD OF
 1.6KW IS SHOWN. IS THIS AT 200VA PER FT?
 THIS IS NOT SHOWN IN CALCUALTIONS.
 AS STATED IN BOTH PREVIOUS REVIEWS,
 PLEASE SEE 210.62,220.12A.
  
  
 ** PREVIOUS NOTE**NOTE #5 OK, HOWEVER
 PLEASE SEE THESE ARE NOW ADDED, BUT TO
 THE GENERAL
 RECEPTS IN DINING AREA. PLEASE KNOW,
 THESE SHOULD BE DEDICATED PER LOADS.
 PLEASE SEE210.62,220.12A,220.3(B)(7)
 CODE COMMENTARY FOLLOWING IN THE 2002
 NEC HANDBOOK.
  
 ** PRE-REVIEW**
 PLEASE SEE MISSING REQUIRED
 WINDOW OUTLETS ABOVESTORE FRONT.
 210.62.
 PLEASE SEE MIN KVA TO BE FIGURED PER
 220.12A
 THIS IS TO DISCOURAGE FLOOR RECEPTACLES
 AND UNSIGHTLY EXTENSION CORDS USED FOR
 SIGNAGE, DIPLAYS ETC WHICH ARE LIKELY TO
 CAUSE PHYSICAL INJURY, RECEPTACLES MUST
 BE INSTALLED DIRECTLY ABOVE THE WINDOW.
  
 6)NOTE:NOTE #6 OK, NOW SHOWN CIRCUITED
 TO LOCAL LIGHTING.
  
 ** PREVIOUS NOTE **
 NOTE #6 NO, PLEASE SEE THESE ARE
 STILLNOT SHOWN CIRCUITED TO THE LOCAL
 BRANCH CIRCUIT AS REQUIRED PER 700.12E.
 PLEASE SEE CIRCUITING AS SHOWN AND
 "LOCK-OFF" DEVICE LISTED ON PANEL
 SCHEDULE DOES NOT MEET THE "EXCEPTION"
 AS NOTED.
  
 ** PRE-REVIEW**
 PLEASE SEE 700.12E WHICH
 REQUIRES THE BRANCH CIRCUIT FEEDING THE
 UNIT EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
 PLEASE ADJUST CIRCUITING SHOWN ON PLANS.
  
 7)NOTE: NOTE #7 OK.
  
 ** PRE-REVIEW**
 PLEASE COMPLETE SWITCH
 LEGS.SWITCH BANK ON PLANS.
 CAN NOT VERIFY AT THIS TIME.
  
 8)NOTE: NOTE #8 OK.
  
 ** PREVIOUS NOTE **
 NOTE #8 OK, HOWEVER SEE NEW
 NOTE FOR HAND-DRAWN ITEMS ON SIGNED AND
 SEALED PLANS.
  
 ** PRE-REVIEW **
 PLEASE SEE 2002 NEC 210.8B3
 WHICH REQUIRES ALL 15- AND 20-AMPERE,
 125-VOLT RECEPTACLES IN NONDWELLING-TYPE
 KITCHENS TO BE GFCI PROTECTED. THIS
 REQUIREMENT APPLIES TO EACH AND EVERY
 15- AND 20-AMPERE, 125-VOLT KITCHEN
 RECEPTACLE, WHETHER OR NOT THE
 RECEPTACLE SERVES COUNTERTOP APPLIANCES.
  
  
 9)NOTE: NOTE #9 NO, NEW LOADS SUBMITTED
 HOWEVER PLEASE SEE COMMENTS AS LOADS
 FROM E-1 AND E-2 DO NOT CORRELATE.
 PLEASE CLARIFY WHAT IS NOW BEING SHOWN
 AS 85% POWER FACTOR? WHAT IS THIS?
 PLEASE SEE AS STATED ON PREVIOUS
 REVIEWS, SUBMIT EITHER COMPLETE LOAD
 CALCULATIONS, OR A 12 MONTH READING FROM
 FPL,WITH NEW LOADS ADDED AT 125%.
 PLEASE SEE NEC 220.35
  
 ** PREVIOUS NOTE **
 NOTE # 9 NO. NONE SUBMITTED.
 PLEASE SEE NEW SERVICE AS SHOWN COMES
 FROM AN EXISTING SERVICE ON MAIN
 BUILDING AND ADDED LOAD TO THE EXISTING
 SERVICE MUST BE VERIFIED.
 PLEASE SEE NEW COMMENTS FOR MANY CHANGES
 ON RISER.
  
 ** PRE-REVIEW**
 PLEASE PROVIDE COMPLETE LOAD
 CALCULATION ON EXISTING SERVICE WHICH
 THIS SERVICE IS BEING TIED INTO.
 IT IS KNOWN TO THIS OFFICE THAT THE
 SERVICE AT THIS LOCATION CONTAINS LOADS
 ON SOME OF THE MAIN SERVICES WHICH ARE
 CLOSE TO EXCEEDING RATED LOADS.
 215.5,220
  
 10)NOTE: NOTE #10, OK, HOWEVER PLEAS
 KNOW, THE AVAILABLE FAULT CURRENT IS
 STILL SHOWN AS 37,880 AND AIC RATINGS
 FOR MAINS AND BRANCH BRKRS ARE BEING
 SHOWN AT 100,000. PLEASE KNOW, THIS IS
 PERMITTED AND COMMENT HAS BEEN
 ADDRESSED. IT IS BEING NOTED AS THE 100K
 RATTING SEEMS VERY HIGH. IF SHOWN ON
 PLANS, THEN THIS IS WHAT WILL BE
 REQUIRED TO BE INSTALLED.
  
 ** PREVIOUS NOTE **
 NOTE #10 NO?? PLEASE SEE A NOTE
 WAS ADDED FOR "DOWN SYSTEM BREAKER
 SERIES". THIS IS UNCLEAR AS AN AVAILABLE
 FAULT CURRENT IS NOTED AS 37,880 FROM
 FPL, YET THE SERIES RATINGS ARE NOW
 SHOWING 100K??
 PLEASE KNOW, AIC RATINGS SHALL BE STATED
 FOR NEW MAINS, NEW PANELS AND SERIES
 RATING ON BRANCH BRKRS.
 110.9,215.5
  
 ** PRE-REVIEW **PLEASE SUBMIT AIC
 RATINGS FOR ALL NEW SERVICE EQUIPMENT
 BEING INSTALL-ED. MAINS/BRKRS AND PANELS
 ARE ALL TO BE RATED FOR THE AVAILABLE
 FAULT CURRENT.
 PER 110.9/215.5
  
 11)NOTE: NOTE #11 OK, PLEASE SEE NO MAIN
 IS BEING SHOWN ON THE LINE SIDE OF
 SERVICE MAINS.
 PLEASE SEE NEW COMMENT FOR THE NUMBER OF
 MAINS.
  
 ** PREVIOUS NOTE **NOTE: 11 NO, PLEASE
 SEE THE
 "EQUIPMENT GROUNDING CONDUCTOR" IS NOW
 REMOVED, HOWEVER MAY BE REQUIRED AS THE
 "SERVICE MAIN" IS STILL NOT SHOWN OR
 INDICATED ON PLANS.
 PLEASE KNOW, IF THE "SERVICE MAIN" FOR
 BUILDING IS LOCATED AHEAD OF GUTTER
 SHOWN, THE NEUTRAL AND EQUIPMENT
 GROUNDING CONDUCTORS SHALL NOT BE BONDED
 AFTER THE FIRST MEANS OF DICSCONNECT.A
 "FLOATING NEUTRAL" WILL BE REQUIRED.
  
 ** PRE-REVIEW**
 PLEASE SEE 250.6 , 250.24, IT
 IS NOT SHOWN IF THERE IS A "MAIN" ON THE
 LINE SIDE OF THE GUTTER SHOWN.
 THEREFORE, THE 'EQUIPMENT GROUND" SHOWN
 FROM GUTTER TO METER AND METER TO MAIN
 SHOWN, MAY BE PARALLING THE NEUTRAL.??
 CAN NOT VERIFY AT THIS TIME?
  
 12)NOTE: NOTE #12, OK. SEE NEW NOTES FOR
 OTHER CHANGES.
  
 ** PREVIOUS NOTE **
 NOTE#12 NO, PLEASE SEE NEW
 COMMENTS AS RISER DIAGRAM HAS COMPLETELY
 CHANGED FROM PREVIOUS PLANS AND MANY
 CHANGES TO SERVICE WERE MADE.
  
 **PRE-REVIEW**
 PLEASE CORRELATE RISER WITH
 PANELS. PLEASE SEE PANEL "B" IS SHOWN AS
 MLO ON SCHEDULE, HOWEVER RISER SHOWS
 MCB.
  
 13)NOTE:NOTE #13 OK.
  
 **PRE-REVIEW**
 PLEASE SEE CONTINUOUS LOADS ARE
 SHOWN AT 125%, HOWEVER PLEASE ALSO
 INDICATE ANY LARGEST MOTORS LOADS ALSO
 @125%.
 215.3, 230.42 ETC.
  
 14)NOTE: NOTE #14 OK.
  
 ** PRE-REVIEW** PLEASE PROVIDE DETAIL
 FOR MEANS
 OF SHUT DOWN OF ALL ELECTRICAL FOR HOOD.
 NFPA-96
  
  
 ***************************************
 ******* NEW COMMENTS "2ND REVIEW"******
  
 15) NOTE: NOTE: OK.
  
 ** PREVIOUS NOTE **
 PLEASE KNOW, THESE PLANS ARE
 SIGNED DATED AND SEALED PLANS BY AN
 ENGINEER UNDER FLORIDA STATUES 471.
 PLEASE KNOW, HAND DRAWN CHANGES TO
 PLANS, FOR CIRCUITING, DESIGN, NOTES ETC
 ARE NOT PERMITTED UNDER FS 471.
 PLEASE KNOW, AN ENGINEER MAY MAKE
 CHANGES TO SAID PLANS, HOWEVER EACH AND
 EVERY ITEM IS REQUIRED TO BE SIGNED AND
 DATED AND "WHITE-OUT" ON PLANS IS NOT
 PERMITTED.
 PLEASE SEE PLANS CONATIN MANY AREAS
 WHERE CHANGES WERE MADE , SOME AREAS
 WHERE "WHITE-OUT WAS USED AND AREA WHERE
 CORRECTIONS WERE "PASTED" OVER PLANS.
 PLANS SHALL BE RE-PRINTED WITH ALL
 CORRECTIONS, SIGNED, DATED AND SEALED BY
 SAID ENGINEER OF RECORD.
 PLEASE SEE COMMENT BELOW AS COPIES OF
 PLANS ARE BEING RETAINED.
  
 16)NOTE: NOTE #16 NO, PLEASE SEE MANY
 LOADS DO NOT MATCH.
 PLEASE SEE LOADS HAVE DECREASED ON PANEL
  
 SCHEDULES ON CALCS AT THE BOTTOM OF THE
 PANEL SCHEDULES, HOWEVER THE LOADS WERE
 INCREASED. PLEASE SEE ALL LOADS ON
 PANELS "A" AND "B". PLEASE SEE PANEL "A"
 WHICH WENT FROM 41.5KVA WHICH INDICATED
 120A'S TO 38.8 KVA AND IS NOW 132A'S??
 THE LOAD DECREASED DUE TO CHANGES,
 HOWEVER LOAD AT PANEL INCREASED??
 PLEASE SEE IN EITHER CASE THE FINAL
 AMPERAGE FROM THE KVA'S SHOWN ARE NOT
 ACCUARATE.
 PLEASE SEE "C" PHASE LOAD INCREASED, YET
 NO LOADS ON PANEL SCHEDULE INCREASED??
  
 PLEASE ALSO SEE THE SAME FOR PANEL "B",
 WHICH SHOWS A SMALL INCREASE DUE TO THE
 ADDITION OF THE SHOW WINDOW KVA, HOWEVER
 PLEASE SEE LOAD CALCULATIONS STILL DO
 NOT CORRELATE. PLEASE SEE KVA IS SHOWN
 @33.9KVA WHICH AT 120/208 3-PHASE IS NOT
 102A'S.
 PLEASE SEE E-2 NOW MENTIONS FOR SERVICE
 TO BE A 250A, YET RISER SHOWS 225A?
 PLEASE SEE LOAD ON E-1 IS NOW THE SAME
 AS THE LOAD ON E-2 FOR SERVICE.
 PLEASE CLARIFY WHERE THESE EXTRA LOADS
 ARE COMING FROM?
 PLEASE SEE NEW NOTES FOR A/C LOADS WHICH
 HAVE COMPLETELY CHANGED.
  
 ** PREVIOUS NOTE **
 PLEASE CORRELATE ALL PANELS ON
 RISER, PANEL SCHEDULES AND SEE NOTES AS
 CODE VIOLATIONS ARE SHOWN FOR NEW
 REVISIONS.
 A)PLEASE SEE RISER NOW SHOWS PANELS AS
 200A BEING FED FROM A 400A DISCONNECT
 AND 400A OCP.?? ORIG RISER SHOWED 400A
 PANELS.
 B)PLEASE SEE BOTH PANELS ARE NOW LISTED
 AS 200A ON RISER AND 225A ON PANEL
 SCHEDULES.??? ORIG PLANS INDICATED
 PANELS ON SCHEDULES AS 400A, ONLY PANEL
 "B" WAS SHOWN AS 400A MCB ON RISER, YET
 400A MLO ON SCHEDULE.
 PLEASE SEE FEEDER TO PANEL "A" STILL
 SHOWN AS 500 MCM'S WHICH ARE RATED AT
 400A'S>
 C) PLEASE SEE LOAD CALCULATIONS MENTIONS
 300A SERVICE.? PLEASE CORRELATE.
 215.5, 2002 NEC.
  
 17) NOTE: NOTE#17 NO? PLEASE SEE NOTHING
 WAS SUBMITTED FOR ANY LIGHTING CONTROLS.
 PLEASE SEE NO RESPONSE WAS NOTED FROM
 DESIGNER TO INDICATE COMPLIANCE FOR
 LIGHTING CONTROLS.
  
 ** PREVIOUS NOTE **
 PLEASE SEE PREVIOUS REVIEW
 REQUESTED DESIGN TO MEET 2004 FBC AS
 PLANS WERE SUBMITTED AFTER 1ST OCT, 2005
 WHEN THE CODE CHANGED.
 PLEASE SEE FBC CHAPTER 13,
 13-415.1.ABC.1.1FOR NEW LIGHTING
 CONTROLS REQUIRED. PLEASE SUBMIT A
 METHOD, AND TIME OF DAY SCHEDULING.
 PLEASE ALSO SEE 13-415.1.ABC.1.2
  
 18) NOTE: NOTE #18 NO, PLEASE SEE A
 NOTICE WAS GIVEN TO BE SURE "ALL"
 COMMENTS FOR CODE COMPLIANCE WAS
 ADDRESSED. PLEASE KNOW THE ENGINEER OF
 RECORD TO DATE HAS NOT CONTACTED THIS
 OFFICE WITH ANY QUESTIONS, OR COMMENTS.
 PLEASE KNOW, THE CONTACT WHICH WERE MADE
 WERE DONE BY THE ARCHITECT OF RECORD.
 PLEASE SEE A FEE HAS NOW BEEN ASSESSED.
 THIS IS THE SOLE RESPONSIBILITY OF THE
 DEISGNER OF RECORD AND IS NOT ASSESSED
 TO THE OWNER OR CONTRACTOR.
 PLEASE SEE THE AMOUNT OF $2,520 HAS BEEN
 ATTACHED AND IS REQUIRED TO BE PAID
 BEFORE RESUBMITTING PLANS.
 PLEASE KNOW, IT IT STRONGLY RECOMMENDED
 A MEETING BE HELD WITH PARTIES OF
 RESPONSIBILITY TO THIS PROJECT TO HELP
 ALLEAVIATE ANY FURTHER DELAYS IN
 ISSUANCE OF THIS PROJECT.
  
  
 ** PLEASE KNOW, ONE SET OFELECTRICAL
 PLANS HAVE BEEN RETAINED FOR FILE.
 PLEASE KNOW, PLANS WILL ALSO BE FORWARD
 TO THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS FOR REVIEW.
  
 ** PREVIOUS NOTE **
 PLEASE SEE COPY OF FLORIDA
 STATUES 553.80(2)(B) WITH RESPECT TO
 DESIGN PROFESSIONALS AND REPEAT COMMENTS
 FOR CODE COMPLIANCE. PLEASE KNOW, IF ANY
 OF THE SAME COMMENTS FROM THE FIRST TWO
 REVIEWS ARE NOT ADDRESSED FOR THIRD SUCH
 REVIEW, THIS OFFICE WILL HAVE NO CHOICE
 BUT TO ASSESS A 4X FEE FOR THE PLAN
 REVIEW PORTION OF THE PERMIT FEE. (30%
 OF BASE FEE X4).
 PLEASE KNOW, TO DATE THIS OFFICE HAS NOT
 BEEN CONTACTED FOR ANY QUESTIONS OR
 COMMENTS.
  
  
 ************ NEW NOTES 3RD REVIEW *****
 DUE TO CHANGES IN PLANS , PLEASE SEE
 NOTES BELOW.
  
 1) NOTE: PLEASE SEE MECHANICAL LOADS
 HAVE BEEN NOTED AS BEING 7.8 KW,
 ALTHOUGH LOADS ON THE PANEL SCHEDULE
 ITSELF REMAIN THE SAME AS THE PERVISOU
 TWO SETS??
 PLEASE SEE THE LOADS AHVE NOW DECREASED,
 YET THE OCP FOR ONE HAS INCREASED AND
 THE OTHER HAS REMAINED THE SAME AS
 BEFORE.
 PLEASE SEE THIS DOES NOT CORRELATE WITH
 MECHANICAL PLANS,AS THE MECHANICAL PLANS
 NOW INDICATE THE KW RATINGS LESS THAN
 HALF OF THE PREVIOUS PLANS.
 PLEASE SEE MECHANICAL PLANS, AS THE OCP
 IS MUCH LOWER THAN THE MAX OCP ON THE
 ELECTRICAL PLANS.
 PLEASE CORRELATE, PLEASE ADJUST LOADS,
 PLEASE ADJUST OCP.
 215.5.
  
 2) NOTE: PLEASE SEE AN ELECTRICAL
 SERVICE ELEVATION IS NOW BEING SHOWN.
 PLEASE VERIFY NO MORE THAN 6 MEANS OF
 DISCONNECT FOR SERVICE.
 230.70,230.71,230.72
 PLEAS KNOW, IT HAS BECOME THE
 DETERMINATION OF THIS OFFICE TO VISIT
 SITE TO VERIFY THE INFORMATION SHOWN.
  
 ** PLEASE KNOW, ONE SET OF EACH OF THE
 PLANS SUBMITTED HAVE NOW BEEN RETAINED
 FOR FILE INCLUDING ORIGINAL PLANS.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS
 FROM OTHER TRADES WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-03-30 Cont ID  
Sent By dpalmer Date 2006-03-30 Time 20:47 Rev Time 0.00
Received By dpalmer Date 2006-03-30 Time 18:58 Sent To  
Notes
2006-03-30 00:00:00IN ELEC FOR REVIEW.
 ******** UNSAT 2ND REVIEW *********
  
 PLEASE SEE NOTES FROM PREVIOUS REVIEW
 WHICH ARE STILL NEEDING TO BE ADDRESSED
 AND NEW COMMENTS TO CHNAGES IN PLANS
 FROM PREVIOUS PLANS SUBMITTED.
  
 * PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW AND NEW
 NOTES ARE ADDED TO THE END OF FIRST
 REVIEW NOTES.
  
 ************ UNSAT ************
  
  
 1)NOTE: NOTE #1 NO, PLEASE SEE PREVIOUS
 NOTE AS PLANS ORIGINALLY CAME IN
 DESIGNED UNDER THE 2001 FBC WHEN THE
 CODE IN EFFECT AT THAT TIME WAS THE
 2004. PLEASE SEE PREVIOUS NOTE MENTIONED
 TO PLEASE MAKE ALL CHANGES IN DESIGN TO
 THE 2004 FBC.
 PLEASE SEE NEW NOTES BELOW.
  
 ** PRE-REVIEW**
 PLEASE SEE PLANS STATE THE 2001
 FBC, HOWEVER AS OF OCT. 1ST, 2005 THE
 CODE HAS CHANGED TO THE 2004 FBC AND ALL
 OTHER RELEVANT CODES.
 PLEASE SEE PERMIT WAS NOT APPLIED FOR
 UNTIL NOV. 21ST, 2005
 PLEASE ADJUST ALL PLANS.
  
 2)NOTE: NOTE #2 OK.
  
 ** PRE-REVIEW**
  
 PLEASE SEE ALL SHEETS IN BOTH SETS ARE
 SEALED PHOTOCOPIES OF SIGNED PLANS.
 PLEASE SEE FS 481.221 AND FAC
 61G1-16.003 WHICH REQUIRE THE PLANS TO
 HAVE AN "ORIGINAL WET SIGNATURE AND
 DATE".
 ** PLEASE KNOW THIS IS REQUIRED FOR ALL
 TRADES AND FOR ALL SHEETS WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
 ONE SET MAY BE RETAINED.
  
 3)NOTE:NOTE #3 OK, HOWEVER SEE NEW
 NOTES FOR HAND DRAWN ITEMS ON SIGNED AND
 SEALED PLANS.
  
 ** PRE-REVIEW**
 PLEASE SEE ELECTRICAL SHEETS
 CONTAIN A TITLE BLOCK FOR AN ENGINEER.
 PLEASE KNOW, IF THIS ENGINEER IS
 RESPONSIBLE FOR DESIGN OR ELECTRICAL
 WORK ON SAID PLANS, THEN PLANS MUST BE
 SIGNED DATED AND SEALED BY SAID
 ENGINEER.
 FS 471.025
 PLEASE ALSO SEE FLORIDA ADMINISTRATIVE
 CODE 61G15-23.002 WHICH REQUIRES THE
 TITLE BLOCK FOR ENGINEER TO BE COMPLETE
 WITH ALL INFORMATION AS SET-FORTH IN THE
 LISTED FAC.
  
 4)NOTE:NOTE #4 OK.
  
 ** PRE-REVIEW**
 PLEASE SEE 600.5 FOR MISSING
 REQUIRED SIGN CIRCUIT.
  
 5)NOTE:NOTE #5 OK, HOWEVER PLEASE SEE
 THESE ARE NOW ADDED, BUT TO THE GENERAL
 RECEPTS IN DINING AREA. PLEASE KNOW,
 THESE SHOULD BE DEDICATED PER LOADS.
 PLEASE SEE210.62,220.12A,220.3(B)(7)
 CODE COMMENTARY FOLLOWING IN THE 2002
 NEC HANDBOOK.
  
 ** PRE-REVIEW**
 PLEASE SEE MISSING REQUIRED
 WINDOW OUTLETS ABOVESTORE FRONT.
 210.62.
 PLEASE SEE MIN KVA TO BE FIGURED PER
 220.12A
 THIS IS TO DISCOURAGE FLOOR RECEPTACLES
 AND UNSIGHTLY EXTENSION CORDS USED FOR
 SIGNAGE, DIPLAYS ETC WHICH ARE LIKELY TO
 CAUSE PHYSICAL INJURY, RECEPTACLES MUST
 BE INSTALLED DIRECTLY ABOVE THE WINDOW.
  
 6)NOTE: NOTE #6 NO, PLEASE SEE THESE ARE
 STILLNOT SHOWN CIRCUITED TO THE LOCAL
 BRANCH CIRCUIT AS REQUIRED PER 700.12E.
 PLEASE SEE CIRCUITING AS SHOWN AND
 "LOCK-OFF" DEVICE LISTED ON PANEL
 SCHEDULE DOES NOT MEET THE "EXCEPTION"
 AS NOTED.
  
 ** PRE-REVIEW**
 PLEASE SEE 700.12E WHICH
 REQUIRES THE BRANCH CIRCUIT FEEDING THE
 UNIT EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
 PLEASE ADJUST CIRCUITING SHOWN ON PLANS.
  
 7)NOTE: NOTE #7 OK.
  
 ** PRE-REVIEW**
 PLEASE COMPLETE SWITCH
 LEGS.SWITCH BANK ON PLANS.
 CAN NOT VERIFY AT THIS TIME.
  
 8)NOTE:NOTE #8 OK, HOWEVER SEE NEW
 NOTE FOR HAND-DRAWN ITEMS ON SIGNED AND
 SEALED PLANS.
  
 ** PRE-REVIEW **
 PLEASE SEE 2002 NEC 210.8B3
 WHICH REQUIRES ALL 15- AND 20-AMPERE,
 125-VOLT RECEPTACLES IN NONDWELLING-TYPE
 KITCHENS TO BE GFCI PROTECTED. THIS
 REQUIREMENT APPLIES TO EACH AND EVERY
 15- AND 20-AMPERE, 125-VOLT KITCHEN
 RECEPTACLE, WHETHER OR NOT THE
 RECEPTACLE SERVES COUNTERTOP APPLIANCES.
  
  
 9)NOTE: NOTE # 9 NO. NONE SUBMITTED.
 PLEASE SEE NEW SERVICE AS SHOWN COMES
 FROM AN EXISTING SERVICE ON MAIN
 BUILDING AND ADDED LOAD TO THE EXISTING
 SERVICE MUST BE VERIFIED.
 PLEASE SEE NEW COMMENTS FOR MANY CHANGES
 ON RISER.
  
 ** PRE-REVIEW**
 PLEASE PROVIDE COMPLETE LOAD
 CALCULATION ON EXISTING SERVICE WHICH
 THIS SERVICE IS BEING TIED INTO.
 IT IS KNOWN TO THIS OFFICE THAT THE
 SERVICE AT THIS LOCATION CONTAINS LOADS
 ON SOME OF THE MAIN SERVICES WHICH ARE
 CLOSE TO EXCEEDING RATED LOADS.
 215.5,220
  
 10)NOTE: NOTE #10 NO?? PLEASE SEE A NOTE
 WAS ADDED FOR "DOWN SYSTEM BREAKER
 SERIES". THIS IS UNCLEAR AS AN AVAILABLE
 FAULT CURRENT IS NOTED AS 37,880 FROM
 FPL, YET THE SERIES RATINGS ARE NOW
 SHOWING 100K??
 PLEASE KNOW, AIC RATINGS SHALL BE STATED
 FOR NEW MAINS, NEW PANELS AND SERIES
 RATING ON BRANCH BRKRS.
 110.9,215.5
  
 ** PRE-REVIEW **PLEASE SUBMIT AIC
 RATINGS FOR ALL NEW SERVICE EQUIPMENT
 BEING INSTALL-ED. MAINS/BRKRS AND PANELS
 ARE ALL TO BE RATED FOR THE AVAILABLE
 FAULT CURRENT.
 PER 110.9/215.5
  
 11)NOTE: NOTE: 11 NO, PELASE SEE THE
 "EQUIPMENT GROUNDING CONDUCTOR" IS NOW
 REMOVED, HOWEVER MAY BE REQUIRED AS THE
 "SERVICE MAIN" IS STILL NOT SHOWN OR
 INDICATED ON PLANS.
 PLEASE KNOW, IF THE "SERVICE MAIN" FOR
 BUILDING IS LOCATED AHEAD OF GUTTER
 SHOWN, THE NEUTRAL AND EQUIPMENT
 GROUNDING CONDUCTORS SHALL NOT BE BONDED
 AFTER THE FIRST MEANS OF DICSCONNECT.A
 "FLOATING NEUTRAL" WILL BE REQUIRED.
  
 ** PRE-REVIEW**
 PLEASE SEE 250.6 , 250.24, IT
 IS NOT SHOWN IF THERE IS A "MAIN" ON THE
 LINE SIDE OF THE GUTTER SHOWN.
 THEREFORE, THE 'EQUIPMENT GROUND" SHOWN
 FROM GUTTER TO METER AND METER TO MAIN
 SHOWN, MAY BE PARALLING THE NEUTRAL.??
 CAN NOT VERIFY AT THIS TIME?
  
 12)NOTE: NOTE#12 NO, PLEASE SEE NEW
 COMMENTS AS RISER DIAGRAM HAS COMPLETELY
 CHANGED FROM PREVIOUS PLANS AND MANY
 CHANGES TO SERVICE WERE MADE.
  
 **PRE-REVIEW**
 PLEASE CORRELATE RISER WITH
 PANELS. PLEASE SEE PANEL "B" IS SHOWN AS
 MLO ON SCHEDULE, HOWEVER RISER SHOWS
 MCB.
  
 13)NOTE:NOTE #13 OK.
  
 **PRE-REVIEW**
 PLEASE SEE CONTINUOUS LOADS ARE
 SHOWN AT 125%, HOWEVER PLEASE ALSO
 INDICATE ANY LARGEST MOTORS LOADS ALSO
 @125%.
 215.3, 230.42 ETC.
  
 14)NOTE: NOTE #14 OK.
  
 ** PRE-REVIEW** PLEASE PROVIDE DETAIL
 FOR MEANS
 OF SHUT DOWN OF ALL ELECTRICAL FOR HOOD.
 NFPA-96
  
  
 ***************************************
 ************* NEW COMMENTS ***********
  
 15) NOTE: PLEASE KNOW, THESE PLANS ARE
 SIGNED DATED AND SEALED PLANS BY AN
 ENGINEER UNDER FLORIDA STATUES 471.
 PLEASE KNOW, HAND DRAWN CHANGES TO
 PLANS, FOR CIRCUITING, DESIGN, NOTES ETC
 ARE NOT PERMITTED UNDER FS 471.
 PLEASE KNOW, AN ENGINEER MAY MAKE
 CHANGES TO SAID PLANS, HOWEVER EACH AND
 EVERY ITEM IS REQUIRED TO BE SIGNED AND
 DATED AND "WHITE-OUT" ON PLANS IS NOT
 PERMITTED.
 PLEASE SEE PLANS CONATIN MANY AREAS
 WHERE CHANGES WERE MADE , SOME AREAS
 WHERE "WHITE-OUT WAS USED AND AREA WHERE
 CORRECTIONS WERE "PASTED" OVER PLANS.
 PLANS SHALL BE RE-PRINTED WITH ALL
 CORRECTIONS, SIGNED, DATED AND SEALED BY
 SAID ENGINEER OF RECORD.
 PLEASE SEE COMMENT BELOW AS COPIES OF
 PLANS ARE BEING RETAINED.
  
 16)NOTE:PLEASE CORRELATE ALL PANEL ONS
 RISER, PANEL SCHEDULES AND SEE NOTES AS
 CODE VIOLATIONS ARE SHOWN FOR NEW
 REVISIONS.
 A)PLEASE SEE RISER NOW SHOWS PANELS AS
 200A BEING FED FROM A 400A DISCONNECT
 AND 400A OCP.?? ORIG RISER SHOWED 400A
 PANELS.
 B)PLEASE SEE BOTH PANELS ARE NOW LISTED
 AS 200A ON RISER AND 225A ON PANEL
 SCHEDULES.??? ORIG PLANS INDICATED
 PANELS ON SCHEDULES AS 400A, ONLY PANEL
 "B" WAS SHOWN AS 400A MCB ON RISER, YET
 400A MLO ON SCHEDULE.
 PLEASE SEE FEEDER TO PANEL "A" STILL
 SHOWN AS 500 MCM'S WHICH ARE RATED AT
 400A'S>
 C) PLEASE SEE LOAD CALCULATIONS MENTIONS
 300A SERVICE.? PLEASE CORRELATE.
 215.5, 2002 NEC.
  
 17) NOTE: PLEASE SEE PREVIOUS REVIEW
 REQUESTED DESIGN TO MEET 2004 FBC AS
 PLANS WERE SUBMITTED AFTER 1ST OCT, 2005
 WHEN THE CODE CHANGED.
 PLEASE SEE FBC CHAPTER 13,
 13-415.1.ABC.1.1FOR NEW LIGHTING
 CONTROLS REQUIRED. PLEASE SUBMIT A
 METHOD, AND TIME OF DAY SCHEDULING.
 PLEASE ALSO SEE 13-415.1.ABC.1.2
  
 18) NOTE: PLEASE SEE COPY OF FLORIDA
 STATUES 553.80(2)(B) WITH RESPECT TO
 DESIGN PROFESSIONALS AND REPEAT COMMENTS
 FOR CODE COMPLIANCE. PLEASE KNOW, IF ANY
 OF THE SAME COMMENTS FROM THE FIRST TWO
 REVIEWS ARE NOT ADDRESSED FOR THIRD SUCH
 REVIEW, THIS OFFICE WILL HAVE NO CHOICE
 BUT TO ASSESS A 4X FEE FOR THE PLAN
 REVIEW PORTION OF THE PERMIT FEE. (30%
 OF BASE FEE X4).
 PLEASE KNOW, TO DATE THIS OFFICE HAS NOT
 BEEN CONTACTED FOR ANY QUESTIONS OR
 COMMENTS.
 ** PLEASE KNOW, ONE SET OF EACH OF THE
 PLANS SUBMITTED HAVE NOW BEEN RETAINED
 FOR FILE INCLUDING ORIGINAL PLANS.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS
 FROM OTHER TRADES WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-12-24 Cont ID  
Sent By dpalmer Date 2005-12-24 Time 08:16 Rev Time 0.00
Received By dpalmer Date 2005-12-24 Time 07:27 Sent To  
Notes
2005-12-24 00:00:00************ UNSAT ************
  
 ** PLEASE SEE THIS IS A CHANGE IN
 OCCUPANCY AND ALL ITEMS MUST BE BROUGHT
 UP TO CODE.
  
 ** PLEASE ALSO SEE ADDRESSING NEEDS TO
 BE CORRECTED. PLEASE SEE PERMIT
 APPLICATION PCN USED DIRECTS ADDRESS TO
 831 VILLAGE , HOWEVER PERMIT APPLICATION
 SHOWS 871 VILLAGE, AND PLANS ALSO SHOW
 871 VILLAGE.
  
 1)NOTE: PLEASE SEE PLANS STATE THE 2001
 FBC, HOWEVER AS OF OCT. 1ST, 2005 THE
 CODE HAS CHANGED TO THE 2004 FBC AND ALL
 OTHER RELEVANT CODES.
 PLEASE SEE PERMIT WAS NOT APPLIED FOR
 UNTIL NOV. 21ST, 2005
 PLEASE ADJUST ALL PLANS.
  
 2)PLEASE SEE ALL SHEETS IN BOTH SETS ARE
 SEALED PHOTOCOPIES OF SIGNED PLANS.
 PLEASE SEE FS 481.221 AND FAC
 61G1-16.003 WHICH REQUIRE THE PLANS TO
 HAVE AN "ORIGINAL WET SIGNATURE AND
 DATE".
 ** PLEASE KNOW THIS IS REQUIRED FOR ALL
 TRADES AND FOR ALL SHEETS WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
 ONE SET MAY BE RETAINED.
  
 3)NOTE: PLEASE SEE ELECTRICAL SHEETS
 CONTAIN A TITLE BLOCK FOR AN ENGINEER.
 PLEASE KNOW, IF THIS ENGINEER IS
 RESPONSIBLE FOR DESIGN OR ELECTRICLA
 WORK ON SAID PLANS, THEN PLANS MUST BE
 SIGNED DATED AND SEALED BY SAID
 ENGINEER.
 FS 471.025
 PLEASE ALSO SEE FLORIDA ADMINISTRATIVE
 CODE 61G15-23.002 WHICH REQUIRES THE
 TITLE BLOCK FOR ENGINEER TO BE COMPLETE
 WITH ALL INFORMATION AS SET-FORTH IN THE
 LISTED FAC.
  
 4)NOTE: PLEASE SEE 600.5 FOR MISSING
 REQUIRED SIGN CIRCUIT.
  
 5)NOTE: PLEASE SEE MISSING REQUIRED
 WINDOW OUTLETS ABOVESTORE FRONT.
 210.62.
 PLEASE SEE MIN KVA TO BE FIGURED PER
 220.12A
 THIS IS TO DISCOURAGE FLOOR RECEPTACLES
 AND UNSIGHTLY EXTENSION CORDS USED FOR
 SIGNAGE, DIPLAYS ETC WHICH ARE LIKELY TO
 CAUSE PHYSICAL INJURY, RECEPTACLES MUST
 BE INSTALLED DIRECTLY ABOVE THE WINDOW.
  
 6)NOTE: PLEASE SEE 700.12E WHICH
 REQUIRES THE BRANCH CIRCUIT FEEDING THE
 UNIT EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
 PLEASE ADJUST CIRCUITING SHOWN ON PLANS.
  
 7)NOTE: PLEASE COMPLETE SWITCH
 LEGS.SWITCH BANK ON PLANS.
 CAN NOT VERIFY AT THIS TIME.
  
 8)NOTE: PLEASE SEE 2002 NEC 210.8B3
 WHICH REQUIRES ALL 15- AND 20-AMPERE,
 125-VOLT RECEPTACLES IN NONDWELLING-TYPE
 KITCHENS TO BE GFCI PROTECTED. THIS
 REQUIREMENT APPLIES TO EACH AND EVERY
 15- AND 20-AMPERE, 125-VOLT KITCHEN
 RECEPTACLE, WHETHER OR NOT THE
 RECEPTACLE SERVES COUNTERTOP APPLIANCES.
  
  
 9)NOTE: PLEASE PROVIDE COMPLETE LOAD
 CALCULATION ON EXISTING SERVICE WHICH
 THIS SERVICE IS BEING TIED INTO.
 IT IS KNOWN TO THIS OFFICE THAT THE
 SERVICE AT THIS LOCATION CONTAINS LOADS
 ON SOME OF THE MAIN SERVICES WHICH ARE
 CLOSE TO EXCEEDING RATED LOADS.
 215.5,220
  
 10)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 11)NOTE: PLEASE SEE 250.6 , 250.24, IT
 IS NOT SHOWN IF THERE IS A "MAIN" ON THE
 LINE SIDE OF THE GUTTER SHOWN.
 THEREFORE, THE 'EQUIPMENT GROUND" SHOWN
 FROM GUTTER TO METER AND METER TO MAIN
 SHOWN, MAY BE PARALLING THE NEUTRAL.??
 CAN NOT VERIFY AT THIS TIME?
  
 12)NOTE: PLEASE CORRELATE RISER WITH
 PANELS. PLEASE SEE PANEL "B" IS SHOWN AS
 MLO ON SCHEDULE, HOWEVER RISER SHOWS
 MCB.
  
 13)NOTE: PLEASE SEE CONTINUOUS LOADS ARE
 SHOWN AT 125%, HOWEVER PLEASE ALSO
 INDICATE ANY LARGEST MOTORS LOADS ALSO
 @125%.
 215.3, 230.42 ETC.
  
 14)NOTE: PLEASE PROVIDE DETAIL FOR MEANS
 OF SUT DOWN OF ALL ELECTRICAL FOR HOOD.
 NFPA-96
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS
 FROM OTHER TRADES WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2006-06-07 Cont ID  
Sent By mwennerg Date 2006-06-07 Time 14:36 Rev Time 0.00
Received By mwennerg Date 2006-06-07 Time 14:36 Sent To  
Notes
2006-06-07 00:00:00PLANS RED LINED REFERENCE TO CORRECT
 LIFE SAFETY CODE EDITION.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2006-05-31 Cont ID  
Sent By mwennerg Date 2006-05-31 Time 13:31 Rev Time 0.00
Received By mwennerg Date 2006-05-31 Time 13:31 Sent To  
Notes
2006-05-31 00:00:00***DENIED***
  
 1) PLEASE BE AWARE THAT DOOR SCHEDULE
 NOTE ON A.3 STILL REFERENCES THE
 INCORRECT LIFE SAFETY CODE. NFPA 101,
 2003 EDITION SHALL BE REFERENCED. PLEASE
 REFER TO LAST FIRE REVIEW.
  
 2) EXTERIOR DOORS SHALL NOT BE EQUIPED
 WITH KEY LOCKS UNLESS THE CRITERIA OF
 NFPA 101, SECTION 7.2.1.5.3 IS MET.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-04-12 Cont ID  
Sent By mwennerg Date 2006-04-12 Time 11:09 Rev Time 0.00
Received By mwennerg Date 2006-04-12 Time 11:09 Sent To  
Notes
2006-04-12 00:00:00******PROVISO******
  
 1) PLEASE NOTE THAT NFPA 101, 2003
 EDITION SHALL BE REFERENCED. IT WOULD
 APPEAR THAT THE WRONG EDITION IS
 INDICATED ON SHT A-3 DOOR SCHEDULE.
  
 2) SEPARATE SHOP DRAWINGS AND PERMITS
 REQUIRED FOR FIRE SPRINKLER REMODEL AND
 HOOD SUPPRESSION EQUIPMENT.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-12-06 Cont ID  
Sent By mcarsill Date 2005-12-06 Time 15:01 Rev Time 0.00
Received By mcarsill Date 2005-12-06 Time 14:50 Sent To  
Notes
2005-12-06 00:00:001. CHANGE OF USE FROM BUSINESS TO
 ASSEMBLY OCCUPANCY.NEW SPACE IS REQUIRED
 TO MEET NEW ASSEMBLY CRITERIA.
  
 2. DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 3. DEBRIS SHALL BE REMOVED FROM SITE
 DAILY.
  
 4. SEPERATE PLANS AND PERMITS REQUIRED
 FOR THE HOOD, DUCT, AND SUPPRESSION
 SYSTEM PLANNED FOR USE.
  
 5. IF DUCT WRAP IS PLANNED, DETAILS ARE
 TO BE PROVIDED.
  
 6. OCCUPANT LOAD IS TO BE POSTED.
  
 7. PORTABLE FIRE EXTINGUISHERS ARE
 REQUIRED.
  
 8. ARE YOU SURE THE BUILDING IS NOT FIRE
 SPRINKLER PROTECTED.
  
 9. PLEASE INDICATE SEATING FOR THE
 HANDICAPPED.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2006-05-03 Cont ID  
Sent By pschmitz Date 2006-05-03 Time 14:02 Rev Time 0.00
Received By pschmitz Date 2006-05-03 Time 13:46 Sent To  
Notes
2006-05-04 00:00:00GAS PLAN REVIEW RE- SUB PROVISO:
 SHT P.3 DRIP LEG MOVED TO INSTANT HOT
 DROP.
 SHT P.3 GAS PIPE MATERIAL, GALV SCH 40

Review Stop G GAS REVIEW
Rev No 3 Status N Date 2006-04-25 Cont ID  
Sent By pschmitz Date 2006-04-25 Time 15:04 Rev Time 0.00
Received By pschmitz Date 2006-04-25 Time 15:04 Sent To  
Notes
2006-04-25 00:00:00CONFERENCE CALL WITH BOB GREG.
 PREVIOUS COMMENTS FOR RE-SUB ADDRESSED,
 SATISFACTORILY.

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2006-04-15 Cont ID  
Sent By pschmitz Date 2006-04-15 Time 06:40 Rev Time 0.00
Received By pschmitz Date 2006-04-15 Time 06:40 Sent To  
Notes
2006-04-15 00:00:00PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE,
  
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
 UNSAT
  
 1) REVIOUS NOTE #8 NOT ADDRESSED.
 8. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 2)SHT M.2 NOTE "H" GAS FIRED DUCT
 HEATER.
 NOT INCLUDED ON GAS ISOMETRIC, 175 BTU
  
 3)SEC 409.5 EQUIPMENT SHUT OFFF VALVES.
 SHT MH.2EMERGENCY HOOD SHUT DOWN SHUT
 OFF VALVE TO BE BELOW CEILING. MANUAL
 SHUT OFF VALVE TO BE UPSTREAM. UNION TO
 BE DOWNSTREAM OF MANUAL SHUT OFF VALVE.
  
 END OF COMMENTS, QUESTIONS 561-805-6692

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-04-12 Cont ID  
Sent By pschmitz Date 2006-02-01 Time 10:00 Rev Time 0.00
Received By pschmitz Date 2006-02-01 Time 10:00 Sent To  
Notes
2006-02-01 00:00:00REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR THE GAS PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 3. TYPE OF GAS, (LP OR NATURAL)
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304
 .
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
 9. SEPERATE GAS PERMIT REQUIRED.
  
 END OF COMMENTS, QUESTIONS 561-805-6692
  

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-07-26 Cont ID  
Sent By adarroug Date 2006-07-26 Time 14:27 Rev Time 0.00
Received By adarroug Date 2006-07-26 Time 14:27 Sent To M
Notes
2006-07-26 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-07-22 Cont ID  
Sent By adarroug Date 2006-07-22 Time 13:23 Rev Time 0.00
Received By adarroug Date 2006-07-22 Time 13:23 Sent To E
Notes
2006-07-22 00:00:00TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-06-26 Cont ID  
Sent By adarroug Date 2006-06-26 Time 15:10 Rev Time 0.00
Received By adarroug Date 2006-06-26 Time 15:10 Sent To E
Notes
2006-06-26 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-05-24 Cont ID  
Sent By adarroug Date 2006-05-24 Time 11:38 Rev Time 0.00
Received By adarroug Date 2006-05-24 Time 11:38 Sent To  
Notes
2006-05-24 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-05-04 Cont ID  
Sent By adarroug Date 2006-05-04 Time 11:46 Rev Time 0.00
Received By adarroug Date 2006-05-04 Time 11:46 Sent To  
Notes
2006-05-24 00:00:00TO "COMM" BD#10
2006-05-04 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-05-03 Cont ID  
Sent By adarroug Date 2006-05-03 Time 13:42 Rev Time 0.00
Received By adarroug Date 2006-05-03 Time 13:42 Sent To P
Notes
2006-05-03 00:00:00TO "PSCHMITZ" DESK/RESUB-EXPEDITED PLANS

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-03-06 Cont ID  
Sent By adarroug Date 2006-03-06 Time 16:46 Rev Time 0.00
Received By adarroug Date 2006-03-06 Time 16:46 Sent To  
Notes
2006-03-31 00:00:00TO "COMM" BD#56
2006-03-06 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-02-07 Cont ID  
Sent By jwitmer Date 2006-02-07 Time 16:55 Rev Time 0.00
Received By jwitmer Date 2005-11-28 Time 11:04 Sent To  
Notes
2005-12-06 00:00:00TO "COMM" BD#57
2005-11-28 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-06-13 Cont ID  
Sent By pkrauss Date 2006-06-13 Time 15:42 Rev Time 0.00
Received By pkrauss Date 2006-06-13 Time 15:26 Sent To  
Notes
2006-06-13 00:00:00PROVISO:
  
 1.ROOF CURBS SHALL EXTEND A MINIMUM OF
 8" ABOVE THE ROOF SURFACE IN ACCORDANCE
 WITH 2004 FBC 1509.7.
  
 2.ADDITIONAL PERMITS REQUIRED FOR THE
 HOOD, FIRE SUPPRESSION, & HOOD.PLEASE
 PROVIDE THE MANUFACTURE SUBMITTAL DATA
 FOR THE WALK-IN COOLER WITH PERMIT
 APPLICATION.HOOD & FIRE SUPPRESSION
 PLANS SUBMTITED WITH BUILDING PLANS.
  
 3.FAN SHUTDOWN BY DUCT SMOKE DETECTORS
 REQUIRED PER 2004 FMC 606.2.1 WITH
 NOTIFICATION AS SPECIFIED IN 2004 FMC
 606.4 & 606.4.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT(561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2006-05-09 Cont ID  
Sent By pkrauss Date 2006-05-09 Time 09:24 Rev Time 0.00
Received By pkrauss Date 2006-05-09 Time 09:24 Sent To I
Notes
2006-05-09 00:00:00PROVISO:
  
 FIRE DAMPERS REQUIRED WHERE DUCTS
 PENETRATE WALL BETWEEN THE KITCHEN AND
 THE CORRIDOR.PLAN SHEET A.1 INDICATES
 THIS AS A 1 HR CORRIDOR.PLANS DO NOT
 INDICATE RATING OF THE WALL BETWEEN THE
 CORRIDOR AND THE RESTROOMS. THE "1 HR
 CORRIDOR" WOULD INDICATE ALL WALLS
 ENCLOSING THE CORRIDOR WILL BE RATED IN
 WHICH THE PENETRATIONS FROM THE CORRIDOR
 INTO THE RESTROOMS WOULD ALSO REQUIRE
 FIRE DAMPERS.PLEASE REVISE
 ARCHITECTURAL PLANS SHOULD THE PARTITION
 BETWEEN THE CORRIDOR AND THE RESTROOMS
 IS NOT IN FACT A "1 HR" PARTITION.
  
 PLEASE NOTE, PLAN SHEET M.1 FIRE DAMPER
 DETAIL STATES FIRE DAMPER PENETRATION TO
 HAVE 3M FIRE STOP.PLEASE CHECK FIRE
 DAMPER INSTALLATION INSTRUCTIONS FOR
 APPROVAL OF THIS APPLICATION.FIRE
 DAMPERS ARE MADE TO EXPAND AND WILL NOT
 FUCTION PROPERLY WITH FIRE STOP.
 PROVIDE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS FOR THE FIRE DAMPERS ON THE
 JOBSITE FOR INSPECTION.
  
 HOOD AND FIRE SUPPRESSION PLANS
 SUBMITTED AND APPROVED WITH BUILDING
 PLANS.ADDITIONAL PERMIT REQUIRED FOR
 HOOD, FIRE SUPPRESSION, AND WALK-IN
 COOLERS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-04-17 Cont ID  
Sent By rregueir Date 2006-04-17 Time 13:47 Rev Time 0.00
Received By rregueir Date 2006-04-17 Time 13:33 Sent To PC
Notes
2006-04-17 00:00:00----------------PROVISO-----------------
  
 PROVIDE U.L. LISTED FIRE DAMPER
 MANUFACTURER'S INSTALLATION INSTRUCTIONS
 ON SITE FOR FIELD INSPECTOR.
  
 RONALD J REGUEIRO
 561-805-6734

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2005-12-13 Time   Rev Time 0.00
Received By rregueir Date 2005-12-13 Time 14:19 Sent To  
Notes
2005-12-13 00:00:00------------------DENIED----------------
  
 1)PAGE EQ.1 GENERAL NOTE #2 REFERS TO
 BUILDING CODE BODIES NOT APPLICABLE IN
 THIS JURISDICTION.PLEASE REFERENCE FBC
 2004.
  
 2)PAGE A.1 BUILDING PLAN SHOWS ONE HOUR
 RATED CORRIDOR TO BACK EXIT FROM DINING
 ROOM.DUCTS PENETRATING RATED ASSEMBLES
 REQUIRE FIRE DAMPERS PER FBC,M 607.5.
 PAGE M.1 SHOWS THREE DUCTS PENETRATING
 CORRIDOR WALL ASSEMBLIES.
  
 3)PAGE M.1 ROOF WORK SHOWS A COOLER
 CONDENSOR NEAR THE ROOF EDGE.A GUARD
 IS REQUIRED IF EQUIPMENT REQUIRING
 SERVICE IS LOCATED WITHIN 10' OF ROOF
 EDGE PER FBC,M 304.10.
  
 4)PAGE EQ.1 EQUIPMENT SCHEDULE #22 SHOWS
 A WALK-IN COOLER. A SEPERATE PERMIT
 APPLICATION IS REQUIRED FOR THIS WORK.
  
 5)PAGES MH.1 THRU MH.3 SHOW MECHANICAL
 HOOD AND HOOD SUPPRESSION SYSTEMS.
 SEPERATE PERMIT APPLICATIONS AND
 SUPPORTING DOCUMENTATION IS REQUIRED FOR
 EACH OF THOSE SYSTEMS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 RON REGUEIRO AT 561.805.6734 OR PATTY
 KRAUSS AT 561.805.6719

Review Stop P PLUMBING
Rev No 5 Status P Date 2006-06-16 Cont ID  
Sent By pschmitz Date 2006-06-16 Time 14:05 Rev Time 0.00
Received By pschmitz Date 2006-06-16 Time 14:05 Sent To  
Notes
2006-06-16 00:00:00PROVISO:
 WATER ISOMERTRIC, SOV ON ALL WATER DOWN
 FEEDS.

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-05-04 Cont ID  
Sent By pschmitz Date 2006-05-04 Time 10:43 Rev Time 0.00
Received By pschmitz Date 2006-05-04 Time 10:42 Sent To  
Notes
2006-05-04 00:00:00PLUMBING RE-SUB 5-4-06 PROVISO
 ALL WATER SOV'S ON DROPS
 INSTANT HOT SHOWS COLD WATER IN AND OUT.

Review Stop P PLUMBING
Rev No 3 Status N Date 2006-04-25 Cont ID  
Sent By pschmitz Date 2006-04-25 Time 15:13 Rev Time 0.00
Received By pschmitz Date 2006-04-25 Time 15:13 Sent To  
Notes
2006-04-25 00:00:00CONFERENCE CALL WITH BOB GREG
 PREVIOUS COMMENTS FOR RE-SUB ADDRESSED
 SATISFACTORILY.

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-04-15 Cont ID  
Sent By pschmitz Date 2006-04-15 Time 07:39 Rev Time 0.00
Received By pschmitz Date 2006-04-15 Time 07:38 Sent To  
Notes
2006-04-15 00:00:00PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPT.1, ADMINISTRATION, 2004 EDITION
 UNSAT
 1) WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE
 ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 2) PREVIOUS NOTE #3 NOT ADDRESSED.
 SHT P.2 GREASE INTERCEPTOR TO BE SIZED
 BY WEST PALM BEACH WATER LABORATORY.
 SHT.P-1,P-2 SEC 1003 GREASE TRAP.
 CONTACT W P BEACHWATERPLANT LAB
 SUPERVISOR, INDUSTRIAL COORDINATOR,
 LYNN MASSON OFFICE 561-822-2271
 E-MAIL [email protected]
  
 3) SHT P.2 SEC 504.7.1WATER HEATER
 DETAIL, PAN DRAIN REQUIRED,MINIMUM
 SIZE 3/4", MATERIA: PVC NOT APPROVED.
  
 4)SHT P.3 SEC 912 COMBINATION WASTE AND
 VENT SYSTEM.
 (A) SEC 1002.5 SIZE OF FIXTURE TRAP.
 A TRAP SHALL NOT BE LARGER THAN THE
 DRAINAGE PIPE INTO WHICH THE TRAP
 DISCHARGES. FS, FIXTURE DRAINS
 (B) TAB 906.1 MAXIMUM DISTANCE OF
 FIXTURE TRAP FROM VENT.EQUIPMENT #7,
 #8 ICE , SODA DISPENSER FS
  
 5) SHT P.1PLEASE CLARIFI,FS BETWEEN
 HAND SINK AND SODA & ICE DISPENSER IS
 SHOWN IN A WALK AREA. 4'1" FROM WALL,
 FS ARE FOR INDIRECT WASTE, NOT TO BE
 USED AS A FLOOR DRAIN.
 END OF COMMENTS, QUESTIONS 561-805-6692

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-02-04 Cont ID  
Sent By pschmitz Date 2006-02-04 Time 08:42 Rev Time 0.00
Received By pschmitz Date 2006-02-04 Time 08:41 Sent To  
Notes
2006-01-30 00:00:00PAUL SCHMITZ
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 PLUMBING CODEPLAN REVIEW
 FBC 2004 FL ACESSIBILITY CODE PLAN
 REVIEW
 1)SHT.C-S APPLICABLE CODES, FBC 2004
  
 2)PLANS SHALL BE ROUTED TO DBPR
 BUSINESS AND HOTEL DIVISION FOR
 REVIEW. MINIMUM 2 SETS OF PLANS
 SHALL BE REVIEWED AND STAMPED
 AND THE TWO PAGE ?WORKSHEETS?
 ATTACHED TO EACH SET OF PLANS
 PRIOR TO RESUBMITTING TO CITY OF WEST
 PALM BEACH
 FOR REVIEW. PLEASE CONTACT DBPR
 AT (850) 487-1395.
 3)SHT.P-1,P-2 SEC 1003 GREASE TRAP.
 SHALL NOT BE LOCATED IN FOOD PREPREATION
 AREA.FOR GREASE TRAP SIZE.
 CONTACT W P BEACHWATERPLANT LAB
 SUPERVISOR, INDUSTRIAL COORDINATOR,
 LYNN MASSON OFFICE 561-822-2271
 E-MAIL [email protected]
 4)SHT P-3 WATER RISER: SHOW SOURCE
 OF WATER SUPPLY ANDLOCATION OF BACK
 FLOW PREVENTER, LOCAL ORDINANCE #2853-95
 5)WATER RISER SEC 607.3.2 THERMAL
 EXPANSION A MEANS OF CONTROLLING THERMAL
 EXPANSION SHALL BE PROVIDED.
 6) SHT.P-1 SEC 606.1(4) LOCATION OF FULL
 OPEN VALVES. SHALL BE ON THE TOP OF
 EVERY DOWN FEED PIPE IN OCCUPANCIES
 OTHER THAN ONE AND TWO FAMILY RESIDENTAL
 OCCUPANCIES.
 7) SHT P-3 SEC 601.1 SCOPE. TYPE OF
 MATERIAL FOR WATER PIPING.
 8) SHT.P-3 SEC 701.1 SCOPE. TYPE OF
 MATERIAL FOR DRAIN WASTE AND VENT.
 END OF COMMENTS, QUESTIONS 561-805-6692

Review Stop Z ZONING
Rev No 1 Status P Date 2006-01-24 Cont ID  
Sent By mmclean Date 2006-01-24 Time 13:12 Rev Time 0.00
Received By mmclean Date 2006-01-24 Time 13:12 Sent To  
Notes
2006-01-24 00:00:00OK FOR CHANGE OF USE.