Plan Review Details - Permit 05110586
Plan Review Stops For Permit 05110586
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-12-27 Cont ID  
Sent By alange Date 2005-12-27 Time 08:42 Rev Time 3.25
Received By alange Date 2005-12-27 Time 08:41 Sent To  
Notes
2005-12-27 00:00:00DENIED
  
 1. 713.13(2) F.S.THE NOTICE OF
 COMMENCEMENT MUST BE RE-RECORDED BECAUSE
 THE DESCRIBED IMPROVEMENT OR
 CONSTRUCTION DID NOT COMMENCE WITHIN 90
 DAYS OF RECORDING.
  
 2.SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR STRAPS AND LINTELS.
 PRODUCT APPROVALS SUBMITTED SHALL HAVE
 THE FOLLOWING STATE PRODUCT APPROVAL
 ATTACHED.
  
 3.SUBMIT ENERGY CALCS TO THE 2004 FBC.
  
 4.ALL PLANS SUBMITTED AFTER OCTOBER,
 1, 2004 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE.
  
 5.SHOW DETAIL HOW GUARD RAILS WILL
 COMPLY WITH FBC R312.1 AND R312.2
  
 6.BASED ON SBCCI BUILDING VALUATION
 DATA THE PERMIT VALUATION HAS BE REVISED
 TO $205,583.ADDITIONAL PERMIT FEES ARE
 DUE.SEE ATTACHED INVOICE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-12-07 Cont ID  
Sent By dpalmer Date 2005-12-12 Time 09:05 Rev Time 0.75
Received By dpalmer Date 2005-12-07 Time 06:58 Sent To M
Notes
2005-12-07 00:00:00*********** UNSAT *************
  
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2)NOTE: PLEASE SEE MANY MISSING RECEPTS
 PER 210.52
  
 3)NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52H
  
 4)NOTE: PLEASE SEE MISSING RECEPT PER
 210.63 FOIR AHU LOCATED IN ATTIC.
  
 5)NOTE: PLEASE MISSING RECEPT REQUIRED
 FOR BATH/POWDER RM PER 210.52D.
  
 6)NOTE: PLEASE INDICATE ALL REQUIRED
 RECEPTS TO BE GFI AS GFI.
 PLEASE SEE BATH RMS, GARAGE ETC.
 210.8A1,2 ETC.
  
 7)NOTE: PLEASE SEE PLANS SHOW SD IN
 BATHROOM AND OUTSIDE BATHRM DOOR WITHIN
 3'. PLEASE SEE THIS IS NOT PERMITTED.
 NFPA-72 11.8.3.5
 PLEASE ALSO SEE ONE BEDRM WHERE SD LOOKS
 TO BE JUST OUTSIDE THE DOOR, WHERE
 REQUIRED TO BE LOCATED INSIDE. THESE ARE
 REDLINED ON PLANS FOR CLARIFICATION.
  
 8)NOTE: PLEASE SEE MISSING DEDICATED GDO
 CIRCUIT IN PANELAND IN LOAD CALCS.
 215.5,230.24, 220 ETC .
  
 9)NOTE: PLEASESEE THAT PLANS SPECIFY
 THE CODE WHICH IS IN EFFECT.(2002)
 PLEASE ALSO SEE PLANS CALL FOR ALL TO
 MEET CITY OF RIVERA BEACH? PLEASE SEE
 THIS PROJECT IS LCATED IN THE CITY OF
 WEST PALM BEACH.
 215.5
  
 10)NOTE: PLEASE SEE 424.3B FOR MIN OCP
 FOR AHU 10KW HEAT.
 50A IS NOT LARGE ENOUGH.
  
 11)NOTE: PLEASE SEE 210.52D,210.11C3,
 WHICH REQUIRES ALL BATH CIRCUITS (S) TO
 BE 20A AND #12 AWG. PLEASE SEE 20A OCP
 SHOWN ON #14 AWG ETC.
  
 12)NOTE: PLEASE SEE SEE PLANS INDICATE A
 "AHU" PAD LOCATED OUTSIDE?
 PLEASE ASJUST AS NEEDED FOR CU.
 PLEASE ALSO SEE MISSING DISCONNECT PER
 440.11 NOT SHOWN.
  
 13)NOTE: PLEASE SEE NOTES ON PLANS
 INDICATE THE SD'S WIRED TO BATH AND
 KITCHEN LIGHTING CIRCUIT. PLEASE SEE
 SD'S ARE ALL REQUIRED TO BE WIRED
 "IN-LINE" (NFPA 72_) AND ARE ALL
 REQUIRED TO BE AFCI PROTECTED AS PER
 210.12 OF THE 2002 NEC.
 PLEASE ADJUST NOTE, UNLESS AFCI BRKRS
 ARE GOING TO BE NOTED FOR KITCHEN LTS
 AND BATH LTS.
 PLEASE CALL TO GO OVER THIS SCENERIO.
  
 14)NOTE: PLEASE SEE 210.11C2 WHICH
 REQUIRES LAUNDRY/WASHER CIRCUITS TO HAVE
 A MIN OF 1.5KW FOR EACH. PLEASE SEE
 PLANS INDICATE LESS VA.
 215.5
  
 15)NOTE: PLEASE SEE 210.52C2,4 FOR
 KITCHEN ISLAND AND REQUIRES GFI RECEPTS
 FOR SEPARATE SPACES.
 PLEASE SEE A GFI IS BEING SHOWN AS
 SWICTHED?IS THIS FOR DISPOSAL?TYPICALLY
 THIS IS NOT GFI. PLEASE ALSO SEE DW IS
 ALSO SHOWN AAS GFI, YET ISLAND RECEPT
 WHICH IS REQUIRED TO BE GFI IS NOT
 INDCATED AS SO.
 210.8A6
  
 16)NOTE: PLEASE SEE THE NOC RECORDED ON
 9/2/05 HAS EXPIRED AND WILL BE REQUIRED
 TO BE RE-RECORDED.
 PLEASE SEE FS 713.12(2) WHICH MENTIONS,
 IF WORK HAS NOT COMMENCED WITH IN 90
 DAYS OF RECORDING, SUCH NOC SHALL BECOME
 VOID.
  
 17)NOTE: PLEASE SEE LOADS FOR SM APPL,
 TO BE A MIN OF 1500VA.
 210.11C3
  
 18)NOTE: PLEASE SEE MANY OTHER LOADS
 INDICATED ON PANEL SCHEDULE DO NOT SEEM
 TO CORRELATE.
 PLEASE ALSO SEE LIGHTING LOADS ON 15A
 CIRCUITS, SHOWN EXCEED RATING OF
 CIRCUITS.1440 VA 15A. 1920VA 20A.
 215.5
  
  
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 TWO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 PLEASE SUBMIT ONE COPY OF OLD/VOIDED
 SHEETS FOR REFERENCE.
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 **PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW AND IF THERE ARE ANY
 QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 **PLEASE SEE MANY OF THE ABOVE ITEMS
 HAVE BEEN REDLNED ON PLANS WHICH ARE
 NOTED.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-12-06 Cont ID  
Sent By adarroug Date 2005-12-06 Time 14:24 Rev Time 0.00
Received By adarroug Date 2005-12-06 Time 14:24 Sent To E
Notes
2005-12-06 00:00:00TO "SFR "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-12-27 Cont ID  
Sent By alange Date 2005-12-27 Time 08:50 Rev Time 0.00
Received By alange Date 2005-11-22 Time 13:54 Sent To  
Notes
2005-11-22 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-12-07 Cont ID  
Sent By tgordon Date 2005-12-07 Time 13:31 Rev Time 0.30
Received By tgordon Date 2005-12-07 Time 13:31 Sent To P
Notes
2005-12-07 00:00:00*** DENIED ***
 1) RETURN AIR REQUIRED IN MASTER
 BEDROOM, PER 2004 FBC/R M1602.4 .
 2) SUPPLY AIR DUCT FROM AHU TO TRIANGLE
 NOT SIZED.
 3) LOCATION OF CONDENSER UNIT NOT
 SHOWING ON MECH. PLANS .
 4) ENERGY CALCULATIONS NEED TO BE ON
 FORM 600A-04 (2004), PER 2004 FBC
 13-600.0 ABC .
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-12-08 Cont ID  
Sent By jleech Date 2005-12-08 Time 08:53 Rev Time 0.75
Received By jleech Date 2005-12-08 Time 08:53 Sent To B
Notes
2005-12-08 00:00:00DENIED;
 1.SCUPPERS, PAGE 5 PLEASE SIZE PER
 FBC-2004 PLUMBING TABLE 1106.7.
 2.SECONDARY DRAINS REQUIRED PER 1107.3.
 SHOW CALKS ON PLANS.
 3.SIZE DOWN SPOUTS PER TABLE 1106.2.
 4.PAGE 7, HORIZONTAL DRY VENTS ARE NOT
 TO CODE SEC.905.3.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status F Date 2005-12-05 Cont ID  
Sent By mmclean Date 2005-12-05 Time 16:00 Rev Time 0.00
Received By mmclean Date 2005-12-05 Time 16:00 Sent To I
Notes
2005-12-05 00:00:00DENIED,
 1. PROVIDE RECORDED DOCUMENTATION
 INCORPORATING CITY SIDEWALK ON SURVEY.
 2. MUST PROVIDE THE SIDE & REAR SETBACK
 OF THE PROPOSED NSF.
 3. MUST PROVIDE THE DIMENSION OF THE
 PROPOSED DRIVEWAY.
  
 NOTE: MUST MAINTAIN 1000SQ FT OR 75% OF
 LANDSCAPE WHICHEVER IS LESS WITHIN THE
 FIRST 25FT FRONT SETBACK.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720