Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-11-28 Cont ID  
Sent By tgordon Date 2005-11-28 Time 11:36 Rev Time 0.20
Received By tgordon Date 2005-11-28 Time 11:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-11-18 Cont ID  
Sent By tgordon Date 2005-11-18 Time 14:44 Rev Time 0.30
Received By tgordon Date 2005-11-18 Time 14:44 Sent To  
Notes
2005-11-18 00:00:00*** DENIED ***
 1) RETURN AIR TRANSFER DUCTS IN BEDROOMS
 NEED TO BE 7" FLEX. PER FBC/R M1602.44 .
 2)RETURN AIR GRILL AT AIR HANDLER NEEDS
 TO BE SIZED.
 3) PLEASE PUT JOB LOCATION ON PLANS.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.