Plan Review Details - Permit 05110560
Plan Review Stops For Permit 05110560
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-10-26 Cont ID  
Sent By alange Date 2006-10-26 Time 08:29 Rev Time 0.00
Received By alange Date 2006-10-26 Time 08:29 Sent To  
Notes
2006-10-26 08:37:00DENIEDFOURTH REVIEW
  
 3.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THE 2004
 EXISTING BUILDING CODE 301.5
 INCORRECT LEVEL OF ALTERATION SELECTED.IT SHOULD BE
 LEVEL 3.SHOW ON PLANS.
  
 6.STATE PRODUCT APPROVAL FOR PGT SH-701 IS
 INCORRECT.STATE PRODUCT APPROVAL SHOULD SHOW
 MAUFACTURER, MODEL AND APPROVAL STATUS.
 ALL PRODUCT APPROVALS SUBMITTED
 SHALL HAVE THE FOLLOWING STATE PRODUCT
 APPROVAL ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 8.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMMENDMENT TO FBC 106.3.3
  
 A.TRUSS DRAWINGS ARE TO BE REVIEWED
 AND APPROVED PRIOR TO INSTALLATION
 R-802.10.1DRAWINGS SUBMITTED SHALL BE
 SIGNED AND SEALED.SUBMIT TWO SETS.
  
 3A.PERMIT VALUATION SHALL INCLUDE ALL
 MATERIALS AND LABOR.ADJUST PERMIT
 VALUE AND PAY ADDITIONAL PERMIT FEES
 PRIOR TO RESUBMITTING.
  
 NEW COMMENTSFOURTH REVIEW.
  
 1B.SCOPE OF WORK ON PERMIT APPLICATION DOES NOT
 REFLECT WORK SHOWN ON PLANS.CHANGE SCOPE OF WORK ON
 PERMIT APPLICATION.
  
 2B.CLEARLY SHOW ON PLANS EXISTING AREAS AND AREAS OF
 NEW WORK.SHOW EXISTING FLOOR PLANS AND REVISED FLOOR
 PLAN INCLUDING NEW WALLS.
  
  
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-09-08 Cont ID  
Sent By alange Date 2006-09-08 Time 11:25 Rev Time 1.00
Received By alange Date 2006-09-08 Time 11:25 Sent To  
Notes
2006-09-08 00:00:00DENIED
  
 3.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THE 2004
 EXISTING BUILDING CODE 301.5
  
 5.SUBMIT TWO COMPLETE SETS OF PRODUCT
 APPROVALS.PRODUCT APPROVALS ARE
 MISSING OR INCOMPLETE FOR THE FOLLOWING;
 STRAPS AND TIEDOWNS.
  
 6.ALL PRODUCT APPROVALS SUBMITTED
 SHALL HAVE THE FOLLOWING STATE PRODUCT
 APPROVAL ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 8.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMMENDMENT TO FBC 106.3.3
  
 A.TRUSS DRAWINGS ARE TO BE REVIEWED
 AND APPROVED PRIOR TO INSTALLATION
 R-802.10.1DRAWINGS SUBMITTED SHALL BE
 SIGNED AND SEALED.
  
 NEW COMMENTS:
 1A.PRODUCT APPROVALS ARE MISSING FOR
 DOORS, WINDOWS ROOFING AND OVERHEAD
 DOOR.
 2A.SUBMIT TWO COMPLETE SIGNED AND SEAL
 SETS OF PLANS.
 3A.PERMIT VALUATION SHALL INCLUDE ALL
 MATERIALS AND LABOR.ADJUST PERMIT
 VALUE AND PAY ADDITIONAL PERMIT FEES.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-06-07 Cont ID  
Sent By alange Date 2006-06-07 Time 14:20 Rev Time 1.50
Received By alange Date 2006-06-07 Time 14:20 Sent To  
Notes
2006-06-07 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 3.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THE 2004
 EXISTING BUILDING CODE 301.5
  
 4.SUBMIT TWO COPIES OF ENERGY CALCS.
  
 5.SUBMIT TWO COMPLETE SETS OF PRODUCT
 APPROVALS.PRODUCT APPROVALS ARE
 MISSING OR INCOMPLETE FOR THE FOLLOWING;
 STRAPS AND TIEDOWNS.
  
 6.ALL PRODUCT APPROVALS SUBMITTED
 SHALL HAVE THE FOLLOWING STATE PRODUCT
 APPROVAL ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 8.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMMENDMENT TO FBC 106.3.3
  
 A.TRUSS DRAWINGS ARE TO BE REVIEWED
 AND APPROVED PRIOR TO INSTALLATION
 R-802.10.1
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-02-14 Cont ID  
Sent By alange Date 2006-02-14 Time 10:53 Rev Time 2.00
Received By alange Date 2006-02-14 Time 09:18 Sent To  
Notes
2006-02-14 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.PERMIT APPLICATION AND OWNER BUILDER
 DISCLOSURE STATMENT ARE REQUIRED TO BE
 NOTORIZED.
  
 3.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THE 2004
 EXISTING BUILDING CODE 301.5
  
 4.SUBMIT TWO COPIES OF ENERGY CALCS.
  
 5.SUBMIT TWO COMPLETE SETS OF PRODUCT
 APPROVALS.PRODUCT APPROVALS ARE
 MISSING OR INCOMPLETE FOR THE FOLLOWING;
 ROOFING, ROOFING UNDERLAYMENT, STRAPS
 AND TIEDOWNS.
  
 6.ALL PRODUCT APPROVALS SUBMITTED
 SHALL HAVE THE FOLLOWING STATE PRODUCT
 APPROVAL ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 7.ALL PLANS SUBMITTED AFTER OCTOBER,
 1, 2004 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE.
  
 8.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMMENDMENT TO FBC 106.3.3
  
 9. SHOW SIZE AND LOCATION OF ATTIC
 ACCESS COMPLYING WITH R-807.
  
 10.SHOW CORRECT SIZE OF ROOF SHEATHING
 AND FASTENING PER FBC R2304.9.1
 MIN ROOF SHEATHING IS 5/8"
  
 11.SHOW HOW "R" 30 INSULATION WILL BE
 USED IN 2 X 6 ROOF ON COTTAGE 2.
  
 12.PERMIT VALUATION IS TOO LOW, REVISE
 PERMIT VALUATION TO INCLUDE ALL
 MATERIALS AND LABOR OR WE WILL ADJUST IT
 ACCORDING TO MARSHALL AND SWIFT
 ESTIMATING GUIDE.
  
 13.SEE LEGAL DESCRIPTION SHALL BE FOR
 PALM BEACH COUNTY NOT BROWARD COUNTY.
  
 14.CLEARLY SHOW EXISTING AREAS AND
 AREAS OF NO WORK.SHOW EXISTING AND NEW
 FLOOW PLANS.IT APPEARS THAT THE ENTIRE
 BUILDING IS NEW?
  
 15.SHOW SIZE AND TYPE OF BEDROOM
 WINDOWS SO THAT EGREES REQUIREMENTS CAN
 BE CHECKED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-12-05 Cont ID  
Sent By btrobaug Date 2006-12-05 Time 16:33 Rev Time 0.50
Received By btrobaug Date 2006-12-05 Time 15:34 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-10-20 Cont ID  
Sent By btrobaug Date 2006-10-20 Time 11:40 Rev Time 0.50
Received By btrobaug Date 2006-10-20 Time 10:31 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-09-07 Cont ID  
Sent By btrobaug Date 2006-09-07 Time 11:47 Rev Time 1.00
Received By btrobaug Date 2006-08-22 Time 13:03 Sent To P
Notes
2006-08-22 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} ALL DOCUMENTS SUBMITTED OR
 RESUBMITTED FOR REVIEW, THAT ARE
 NECESSARY TO COMPLETE THE ORIGINAL
 DESIGN, MUST BE SUBMITTED BY THE
 DESIGNER OF RECORD. IN THIS CASE THE
 ARCHITECT, NOT THE OWNER/BUILDER OR AN
 ELECTRICAL CONTRACTOR. 481.221 F.S.
  
 NOTE: THE ELECTRICAL CONTRACTOR DRAWING
 PLANS UNDER THE ENGINEERING EXEMPTION
 471.003, MUST FIRST OF ALL BE THE
 CONTRACTOR OF RECORD, HAVING OBTAINED A
 PERMIT BY APPLICATIION OR BEING SIGNED
 ON THE ORIGINAL APPLICATION, AND
 ASSIGNED A PERMIT NUMBER. AND SECOND,
 MUST HAVE DRAWN THE PLANS ORIGINALLY.
  
 2} THE PREVIOUS COMMENTS STILL NEED TO
 BE ADDRESSED BY THE ARCHITECT ON NEW
 SHEETS, NOT HAND DRAWN, AND CONTAIN THE
 DATE OF THE CHANGE AS REQUIRED BY
 481.221.
  
 REGARDING COTTAGE #1.
  
 A) THE GROUNDING ELECTRODE CONDUCTOR
 MUST BE #2 CU TO COMPLY WITH 250.66, FOR
 A 250 AMP SERVICE, WHICH REQUIRES #4/0
 FEED CONDUCTORS.
  
 B) THE #8 GROUND RAN WITH THE FEEDERS
 FROM THE 125 AMP MAIN BREAKER TO THE 2ND
 FLOOR PANEL IS REQUIRED TO BE #6 PER
 250.122. #8 IS LISTED FOR A 100 AMP
 BREAKER.
  
 C) THERE ARE TWOKITCHENS UNITS ON THE
 SECOND FLOOR, NOT ALLOWED BY ZONING.
  
 D} INDICATE HOW THE PANEL ON THE 2ND
 FLOOR IS BEING FED, SEE 230.3.
  
 E} PANEL SCHEDULES AND CALCULATIONS MUST
 BE SUBMITTED BY THE DESIGNER OF RECORD.
  
  
 COTTAGE #2.
  
 INDICATE THE PANEL LOCATION, DISCONNECTS
 PER 225.31, AND GROUNDING PER 250.32
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-05-23 Cont ID  
Sent By btrobaug Date 2006-05-23 Time 10:17 Rev Time 1.00
Received By btrobaug Date 2006-05-23 Time 07:50 Sent To P
Notes
2006-05-23 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE PROVIDE A RISER DIAGRAM AND
 LOAD CALCULATIONS FOR THE SERVICE. SHOW
 ALL FEEDERS. 215.5.
  
 2} SHOW COMPLIANCE WITH ARTICLE 225.31
 AND 250.32 FOR THE SEPERATE STRUCTURES.
  
 3} PROVIDE PANEL SCHEDULES FOR THE
 COTTAGE PANELS SO BRANCH CIRCUIT CODE
 COMPLIANCE CAN BE DETERMINED. 210.52.
  
 4} IN REFERENCE TO THE ELECTRICAL PANEL
 IN THE STORAGE ROOM, SEE 240.24(D) NOT
 IN VICINITY OF EASILY IGNITIBLE
 MATERIAL. OVERCURRENT DEVICES SHALL NOT
 BE LOCATED IN THE VICINITY OF EASILY
 IGNITIBLE MATERIAL, SUCH AS IN CLOTHES
 CLOSETS. EXAMPLES OF LOCATIONS WHERE
 COMBUSTIBLE MATERIALS MAY BE STORED ARE
 LINEN CLOSETS, PAPER STORAGE CLOSETS,
 AND CLOTHES CLOSETS.
  
 THE FIRST THREE COMMENTS WERE ON THE
 PREVIOUS REVIEW. PLEASE SEE FLORIDA
 STATUTE 553.80(2)(B), ATTACHED. THIS IS
 THE SECOND REVIEW WITH AN INCOMPLETE, OR
 NO, PLAN OF THE SERVICE, CAUSING THE
 PLANS TO BE REJECTED AND ULTIMETLY
 RESUBMITTED A THIRD TIME, CREATING AN
 UNNECESSARY DELAY IN PERMITTING AND
 CONSRUCTION. PLEASE SEE THE STATUTE IS
 DIRECTED TO THE DESIGNER OF RECORD.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-12-15 Cont ID  
Sent By btrobaug Date 2005-12-15 Time 13:03 Rev Time 0.50
Received By btrobaug Date 2005-12-15 Time 11:11 Sent To Z
Notes
2005-12-15 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE PROVIDE A RISER DIAGRAM AND
 LOAD CALCULATIONS FOR THE SERVICE. SHOW
 ALL FEEDERS. 215.5.
  
 2} SHOW COMPLIANCE WITH ARTICLE 225.31
 AND 250.32 FOR THE SEPERATE STRUCTURES.
  
 3} PROVIDE PANEL SCHEDULES FOR THE
 COTTAGE PANELS SO BRANCH CIRCUIT CODE
 COMPLIANCE CAN BE DETERMINED. 210.52.
  
 4} SEE R313 FBC RESIDENTIALCODE FOR
 SMOKE DETECTOR REQUIREMENTS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-12-04 Cont ID  
Sent By adarroug Date 2006-12-04 Time 09:32 Rev Time 0.00
Received By adarroug Date 2006-12-04 Time 09:32 Sent To E
Notes
2006-12-04 09:32:23TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-11-15 Cont ID  
Sent By adarroug Date 2006-11-15 Time 16:31 Rev Time 0.00
Received By adarroug Date 2006-11-15 Time 16:31 Sent To Z
Notes
2006-11-15 16:41:57TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-10-20 Cont ID  
Sent By adarroug Date 2006-10-20 Time 09:41 Rev Time 0.00
Received By adarroug Date 2006-10-20 Time 09:41 Sent To E
Notes
2006-10-20 09:42:19TO "BTROBAUG" DESK/RESUB--PLANS IN INCOMING TODAY

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-08-18 Cont ID  
Sent By adarroug Date 2006-08-18 Time 08:56 Rev Time 0.00
Received By adarroug Date 2006-08-18 Time 08:56 Sent To E
Notes
2006-08-18 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-05-22 Cont ID  
Sent By adarroug Date 2006-05-22 Time 16:18 Rev Time 0.00
Received By adarroug Date 2006-05-22 Time 16:18 Sent To E
Notes
2006-05-22 00:00:00TO "BTROBAUGH" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-05-18 Cont ID  
Sent By adarroug Date 2006-05-18 Time 16:33 Rev Time 0.00
Received By adarroug Date 2006-05-18 Time 16:32 Sent To Z
Notes
2006-05-18 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-01-09 Cont ID  
Sent By adarroug Date 2006-01-09 Time 09:47 Rev Time 0.00
Received By adarroug Date 2006-01-09 Time 09:47 Sent To P
Notes
2006-01-09 00:00:00TO "P" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-02-14 Cont ID  
Sent By alange Date 2006-02-14 Time 10:53 Rev Time 0.00
Received By alange Date 2005-11-18 Time 09:13 Sent To  
Notes
2005-11-18 00:00:00TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-01-11 Cont ID  
Sent By tgordon Date 2006-01-11 Time 14:27 Rev Time 0.15
Received By tgordon Date 2006-01-11 Time 14:27 Sent To B
Notes
2006-01-11 00:00:00NO MECH. PLANS OR MECH. CONTRACTOR
 SUBMITTED AT THIS TIME.

Review Stop P PLUMBING
Rev No 5 Status P Date 2006-12-06 Cont ID  
Sent By jleech Date 2006-12-06 Time 13:00 Rev Time 0.00
Received By jleech Date 2006-12-06 Time 13:00 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2006-10-25 Cont ID  
Sent By jleech Date 2006-10-25 Time 09:16 Rev Time 0.00
Received By jleech Date 2006-10-25 Time 09:16 Sent To B
Notes
2006-10-25 09:26:59DENIED;
 AUTOMATIC CLOTHES WASHING FACILITIES REQUIRED PER.
 FBC-2004 PLUMBING TABLE 403.1(R-3).
 A CENTALLYW/M CAN BE INSTALLED INPLACE OF ONE IN EACH
 UNIT. PLEASE SHOW ON FLOOR PLAN
 AND AND ON SANITARY RISER DIAGRAM.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-09-07 Cont ID  
Sent By jleech Date 2006-09-07 Time 14:33 Rev Time 0.00
Received By jleech Date 2006-09-07 Time 14:33 Sent To B
Notes
2006-09-07 00:00:00DENIED;
 1.WATER HEATER IN COTTAGE 2 MUST HAVE A
 SEPARATION FROM CLOSET. ELECTRICAL CODE.
 2.NEW PLAN DOES NOT HAVE A NOTE ABOUT A
 BACK FLOW INSTALLATION PLEASE ADD THAT
 NOTE.
 3.PLEASE ADD NOTES ABOUT WATER PIPING.
 TYPE OF MATERIAL AND MUST BE TESTED AND
 INSPECTED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-06-02 Cont ID  
Sent By jleech Date 2006-06-02 Time 12:12 Rev Time 0.00
Received By jleech Date 2006-06-02 Time 12:12 Sent To B
Notes
2006-06-02 00:00:00DENIED;
 1.WATER HEATERS MUST BE ACCESSIBLE, ALL
 UNITS. SHOW DETAIL OF REMOVABLE SECTION
 OF CABINETS. SUBMIT A CUT SHEET OF
 HEATER TO BE USED, OPENING MUST BE
 WIDER THAN THE HEATER SO IT CAN BE
 REPLACED WITHOUT DAMAGING THE KITCHEN
 CABINETS.
 2.ARCHITECT LICENSE NUMBER REQUIRED ON
 TITAL BLOCK. FLORIDA ADMINISTRATION CODE
 SEC. 61G15-23.002.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-01-11 Cont ID  
Sent By jleech Date 2006-01-11 Time 13:11 Rev Time 0.50
Received By jleech Date 2006-01-11 Time 13:11 Sent To M
Notes
2006-01-11 00:00:00DENIED;
 1. SORCE OF HOT WATER NOT SHOWN.
 2.IS EACH UNIT ON A SEPARATE WATER
 METER? IF NOT A BACKFLOW PREVENTOR IS
 REQUIRED ON WATER SERVICE AT METER.
 3. SCOPE OF PLUMBING WORK IS NOT SHOWN
 ON DRAWINGS SUBMITED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 4 Status P Date 2006-12-21 Cont ID  
Sent By mmclean Date 2006-12-21 Time 14:23 Rev Time 0.00
Received By mmclean Date 2006-12-21 Time 14:23 Sent To  
Notes
2006-12-21 14:32:0312/21/06 HAND DELIVERED TO LUIS MARTINEZ FOR RYAN TO
 REVIEW.
2006-12-21 14:24:40RESUB - ADDITION TO THE EXISTING STRUCTURE (CHANGE IN
 STRUCTURE LAYOUT.
 OK TO ISSUE PER ANGELLA JONES-VANN, DEPUTY PLANNING
 DIRECTOR.

Review Stop Z ZONING
Rev No 3 Status F Date 2006-11-20 Cont ID  
Sent By mmclean Date 2006-11-20 Time 18:36 Rev Time 0.00
Received By mmclean Date 2006-11-20 Time 18:36 Sent To I
Notes
2006-11-20 18:38:29DENIED,
 1. THE ORIGINAL REVIEW INDICATED NO CHANGE IN SETBACK,
 PLANS SUBMITTED SHOWS A BALCONY ADDITION AND UTILITY
 ROOM
 2. PLEASE REMOVE ON THE SITEPLANS, "EXISTING BUILDING
 SETBACKS HAVE NOT BEEN CHANGED", SETBACK WILL CHANGE AS
 THE FLOOR PLANS CHANGES WITH THE ADDITIONS.
 3. VOID THE FIRST APPROVAL ON THE SURVEYS.
 4. CANNOT ADD ADDITIONAL SQUARE FOOTAGEFOR WASHER &
 DRYER UNDER STAIRS/BATH TO THE EXISTING STRUCTURE,
 STRUCTURE IS NON-CONFORMING.
 5. THE PROPOSED IMPROVEMENT CANNOT EXCEED THE VALUE OF
 THE STRUCTURE TO WHERE THE PROPOSED WORK IS BEING
 PROPOSED.
 THE EXISTING STRUCTURE IS NON-CONFORMING. THE VALUE OF
 THE IMPROVEMENTS CANNOT EXCEED 50% OF THE VALUE OF THE
 STRUCTURE.
 6. PLEASE PROVIDE A COPY OF THE APPRAISED STRUCTURE.(OF
 THE PROPOSED WORK).
  
  
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 2 Status P Date 2006-05-22 Cont ID  
Sent By mmclean Date 2006-05-22 Time 14:26 Rev Time 0.00
Received By mmclean Date 2006-05-22 Time 14:26 Sent To I
Notes
2006-05-22 00:00:00NO CHANGE IN SETBACK PER THE CONTRACTOR.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-01-06 Cont ID  
Sent By mmclean Date 2006-01-06 Time 18:22 Rev Time 0.00
Received By mmclean Date 2006-01-06 Time 18:22 Sent To I
Notes
2006-01-06 00:00:00DENIED,
 1. NEED TO INDICATE ON THE SITEPLAN OR
 SURVEY IF THE REMODEL CHANGES THE
 SETBACK OF THE EXISTING STRUCTURES.IF
 SETBACK CHANGES, INDICATE THE PROPOSED
 WORK WITH SETBACKS.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720