Plan Review Details - Permit 05110636
Plan Review Stops For Permit 05110636
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-07-05 Cont ID  
Sent By alange Date 2006-07-05 Time 14:49 Rev Time 1.00
Received By alange Date 2006-07-05 Time 14:49 Sent To  
Notes
2006-07-05 00:00:00PATIO REV OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-04-20 Cont ID  
Sent By alange Date 2006-04-20 Time 14:18 Rev Time 0.75
Received By alange Date 2006-04-20 Time 14:18 Sent To Z
Notes
2006-04-20 00:00:00REVISION DENIED
  
 1. ADJUST PERMIT VALUATION AND PAY
 ADDITIONAL PERMIT FEES TO REFLECT THE
 NEW WORK.
  
 2.REVISED WORK IS NOT CLEAR.PAGES DO
 NOT MATCH UP WITH ORIGONAL PLANS AND
 PAGE NUMBERING IS ALSO DIFFERENT.
  
 3.SUBMIT PRODUCT APPROVALS FOR THE
 FOLLOWING; NEW DOORS AND SIDE LITES,
 IMPACT PROTECTION, GLASS BLOCK, STRAPS
 AND TIEDOWNS, AND LINTELS.
  
 4.ALL PRODUCT APPROVALS SUBMITTED
 SHALL HAVE THE FOLLOWING STATE PRODUCT
 APPROVAL ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-03-23 Cont ID  
Sent By alange Date 2006-03-23 Time 08:53 Rev Time 2.00
Received By alange Date 2006-03-23 Time 08:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-02-13 Cont ID  
Sent By alange Date 2006-02-13 Time 08:06 Rev Time 1.00
Received By alange Date 2006-02-13 Time 08:06 Sent To  
Notes
2006-02-13 00:00:00DENIED
  
  
 ALL PRODUCT APPROVALS SUBMITTED SHALL
 HAVE THE FOLLOWING STATE PRODUCT
 APPROVAL ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-12-20 Cont ID  
Sent By alange Date 2005-12-20 Time 07:24 Rev Time 1.25
Received By alange Date 2005-12-20 Time 07:24 Sent To  
Notes
2005-12-20 00:00:00DENIED
  
 1.SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR ROOFING.
 PRODUCT APPROVALS SUBMITTED SHALL HAVE
 THE FOLLOWING STATE PRODUCT APPROVAL
 ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-06-29 Cont ID  
Sent By btrobaug Date 2006-06-29 Time 14:00 Rev Time 0.50
Received By btrobaug Date 2006-06-29 Time 12:08 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-04-20 Cont ID  
Sent By btrobaug Date 2006-04-20 Time 11:22 Rev Time 0.50
Received By btrobaug Date 2006-04-20 Time 11:05 Sent To B
Notes
2006-04-20 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THERE HAS BEEN A PANEL ADDED TO THE
 SERVICE EQUIPMENT. PLEASE SUBMIT A RISER
 DIAGRAM SHOWING ALL SERVICE EQUIPMENT
 AND GROUNDING SYSTEM. ALSO PLEASE SHOW
 THE LOCATION OF THE EQUIPMENT ON THE
 PLAN.215.5
  
 2} THE NEW PORCH NEEDS A RECEPTACLE
 ADDED TO COMPLY WITH 210.52(A)(1), SEE
 REVIEWED PLAN.
  
 3} THE NUMBER OF THE SHEET ON THE PLAN
 SUBMITTED FOR REVISION DOES NOT MATCH
 ANY SHEETS PREVIOUSLY SUBMITTED. PLEASE
 CHANGE THE NUMBER TO REFLECT SHEET BEING
 REVISED.
  
 4} PLEASE PROVIDE A PANEL SCHEDULE FOR
 THE NEW PANEL.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-03-06 Cont ID  
Sent By btrobaug Date 2006-03-06 Time 10:00 Rev Time 0.50
Received By btrobaug Date 2006-03-06 Time 09:23 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-02-08 Cont ID  
Sent By btrobaug Date 2006-02-08 Time 11:25 Rev Time 0.33
Received By btrobaug Date 2006-02-08 Time 11:17 Sent To M
Notes
2006-02-08 00:00:00 
 THE PERSON RESPONSIBLE FOR THE PLAN
 MUSRT PRINT AND SIGN THEIR NAME TO SAME.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-12-08 Cont ID  
Sent By btrobaug Date 2005-12-08 Time 10:03 Rev Time 0.50
Received By btrobaug Date 2005-12-08 Time 09:07 Sent To P
Notes
2005-12-08 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} RECEPTACLES SPACED PER 210.52(D), GFI
 PER 210.8(A)(1), ON BRANCH CIRCUITS PER
 210.11(C)(3) ARE REQUIRED, SHOW ON PLAN.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-06-21 Cont ID  
Sent By adarroug Date 2006-06-21 Time 16:12 Rev Time 0.00
Received By adarroug Date 2006-06-21 Time 16:12 Sent To E
Notes
2006-06-21 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-04-15 Cont ID  
Sent By adarroug Date 2006-04-15 Time 14:20 Rev Time 0.00
Received By adarroug Date 2006-04-15 Time 14:20 Sent To E
Notes
2006-04-15 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-03-02 Cont ID  
Sent By adarroug Date 2006-03-02 Time 14:27 Rev Time 0.00
Received By adarroug Date 2006-03-02 Time 14:27 Sent To E
Notes
2006-03-02 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-02-06 Cont ID  
Sent By adarroug Date 2006-02-06 Time 11:27 Rev Time 0.00
Received By adarroug Date 2006-02-06 Time 11:27 Sent To E
Notes
2006-02-06 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-01-28 Cont ID  
Sent By adarroug Date 2006-01-28 Time 17:36 Rev Time 0.00
Received By adarroug Date 2006-01-28 Time 17:36 Sent To Z
Notes
2006-01-28 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-12-06 Cont ID  
Sent By adarroug Date 2005-12-06 Time 14:23 Rev Time 0.00
Received By adarroug Date 2005-12-06 Time 14:23 Sent To E
Notes
2005-12-06 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-12-20 Cont ID  
Sent By alange Date 2005-12-20 Time 07:38 Rev Time 0.00
Received By alange Date 2005-11-22 Time 14:36 Sent To  
Notes
2005-11-22 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-12-13 Cont ID  
Sent By tgordon Date 2005-12-13 Time 09:32 Rev Time 0.20
Received By tgordon Date 2005-12-13 Time 09:32 Sent To B
Notes
2005-12-13 00:00:00NO MECH. PLANS OR MECH. CONTRACTOR
 SUBMITTED AT THIS TIME.

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-03-07 Cont ID  
Sent By jleech Date 2006-03-07 Time 07:07 Rev Time 0.00
Received By jleech Date 2006-03-07 Time 07:07 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-02-10 Cont ID  
Sent By jleech Date 2006-02-10 Time 08:34 Rev Time 0.33
Received By jleech Date 2006-02-10 Time 08:34 Sent To B
Notes
2006-02-10 00:00:00DENIED;
 MISSING TITAL BLOCK INFORMATION
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-12-13 Cont ID  
Sent By jleech Date 2005-12-13 Time 08:50 Rev Time 0.33
Received By jleech Date 2005-12-13 Time 08:50 Sent To M
Notes
2005-12-13 00:00:00DENIED;
 SANITARY RISER DIAGRAM IS REQUIRED PER
 FBC-2004 CHAPTER 1 ADMINISTRATION CODE,
 SEC106.3.5.4(9).
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 3 Status N Date 2006-04-27 Cont ID  
Sent By mmclean Date 2006-04-27 Time 11:29 Rev Time 0.00
Received By mmclean Date 2006-04-27 Time 11:29 Sent To  
Notes
2006-04-27 00:00:00NO CHANGES IN THE SETBACK FOR ZONING.

Review Stop Z ZONING
Rev No 2 Status P Date 2006-02-03 Cont ID  
Sent By mmclean Date 2006-02-03 Time 17:10 Rev Time 0.00
Received By mmclean Date 2006-02-03 Time 17:10 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2005-12-05 Cont ID  
Sent By mmclean Date 2005-12-05 Time 17:11 Rev Time 0.00
Received By mmclean Date 2005-12-05 Time 17:11 Sent To I
Notes
2005-12-05 00:00:00DENIED,
 1. MUST PROVIDE TWO COPY OF CURRENT
 SURVEY SHOWING THE EXISTING STRUCTURE
 WITH SETBACKS.
 2. MUST SHOW THE PROPOSED WITH SETBACKS
 ON TWO COPY OF CURRENT SURVEY.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720