Plan Review Details - Permit 05110448
Plan Review Stops For Permit 05110448
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-11-28 Cont ID  
Sent By lmartine Date 2006-11-28 Time 16:44 Rev Time 0.00
Received By lmartine Date 2006-11-28 Time 16:44 Sent To  
Notes
2006-11-28 16:45:11WINDOW ANCHOR DETAIL ,OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-05-10 Cont ID  
Sent By lmartine Date 2006-05-10 Time 15:50 Rev Time 0.00
Received By lmartine Date 2006-05-10 Time 15:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-04-10 Cont ID  
Sent By lmartine Date 2006-04-10 Time 13:08 Rev Time 0.00
Received By lmartine Date 2006-04-10 Time 13:08 Sent To  
Notes
2006-04-10 00:00:00 
  
  
 BUILDING COMMENTS
 -------- --------
  
  
 SHEET S-2 NOTE #11 REFERENCES WRONG
 CODE.
  
 SHEET S-3 ATTIC VENTILATION CODE
 REFERENCE SHALL READ "FBC 2004 R-806.2.
  
 DESIGN LOADS SHALL BE CORRECTED TO FBC
 1609 EXP. B OR FBC R-301.2 EXP. B.
  
 ENGINEER OF RECORD SHALL MAKE ALL
 CHANGES TO HIS PLAN PERSONALLY.
  
  
  
  
  
  
  
  
 L.MARTINEZ
 561-805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-02-17 Cont ID  
Sent By alange Date 2006-02-17 Time 09:46 Rev Time 1.00
Received By alange Date 2006-02-17 Time 09:46 Sent To  
Notes
2006-02-17 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.ENERGY CALCS SHALL BE TO THE 2004
 FBC AND ALSO NEED TO BE SIGNED BY THE
 OWNER/AGENT.
  
 3.ALL PLANS SUBMITTED AFTER OCTOBER,
 1, 2004 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE.
  
 4.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMMENDMENT TO FBC 106.3.3
  
 5.PRODUCT APPROVALS SUBMITTTED ARE
 INCOMPLETE.SUBMIT TWO COMPETE SETS OF
 THE FOLLOWING.
 PRODUCT APPROVAL WITH QUALITY ASSURANCE
 AND THE FOLLOWING STATE PRODUCT
 APPROVALS ATTACHED TO EACH.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6.SUBMIT PRODUCT APPROVALS FOR LINTELS
 WITH THE ABOVE INFORMATION LISTED IN #5.
  
 7.SHOW SIZE AND LOCATION OF ATTIC
 ACCESS.R-807.1
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-11-28 Cont ID  
Sent By btrobaug Date 2006-11-28 Time 12:47 Rev Time 0.55
Received By btrobaug Date 2006-11-28 Time 12:17 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-05-05 Cont ID  
Sent By jleahy Date 2006-05-05 Time 17:33 Rev Time 0.45
Received By jleahy Date 2006-05-05 Time 16:09 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-04-07 Cont ID  
Sent By jleahy Date 2006-04-07 Time 06:48 Rev Time 0.30
Received By jleahy Date 2006-04-07 Time 06:47 Sent To  
Notes
2006-04-07 00:00:00NEW SHEET NOT SEAL BY G BUCKJL4/6/6

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-01-09 Cont ID  
Sent By btrobaug Date 2006-01-09 Time 11:03 Rev Time 0.50
Received By btrobaug Date 2006-01-09 Time 07:42 Sent To P
Notes
2006-01-09 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE LOAD CALCULATIION MUST BE PER 220
 SECTION II OR 220 SECTION III. PLEASE
 RESUBMIT AND INDICATE THE ARTICLE BEING
 USED, FOR EXAMPLE 220.30. SEE 215.5.
  
 2} RECEPTACLES MUST BE ADDED TO THE NEW
 BEDROOM TO COMPLY WITH 210.52(A)(1), SEE
 REVIEWED SET..
  
 3} A SMOKE DETECTOR MUST BE LOCATED IN
 THE BEDROOM PER 313.1 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-04-04 Cont ID  
Sent By adarroug Date 2006-04-04 Time 08:39 Rev Time 0.00
Received By adarroug Date 2006-04-04 Time 08:39 Sent To E
Notes
2006-04-04 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-03-17 Cont ID  
Sent By adarroug Date 2006-03-17 Time 14:22 Rev Time 0.00
Received By adarroug Date 2006-03-17 Time 14:22 Sent To Z
Notes
2006-03-17 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-01-05 Cont ID  
Sent By adarroug Date 2006-01-05 Time 09:51 Rev Time 0.00
Received By adarroug Date 2006-01-05 Time 09:51 Sent To E
Notes
2006-01-05 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-02-17 Cont ID  
Sent By alange Date 2006-02-17 Time 09:51 Rev Time 0.00
Received By alange Date 2005-12-13 Time 18:32 Sent To  
Notes
2005-12-13 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-05-05 Cont ID  
Sent By tgordon Date 2006-05-05 Time 09:57 Rev Time 0.35
Received By tgordon Date 2006-05-05 Time 09:57 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-04-06 Cont ID  
Sent By tgordon Date 2006-04-06 Time 14:13 Rev Time 0.30
Received By tgordon Date 2006-04-06 Time 14:13 Sent To  
Notes
2006-04-06 00:00:00*** DENIED ***
 1) ENERGY CALCULATIONS ARE CALLING FOR A
 5 KW HEATER, AND THE ELECTRICAL PLANS
 ARE CALLING FOR A 10 KW HEATER. THE
 PLANS CAN NOT CALL FOR MORE THAN THE
 ENERGY CAL'S.,PLEASE CORRECT.
  
 2) PLEASE SHOW ELECTRICAL HEATER SIZE ON
 MECHANICAL PLANS.
  
 3) PLEASE SHOW THE TERMINATION POINT OF
 THE CLOTHES DRYER VENT ON THE MECHANICAL
 PLANS. PLEASE SEE 2004 FBC/M 502.7.3.6 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-01-11 Cont ID  
Sent By tgordon Date 2006-01-11 Time 14:50 Rev Time 0.30
Received By tgordon Date 2006-01-11 Time 14:50 Sent To B
Notes
2006-01-11 00:00:00*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE ON
 FORM 600A-04 (2004) AND SIGNED BY
 OWNER/AGENT,PER FBC 13-600.3.A .
  
 2)NEED A/C EQUIPMENT LISTING
 (MANUFACTURE NAME, MODEL NO., SEER,
 TOTAL BTU'S., SENSIBLE BTU'S., ECT.) ON
 MECHANICAL PLANS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-05-05 Cont ID  
Sent By jleech Date 2006-05-05 Time 10:20 Rev Time 0.00
Received By jleech Date 2006-05-05 Time 10:20 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-04-07 Cont ID  
Sent By jleech Date 2006-04-07 Time 07:59 Rev Time 0.00
Received By jleech Date 2006-04-07 Time 07:58 Sent To B
Notes
2006-04-07 00:00:00DENIED;
 1.PLANS ARE NOT SEALED OR SIGNED.
 2.PLUMBING NOTES REMOVE NOTE ABOUT SAFE
 WASTE OF CONDENSATE. CONDENSATE DISPOSAL
 IS NOT PERMITED TO DUMP INTO CITY SEWER.
 SEE FBC-2004 MECHANICAL SEC. 307 FOR
 APPROVED DISPOSAL .
 3.RISER DIAGRAM SHOWER NOT VENTED AS
 SHOWN, ADD TRAP TO SHOWER.
 4.AUTOMATIC CLOTHES WASHER DRAIN SHALL
 CONNECT TO A 3" BRANCH DRAIN. SEC. 406.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-01-11 Cont ID  
Sent By jleech Date 2006-01-11 Time 09:27 Rev Time 0.75
Received By jleech Date 2006-01-11 Time 09:27 Sent To M
Notes
2006-01-11 00:00:00DENIED;
 1.PLUMBING NOTES; ALLREFORENCE TO THE
 FBC PLUMBING SHOULD BE 2004 NOT 2001.
 2.AUTOMATIC CLOTHES WASHER TO COMPLY
 WITH FBC-2004 PLUMBING SEC. 406.3.
 PLEASE SHOW ON PLANS.
 3.SHOW SANITARY RISER DIAGRAM FOR KIT.
 W/M AND L.T. HOW WILL THEY TIE INTO
 BUILDING DRAIN? SHOW PIPE SIZE, VENT
 SIZE AND CLEANOUTS WHERE REQUIRED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  
  
  
  
  
  
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2006-03-31 Cont ID  
Sent By mmclean Date 2006-03-31 Time 17:22 Rev Time 0.00
Received By mmclean Date 2006-03-31 Time 17:21 Sent To I
Notes
2006-03-31 00:00:00NOTE: NEW GARAGE ADDITION, REMODEL
 CARPORT INTO A BEDROOM & BATHROOM,
 DRIVEWAY (CONCRETE/PAVERS/ASPHALT ONLY)

Review Stop Z ZONING
Rev No 1 Status F Date 2006-01-04 Cont ID  
Sent By mmclean Date 2006-01-04 Time 18:58 Rev Time 0.00
Received By mmclean Date 2006-01-04 Time 18:58 Sent To I
Notes
2006-01-04 00:00:00DENIED,
 1. SITEPLANS PROVIDED DOES NOT PROVIDE
 INFORMATION NEEDED TO COMPLETE A ZONING
 REVIEW.
 2. SITEPLANS MUST PROVIDE THE COMPLETE
 DIMENSION OF LOT AND ADDRESS OF
 PROPERTY.
 3. MAY USE THE SURVEY, SHOWING THE
 PROPOSED DRIVEWAY (CLEARLY) WITH
 DIMENSION (AS NOTED ON SITEPLAN) AND
 NOTE THAT PEBBLE ROCK IS NOT ALLOWED,
 MUST BE A NON-SMOOTH DUSTING SURFACE
 (CONCRETE/ASPHALT/PAVERS).
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720