Plan Review Details - Permit 05110547
Plan Review Stops For Permit 05110547
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-12-09 Cont ID  
Sent By pschmitz Date 2006-12-09 Time 07:27 Rev Time 0.00
Received By pschmitz Date 2006-12-09 Time 07:27 Sent To PC
Notes
2006-12-09 07:28:38SEPERATE PERMIT FOR GAS.
 2004 FBC FUEL GAS CODE

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-08-12 Cont ID  
Sent By pschmitz Date 2006-08-13 Time 14:40 Rev Time 0.00
Received By pschmitz Date 2006-08-12 Time 14:40 Sent To  
Notes
2006-08-13 00:00:00 
 PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE
  
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 UNSAT
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR THE GAS PERMIT APPLICATION.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
  
 3. TYPE OF GAS, (LP OR NATURAL)
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). INCLUDE EXISTING SYSTEM.
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304
 .
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 8. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2.
  
 9.SEC 409.5 EQUIPMENT SHUT OFF VALVE.
 EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWNSTREAM OF MANUAL SHUT OFF VALVE.
  
 QUESTIONS 561-805-6692PAUL SCHMITZ
  
  
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By adarroug Date 2006-11-13 Time 15:22 Sent To  
Notes
2006-11-13 15:22:53TO "P" BOX/RESUB FOR PLUMB AND GAS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-07-21 Cont ID  
Sent By adarroug Date 2006-07-21 Time 14:41 Rev Time 0.00
Received By pschmitz Date 2006-08-12 Time 14:01 Sent To P
Notes
2006-07-21 00:00:00TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-03-10 Cont ID  
Sent By adarroug Date 2006-03-10 Time 11:11 Rev Time 0.00
Received By adarroug Date 2006-03-10 Time 11:11 Sent To P
Notes
2006-03-10 00:00:00TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-21 Cont ID  
Sent By adarroug Date 2006-03-21 Time 14:40 Rev Time 0.00
Received By adarroug Date 2005-11-18 Time 14:26 Sent To  
Notes
2005-11-18 00:00:00TO "P" BOX

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-12-09 Cont ID  
Sent By pschmitz Date 2006-12-09 Time 07:29 Rev Time 0.00
Received By pschmitz Date 2006-12-09 Time 07:29 Sent To PC
Notes
2006-12-09 07:31:10SEE PROVISO
 SEC 912 COMBINATION WASTE AND VENT.
 2004 FBC CODE.

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-08-12 Cont ID  
Sent By pschmitz Date 2006-08-13 Time 14:40 Rev Time 0.00
Received By pschmitz Date 2006-08-12 Time 14:40 Sent To  
Notes
2006-08-13 00:00:00PAUL SCHMITZ
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE
 CHAPT.1, ADMINISTRATION, 2004 EDITION
 UNSAT
  
 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE
 MATERIAL. ELECTRONIC MEDIA DOUCMENTS ARE
 PERMITTED TO BE SUBMITTED WHEN APPROVED
 BY THE BUILDING OFFICAL.
 CONSTRUCTION DOUCMENTS SHALL BE OF
 SUFFICENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TOTHE PROVISIONS OF THIS
 CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS AS DETERMINED BY
 THE BUILDING OFFICAL ( SEE ALSO SECTION
 106.3.5)
  
 1. SHT 1. PLEASE CORELATE AS BUILT FLOOR
 PLAN WITH PLUMBING RISER DIAGRAM.
 PROVIDE A PLUMBING SYMBOL LEGEND TO
 DISTINGUISH WHICH LINES ARE GREASE
 WASTE. AND WHICH ARE SANITARY.
 ALSO THE EXISTING FROM NEW.
  
 2. CLOUDED NOTE: SAYS CONTRCTOR TO
 INSTALL NEW DRAINS LINES AS SHOWN,
 PLEASE CLARIFY.
  
 3. SEC 106.3.5.1.3 PLUMBING (3)
 WATER RISER REQUIRED.
  
 4. SUBMITAL FOR GREASE TRAP, NOT
 APPROVED. ALL SUBMITTALS ARE TO BE
 REVIEWED AND APPROVED BY THE ENGINEER OF
 RECORD, WITH HIS STAMP OF APPROVAL,
 PRIOR TO BUILING DEPARTMENT REVIEW.
  
 5. SEC 802.3 WASTE RECEPTORS:
 ALL INDIRECT WASTEIN THE FOOD HANDLING
 AREA SHALL BE TO A FLOOR SINK.
  
 6. SEC 608 PROTECTION OF THE POTABLE
 WATER SUPPLY. IF EXISTING BACK FLOW
 PREVENTER, SHOW THE LOCATION.
  
 7. 905.3 VENT CONNECTION TO DRAINAGE
 SYSTEM. EVERY DRY VENT CONNECTING TO A
 HORIZONTAL DRAIN SHALL CONNECT ABOVE THE
 CENTERLINE OF THE HORIZONTAL DRAIN PIPE.
  
 8 GRESAE TANK DETAIL
 MAN HOLE LIDS SHALL HAVE GREASE EMBOSSED
 ON THEM.
  
 END OF COMMENTS, QUESTIONS 561-805-6692

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-03-21 Cont ID  
Sent By pschmitz Date 2006-03-21 Time 15:19 Rev Time 0.00
Received By pschmitz Date 2006-03-21 Time 15:19 Sent To  
Notes
2006-03-21 00:00:00PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPT.1, ADMINISTRATION, 2004 EDITION
 DENIED
  
 1)
 SEC 608.2 PLUMBING FIXTURES.
 THE WATER SUPPLY LINES FOR EVERY FIXTURE
 SHALL BE INSTALLEDSO AS TO PREVENT
 BACK FLOW.
 SEC 106.3.5.1.3 (4.)COMMERICAL
 BUILDINGS, PLUMBING SANITARY DRAINAGE.
 ( DWV ISOMETRIC ) REQUIRED
 PLUMBING RISER.
 SEPERATE THESANITARY WASTE, FROM WATER
 SUPPLY PIPING.
 2)
 NOTE: EXISTING WATER HEATER IS BEING
 REMOVED, SHOW NEW LOCATION, PROVIDE MFG
 INFORMATION, GAS OR ELECTRIC
 3)
 DETAIL STD GS-1
 NOTE 2: MAN HOLES LOCATED ON PRIVATE
 PROPRTY SHALL NOT HAVE " WEST PALM
 BEACH" EMBOSSED ON THEM.
 4)
 GREASE TRAP INLET AND OUTLET ARE
 LOCATED ON THE ENDS OF THE TANK, UNLESS
 SPECIAL ORDERED. PLEASE CLARIFI.
 5)
 BEVERAGE SERVICE AREA WASTE:
 PROVIDE A INDIRECT WASTE RECEPTOR.
 (FLOOR SINK)
 6)
 WASTE LINE SIZES, SEE TABLE 709.1 FOR
 FIXTURE DRAIN MINIMUM SIZE.
 7)ICE MACHINE DRAIN LINE, TO INDERICT
 WASTE RECEPTOR (FLOOR SINK)
  
 END OF COMMENTS, QUESTIONS 561-805-6692

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-03-21 Cont ID  
Sent By pschmitz Date 2006-03-21 Time 15:18 Rev Time 0.00
Received By pschmitz Date 2005-12-03 Time 11:59 Sent To  
Notes
2005-12-03 00:00:00PAUL SCHMITZ
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 704 BELVEDER RD TULIPAN BAKERY
 561-820-6107
 DENIED
  
 SEC106.1.1 PLANS REQUIRED
 (1) SITE PLAN, SHOW BUILDING FOOT
 PRINT,LOCATION OF THE 750 GALLON GREASE
 TANK.
 (2) SHOW DRAIN LINE PIPING, CLEAN OUT ON
 INLET AND OUT LET OF TANK.
 (3) PROVIDE A ISOMETRIC DRAWING OF THE
 GREASE WASTE SYSTEM.
 ALL INDIRECT WASTE TO FLOOR SINKS.
 CAN WASH AND LOCATION.
 (4) ALL FLOOR DRAINS IN FOOD PREPARATION
 AREA TO GREASE WASTE.
 SHOW LOCATION OF THREE COMPARTMENT SINK.
  
 (5) GREASE TRAP SIZE
 CONTACT W P BEACHWATERPLANT LAB
 SUPERVISOR
 INDUSTRIAL COORDINATOR, LYNN MASSON
  
 OFFICE 561-822-2271E-MAIL
 [email protected]
 (6) WATER HEATER LOCATED OUT SIDE: SHALL
 HAVE A WEATHER PROTECTION ENCLOSER.
 END OF COMMENTS QUESTIONS 561-805-6692