Plan Review Details - Permit 05110557
Plan Review Stops For Permit 05110557
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-05-12 Cont ID  
Sent By amorse Date 2006-05-12 Time 06:48 Rev Time 0.50
Received By amorse Date 2006-05-12 Time 06:48 Sent To PC
Notes
2006-05-12 00:00:00 
  
 ******REVISION-NEW JOIST ATTACHMENT*****

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-03-14 Cont ID  
Sent By amorse Date 2006-03-23 Time 11:34 Rev Time 0.50
Received By amorse Date 2006-03-23 Time 07:28 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-02-16 Cont ID  
Sent By amorse Date 2006-02-16 Time 10:29 Rev Time 1.00
Received By amorse Date 2006-02-16 Time 10:29 Sent To PC
Notes
2006-02-16 00:00:00 
  
 DENIED
  
 1) DETAIL 2 ON SHEET 2 OF 4 SHOWS WOOD
 TO WOOD CONNECTION, IS THIS NOT WOOD TO
 STEEL COLUMN, ALSO ARE EXISTING WALLS
 WOOD AS IN LEGEND OR BLOCK, CLARIFY
  
 2) DETAILS 1/3 AND 6/3 2X6 WALLS REQUIRE
 R19 INSULATION
  
 3) DESIGN PRESSURE TABLE 1606.2E HAS
 CHANGED IN 2004 FBC TO TABLE 1609.6B
  
 4) DETAILS ON FRAME-IN DIFFER FROM
 DETAIL 6/3. PC64 CONNECTOR IS ATTACHED
 TO 3X8 HEADER WHICH IS TIGHT TO EXISTING
 BEAM, CLARIFY
  
 5) SPECIFY ANCHORS TO BE USED IN ABU46
 AND 6X6 COLUMNS (EG. WEDGE ANCHORS,
 EPOXYED THREADED ROD OR RBF #5X? ETC.)
  
 6) CHECK SIMPSON CONNECTOR PC46 AS
 EXISTING BEAM OVER 2X6 WALL SHOULD BE
 5 1/2" WIDE AND MAY NEED PC64
  
 7) ENERGY CALC'S SHALL BE SIGNED AND
 DATED BY OWNER AGENT
  
 8) SIMPSON WOOD CONNECTORS REQUIRE
 PRODUCT APPROVALS. FL STATE COVER SHEET
 WITH ALL CONNECTORS THAT WILL BE USED
 MARKED ON IT WILL BE OK (NO NOA'S WILL
 BE REQUIRED)
  
 9) THOSE PRODUCTS WHICH ARE REGULATED BY
 DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 WPB
 AMENDMENTS TO FBC 2004. (APPROVED BY
 ENGINEER ON DRAWINGS) STAMP APPROVED AND
 INITIAL
  
 NOTE: IF NEEDED CALL FOR CLARIFICATION
  
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-12-29 Cont ID  
Sent By amorse Date 2005-12-29 Time 15:57 Rev Time 1.50
Received By amorse Date 2005-12-29 Time 15:56 Sent To PC
Notes
2005-12-29 00:00:00 
  
 DENIED
  
  
 1) PAY PALM BEACH COUNTY IMPACT FEES IF
 REQUIRED. HAVE BOTH SETS OF PLANS
 STAMPED AND A COPY OF THE RECEIPT FOR
 THE WEST PALM BEACH CONSTRUCTION
 SERVICES DEPT.
  
 2) DRAWINGS AND SPECIFICATIONS SHALL
 COMPLY WITH THE 2004 FL BLDG CODE
 EFFECTIVE OCT.1, 2005. ADJUST
 REFERENCES, TABLES AND CODES ACCORDINGLY
 EG. WIND LOADS PER 1609, TABLES 1609A
 AND 1609B
  
 3) CONNECTOR PC66 ON FOUNDATION PLAN IS
 FOR 6X6 POST SPEC THE CORRECT CONNECTOR
 FOR 4X6 POST
  
 4) DETAIL 1/3 & 4/3 CALL FOR CONNECTOR
 HD2A DOES THIS APPLY TO DOUBLE STUDS AT
 DOOR AND WINDOW OPENINGS, IF SO PLEASE
 SPECIFY. ALSO DOES IT APPLY TO THE BUILT
 UP STUDS ON THE FOUNDATION PLAN WHERE
 THE NEW WALL BUTTS INTO EXISTING BLOCK
 WALL
  
 5) SHOW DETAIL OF FRAMING AT DOOR AND
 WINDOW OPENINGS C/W CONNECTORS FOR STUD
 TO HEADER ATTACHMENT TO MEET WIND LOADS
  
 6) INDICATE ON DRAWINGS ROOM THAT AJOINS
 NEW FAMILY ROOM ADDITION
  
 7) PROVIDE 2 COPIES OF NEW ENERGY CALCS
 TO VERIFY EXISTING A/C UNIT ARE ABLE TO
 HANDLE THE EXTRA SQ FOOTAGE
  
 8) PROVIDE 2 COPIES OF PRODUCT APPROVALS
 FOR ANY EXTERIOR BUILDING COMPONENT SUCH
 AS WINDOWS, SLIDING GLASS DOORS, STORM
 PANELS ETC THAT WILL BE USED IN
 CONSTRUCTION OF ADDITION. PRODUCT
 APPROVAL COVER SHEETS WITH FL#'S AND
 PRODUCT NOA'S CAN BE FOUND ON THE WEB
 SITE WWW.FLORIDABUILDING.ORG
  
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-05-02 Cont ID  
Sent By dpalmer Date 2006-05-02 Time 18:46 Rev Time 0.00
Received By dpalmer Date 2006-05-02 Time 18:45 Sent To PC
Notes
2006-05-02 00:00:00REDLINED,
  
 210.52, 680.22

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-03-23 Cont ID  
Sent By dpalmer Date 2006-03-23 Time 07:08 Rev Time 0.00
Received By dpalmer Date 2006-03-23 Time 07:08 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-03-10 Cont ID  
Sent By dpalmer Date 2006-03-10 Time 16:50 Rev Time 0.00
Received By dpalmer Date 2006-03-10 Time 16:46 Sent To B
Notes
2006-03-10 00:00:00*********** UNSAT 3RD REVIEW *********
  
 ** PLEASE SEE PLANS ARE NOW COMING BACK
 WITH COMMENTS FROM OTHER TWO REVIEWS
 STILL NOT ADDRESSED.
 PLEASE ALSO SEE NEW NOTE PERTAINING TO
 THE ENGINEER.
  
  
  
 1)NOTE: PLEASE SEE A PANEL SCHEDULE/LOAD
 CALCULATIONS ARE SUBMITTED , HOWEVER
 THESE DO NOT SEEM TO CORRELATE WITH THE
 SINGLE CIRCUIT BEING ADDED. PLEASE SEE
 LOAD OF 26A'S DOES NOT SEEM TO BE WHAT
 THE NEW LOAD SHOULD BE AND IT DOES NOT
 SEEM TO BE WHAT THE NEW AND EXISTING
 LOADS SHOW BE??
 THIS NOTE WAS ON THE FIRST REVIEW,
 HOWEVER NOT ON SECOND REVIEW AS THE
 PANEL/LOADS ETC WERE REMOVED FROM THE
 SUBMITTED PLANS.
  
 2)NOTE: PLEASE SEE PLANS STILL MISSING
 CONTROL FOR EGRESS LIGHTING AS REQUIRED
 PER 210.70 NFPA-70 (2002), NFPA-101 7.8
 (2003).
 PLEASE SEE MISSING RECEPT 210.52
 PLEASE SEE THESE WERE NOTED/REDLINED ON
 PREVIOUSREVIEW ALSO?
  
 3)NOTE: PLEASE SEE NOW PLANS ARE COMING
 BACK IN WITH OUT THE TITLE BLOCK FOR THE
 ENGINEER OF RECORD??
  
 4)NOTE: PLEASE SEE NOTICE PER FS
 553.80(2)(B) IS NOW ATTACHED TO NOTES
 WITH RESPECT TO THE DESIGN PROFESSIONAL
 AND REPEAT COMMENTS NOT BEING ADDRESS
 FOR MORE THAN THREE REVIEWS. IF COMMENTS
 ARE NOT 100% ON NEXT REVIEW THIS OFFICE
 WILL HAVE NO CHOICE BUT TO ASSESS A 4X
 FEE FOR THE PLAN REVIEW PORTION OF THE
 PERMIT FEE TO THE DESIGN PROFESSIONAL.
 THIS FEE IS "NOT" TO THE OWNER OR
 CONTRACTOR AND SHALL BE THE SOLE
 RESPONSIBILTY OF THE ENGINEER.
 PLEASE KNOW, THAT PLANS SHALL ALSO BE
 TURNED OVER TO THE FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS FOR REVIEW OF
 SAID PLANS.
 THIS IS A SIMPLE BUILD OUT OF AN
 EXISTING AREA IN A SINGLE FAMILY
 DWELLING AND IT IS RECOMMENDED BY THIS
 OFFICE, IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE. PLEASE KNOW, TO DATE THE
 DESIGN PROFESSIONAL HAS NOT CONTACTED
 THIS OFFICE FOR ANY QUESTIONS OR
 COMMENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-02-14 Cont ID  
Sent By dpalmer Date 2006-02-14 Time 17:35 Rev Time 0.00
Received By dpalmer Date 2006-02-14 Time 17:31 Sent To B
Notes
2006-02-14 00:00:00******* UNSAT 2ND REVIEW ********
  
 1)NOTE: PLEASE SEE ELECTRICAL DETAILS ,
 PLANS , LOADS ETC HAVE NOW BEEN REMOVED
 FROM PLANS AND NO ELECTRICAL PLANS WERE
 SUBMITTED FOR SCOPE OF WORK AND MIN
 REQUIRED PER NEC.
 215.5, 210.52,210.70 ETC
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-12-29 Cont ID  
Sent By dpalmer Date 2005-12-29 Time 11:28 Rev Time 0.00
Received By dpalmer Date 2005-12-29 Time 11:28 Sent To B
Notes
2005-12-29 00:00:00PLANS WERE OUT FRONT, BROUGHT BACK FOR
 REVIEWS BY ELEC AND BLDG.
 ********** UNSAT ***********
  
  
 1)NOTE: PLEASE SEE PLANS STATE THE 2001
 FBC , WHERE AS OF OCT. 1ST, 2005 THE
 STATE ADOPTED THE NEW 2004 FBC. PLEASE
 SEE BLDG REVIEW COMMENTS AS THIS WILL
 AFFECT THE DESIGN.
  
 2)NOTE: PLEASE SEE A PANEL SCHEDULE/LOAD
 CALCULATIONS ARE SUBMITTED , HOWEVER
 THESE DO NOT SEEM TO CORRELATE WITH THE
 SINGLE CIRCUIT BEING ADDED. PLEASE SEE
 LOAD OF 26A'S DOES NOT SEEM TO BE WHAT
 THE NEW LOAD SHOULD BE AND IT DOES NOT
 SEEM TO BE WHAT THE NEW AND EXISTING
 LOADS SHOW BE??
  
 215.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-05-11 Cont ID  
Sent By adarroug Date 2006-05-11 Time 14:27 Rev Time 0.00
Received By adarroug Date 2006-05-11 Time 14:27 Sent To B
Notes
2006-05-11 00:00:00TO "AMORSE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-04-29 Cont ID  
Sent By adarroug Date 2006-04-29 Time 14:10 Rev Time 0.00
Received By adarroug Date 2006-04-29 Time 14:10 Sent To E
Notes
2006-04-29 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-03-21 Cont ID  
Sent By dpalmer Date 2006-03-21 Time 20:06 Rev Time 0.00
Received By dpalmer Date 2006-03-21 Time 20:06 Sent To E
Notes
2006-03-21 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-03-09 Cont ID  
Sent By adarroug Date 2006-03-09 Time 09:06 Rev Time 0.00
Received By adarroug Date 2006-03-09 Time 09:06 Sent To E
Notes
2006-03-09 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-03-02 Cont ID  
Sent By adarroug Date 2006-03-02 Time 14:00 Rev Time 0.00
Received By adarroug Date 2006-03-02 Time 14:00 Sent To Z
Notes
2006-03-02 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-02-13 Cont ID  
Sent By adarroug Date 2006-02-13 Time 09:45 Rev Time 0.00
Received By adarroug Date 2006-02-13 Time 09:45 Sent To E
Notes
2006-02-13 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-02-13 Cont ID  
Sent By adarroug Date 2006-02-13 Time 09:37 Rev Time 0.00
Received By adarroug Date 2006-02-13 Time 09:37 Sent To E
Notes
2006-02-13 00:00:00TO "DPALMER' DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-02-06 Cont ID  
Sent By adarroug Date 2006-02-06 Time 16:48 Rev Time 0.00
Received By adarroug Date 2006-02-06 Time 16:48 Sent To Z
Notes
2006-02-06 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-12-29 Cont ID  
Sent By amorse Date 2005-12-29 Time   Rev Time 0.00
Received By rbrown Date 2005-11-18 Time 16:01 Sent To  
Notes
2005-11-18 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-12-29 Cont ID  
Sent By dpalmer Date 2005-12-29 Time 11:50 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
2005-12-29 00:00:00NO MECH BEING SHOWN,NO CONTRACTOR SIGNED
 ON APPLICATION.

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-12-29 Cont ID  
Sent By dpalmer Date 2005-12-29 Time 11:24 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
2005-12-29 00:00:00NO PLUMB WORK BEING DONE, NO PLUMB
 CONTRACTOR SIGNED ON.

Review Stop Z ZONING
Rev No 3 Status N Date 2006-03-08 Cont ID  
Sent By mmclean Date 2006-03-08 Time 14:44 Rev Time 0.00
Received By mmclean Date 2006-03-08 Time 14:44 Sent To I
Notes
2006-03-08 00:00:00THE PROPOSED WORK IS WITHIN THE SETBACK
 OF THE EXISTING STRUCTURE.

Review Stop Z ZONING
Rev No 2 Status F Date 2006-02-10 Cont ID  
Sent By mmclean Date 2006-02-10 Time 14:02 Rev Time 0.00
Received By mmclean Date 2006-02-10 Time 14:02 Sent To I
Notes
2006-02-10 00:00:00DENIED,
 1. THE TWO SURVEY PROVIDED, BUT DID NOT
 INDICATE THE LOCATION OF THE PROPOSED
 WORK (WITH SETBACK IF APPLICABLE).
 2. PLEASE SHOW THE PROPOSED WORK ON THE
 TWO COPY OF SURVEY.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2005-11-28 Cont ID  
Sent By mmclean Date 2005-11-28 Time 11:01 Rev Time 0.00
Received By mmclean Date 2005-11-28 Time 11:19 Sent To I
Notes
2005-12-07 00:00:0012/7/05 DENIED AND REVIEWED BY SHIRLEY
 ON 11/28/05
2005-11-28 00:00:00DENIED, NEED SURVEY SHOWING NEW WORK