| Plan Review Stops For Permit 05110709 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2006-04-26 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2006-04-26 |
Time |
16:41 |
Rev Time |
1.00 |
| Received By |
jgomez |
Date |
2006-04-26 |
Time |
16:41 |
Sent To |
PC |
|
| Notes |
| 2006-04-26 00:00:00 | PLANS UNDER "T". JG. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2006-03-23 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2006-03-23 |
Time |
07:58 |
Rev Time |
2.50 |
| Received By |
jgomez |
Date |
2006-03-23 |
Time |
07:52 |
Sent To |
Z |
|
| Notes |
| 2006-03-23 00:00:00 | BUILDING REVIEW CHECKLIST: | | | 1- MISSING DRAWING A-3, ROOF FRAMING | | | PLAN. | | | | | | 2- SURVEY NOT SUBMITTED. NEED SURVEY TO | | | VERIFY HOUSE ORIENTATION FOR ENERGY | | | CALCULATIONS. | | | | | | 3- NEED RECORDED NOTICE OF COMMENCEMENT. | | | | | | 4- PROVIDE BATHROOM WITH DOOR THAT | | | ALLOWS 29" MIN. CLEAR OPENING. SEC. 322 | | | 2004 RESIDENTIAL CODE. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-12-29 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2005-12-29 |
Time |
11:09 |
Rev Time |
3.00 |
| Received By |
jgomez |
Date |
2005-12-29 |
Time |
11:09 |
Sent To |
M |
|
| Notes |
| 2005-12-29 00:00:00 | BUILDING REVIEW CHECKLIST: | | | 1- ALL PLANS SUBMITTED AFTER OCTOBER 1ST | | | 2005 ARE REQUIRED TO COMPLY WITH FBC | | | 2004. REVISE ALL PLANS, GENERAL NOTES, | | | DESIGN PARAMETERS, CONSTRUCTION TYPE AND | | | ALL PERTINENT ITEMS SHOWN ON PLANS AS | | | REQUIRED TO COMPLY WITH FBC 2004. | | | | | | 2- ENERGY CALCULATIONS: | | | A) REVISE UNDER ATTIC AREA TO COMPLY | | | WITH SEC. 13-604.1.A.1 FBC 2004. | | | | | | B) ENERGY CALCS ARE TO BE CALCULATED | | | FOR WORST CASE SCENARIO OR BE SPECIFIC | | | TO THE LOCATION OF THE HOUSE. ENERGY | | | CALCS SUBMITTED ARE NOT FOR WORST CASE | | | SCENARIO AND DON'T MATCH SPECIFIC | | | ORIENTATION OF THIS HOUSE. REVISE AS | | | REQUIRED. | | | | | | 3- TRUSS DESIGN DRAWINGS NEED TO BE | | | PROVIDED TO THE BUILDING OFFICIAL FOR | | | APPROVAL PRIOR TO INSTALLATION. SEC. | | | R802.10.1 RESIDENTIAL FBC 2004. | | | (REMAINDER: DESIGNER OF RECORD TO REVIEW | | | ALL TRUSSES PRIOR TO SUBMITTAL TO THIS | | | OFFICE). | | | | | | 4- DESIGNER OF RECORD TO REVIEW ALL | | | PRODUCT APPROVALS PRIOR TO SUBMITTAL TO | | | THIS OFFICE AS REQUIRED BY SEC. 106.3.3 | | | CITY AMENDMENTS TO FBC 2004 | | | | | | 5- PROVIDE ALL INFORMATION ON PLANS | | | REGARDING THE GARAGE SEPARATION AND | | | OPENING PROTECTION AS REQUIRED BY SEC. | | | R309 OF RESIDENTIAL FBC 2004. | | | | | | 6- NEED RECORDED NOTICE OF COMMENCEMENT. | | | | | | 7- AREA CALCULATIONS ON SHEET A2 DON'T | | | INCLUDE THE EXERCISE ROOM NEXT TO THE | | | GOLF CART AREA. ALSO, A/C PLANS SHOW | | | GOLF CART AND EXERCISE AREAS TO BE A/C. | | | REVISE ALL CALCULATIONS AS REQUIRED. | | | | | | 8- PROVIDE FLORIDA OR LOCAL PRODUCT | | | APPROVAL FOR: | | | A) TRUSS CONNECTORS. PROVIDE ONLY THE | | | COVER PAGE AND THE PAGES SHOWING THE | | | SPECIFIC CONNECTORS THAT ARE SPECIFIED | | | ON PLANS. PLEASE, DON'T SUBMITT ALL | | | PRODUCT APPROVAL REPORT TO EXPEDITE THE | | | REVIEW PROCESS AND SAVE PAPER. | | | | | | B) CASEMENT WINDOWS: NEED 2004 CODE | | | VERSION FLORIDA PRODUCT APPROVAL PAGE | | | AND THE DADE COUNTY NOA THAT MATCHES NOA | | | SUBMITTED FOR FLORIDA APPROVAL. | | | | | | C) ENTRY DOORS PRODUCT APPROVAL | | | SUBMITTED SPECIFIES ON SHEET 1 OF 5 THAT | | | SHUTTERS ARE REQUIRED. THIS HOUSE IS | | | SUPPOSED TO HAVE IMPACT GLAZING IN ALL | | | DOORS AND WINDOWS. SUBMIT PROPER PRODUCT | | | APPROVAL. | | | | | | D) 2" WINDOW MULLIONS: PROVIDE CURRENT | | | 2004 CODE VERSION FLORIDA PRODUCT | | | APPROVAL AND DADE COUNTY NOA THAT | | | MATCHES NOA SUBMITTED FOR FLORIDA | | | APPROVAL. | | | | | | E) GARAGE DOORS: NEED 2004 FLORIDA CODE | | | VERSION. FL #542 IS NO LONGER LISTED IN | | | THE FLORIDA WEBSITE. | | | | | | 9- SOIL TEST REPORT WAS DONE BASED ON | | | FBC 2001. NEED CURRENT SOIL TEST REPORT | | | COMPLYING WITH FBC 2004. | | | | | | 10- SHEET A6: PROVIDE DETAILS AND SPECS | | | FOR GATED COURTYARD ENTRANCE | | | CONSTRUCTION. SEC. 106.1.2 CITY | | | AMENDMENTS TO FBC 2004. | | | | | | 11- A) REVISE REAR AND RIGHT ELEVATIONS | | | TO SHOW BBQ AREA AND BBQ HOOD. | | | | | | B) FLOOR PLAN ON SHEET A2 TO | | | INDICATE HOOD ABOVE BBQ GRILL. | | | | | | 12- PROVIDE BATHROOM WITH DOOR THAT | | | ALLOWS 29" CLEAR OPENING. SEC. R322 | | | RESIDENTIAL FBC 2004. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2007-04-20 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-04-20 |
Time |
13:07 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2007-04-20 |
Time |
12:43 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2006-12-08 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-12-08 |
Time |
14:50 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2006-12-08 |
Time |
14:13 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2006-10-20 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-10-20 |
Time |
13:12 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2006-10-20 |
Time |
12:06 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2006-03-14 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-03-14 |
Time |
08:47 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2006-03-14 |
Time |
07:37 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2005-12-08 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2005-12-08 |
Time |
08:31 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2005-12-08 |
Time |
06:42 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
11 |
Status |
N |
Date |
2007-04-09 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-04-09 |
Time |
14:22 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-04-09 |
Time |
14:22 |
Sent To |
E |
|
| Notes |
| 2007-04-09 14:22:42 | TO "BTROBAUG" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
10 |
Status |
N |
Date |
2007-01-09 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-01-09 |
Time |
16:22 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-01-09 |
Time |
16:22 |
Sent To |
P |
|
| Notes |
| 2007-01-09 16:22:14 | TO "P" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
N |
Date |
2006-11-30 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-11-30 |
Time |
11:48 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-11-30 |
Time |
11:48 |
Sent To |
E |
|
| Notes |
| 2006-11-30 11:48:27 | TO "BTROBAUG" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2006-10-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-10-14 |
Time |
14:31 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-10-14 |
Time |
14:31 |
Sent To |
E |
|
| Notes |
| 2006-10-14 14:32:00 | TO "BTROBAUG" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2006-10-10 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-10-10 |
Time |
12:56 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-10-10 |
Time |
12:55 |
Sent To |
M |
|
| Notes |
| 2006-10-10 12:56:29 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2006-04-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-04-14 |
Time |
10:22 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-04-14 |
Time |
10:22 |
Sent To |
B |
|
| Notes |
| 2006-04-14 00:00:00 | TO "JGOMEZ" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2006-04-05 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-04-05 |
Time |
14:21 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-04-05 |
Time |
14:21 |
Sent To |
Z |
|
| Notes |
| 2006-04-05 00:00:00 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2006-03-07 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-03-07 |
Time |
08:13 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-03-07 |
Time |
08:13 |
Sent To |
E |
|
| Notes |
| 2006-03-07 00:00:00 | TO "BTROBAUG" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-02-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-02-24 |
Time |
09:39 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-02-24 |
Time |
09:39 |
Sent To |
Z |
|
| Notes |
| 2006-02-24 00:00:00 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-12-07 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-12-07 |
Time |
09:32 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-12-07 |
Time |
09:32 |
Sent To |
E |
|
| Notes |
| 2005-12-07 00:00:00 | TO "SFR" "E" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-12-29 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2005-12-29 |
Time |
14:15 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2005-11-28 |
Time |
10:31 |
Sent To |
|
|
| Notes |
| 2005-11-28 00:00:00 | TO "Z" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2006-10-11 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-10-11 |
Time |
11:44 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2006-10-11 |
Time |
11:44 |
Sent To |
|
|
| Notes |
| 2006-10-11 11:44:43 | REVISION TO MECH. PLANS. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2006-03-14 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-03-14 |
Time |
10:40 |
Rev Time |
0.35 |
| Received By |
tgordon |
Date |
2006-03-14 |
Time |
10:40 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2005-12-30 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2005-12-30 |
Time |
08:36 |
Rev Time |
0.45 |
| Received By |
tgordon |
Date |
2005-12-30 |
Time |
08:36 |
Sent To |
|
|
| Notes |
| 2005-12-30 00:00:00 | *** DENIED *** | | | 1) ALL INFORMATION, DRAWINGS, | | | SPECIFICATIONS AND ACCOMPANYING DATA | | | SHALL BEAR THE NAME AND SIGNATURE OF THE | | | PERSON RESPONSIBLE FOR THE DESIGN. PER | | | FBC 104.2.1 . PLEASE HAVE THE COMBUSTION | | | AIR CAL'S. AND MECHANICAL PLANS SIGNED. | | | | | | 2) PLEASE SHOW JOB LOCATION ON | | | MECHANICAL PLANS. | | | | | | 3) NO DUCT OPENINGS ARE PERMITTED IN A | | | GARAGE, PER 2004 FBC/R 309.1.1 . THE | | | GOLF CART ROOM AND THE EXERCISE ROOM | | | HAVE GARAGE DOORS AND MAY BE USED AS A | | | GARAGE. | | | | | | 4) PLANS ARE CALLING FOR A VENTLESS | | | FIREPLACE IN THE OUTDOOR ENTERAINMENT | | | AREA MANUFACTURE'S SPEC'S. ARE FOR A | | | VENTED FIREPLACE, PLEASE CORRECT. | | | | | | 5) PLEASE SHOW AHU #4 AND COUDENSER UNIT | | | #4 ON ELECTRICAL PLAN. | | | | | | 6) MANUL J CAL'S. ARE CALLING FOR THREE | | | A/C UNITS TOTALING 79,081 SENSIBLE | | | BTU'S. THE MECHANICAL PLANS ARE CALLING | | | FOR, FOUR A/C SYSTEMS TOTALING 106,000 | | | SENSIBLE BTU'S. PLEASE COMPLY WITH 2004 | | | FBC 13-607.1.ABC.1.1 . | | | | | | 7) PLEACE SHOW IF AHU #4 IS GOING IN A | | | CLOSET OR THE ATTIC. | | | | | | 8) PLEASE NOTE DUCTS PENETRATING THE | | | GARAGE CEILING CAN NOT BE FLEX. DUCT, | | | PER 2004 FBC/R309.1.1 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2005-12-30 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2005-12-08 |
Time |
11:20 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2005-12-30 |
Time |
09:38 |
Sent To |
P |
|
| Notes |
| 2005-12-08 00:00:00 | SEE REVIEW M-2 . |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2007-02-01 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-02-01 |
Time |
11:01 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-02-01 |
Time |
11:01 |
Sent To |
|
|
| Notes |
| 2007-02-01 11:02:04 | REVISED SANITARY RISER DIAGRAM OK |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2006-03-20 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-03-20 |
Time |
14:01 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-03-20 |
Time |
14:00 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2005-12-12 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2005-12-30 |
Time |
09:39 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2005-12-12 |
Time |
12:37 |
Sent To |
B |
|
| Notes |
| 2005-12-12 00:00:00 | DENIED; | | | 1.SAUNA FLOOR DRAIN NOT VENTED. | | | 2.W/M AND L/T ARE ON DIFFERENT WALLS, | | | CANNOT BE INSTALLED AS SHOWN ON RISER | | | DIAGRAM. | | | 3.BATHROOM 4 HAS A SHOWER NOT TUB. | | | 4.KITCHEN SINK SHOULD BE STUDER VENTED. | | | (NO WALL FOR VENT STACK.) | | | 5.COULDNOT FIND LOCATION OF THIRD SINK | | | SHOWN ON RISER DIAGRAM. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2006-04-13 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-04-13 |
Time |
09:37 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-04-13 |
Time |
09:37 |
Sent To |
I |
|
| Notes |
| 2006-04-13 00:00:00 | NOTE: DECORATIVE FENCE SITS BEYOND THE | | | 25FT FRONT SETBACK. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2006-03-06 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-03-06 |
Time |
17:36 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-03-06 |
Time |
17:36 |
Sent To |
I |
|
| Notes |
| 2006-03-06 00:00:00 | DENIED, | | | 1. NEED TO PROIVIDE THE APPROVED | | | SITEPLAN/SURVEY OR PLANS TWO COPY OF | | | CURRENT SURVEY & SITEPLAN SHOWING THE | | | PROPOSED WORK WITH SETBACKS. | | | | | | NOTE: NO SITEPLAN AND SURVEY SUBMITTED. | | | | | | 2. THE DECORATIVE GATE IS OVER THE | | | HEIGHT REQUIREMENT OF 4FT MAXIMUM WITHIN | | | THE FIRST 25FT FRONT SETBACK (A-6) | | | | | | MICHELLE MCLEAN | | | ZONING TECHNICIAN | | | 805-6720 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2005-12-06 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-12-06 |
Time |
13:48 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-12-06 |
Time |
13:48 |
Sent To |
I |
|
| Notes |
|
|