Plan Review Details - Permit 05110446
Plan Review Stops For Permit 05110446
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-12-28 Cont ID  
Sent By amorse Date 2005-12-28 Time 16:09 Rev Time 0.33
Received By amorse Date 2005-12-28 Time 16:09 Sent To PC
Notes
2005-12-30 00:00:00?PROVISO?
  
 POOL BARRIER REQUIREMENTS PER 424.2.17 &
 R4101.17
 SHALL BE IN PLACE AT POOL FINAL
 INSPECTION PER
 R4101.19

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-12-09 Cont ID  
Sent By btrobaug Date 2005-12-09 Time 12:44 Rev Time 0.33
Received By btrobaug Date 2005-12-09 Time 12:41 Sent To P
Notes
2005-12-09 00:00:00PLEASE SUBMIT DETAILS FOR THE PANEL
 SHOWN ON THE SCHEMATIC, FEEDER AND CONDU
 IT SIZE AND TYPE, PANEL RATING AND OCP,
 PANEL SCHEDULE AND COMPUTED LOAD, ETC.
 IF AN ELECTRIC HEATER IS TO BE INSTALLED
 PLEASE SUBMIT CALCULATIONS FOR THE MAIN
 SERVICE.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-11-23 Cont ID  
Sent By adarroug Date 2005-11-23 Time 15:43 Rev Time 0.00
Received By adarroug Date 2005-11-23 Time 15:43 Sent To E
Notes
2005-11-23 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2005-11-17 Time   Rev Time 0.00
Received By adarroug Date 2005-11-17 Time 09:18 Sent To  
Notes
2005-11-17 00:00:00TO "Z" BOX

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-12-15 Cont ID  
Sent By mperson Date 2005-12-15 Time 13:06 Rev Time 1.25
Received By mperson Date 2005-12-15 Time 13:06 Sent To B
Notes
2005-12-15 00:00:00DENIED
 REFERENCE:FBC-2004 424.2 SWIMMING POOLS
  
 1) COMPLY WITH FBC-2004 SEC 424.2
 PRIVATE SWIMMING POOLS.(ADD TO NOTES)
 2) FBC-2004 424.2.7.2 PUMPS AND
 EQUIPMENT SHALL BE MOUNTED ON A
 SUBSTANTIAL BASE IN A MANNER THAT WILL
 ELIMINATE STRAIN ON PIPING.SLAB SHALL
 BE A NOMINAL 4" THICK. (DETAIL)(ADD TO
 NOTES)
 3)FBC-2004 424.2.9 WATER SUPPLY,LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON
 WATER SERVICE.(ADD TO NOTES)
 4) FBC-2004 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 5) FBC-2004 424.2.13.2 JOINTS AND
 CONNECTIONS,FBC PLMG. SEC. 605.21,
 PURPLE PRIMER REQUIRED ON PVC PIPING.
 (ADD TO NOTES)
  
 REVIEW BY MIKE PERSON
 (561)805-6730
 FAX (561)653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2005-11-22 Cont ID  
Sent By mmclean Date 2005-11-22 Time 16:54 Rev Time 0.00
Received By mmclean Date 2005-11-22 Time 16:54 Sent To I
Notes
***NONE***