Plan Review Details - Permit 05110599
Plan Review Stops For Permit 05110599
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-03-08 Cont ID  
Sent By amorse Date 2006-03-08 Time 10:04 Rev Time 0.33
Received By amorse Date 2006-03-08 Time 10:04 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-01-26 Cont ID  
Sent By amorse Date 2006-01-26 Time 10:18 Rev Time 0.33
Received By amorse Date 2006-01-26 Time 10:18 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-12-30 Cont ID  
Sent By amorse Date 2005-12-30 Time 10:22 Rev Time 0.50
Received By amorse Date 2005-12-30 Time 10:21 Sent To PC
Notes
2005-12-30 00:00:00 
  
 DENIED
  
 1) A RECORDED COPY OF NOC IS REQUIRED
 PRIOR TO A PERMIT BEING ISSUED
  
 2) REFERENCE 2004 FL BLDG CODE ON ALL
 ENGINEERING AFTER OCT. 1, 2005
  
 3) VALUATION ON PERMIT IS LOW PER
 MARSHALL & SWIFT CONSTRUCTION PRICING
 GUIDE. POOL, HAETER AND PAVER DECK WILL
 RUN 18,000.00
  
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-03-08 Cont ID  
Sent By btrobaug Date 2006-03-06 Time 07:17 Rev Time 0.33
Received By btrobaug Date 2006-03-06 Time 07:02 Sent To P
Notes
2006-03-06 00:00:00 

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-01-23 Cont ID  
Sent By btrobaug Date 2006-01-23 Time 13:00 Rev Time 0.33
Received By btrobaug Date 2006-01-23 Time 12:47 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-12-15 Cont ID  
Sent By btrobaug Date 2005-12-15 Time 17:23 Rev Time 0.33
Received By btrobaug Date 2005-12-15 Time 17:16 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-02-28 Cont ID  
Sent By adarroug Date 2006-02-28 Time 16:28 Rev Time 0.00
Received By adarroug Date 2006-02-28 Time 16:28 Sent To E
Notes
2006-02-28 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-01-22 Cont ID  
Sent By adarroug Date 2006-01-22 Time 11:58 Rev Time 0.00
Received By adarroug Date 2006-01-22 Time 11:58 Sent To E
Notes
2006-01-22 00:00:00TO "BTROBAUG" DESK/RESUB-NEW SHEETS

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-11-28 Cont ID  
Sent By adarroug Date 2005-11-28 Time 10:19 Rev Time 0.00
Received By adarroug Date 2005-11-28 Time 10:19 Sent To E
Notes
2005-11-28 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2005-11-22 Time   Rev Time 0.00
Received By adarroug Date 2005-11-22 Time 08:44 Sent To  
Notes
2005-11-22 00:00:00TO "Z" BOX

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-03-07 Cont ID  
Sent By btrobaug Date 2006-03-08 Time 11:36 Rev Time 0.45
Received By mperson Date 2006-03-07 Time 09:59 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-01-26 Cont ID  
Sent By mperson Date 2006-01-26 Time 07:19 Rev Time 1.25
Received By mperson Date 2006-01-26 Time 07:19 Sent To B
Notes
2006-01-26 00:00:00DENIED 2ND TIME
 REFERENCE: FBC-2004 SWIMMING POOLS
  
 PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING
 INFORMATION REQUIRED FOR PLAN REVIEW.
 1. THERE IS NO POOL HEATER INDICATED ON
 POOL SPECIFICATIONS, WITH MODEL NUMBER,
 OR IN THE EQUIPMENT LAYOUT OR LEGEND.
 PRINT MUST SHOW THIS. ALSO SEE PAGE 14
 FIGURE 27 IN THE POOL HEATER SUBMITTAL.
 THIS MODEL HEATER HAS NO POSITIVE MEANS
 OF RETAINING WATER IN HEATER WHEN PUMP
 IS NOT IN OPERATION, THEREFORE AN
 EXTERNAL HARTFORD LOOP IS REQUIRED FOR
 THE HEATER. PLEASE INDICATE THIS ON THE
 EQUIPMENT LAYOUT DRAWING.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561)805-6730
 FAX (561)805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561)805-6721

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-12-21 Cont ID  
Sent By mperson Date 2005-12-21 Time 13:38 Rev Time 1.25
Received By mperson Date 2005-12-21 Time 13:37 Sent To B
Notes
2005-12-21 00:00:00DENIED
 REFERENCE: FBC-2004 424.2 SWIMMING POOLS
  
 1) FBC-2004 SEC. 424.2.9 WATER SUPPLY,
 LOCAL ORD. #2853-95, BACKFLOW REQUIRED
 ON WATER SERVICE. (ADD TO NOTES)

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2005-11-28 Time   Rev Time  
Received By   Date 2005-11-28 Time   Sent To  
Notes
***NONE***