Plan Review Details - Permit 05110583
Plan Review Stops For Permit 05110583
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-12-16 Cont ID  
Sent By shill Date 2005-12-16 Time 18:17 Rev Time 0.00
Received By shill Date 2005-12-16 Time 18:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-12-09 Cont ID  
Sent By shill Date 2005-12-09 Time 14:10 Rev Time 0.50
Received By shill Date 2005-12-09 Time 14:10 Sent To FIRE
Notes
2005-12-09 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2004
  
 1.)STRUCTURAL BUCKS TO BE SPECIFIED BY
 AN ENGINEER.
  
 2.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED, FAC9B72.
 WWW.FLORIDABUILDING.ORG.THE CASEMENT
 WINDOW HAS AN APPROVAL (PLEASE PROVIDE
 TWO COPIES) BUT I WAS UNABLE TO LOCATE
 THE FIXED WINDOW OR THE AWNING WINDOW ON
 THE STATE WEBSITE.A LOCAL PRODUCT
 APPROVAL APPLICATION IS AVAILABLE ON THE
 WEBSITE WWW.FLORIDABUILDING.ORG
  
 3.)PROVIDE A FLOOR PLAN SHOWING
 WINDOWS TO BE INSTALLED; LOCATIONS,
 SIZES, WINDOW TYPE, ROOM DESIGNATION.
 BEDROOMS ARE TO COMPLY WITH EMERGENCY
 EGRESS REQUIREMENTS FBC R310.
  
 4.)PROVIDE SOME INFORMATION IN REGARDS
 TO THE EXISTING BUILDINGS.THE
 APPLICATIONS STATE "FIRST FLOOR", IS
 THERE MORE THAN ONE FLOOR?ARE THERE
 ANY FIRE RESISTANCE REQUIREMENTS
 (STAIRS), FBC CHAPTER 10?
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status N Date 2005-12-16 Cont ID  
Sent By mwennerg Date 2005-12-16 Time 14:18 Rev Time 0.00
Received By mwennerg Date 2005-12-16 Time 14:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-12-15 Cont ID  
Sent By mwennerg Date 2005-12-15 Time 14:01 Rev Time 0.00
Received By mwennerg Date 2005-12-15 Time 14:01 Sent To  
Notes
2005-12-15 00:00:00******DENIED******
  
 1) NOT ENOUGH INFORMATION SUBMITTED TO
 DO A FIRE PLAN REVIEW AT THIS TIME.
  
 2) MORE INFORMATION REQUIRED REGARDING
 OCCUPANY TYPE, NUMBER OF STORIES ETC.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-12-16 Cont ID  
Sent By adarroug Date 2005-12-16 Time 14:24 Rev Time 0.00
Received By adarroug Date 2005-12-16 Time 14:24 Sent To B
Notes
2005-12-16 00:00:00TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-12-16 Cont ID  
Sent By adarroug Date 2005-12-16 Time 14:08 Rev Time 0.00
Received By adarroug Date 2005-12-16 Time 14:08 Sent To FIRE
Notes
2005-12-16 00:00:00TO "F" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-12-16 Cont ID  
Sent By shill Date 2005-12-19 Time 18:17 Rev Time 0.00
Received By shill Date 2005-11-22 Time 10:21 Sent To  
Notes
2005-11-22 00:00:00TO "MISC" BOX#1