Plan Review Details - Permit 05110469
Plan Review Stops For Permit 05110469
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-12-20 Cont ID  
Sent By jwitmer Date 2005-12-20 Time 07:01 Rev Time 0.75
Received By jwitmer Date 2005-12-20 Time 07:01 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-12-01 Cont ID  
Sent By jwitmer Date 2005-12-01 Time 07:05 Rev Time 0.55
Received By jwitmer Date 2005-12-01 Time 07:02 Sent To PC
Notes
2005-12-01 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05110469
 ADD: 515 N FLAGLER # 300
 CONT: SUFFOLK
 TEL: (561)832-1616
 FL BLD CODE= 200$ FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
  
 1)110.2 REQUIREMENTS OF THE 2004 FOR
 C.O. AND FOR RECORD KEEPING PURPOSES
 REQUIRES :
 1A) THE EDITION OF THE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 1B) THE USE & OCCUPANCY IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 1C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6.
 1D) THE DESIGN OCCUPANT LOAD.
 1E) IF AN AUTOMATIC FIRE SPREINKLER
 SYSTEM IS PROVIDED , WHETHER THE
 SPRINKLER SYSTEM IS REQUIRED.
 1F) ANY SPECIAL STIPULATIONS &
 CONDITIONS OF THE BUILDING PERMIT.
  
 2) CORRECT THE BUILDING TYPE AND
 REFRENCE TO TABLE 600. SEE TABLE 601
 FIRE RESITANCE REQUIREMENTS FOR BUILDING
 ELEMENTS.
  
 3) TI-1 DOOR BUCKS TO BE
 603.1 ALLOWABLE MATERIALS.
 COMBUSTIBLE MATERIALS SHALL BE PERMITTED
 IN BUILDINGS OF TYPE I OR II
 CONSTRUCTION IN THE FOLLOWING
 APPLICATIONS AND IN ACCORDANCE WITH
 SECTIONS 603.1.1 THROUGH 603.1.3 :
 1.FIRE-RETARDANT-TREATED WOOD SHALL
 BE PERMITTED IN:
 1.1.NONBEARING PARTITIONS WHERE THE
 REQUIRED FIRE-RESISTANCE RATING IS 2
 HOURS OR LESS.
 1.2.NONBEARING EXTERIOR WALLS WHERE
 NO FIRE RATING IS REQUIRED.
 1.3.ROOF CONSTRUCTION AS PERMITTED
 IN TABLE 601 , NOTE C, ITEM 3.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-11-28 Cont ID  
Sent By jleahy Date 2005-11-28 Time 07:09 Rev Time 0.30
Received By jleahy Date 2005-11-28 Time 07:09 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-11-28 Cont ID  
Sent By nmccray Date 2005-11-28 Time 10:35 Rev Time 0.00
Received By nmccray Date 2005-11-28 Time 10:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-02-22 Cont ID  
Sent By adarroug Date 2006-02-22 Time 16:15 Rev Time 0.00
Received By adarroug Date 2006-02-22 Time 16:15 Sent To M
Notes
2006-02-22 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-12-14 Cont ID  
Sent By adarroug Date 2005-12-14 Time 16:16 Rev Time 0.00
Received By adarroug Date 2005-12-14 Time 16:16 Sent To B
Notes
2005-12-14 00:00:00TO "JWITMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date 2005-12-01 Cont ID  
Sent By jwitmer Date 2005-12-01 Time 07:02 Rev Time 0.00
Received By jwitmer Date 2005-11-18 Time 16:07 Sent To  
Notes
2005-11-18 00:00:00TO "BOB"#14

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-02-23 Cont ID  
Sent By hmoser Date 2006-02-23 Time 16:50 Rev Time 0.00
Received By hmoser Date 2006-02-23 Time 16:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-11-28 Cont ID  
Sent By hmoser Date 2005-11-28 Time 15:51 Rev Time  
Received By hmoser Date   Time   Sent To  
Notes
2005-11-28 00:00:00PASS PRIVISO
 PLEASE REFER TO SECTION 606.2.1 2004
 FBC(M)SUPPLY AIR SYSTEM.SMOKE DETECTORS.
  
 AND SECTION 606.4.1 SUPERVISION 2004
 FBC(M).
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-11-29 Cont ID  
Sent By jleech Date 2005-11-29 Time 16:46 Rev Time 0.33
Received By jleech Date 2005-11-29 Time 16:46 Sent To  
Notes
2005-11-29 00:00:00NO PLUMBING SHOWN ON DRAWINGS.