| 2005-11-30 00:00:00 | DENIED |
| | |
| | |
| | |
| | 1) OWNER OR OWNERS AGENT SHALL SUBMIT A |
| | NOTICE OF COMMENCEMENT BEFORE A PERMIT |
| | CAN BE ISSUED. |
| | |
| | 2) THE NOA'S FOR PGT INDUSTRIES |
| | HORIZONTAL SLIDERS ARE INCOMPLETE DUE TO |
| | OFF CENTER PHOTOCOPIES. RE-SUBMIT CLEAR |
| | COPIES |
| | |
| | 3) WHERE DOORS AND WINDOWS ARE ATTACHED |
| | TO WOOD BUCKS AND THE ATTACHMENT METHOD |
| | IS NOT SPECIFIED, THE ANCHORING |
| | PERFOMANCE SHALL BE EQUAL TO OR GREATER |
| | THAN THAT OF THE WINDOW OR DOOR |
| | ASSEMBLIES ATTACHMENT AS DEMONSTRATED BY |
| | ACCEPTED ENGINEERING PRACTICES. R613.6.1 |
| | FBC. RES |
| | |
| | 4) SPECIFY THE PANEL GAUGE, MOUNTING |
| | METHOD AND CONNECTION TYPE IN THE STORM |
| | PANEL NOA'S |
| | |
| | 5) THE SINGLE HUNG WINDOWS SPECIFIED DO |
| | NOT MEET THE EMERGENCY EGRESS FOR |
| | MINIMUM HEIGHT OF CLEAR OPENING AS |
| | SPECIFIED IN R310.1.2 OF FBC. RES. IF |
| | USED IN A BEDROOM |
| | |
| | 6) PROVIDE A FLOOR PLAN FOR THE LOCATION |
| | OF THE BEDROOM WINDOWS THAT SHALL MEET |
| | THE EMERGENCY EGRESS REQUIREMENTS AS |
| | ESCAPE AND RESCUE OPENINGS. |
| | |
| | 7) WINDOW OPENINGS THAT REQUIRE |
| | STRUCTURAL CHANGES TO THE BUILDING WILL |
| | NEED DRAWINGS TO BE SUBMITTED THAT ARE |
| | SIGNED AND SEALED BY A DESIGN |
| | PROFFESIONAL. |
| | |
| | 8) NOTE THAT THE JELD-WEN DOOR SPECIFIED |
| | IN THE PRODUCT APPROVAL CAN HAVE |
| | OPTIONAL SIDE LITES ATTACHED. IF USED |
| | IMPACT PROTECTION IS REQUIRED. |
| | |
| | |
| | BLDG PLAN REVIEW |
| | ADRIAN MORSE |
| | (561)805-6716 |