| 2005-11-15 00:00:00 | DENIED |
| | |
| | 1) THE FLORIDA PRODUCT APPROVAL COVER |
| | SHEET FOR THE FIRESTONE MODIFIED ROOFING |
| | WAS NOT SUBMITTED. |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | 2) THE SBS SYSTEM THAT IS SPECIFIED IN |
| | THE FIRESTONE NOA HAS A MAXIMUM DESIGN |
| | PRESSURE OF -45 PSF WITH NO INCREASE |
| | ALLOWED FOR ENHANCED FASTENING PER |
| | LIMITATION #9. THIS DOES NOT MEET THE |
| | REQUIRED UPLIFT PRESSURES AT THE ROOF |
| | CORNERS OR EDGES (ZONES 2 & 3) FOR |
| | EXPOSURE B AND 140 MPH WIND SPEED. |
| | |
| | 3) THE MAXIMUM DESIGN PRESSURE SPECIFIED |
| | IN THE MULE-HIDE PRODUCT APPROVAL OF -45 |
| | PSF WITH LIMITATION #9 DOES NOT MEET THE |
| | REQUIRED UPLIFT PRESSURE. |
| | |
| | 4) THE FLORIDA PRODUCT APPROVAL FOR THE |
| | MULE-HIDE PRODUCT HAS A STATUS OF |
| | VALIDATED AND HAS NOT YET BEEN APPROVED |
| | BY THE STATE. |
| | |
| | 5) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |