| 2005-11-17 00:00:00 | DENIED | | | | | | 1) THE ASSEMBLY SUBMITTED HAS A MAXIMUM | | | DESIGN PRESSURE OF -45 PSF WITH NO | | | INCREASE ALLOWED FOR ENHANCED FASTENING | | | DUE TO LIMITATION #9. THE REQUIRED | | | UPLIFT ZONE 3 IS -89 PSF. | | | | | | 2) A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|
|
|