| Plan Review Stops For Permit 05110699 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2006-02-02 |
|
|
Cont ID |
|
| Sent By |
kconrad |
Date |
2006-02-02 |
Time |
20:47 |
Rev Time |
1.25 |
| Received By |
kconrad |
Date |
2006-02-02 |
Time |
19:32 |
Sent To |
|
|
| Notes |
| 2006-02-06 00:00:00 | THE FOLLOWING MUST MEET THE MINIMUM | | | REQUIREMENTS AS PER THE FLORIDA BUILDING | | | CODE 2004: | | | | | | ACCESSIBILITY: | | | A)SECTION 11-1.2 | | | B)SECTION 11-5.2/5.3:SERVICE | | | COUNTERS/BARS:MAXIMUM HEIGHT 34" | | | C)SECTION | | | 11.5.6/11-4.2.5:TABLEWARE/CONDIMENT | | | AREAS AND MAXIMUM REACH DISTANCE. | | | | | | EGRESS REQUIREMENTS: | | | AS PER SECTION 812.3.1. | | | | | | INTERIOR FINISHES: | | | INTERIOR FINISHES MAY BE CLASS C AS | | | PER SECTION/TABLE 803.5 | | | | | | OCCUPANCY CHANGE: | | | A)SECTION 801.2/812.3.1:MUST MEET THE | | | MINIMUM REQUIREMENTS OF THE FOLLOWING: | | | A)MEANS OF EGRESS CAPACITY | | | B)INTERIOR WALL/CEILING FINISHES | | | C)FLORIDA FIRE PREVENTION CODE | | | | | | OCCUPANCY SEPARATION: | | | A)NOT REQUIRED AS PER TABLE 302.3.2.B |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
N |
Date |
2005-12-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-12-30 |
Time |
16:04 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2005-12-30 |
Time |
16:04 |
Sent To |
|
|
| Notes |
| 2005-12-30 00:00:00 | **** NOTES REDLINED **** | | | | | | 1)NOTE: PLEASE SEE NO ELECTRICAL PLANS | | | AND NO ELECTRICAL CONTRACTOR WAS | | | SUBMITTED FOR SCOPE OF WORK.?? | | | APPLICATION MENTIONS REMODEL, HOWEVER | | | ONLY SEEMS TO HAVE ID PLANS SUBMITTED | | | WHICH ARE NOTED"NOT FOR CONSTRUCTION"? | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2005-12-23 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2005-12-23 |
Time |
10:55 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2005-12-23 |
Time |
10:49 |
Sent To |
|
|
| Notes |
| 2005-12-23 00:00:00 | 1. DEMOLITION, RENOVATION, AND | | | CONSTRUCTION TO COMPLY WITH NFPA 241. | | | | | | 2. DEBRIS SHALL BE REMOVED FROM THE SITE | | | DAILY. | | | | | | 3. NO CHANGES TO ANY EXITING, OR FIRE | | | AND LIFE SAFETY EQUIPMENT OF DEVICES | | | WILL BE ALLOWED. | | | | | | 4. ANY MODIFICATIONS TO THE REQUIRED | | | FIRE SPRINKLER OR FIRE ALARM SYSTEM MUST | | | BE MADE WITH A VALID PERMIT. | | | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | | OFFICER | | | 804-4709 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-03-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-03-02 |
Time |
14:22 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-03-02 |
Time |
14:22 |
Sent To |
P |
|
| Notes |
| 2006-03-02 00:00:00 | TO "P" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-02-06 |
|
|
Cont ID |
|
| Sent By |
kconrad |
Date |
2006-02-06 |
Time |
16:10 |
Rev Time |
0.00 |
| Received By |
kconrad |
Date |
2005-11-23 |
Time |
09:01 |
Sent To |
|
|
| Notes |
| 2005-12-09 00:00:00 | COMM BD #11 | | 2005-11-23 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2006-02-06 |
|
|
Cont ID |
|
| Sent By |
kconrad |
Date |
2006-02-06 |
Time |
16:11 |
Rev Time |
0.00 |
| Received By |
kconrad |
Date |
2006-02-02 |
Time |
10:29 |
Sent To |
|
|
| Notes |
| 2006-02-02 00:00:00 | MECHANICAL PERMIT ISSUED |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2006-03-08 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-03-08 |
Time |
07:50 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-03-08 |
Time |
07:50 |
Sent To |
|
|
| Notes |
| 2006-03-08 00:00:00 | REVISED RISER DIAGRAM |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2006-02-06 |
|
|
Cont ID |
|
| Sent By |
kconrad |
Date |
2006-02-06 |
Time |
16:12 |
Rev Time |
0.00 |
| Received By |
kconrad |
Date |
2006-02-02 |
Time |
10:21 |
Sent To |
|
|
| Notes |
| 2006-02-02 00:00:00 | PROVISO: | | | SHT P-2 | | | FLOOR SINKS FOR ALL INDIRECT WASTE. |
|
|