Plan Review Details - Permit 05110591
Plan Review Stops For Permit 05110591
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-03-13 Cont ID  
Sent By alange Date 2006-03-13 Time 08:17 Rev Time 1.00
Received By alange Date 2006-03-13 Time 08:01 Sent To M
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-02-06 Cont ID  
Sent By alange Date 2006-02-06 Time 08:12 Rev Time 2.00
Received By alange Date 2006-02-06 Time 08:12 Sent To  
Notes
2006-02-06 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
 ALL PLANS SUBMITTED AFTER OCTOBER, 1,
 2004 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE.
  
  
 2. ALL PLANS SUBMITTED AFTER OCTOBER, 1,
 2004 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-12-07 Cont ID  
Sent By dpalmer Date 2005-12-07 Time 20:47 Rev Time 0.00
Received By dpalmer Date 2005-12-07 Time 20:39 Sent To  
Notes
2005-12-07 00:00:00STAMPED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-12-06 Cont ID  
Sent By mcarsill Date 2005-12-06 Time 14:37 Rev Time 0.00
Received By mcarsill Date 2005-12-06 Time 14:03 Sent To  
Notes
2005-12-06 00:00:001. DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY.
  
 2. CONSTRUCTION, RENOVATION, AND
 DEMOLITION SHALL COMPLY WITH NFPA 241.
  
 3.SEPERATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER SYSTEM REMODEL.
  
 4. SEPERATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM REMODEL.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-06-27 Cont ID  
Sent By adarroug Date 2006-06-27 Time 15:05 Rev Time 0.00
Received By adarroug Date 2006-06-27 Time 15:05 Sent To P
Notes
2006-06-27 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-03-22 Cont ID  
Sent By dpalmer Date 2006-03-22 Time 15:24 Rev Time 0.00
Received By dpalmer Date 2006-03-22 Time 15:24 Sent To M
Notes
2006-03-22 00:00:00TO R R.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-02-14 Cont ID  
Sent By adarroug Date 2006-02-14 Time 09:11 Rev Time 0.00
Received By adarroug Date 2006-02-14 Time 09:11 Sent To  
Notes
2006-02-14 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-02-06 Cont ID  
Sent By alange Date 2006-02-06 Time 08:14 Rev Time 0.00
Received By adarroug Date 2005-12-06 Time 09:11 Sent To  
Notes
2005-12-06 00:00:00TO "COMM" BD#27
2005-11-22 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-03-22 Cont ID  
Sent By rregueir Date 2006-03-22 Time 15:43 Rev Time 0.00
Received By rregueir Date 2006-03-22 Time 15:43 Sent To PC
Notes
2006-03-22 00:00:00----------------PROVISO-----------------
 PAGE M1 REQUIRES FIRE DAMPERS IN ALL
 DUCTS PENETRATING TENANT WALL BETWEEN
 SUITES 510 AND 520.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-03-13 Cont ID  
Sent By rregueir Date 2006-03-13 Time 16:38 Rev Time 0.00
Received By rregueir Date 2006-03-13 Time 16:38 Sent To PC
Notes
2006-03-13 00:00:00------------------DENIED----------------
 1) PER COMMENT #2 FROM PREVIOUS REVIEW,
 ONLY ONE OF THE TWO EXISTING DUCTS
 TRAVELING FROM SUITE 520 INTO SUITE 510
 THROUGH AN NEW 1-HOUR RATED WALL SHOWS A
 FIRE DAMPER. I HAVE HIGHLIGHTED THIS
 LOCATION.
  
 2) PLAN INDICATES NEW TENANT SEPARATION
 WALL BETWEEN SUITES 510 AND 560. PLAN
 ALSO SHOWS A NEW TENANT SEPARATION WALL
 BETWEEN SUITES 540 AND 550. ALSO BETWEEN
 SUITES 510 AND 520. PROJECT DATA BLOCK
 ON SHEET T INDICATE TENANT SEPARATION
 WALLS TO BE 1-HOUR RATED. PLEASE
 INDICATE CORRECT WALL ASSEMBLY TYPE ON
 PAGE A1.1 AND TREAT ALL WALL
 PENETRATIONS AS RATED PENETRATIONS BY
 INDICATING NEW FIRE DAMPER LOCATIONS.
  
 RONALD J REGUEIRO
 561.805.6734
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-12-13 Cont ID  
Sent By rregueir Date 2005-12-13 Time 16:05 Rev Time 0.00
Received By rregueir Date 2005-12-13 Time 15:28 Sent To  
Notes
2005-12-13 00:00:00------------------DENIED----------------
  
 1) PAGE M1 DRAWING NOTE #3 SHOWS FIVE
 NEW 48X12 T.A.OS LOCATED AT TENANT
 SEPERATION 1-HOUR RATED WALLS. PLAN DOES
 NOT SHOW FIRE DAMPERS AT FOUR OF THEM.
 FIRE DAMPERS ARE REQUIRED AT THESE
 LOCATIONS PER FBC,M 607.5.
  
 2) PAGE M1 SHOWS NEW TENANT SEPERATION
 1-HOUR RATED WALL BETWEEN SUITES 510 AND
 520 WITH TWO EXISTING DUCTS RUNNING
 THROUGH IT. FIRE DAMPERS ARE REQUIRED AT
 THESE LOCATIONS PER FBC,M 607.5.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL
 RON REGUEIRO @ 561.805.6734

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-07-08 Cont ID  
Sent By pschmitz Date 2006-07-08 Time 12:42 Rev Time 0.00
Received By pschmitz Date 2006-07-08 Time 12:42 Sent To  
Notes
2006-07-08 00:00:00DELETE BREAK ROOM SINK UNIT #540

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-03-11 Cont ID  
Sent By pschmitz Date 2006-03-11 Time 05:45 Rev Time 0.00
Received By pschmitz Date 2006-03-11 Time 05:45 Sent To B
Notes
2006-03-11 00:00:00RE SUB

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-01-27 Cont ID  
Sent By pschmitz Date 2006-01-27 Time 11:32 Rev Time 0.00
Received By pschmitz Date 2006-01-27 Time 09:16 Sent To  
Notes
2006-01-27 00:00:00PLUMBING PLAN REVIEW EXAMINER
 PAUL SCHMITZ 561-805-6692
 [email protected]
 FBC PLUMBING 2004
 FBC 2004 BUILDING CH 11
 1) SHT A1.1 TOILET RM 545
 SEC 11-4.22.2 DOORS.
 ALL DOORS TO ACCESSIBLE TOILET ROOMS
 SHALL NOT SWING INTO THE CLEAR FLOOR
 SPACE REQUIRED FOR ANY FIXTURE.
  
 2) SHT A4.1 DETAIL L1,H1 CABINET ELV.
 ?11-4.24 SINKS.
 ?11-4.24.1 GENERAL. SINKS REQUIRED TO
 BE ACCESSIBLE BY ?11-4.1 SHALL
 COMPLY WITH ?11-4.24.
 ?11-4.24.2 HEIGHT. SINKS SHALL BE
 MOUNTED WITH THE COUNTER OR RIM NO
 HIGHER THAN 34 IN. (865 MM) ABOVE THE
 FINISH FLOOR.
 ?11-4.24.3 KNEE CLEARANCE. KNEE
 CLEARANCE THAT IS AT LEAST 27 IN. (685
 MM) HIGH, 30 IN. (760 MM) WIDE, AND 19
 IN (485 MM) DEEP SHALL BE
 PROVIDED UNDERNEATH SINKS.
 ?11-4.24.4 DEPTH. EACH SINK SHALL BE A
 MAXIMUM OF 6-1/2 IN (165 MM)
 DEEP.
 ?11-4.24.5 CLEAR FLOOR SPACE. A CLEAR
 FLOOR SPACE AT LEAST 30 IN. BY 48
 IN. (760 MM BY 1220 MM) COMPLYING WITH
 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD
 APPROACH.THE CLEAR FLOOR SPACE SHALL
 BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 IN. (485 MM)
 UNDERNEATH THE SINK (SEE FIGURE
 11-32).
 ?11-4.24.6 EXPOSED PIPES AND SURFACES.
 HOT WATER AND DRAIN PIPES EXPOSED
 UNDER SINKS SHALL BE INSULATED OR
 OTHERWISE CONFIGURED SO AS TO PROTECT
 AGAINST CONTACT.THERE SHALL BE NO
 SHARP OR ABRASIVE SURFACES UNDER
 SINKS.
 ?11-4.24.7 FAUCETS. FAUCETS SHALL
 COMPLY WITH ?11-4.27.4.LEVER-
 OPERATED, PUSH-TYPE, TOUCH-TYPE, OR
 ELECTRONICALLY CONTROLLED MECHANISMS
 ARE ACCEPTABLE DESIGNS.
  
 3) SHT P-1
 SECTION P909WET VENTING
  
 ?P909.1 WET VENT PERMITTED. ANY
 COMBINATION OF FIXTURES WITHIN TWO
 BATHROOM GROUPS LOCATED ON THE SAME
 FLOOR LEVEL ARE PERMITTED TO BE VENTED
 BY A WET VENT.THE WET VENT SHALL BE
 CONSIDERED THE VENT FOR THE FIXTURES
 AND SHALL EXTEND FROM THE CONNECTION OF
 THE DRY VENT ALONG THE DIRECTION OF
 THE FLOW IN THE DRAIN PIPE TO THE MOST
 DOWNSTREAM FIXTURE DRAIN CONNECTION
 TO THE HORIZONTAL BRANCH DRAIN.ONLY
 THE FIXTURES WITHIN THE BATHROOM
 GROUPS SHALL CONNECT TO THE WET-VENTED
 HORIZONTAL BRANCH DRAIN.ANY
 ADDITIONAL FIXTURES SHALL DISCHARGE
 DOWNSTREAM OF THE WET VENT.
 END OF COMMENTS, QUESTIONS 561-805-6692
  