Plan Review Details - Permit 05110474
| Plan Review Stops For Permit 05110474 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2005-11-30 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2005-11-30 |
Time |
08:51 |
Rev Time |
0.45 |
| Received By |
jleahy |
Date |
2005-11-30 |
Time |
08:50 |
Sent To |
FIRE |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2005-12-07 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2005-12-07 |
Time |
10:38 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2005-12-07 |
Time |
10:38 |
Sent To |
|
|
| Notes |
| 2005-12-07 00:00:00 | 1. REQUIRED SMOKE MANAGEMENT SYSTEM IS | | | TO BE CONNECTED TO EMERGENCY POWER. | | | | | | 2. SYSTEM IS TO CONFORM TO NFPA 92B AND | | | NFPA 101, 2003 EDITION SECTION 8.6.7. | | | | | | 3. A TIME EGRESS ANALYSIS REPORT IS TO | | | BE SUBMITTED TO THIS OFFICE. | | | | | | 4. WHEN COMPLETED THE SYSTEM IS TO BE | | | FULLY TESTED WITH MECHANICAL AND FIRE | | | RESCUE DEPARTMENTS. | | | | | | 5. SOME SMOKE BOMBS WILL BE NEEDED TO | | | PERFORM THE TEST TO ENSURE PROPER | | | OPERATION. | | | | | | 6. ATRIUM SMOKE SYSTEM SHALL BE | | | INITIATED BY THE FIRE ALARM SYSTEM OR BY | | | THE FIREFIGHTERS SMOKE PANEL. HOA | | | SWITCHES ONLY WILL NOT BE PERMITTED TO | | | BE USED. A GRAPHIC REPRESENTATION OF THE | | | ATRIUM SHALL BE SHOWN ON THIS PANEL. | | | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | | OFFICER | | | 804-4709 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-12-07 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2005-12-07 |
Time |
14:37 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2005-11-18 |
Time |
11:20 |
Sent To |
E |
|
| Notes |
| 2005-11-18 00:00:00 | TO "JLEAHY" DESK |
|
|
|