Plan Review Details - Permit 05110482
Plan Review Stops For Permit 05110482
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-07-06 Cont ID  
Sent By alange Date 2006-07-06 Time 10:26 Rev Time 2.00
Received By alange Date 2006-07-06 Time 08:57 Sent To  
Notes
2006-07-06 00:00:00DENIED
  
 ALL NEW COMMENTS:
  
 ** PROJECT DESCRIPTION ON APPLICATION
 DOES NOT DESCRIBE PROJECT IN DETAIL.
 THIS PROJECT IS A "CHANGE OF OCCUPANCY"
 TO AN EXISTING BUILDING. SEE THE
 FOLLOWING COMMENTS FOR REQUIRED
 INFORMATION NEEDED WITH A CHANGE OF
 OCCUPANCY.
  
 1. FBC 106.3.5 MINIMUM PLAN REVIEW
 CRITERIA FOR BUILDINGS.
 THE EXAMINATION OF THE DOCUMENTS BY THE
 BUILDING OFFICIAL SHALL INCLUDE THE
 FOLLOWING MINIMUM CRITERIA AND
 DOCUMENTS: A FLOOR PLAN; SITE PLAN;
 FOUNDATION PLAN; FLOOR/ROOF FRAMING PLAN
 OR TRUSS LAYOUT; AND ALL EXTERIOR
 ELEVATIONS.
  
 COMMERCIAL BUILDINGS:
  
 BUILDING
 1.SITE REQUIREMENTS:
  
 PARKING
 FIRE ACCESS
 VEHICLE LOADING
 DRIVING/TURNING RADIUS
 FIRE HYDRANT/WATER SUPPLY/POST INDICATOR
 VALVE (PIV)
 SET BACK/SEPARATION (ASSUMED PROPERTY
 LINES)
 LOCATION OF SPECIFIC TANKS, WATER LINES
 AND SEWER LINES
 2.OCCUPANCY GROUP AND SPECIAL
 OCCUPANCY REQUIREMENTS SHALL BE
 DETERMINED.
 3.MINIMUM TYPE OF CONSTRUCTION
 SHALL BE DETERMINED (SEE TABLE 503 ).
 4.FIRE-RESISTANT CONSTRUCTION
 REQUIREMENTS SHALL INCLUDE THE FOLLOWING
 COMPONENTS:
  
 FIRE-RESISTANT SEPARATIONS
 FIRE-RESISTANT PROTECTION FOR TYPE OF
 CONSTRUCTION
 PROTECTION OF OPENINGS AND PENETRATIONS
 OF RATED WALLS
 FIRE BLOCKING AND DRAFTSTOPPING AND
 CALCULATED FIRE RESISTANCE
 5.FIRE SUPPRESSION SYSTEMS SHALL
 INCLUDE:
  
 EARLY WARNING SMOKE EVACUATION SYSTEMS
 SCHEMATIC FIRE SPRINKLERS
 STANDPIPES
 PREENGINEERED SYSTEMS
 RISER DIAGRAM
 SAME AS ABOVE.
 6.LIFE SAFETY SYSTEMS SHALL BE
 DETERMINED AND SHALL INCLUDE THE
 FOLLOWING REQUIREMENTS:
  
 OCCUPANT LOAD AND EGRESS CAPACITIES
 EARLY WARNING
 SMOKE CONTROL
 STAIR PRESSURIZATION
 SYSTEMS SCHEMATIC
 7.OCCUPANCY LOAD/EGRESS
 REQUIREMENTS SHALL INCLUDE:
  
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 STAIRS CONSTRUCTION/GEOMETRY AND
 PROTECTION
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
 SPECIFIC OCCUPANCY REQUIREMENTS
 CONSTRUCTION REQUIREMENTS
 HORIZONTAL EXITS/EXIT PASSAGEWAYS
 8.STRUCTURAL REQUIREMENTS SHALL
 INCLUDE:
  
 SOIL CONDITIONS/ANALYSIS
 TERMITE PROTECTION
 DESIGN LOADS
 WIND REQUIREMENTS
 BUILDING ENVELOPE
 STRUCTURAL CALCULATIONS (IF REQUIRED)
 FOUNDATION
 WALL SYSTEMS
 FLOOR SYSTEMS
 ROOF SYSTEMS
 THRESHOLD INSPECTION PLAN
 STAIR SYSTEMS
 9.MATERIALS SHALL BE REVIEWED AND
 SHALL AT A MINIMUM INCLUDE THE
 FOLLOWING:
  
 WOOD
 STEEL
 ALUMINUM
 CONCRETE
 PLASTIC
 GLASS
 MASONRY
 GYPSUM BOARD AND PLASTER
 INSULATING (MECHANICAL)
 ROOFING
 INSULATION
 10.ACCESSIBILITY REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING:
  
 SITE REQUIREMENTS
 ACCESSIBLE ROUTE
 VERTICAL ACCESSIBILITY
 TOILET AND BATHING FACILITIES
 DRINKING FOUNTAINS
 EQUIPMENT
 SPECIAL OCCUPANCY REQUIREMENTS
 FAIR HOUSING REQUIREMENTS
 11.INTERIOR REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING:
  
 INTERIOR FINISHES (FLAME SPREAD/SMOKE
 DEVELOPMENT)
 LIGHT AND VENTILATION
 SANITATION
  
 3.PRODUCT APPROVALS REQUIRED FOR FLAT
 ROOF.ONLY UNDERLAYMENT SUBMITTED.
 SUBMIT AND ATTACH STATE PRODUCT
 APPROVAL.
  
 4.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 6.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 7.SHOW COMPLIANCE WITH 2004 EXISTING
 BUILDING CODE CHAPTER 8 CHANGE OF
 OCCUPANCY.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE . A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-12-05 Cont ID  
Sent By alange Date 2005-12-05 Time 15:04 Rev Time 1.50
Received By alange Date 2005-12-05 Time 14:16 Sent To  
Notes
2005-12-05 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.SUBMIT TWO ORIGONAL SIGNED AND
 SEALED SURVEYS. FS 472.025
  
 4.PLANS SUBMIITED AFTER OCTOBER 1,
 2005 SHALL BE DESIGNED TO THE 2004 FBC.
  
 5.SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR WINDOWS, IMPACT
 PROTECTION, DOORS AND STRAPS AND
 TIE-DOWNS AND ROOFING.
 ALL PRODUCT APPROVALS SUBMITTED SHALL
 HAVE THE FOLLOWING STATE PRODUCT
 APPROVAL ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6.SUBMIT 2 COPIES OF ENERGY CALCS.
  
 7.TRELLIS DETAIL;SHOWS 5/8" LAG BOLT
 GOING INTO A 2 X 10.NOT A RECOMMENDED
 INSTALLATION HOLE DRILL WILL ALMOST
 SPLIT THE 2 X 10 IN HALF.
 HU312 SIMPSON HANGER NOT THE RECOMMENDED
 HANGER FOR A 2 X 10 AND TAPCON FASTENING
 NOT A RECOMMENDED APPROVED INSTALLATION
 BY SIMPSON.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-06-30 Cont ID  
Sent By dpalmer Date 2006-06-30 Time 17:50 Rev Time 0.00
Received By dpalmer Date 2006-06-30 Time 17:39 Sent To  
Notes
2006-06-30 00:00:00********* UNSAT *************
  
 1) NOTE: PLEASE KNOW, THIS IS A CHANGE
 IN OCCUPANCY AND MUST SUBMIT COMPLETE
 PLANS FOR CODE COMPLIANCE UNDER THE 2004
 FBC, NFPA-70 2002, NFPA-72 2002 NFPA-101
 2003.
 ALL MUST BE BROUGHT UP TO CODE FOR
 ELECTRICAL INSTALLATION FOR COMMERCIAL
 OFFICE.
 PLEASE BE SURE TO SUBMIT COMPLETE PLANS
 ** PLEASE SEE THAT ORIG PLANS WILL BE
 REQUIRED FOR BOTH PALM BEACH COUNTY
 IMPACT FEE STAMPS FOR CHANGE IN USE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-12-09 Cont ID  
Sent By dpalmer Date 2005-12-09 Time 06:43 Rev Time 0.00
Received By dpalmer Date 2005-12-07 Time 20:57 Sent To  
Notes
2005-12-09 00:00:00*** UNSAT ***
  
 1)NOTE: PLEASE SEE NOC SUBMITTED IS
 EXPIRED PER FS 713.13(2)>
 PLEASE SEE BLDG REVIEW NOTES ALSO WITH
 RESPECT TO THIS.
  
 2)NOTE: PLEASE PROVIDE EGRESS LIGHTING
 EXITING NEW ADDTION.
 LS101 7.8
  
 3)NOTE: PLEASE NOTE, HOW ADDITIONAL
 RECEPTS WILL BE FED. CIRCUIT #?
  
 4)NOTE: PLEASE SEE NOTE ON PLANS
 MENTIONS TO VERIFY IF METER IS TO BE
 RELOCATED. THIS SHOULD BE VERIFIED AT
 THIS TIME AND NOTED ON PLANS IF NEEDED.
  
  
 ** PLEASE SEE ANY OTHER COMMENT FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW . IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-07-10 Cont ID  
Sent By mcarsill Date 2006-07-10 Time 14:14 Rev Time 0.00
Received By mcarsill Date 2006-07-10 Time 14:08 Sent To  
Notes
2006-07-10 00:00:001. PLEASE DECLARE NEW OCCUPANCY TYPE.
 PLEASE INDICATE EXISTING OCCUPANCY TYPE
 FOR THE STRUCTURE. A CHANGE OF USE IS
 SUSPECTED BY PLAN REVIEWERS.
  
 2. IF OCCUPANCY TYPE IS DECLARED TO BE A
 BUSINESS OCCUPANCY, THEN IT SHALL MEET
 THE CURRENT CODE REQUIREMENTS FOR
 BUSINESS OCCUPANCIES UNDER THE FLORIDA
 FIRE PREVENTION CODE AND THE FLORIDA
 BUILDING CODE.
  
 3. PLEASE ILLUSTRATE EXIT SIGNS AND
 EMERGENCY LIGHT FIXTURES EITHER NEW OR
 EXISTING.
  
 4. PLEASE PROVIDE DETAILS ON ANY
 PORTABLE FIRE EXTINGUISHING EQUIPMENT
 LIKE PORTABLE FIRE EXTINGUISHERS.
  
 5. IF BUILDING IS GOING TO BE USED FOR
 COMMERCIAL PURPOSES, THEN 6" NUMBERS
 WILL BE REQUIRED FOR THE ADDRESS
 INSTALLED ON THE PROPER ELEVATION.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709
2006-06-30 00:00:00CHANGE IN USE FROM SFR TO COMM OFFICE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-12-06 Cont ID  
Sent By mcarsill Date 2005-12-06 Time 14:42 Rev Time 0.00
Received By mcarsill Date 2005-12-06 Time 14:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-06-29 Cont ID  
Sent By adarroug Date 2006-06-29 Time 11:09 Rev Time 0.00
Received By adarroug Date 2006-06-29 Time 11:09 Sent To E
Notes
2006-06-29 00:00:00TO "COMM" BD#1

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-15 Cont ID  
Sent By adarroug Date 2006-06-15 Time 16:33 Rev Time 0.00
Received By adarroug Date 2006-06-15 Time 16:33 Sent To Z
Notes
2006-06-15 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-12-19 Cont ID  
Sent By adarroug Date 2005-12-12 Time 08:38 Rev Time 0.00
Received By adarroug Date 2005-11-18 Time 14:51 Sent To  
Notes
2005-12-02 00:00:00TO "COMM" BD#31
2005-11-18 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-08-08 Cont ID  
Sent By pkrauss Date 2006-08-08 Time 14:37 Rev Time 0.00
Received By pkrauss Date 2006-08-08 Time 14:37 Sent To  
Notes
2006-08-08 00:00:001.PLEASE PROVIDE ENERGY CALCULATIONS
 IS ACCORDANCE WITH 2004 FBC CHAPTER 13
 SUB-CHAPTER 13-4.FORM 600C IS TO BE
 SUBMITTED FOR RESIDENTIAL ONLY.PLANS
 INDICATE A CHANGE IN OCCUPANCY OR USE.
 THIS IS NOW CONSIDERED A COMMERCIAL
 BUILDING AND MUST COMPLY WITH THE
 REQUIREMENTS FOR A BUSINESS OCCUPANCY.
 SEE ALSO 2004 FBC CHAPTER 13 SUB-CHAPTER
 13-101-1.3.
  
 NO MECHANICAL CONTRACTOR INDICATED OR
 PLANS SUBMITTED WITH BUILDING PERMIT
 APPLICATION.PLEASE PROVIDE MECHANICAL
 PLANS AND EQUIPMENT WITH MECHANICAL
 PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
2006-06-30 00:00:00CHANGE IN USE FROM SFR TO COMM OFFICE.

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-08-01 Cont ID  
Sent By kstevens Date 2006-08-01 Time 13:23 Rev Time 0.00
Received By kstevens Date 2006-08-01 Time 13:23 Sent To  
Notes
2006-08-01 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 CHANGE OF OCCUPANCY. SHALL BRING UP TO
 CODE FOR BUSINESS OCCUPANCY.
  
 1. SUBMIT CALCULATIONS FOR MINIMUM
 FIXTURE REQUIREMENTS PER TABLES 1004.1.2
 AND 403.1.
  
 2. SHOW THE LOCATION FOR ALL REQUIRED
 FIXTURES AND ALL EXISTING FIXTURES.
 TABLES 1004.1.2 & 403.1.
  
 3. SUBMIT A DETAIL FOR THE REQUIRED
 FIXTURES SHOWING COMPLIANCE WITH
 SECTIONS 11-4.15, 11-4.16, 11-4.19 AND
 ALL SUBSECTIONS. IF THERE ARE ANY SINKS
 SUBMIT A DETAIL SHOWING COMPLIANCE WITH
 11-4.24 AND ALL SUBSECTIONS.
  
 4. AN RPZV BACKFLOW IS REQUIRE ON THE
 WATER SERVICE TO THE BUILDING. SECTION
 608.
  
 5. IF ANY PLUMBING PIPING WILL BE DONE
 SUBMIT SANITARY AND WATER RISER DIARAMS.
 SECTION 106.3.5.1.3
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
2006-06-30 00:00:00CHANGE IN USE FROM SFR TO COMM OFFICE.

Review Stop Z ZONING
Rev No 2 Status F Date 2006-06-28 Cont ID  
Sent By eschneid Date 2006-06-28 Time 11:10 Rev Time 0.00
Received By eschneid Date 2006-06-28 Time 11:10 Sent To  
Notes
2006-06-28 00:00:001) THE REQUIRED DISABLED PARKING SPACE
 AS SHOWN IS UNABLE TO BE USED AS A
 PARKING SPACE WITHOUT DRIVING ACROSS AN
 ADJACENT LOT.
  
 2) THE SITE PLANS DO NOT ALL SHOW THE
 NEW DISABLED SPACE.
  
 3) THE REMOVAL OF THE SHED WILL REQUIRE
 HISTORIC PRESERVATION DIVISION APPROVAL.
  
 4) THE SURVEY AND SITE PLAN LOT
 DIMENSIONS DO NOT MATCH THE DIMENSIONS
 AS SHOWN ON THE PROPERTY APPRAISOR'S
 SITE.
  
 5) A LANDSCAPE PLAN IS REQUIRED.IT
 SHALL VERIFY THAT THE SITE, INCLUDING
 THE AREA AROUND THE NEW PARKING SPACE
 MEETS THE COMMERCIAL LANDSCPACE
 STANDARDS.
  
 CONTACT ERIC SCHNEIDER (561) 822-1435.
 6/28/06 ROUTED TO INCOMING FOR FURTHER
 PROCESSING
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2005-12-12 Cont ID  
Sent By lshapiro Date 2005-12-12 Time 17:44 Rev Time 0.00
Received By lshapiro Date 2005-12-12 Time 17:44 Sent To  
Notes
2005-12-15 00:00:0012/15/05 GAVE TO INCOMING FOR THE OTHER
 TRADES.
2005-12-12 00:00:001. ANY RESIDENTIAL STRUCTURE CONVERTED
 IN WHOLE OR IN PART TO A PROFESSIONAL
 OFFICE SHALL PROVIDE PARKING AS REQUIRED
 IN ARTICLE XIV OF THIS CHAPTER (SECTION
 94-148).
 2. USE REQUIRES PARKING PER CODE
 REQUIREMENTS, INCLUDE SQUARE FOOTAGE OF
 BUILDING AND SHOW THE PARKING REQUIRED
 AND PROVIDED.IN ADDITION, TO CODE
 REQUIREMENT STANDARDS FOR USE.
 3.SHOW ADJACENT PROPERTY AND SETBACK
 REQUIREMENTS TO SUBJECT STRUCTURE AND
 ANY ADDITIONAL REQUIREMENTS AS SHOWN ON
 CMUD TYPE III CODE SECTION.