Plan Review Details - Permit 05110490
Plan Review Stops For Permit 05110490
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-04-05 Cont ID  
Sent By alange Date 2006-04-05 Time 11:02 Rev Time 1.66
Received By alange Date 2006-04-05 Time 10:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-03-23 Cont ID  
Sent By alange Date 2006-03-23 Time 10:28 Rev Time 1.00
Received By alange Date 2006-03-23 Time 10:28 Sent To  
Notes
2006-03-23 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
  
 6.PRODUCT APPROVAL REQUIRED FOR
 LINTELS WITH THE FOLLOWING STATE PRODUCT
 APPROVAL.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-02-07 Cont ID  
Sent By alange Date 2006-02-07 Time 10:30 Rev Time 1.50
Received By alange Date 2006-02-07 Time 10:29 Sent To  
Notes
2006-02-07 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
  
 3.ALL PLANS SUBMITTED AFTER OCTOBER,
 1, 2004 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE. CHECK ALL
 REFERENCES AND CONSTRUCTION TYPE.
  
  
 6.PRODUCT APPROVAL REQUIRED FOR
 LINTELS WITH THE FOLLOWING STATE PRODUCT
 APPROVAL.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-12-27 Cont ID  
Sent By alange Date 2005-12-27 Time 09:50 Rev Time 3.50
Received By alange Date 2005-12-27 Time 09:50 Sent To  
Notes
2005-12-27 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.ALL PLANS SUBMITTED AFTER OCTOBER,
 1, 2004 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE.
  
 4.ENERGY CALCS. SHALL BE SUBMITTED
 ACCORDING TO THE 2004 FBC.
  
 5."R" VALUES ON PLANS DO NOT MATCH
 ENERGY CALCS.
  
 6.PRODUCT APPROVAL REQUIRED FOR
 LINTELS WITH THE FOLLOWING STATE PRODUCT
 APPROVAL.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-06-21 Cont ID  
Sent By dpalmer Date 2007-06-21 Time 10:40 Rev Time 0.00
Received By dpalmer Date 2007-06-21 Time 10:25 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-06-03 Cont ID  
Sent By dpalmer Date 2007-06-03 Time 16:28 Rev Time 0.00
Received By dpalmer Date 2007-06-03 Time 16:04 Sent To PC
Notes
2007-06-03 16:28:33** UNSAT **
  
  
 1) NOTE: PLEASE SEE MISSING DISCONNECT FOR MASTER
 BEDROOM WATER HEATER.422.31 THE SYMBOL AS SHOWN ON
 PLANS IS FOR A RECEPTACLE.
  
 2) NOTE: PLEASE SEE PANEL SCHEDULES WHICH INDICATE TWO
 AHU'S #2. PLEASE SEE PANEL *B* WHICH INDICATE 10KW AHU
 WITH 30AMP OCP AND #8 CONDUCTORS WHICH ARE NOT OF
 SUFFICIENT SIZE PER 240.4, 424.3B, AND 310.16.
 PLEASE ADJUST.
  
 4) NOTE: PLEASE SEE PANEL SCHEDULES STILL INDICATE 40
 CIRCUITS( MISPRINT).
 PLEASE ADJUST.
 FBC 106.1.2
  
 5) NOTE: PLEASE PROVIDE THE GROUNDING ATTACHMENT FOR
 THE DETACHED GARAGE AS REQUIRED PER 250.32. THIS WAS
 ISSUED WITH NOTE ON PLAN TO COMPLY, HOWEVER THE
 ATTACHMENT SHOULD BE KNOWN AND SHOWN ON PLANS.
  
 6) NOTE: PLEASE SEE PLANS AND PANEL SCHEDULE INDICATE
 SMOKE DEVICES AS *SD* AND SYMBOL LEGEND HAS THESE AS
 SMOKE DETECTORS.
 PLEASE KNOW THAT A MEETING WAS HELD AT THE SOUTHERN
 SECTION MEETING IN OCT 06 WHERE WE WERE DIRECTLY
 INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE DETECTORS
 ON PLANS FOR RESIDENTIAL HOMES IS NOT ACCEPTABLE WHEN
 THESE DEVICES ANY ACTUALLY FALL UNDER THE DEFINITIONS
 OF SMOKE ALARMS WHICH WOULD BE SHOWN AS SA/SMOKE
 ALARMS.
 THIS INFORMATION WAS NEW TO THIS AHJ AS THE GENERAL USE
 OF THE SD FOR SMOKE DETECTORS WAS ALWAYS ACCEPTED. BY
 THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE
 DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL
 NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY
 HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF
 SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS
 SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS
 SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS
 FOR OTHER NEW HOMES.
 ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC
 RESIDENTIAL CODE/ FBC AND IN NFPA-72.
 IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE*.
 PLEASE SEE NFPA-72 11.5.1.1, 11.8.3
  
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-03-10 Cont ID  
Sent By dpalmer Date 2006-03-10 Time 18:01 Rev Time 0.00
Received By dpalmer Date 2006-03-10 Time 17:45 Sent To E
Notes
2006-03-10 00:00:00******* PROVISO ** 3RD REVIEW ********
  
 1)NOTE: PLEASE SEE LOAD SHOWN ON PANEL
 "A"FOR PANEL "C" DOES NOT CORRELATE
 WITH ACTUAL LOAD INDICATED ON PANEL "C",
 PLEASE ADJUST.
  
 2)NOTE: PLEASE SEE RISER INDICATES 40
 CIRCUIT PANELS, AND PANEL SCHEDULES
 INDICATE THESE AS 42 CIRCUIT PANELS.
  
 3)NOTE: PLEASE SEE THE NEW ADDED PANEL
 "D" NOW ALSO INDICATES A NEW GAS POOL
 HEATER?? . PLEASE SEE PANEL "C" ALREADY
 INDICATES ONE GAS POOL HEATER. PLEASE
 ALSO SEE PLANS DO NOT INDICATE TWO GAS
 POOL HEATERS?
 PLEASE CORRELATE.
  
 ** PLEASE REVISE AND SUBMIT THE ABOVE
 INFORMATION FOR REVIEW ALONG WITH ANY
 OTHER REVISIONS BEFORE "ROUGH"
 ELECTRICAL INSPECTION.
  
 PLEASE SUBMIT THE ABOVE INFORMATION , IF
 THERE ARE ANY QUESTIONS, PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-01-30 Cont ID  
Sent By dpalmer Date 2006-01-30 Time 18:15 Rev Time 0.00
Received By dpalmer Date 2006-01-30 Time 17:36 Sent To M
Notes
2006-01-30 00:00:00******** UNSAT2ND REVIEW **********
  
 PLEASE SEE SOME EXISTING NOTES AND SOME
 NEW NOTES.
  
  
  
 1)NOTE: OK
  
 2)NOTE: OK
  
 3)NOTE: OK, HOWEVER PLEASE NOW SEE POOL
 HEATER IS BEING SHOWN AS GAS, YET SHOWS
 4KW LOAD AND SHOWS BEING CONTINUOUS??
 PREVIOUS PLANS CALLED FOR AN ELEC HEAT
 PUMP.
  
 ** PLEASE INDICATE ALL CONTINUOUS
 LOADS ON POOL PANEL AT 125%.
 PLEASE ALSO SEE THIS WILL CHANGE LOAD
 AND EXCEED RATING OF OCP AND FEEDERS TO
 POOL PANEL. PLEASE ADJUST AS NEW OCP AND
 FEEDERS WILL NEED TO BE INCREASED.
 215.5,230.42,215..3,90.8
  
 4)NOTE: OK
  
 5)NOTE: OK
  
 6)NOTE: OK
  
 7)NOTE: OK, HOWEVER PLEASE SEE
 DISCONNECTING NOTE FOR DETACHED GARAGE.
  
 8)NOTE: OK
  
 9)NOTE: OK
  
 10)NOTE: OK, NOTED.
  
 11)NOTE:OK/ NO, PLEASE SEE DISCONNECT
 SWITCH(S) SHOULD BE SHOWN FOR GDO NOW
 ADDED.
 PLEASE SEE NOTE ADDED FOR GROUNDING,
 SHOULD REFERENCE 250.32, HOWS 225.31
 WHICH IS THE DISCONNECT REQUIREMENT.
 PLEASE SEE 250.32 WHICH REQUIRES A
 GROUNDING ELECTRODE TO FOOTER STEEL MIN
 .
  
 **PLEASE SEE THE DETACHED GARAGE
 WOULD REQUIRE MEANS OF DISCONNECT AS
 REQUIRED UNDER 225.31-225.36.
 PLEASE SEE DISCONNECTING MEANS MAY BE A
 TOGGLE SWITCH TYPE DEVICE IF MEETING THE
 EXCEPTIONS.
  
 12)NOTE: OK
  
 13)NOTE: NO, PLEASE SEE PANEL "A" SHOWS
 A 5KW HEAT, LOAD CALCULATIONS INDICATE
 65% AS 6500W??
 PLEASE ALSO SEE PANEL "B" SHOWS TWO
 UNITS AS 10KW, HOWEVER 65% ON LOAD
 CALCUALTIONS INDICATES 9750W??
 PLEASE SEE 655 OF 20KW ,,
 PLEASE CORRELATE ALL KW LOADS
 FOR AHU'S WITH KW RAITNGS SHOWN ON
 MECHANICAL PLANS. PLEASE MAKE ANY
 ADJUSTMENTS NEEDED FOR OCP, AWG, LOAD
 CALCS ETC.
 215.5
  
 NEW NOTES:
  
 1)NOTE: PLEASE SEE POOL PANEL IS SHOWN
 ON PLANS BEING FED FROM WHAT APPEARS TO
 BE THE INSIDE PANEL "B", YET RISER SHOWS
 THIS COMING FROM THE OUTSIDE MCB PANEL.
 ??
 ** PLEASE CORRELATE RISER AND PANELS AS
 PANEL SCHEDULES SHOWN INDICATE THESE AS
 MCB PANELS WHICH ARE 40 CIRCUIT PANELS,
 YET RISER SHOWS THE MCB PANELS AS 8-16?
 PLEASE ALSO SEE RISER AS THESE PANELS DO
 NOT SEEM TO CORRELATE.
 ** PLEASE PROVIDE PANEL SCHEDULES FOR
 OUTDOOR MCB PANELS IF THERE ARE CIRCUITS
 COMING FROM THESE PANELS AS SHOWN.
 ** PLEASE SEE 230.7, SERVICE ENTRANCE
 CONDUCTORS MAY NOT BE IN THE SAME
 RACEWAY/ENCLOSURE WITH THE
 BRANCHCIRCUITS OR FEEDERS.
 PLEASE REVISE RISER DIAGRAM AS MCB PANEL
 "B" MAY NOT BED FED THORUGH MCB PANEL
 "A".
  
 2)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONALS AND REPEAT COMMENTS FOR
 CODE COMPLIANCE.
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 FROM PLANS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING.
 ONE COPYOF OLD/VOIDED SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE.
  
 ** PLEASE SEE ANY OTHER POSSIBLE
 COMMENTS FROM OTHER REVIEWS WHICH MAY
 AFFECT ELECTRICAL PLANS.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-12-07 Cont ID  
Sent By dpalmer Date 2005-12-07 Time 05:51 Rev Time 1.50
Received By dpalmer Date 2005-12-06 Time 17:19 Sent To M
Notes
2005-12-07 00:00:00******** UNSAT **********
  
 1)NOTE: PLEASE SEE ELECTRICAL PLANS DO
 NOT CORRELATE WITH BLDG PLANS/A-SHEETS.
 PLEASE SEE THESE ARE TWO COMPLETELY
 DIFERENT HOUSES.
 PLEASE ADJUST.
 PLEASE VERIFY WHAT APPEARS TO BE A
 CLOSET OF SOME SORT IN WALK IN CLOSET OF
 MASTER BEDRM AREA THAT APPEARS TO SHOW A
 WATER HEATER??
 215.5
  
 2)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTORS FROM MAINS TO SUB
 PANEL(S) A AND B.
 250.110,250.122
  
 3)NOTE: PLEASE INDICATE ALL CONTINUOUS
 LOADS ON POOL PANEL AT 125%.
 PLEASE ALSO SEE THIS WILL CHANGE LOAD
 AND EXCEED RATING OF OCP AND FEEDERS TO
 POOL PANEL. PLEASE ADJUST AS NEW OCP AND
 FEEDERS WILL NEED TO BE INCREASED.
 215.5,230.42,215..3,90.8
  
 4)NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52. PLEASE SEE ONE SET OF PLANS HAVE
 BEEN REDLINED WITH MANY OF THESE
 LOCATIONS INDICATED.
  
 5)NOTE: PLEASE SEE RECEPT MISSING PER
 210.52H FOR HALLWAY. 10' OR MORE OF
 WALL.
  
 6)NOTE: PLEASE SEE MISSING RECEPT PER
 210.52E, FRONT GFI.
  
 7)NOTE: PLEASE CORRELATE THE # OF GDO
 CIRCUITS ON PANEL SCHEDULE WITH THE
 ACTUAL # NEEDED ON PLANS. PLEASE SEE
 OTHER GARAGE.
 PLEASE ALSO SEE PLANS DO NOT INDICATE
 ANY RECEPTS AT THESE LOCATIONS.
 215.5, 430.24. TABLES).
  
 8)NOTE: PLEASE SEE DISC'S FOR A/C CU
 UNITS SHALL MEET 110.26
  
 9)NOTE: PLEASE SEE NFPA -72 11-8.3.5
 WHICH REQUIRES ALL SD'S TO BE INSTALLED
 WITH-IN 12" OF A FLAT CEILING AREA.
 PLEASE SEE "TRAY" CEILING AREA WOULD
 REQUIRE TO THESE SD'S LOCATED AT THESE
 AREAS IF HEY ARE 12" OR MORE HIGHER THAN
 SURROUNDING CEILING AREA. SEE REDLINED
 PLANS.
  
 10)NOTE: PLEASE SEE 410.8 FOR TYPE OF
 FIXTURE AND MIN CLEARENCES PERMITTED
 ABOVE TUB/WHIRLPOOL. PLEASE PLACE NOTE
 ON PLANS AS THIS IS SHOWN AS A "J-BOX"
 FOR FUTURE.
  
 11)NOTE: PLEASE SEE THE DETACHED GARAGE
 WOULD REQUIRE MEANS OF DISCONNECT AS
 REQUIRED UNDER 225.31-225.36.
 PLEASE SEE DISCONNECTING MEANS MAY BE A
 TOGGLE SWITCH TYPE DEVICE IF MEETING THE
 EXCEPTIONS.
  
 12)NOTE: PLEASE CORRELATE THE NUMBER OF
 RECESSED LTS ON PANEL LOAD CALCULATIONS
 WITH THE # OF FIXTURES ON PLANS.
 215.5,220.3B4
  
 13)NOTE: PLEASE CORRELATE ALL KW LOADS
 FOR AHU'S WITH KW RAITNGS SHOWN ON
 MECHANICAL PLANS. PLEASE MAKE ANY
 ADJUSTMENTS NEEDED FOR OCP, AWG, LOAD
 CALCS ETC.
 215.5
  
 ** PLEASE KNOW, DEPENDING ON POSSIBLE
 CHANGES IN "HOUSE PLANS" OR LAYOUT NOT
 ALL COMMENTS MAY BE ON THIS REVIEW IF
 THIS CHANGE OCCURS.
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 FROM PLANS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING.
 ONE COPYOF OLD/VOIDED SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE.
  
 ** PLEASE SEE ANY OTHER POSSIBLE
 COMMENTS FROM OTHER REVIEWS WHICH MAY
 AFFECT ELECTRICAL PLANS.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2005-12-06 00:00:00IN FOR REVIEW.
 NOTES TO FOLLOW.

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2008-03-28 Cont ID  
Sent By adarroug Date 2008-03-28 Time 16:21 Rev Time 0.00
Received By adarroug Date 2008-03-28 Time 16:21 Sent To Z
Notes
2008-03-28 16:22:27TO "Z" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-06-25 Cont ID  
Sent By adarroug Date 2007-06-25 Time 16:55 Rev Time 0.00
Received By adarroug Date 2007-06-25 Time 16:55 Sent To M
Notes
2007-06-25 16:55:29TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-06-18 Cont ID  
Sent By adarroug Date 2007-06-18 Time 10:05 Rev Time 0.00
Received By adarroug Date 2007-06-18 Time 10:05 Sent To E
Notes
2007-06-18 10:06:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-06-18 Cont ID  
Sent By adarroug Date 2007-06-18 Time 10:03 Rev Time 0.00
Received By adarroug Date 2007-06-18 Time 10:03 Sent To M
Notes
2007-06-18 10:03:43TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-05-23 Cont ID  
Sent By adarroug Date 2007-05-23 Time 15:07 Rev Time 0.00
Received By adarroug Date 2007-05-23 Time 15:07 Sent To E
Notes
2007-05-23 15:08:13TO "E" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-03-30 Cont ID  
Sent By adarroug Date 2006-03-30 Time 16:12 Rev Time 0.00
Received By adarroug Date 2006-03-30 Time 16:12 Sent To B
Notes
2006-03-30 00:00:00TO "ALANGE" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-03-09 Cont ID  
Sent By adarroug Date 2006-03-09 Time 14:19 Rev Time 0.00
Received By adarroug Date 2006-03-09 Time 14:19 Sent To E
Notes
2006-03-09 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-01-28 Cont ID  
Sent By adarroug Date 2006-01-28 Time 15:38 Rev Time 0.00
Received By adarroug Date 2006-01-28 Time 15:38 Sent To E
Notes
2006-01-28 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-01-13 Cont ID  
Sent By adarroug Date 2006-01-13 Time 15:00 Rev Time 0.00
Received By adarroug Date 2006-01-13 Time 14:59 Sent To Z
Notes
2006-01-13 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-12-06 Cont ID  
Sent By adarroug Date 2005-12-06 Time 14:33 Rev Time 0.00
Received By adarroug Date 2005-12-06 Time 14:33 Sent To E
Notes
2005-12-06 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-12-27 Cont ID  
Sent By alange Date 2005-12-27 Time 09:54 Rev Time 0.00
Received By alange Date 2005-11-18 Time 15:40 Sent To  
Notes
2005-11-18 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-06-27 Cont ID  
Sent By tgordon Date 2007-06-27 Time 14:56 Rev Time 0.30
Received By tgordon Date 2007-06-27 Time 14:56 Sent To  
Notes
2007-06-27 14:58:25REVISION TO MECH. PLANS.
 *** PROVISO ***
 1) DUCTS IN THE GARAGE AND DUCTS PENETRATING THE WALLS
 OR CEILINGS SEPARATING THE DWELLING FROM THE GARAGE
 SHALL BE CONSTRUCTED OF A MINIMUM NO. 26 GAGE SHEET
 STEEL OR OTHER APPROVED
 MATERIAL AND SHALL HAVE NO OPENINGS INTO THE GARAGE.
 PER 2004 FBC/R 309.1.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-06-18 Cont ID  
Sent By tgordon Date 2007-06-18 Time 13:39 Rev Time 0.20
Received By tgordon Date 2007-06-18 Time 13:39 Sent To  
Notes
2007-06-18 13:42:56*** DENIED ***
 1) TWO COPY'S OF REVISED PLANS MUST BE SUBMITTED, ONLY
 ONE COPY WAS SUBMITTED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-01-31 Cont ID  
Sent By tgordon Date 2006-01-31 Time 10:02 Rev Time 0.35
Received By tgordon Date 2006-01-31 Time 10:02 Sent To P
Notes
2006-01-31 00:00:00*** PROVISO ***
 1) DRYER VENT TERMINATION TO BE 4 FT.
 FROM A/C CONDENSER UNITS.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-12-07 Cont ID  
Sent By tgordon Date 2005-12-07 Time 15:33 Rev Time 0.30
Received By tgordon Date 2005-12-07 Time 15:33 Sent To P
Notes
2005-12-07 00:00:00*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE FORM
 600A-04 (2004), PER 2004 FBC 13-600.0
 ABC .
 2) FLOOR PLANS A-1 DO NOT MATCH MECH.
 FLOOR PLAN.
 3) PLEASE CHECK RETURN AIR GRILL FOR
 AHU #1, 30X18 APPEARS 100 SQUARE INCHES
 TO SMALL.
 4) NEED TO FILE NOTICE OF COMMENCEMENT.
 5) DRYER VENT TERMINATION NEEDS TO BE 4
 FT. MIN. FROM A/C CONDENSER UNITS.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-02-02 Cont ID  
Sent By jleech Date 2006-02-02 Time 10:00 Rev Time 0.50
Received By jleech Date 2006-02-02 Time 10:00 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-12-12 Cont ID  
Sent By jleech Date 2005-12-12 Time 12:07 Rev Time 0.50
Received By jleech Date 2005-12-12 Time 12:07 Sent To B
Notes
2005-12-12 00:00:00DENIED;
 SHEET A-1 FLOOR PLAN DOESNOT MATCH RISER
 DIAGRAM.
 PLEASE HAVE PLUMBING RISER DIAGRAM ON A
 LETTER HEAD PAGE NOT TAPED TO PLAN.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 3 Status P Date 2008-03-31 Cont ID  
Sent By choops Date 2008-03-31 Time 12:54 Rev Time 0.00
Received By choops Date 2008-03-31 Time 12:54 Sent To PC
Notes
2008-03-31 12:53:11***APPROVED - LANDSCAPE PLAN SUBMITTAL (3/31/08)***

Review Stop Z ZONING
Rev No 2 Status P Date 2006-01-28 Cont ID  
Sent By mmclean Date 2006-01-28 Time 08:34 Rev Time 0.00
Received By mmclean Date 2006-01-28 Time 08:34 Sent To I
Notes
2006-01-28 00:00:00NOTE: STRUCTURE WILL BE CONSTRUCTED AT
 THE MAXIMUM HEIGHT OF 33FT SEE A-2
 (FRONT ELEVATION)
  
  
  
 NOTE: MUST PULL A SEPERATE PERMIT FOR
 POOL/DECK/SCREEN ENCLOSURE.
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2005-12-05 Cont ID  
Sent By mmclean Date 2005-12-05 Time 15:26 Rev Time 0.00
Received By mmclean Date 2005-12-05 Time 15:26 Sent To I
Notes
2005-12-05 00:00:00DENIED,
 1. THE STRUCTURE IS OVER THE HEIGHT
 REQUIREMNT, PLANS SHOWS 34+ FT.
 2. STRUCTURE MUST BE 33FT (WITH
 CHIMNEY).
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720