| Plan Review Stops For Permit 05110601 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2005-11-17 |
|
|
Cont ID |
|
| Sent By |
amorse |
Date |
2005-11-17 |
Time |
10:02 |
Rev Time |
0.33 |
| Received By |
amorse |
Date |
2005-11-17 |
Time |
10:02 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-11-16 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2005-11-16 |
Time |
16:31 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2005-11-16 |
Time |
16:31 |
Sent To |
|
|
| Notes |
| 2005-11-16 00:00:00 | DENIED | | | | | | 1) THE PRODUCT APPROVALS THAT WERE | | | SUBMITTED ARE FOR THE 2001 CODE EDITION. | | | THE STATE HAS UPDATED THE FL# AND NOA | | | FOR THE CERTAINTEED MODIFIED FOR THE | | | 2004 CODE. SEE THE STATE WEB SITE AT | | | WWW.FLORIDABUILDING.ORG. | | | | | | 2) THE APPROVED ASSEMBLY THAT IS | | | SPECIFIED FROM THE NOA FOR THE SBS | | | MODIFIED HAS A DESIGN PRESSURE THAT IS | | | TOO LOW FOR THE EDGE AND CORNER ZONES | | | AND CAN NOT INCREASED BY USING ENHANCED | | | FASTENING DUE TO LIMITATION #9. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2005-11-16 00:00:00 | OK PER J PAPA 11-16-05 |
|
|
|