Plan Review Details - Permit 05110390
Plan Review Stops For Permit 05110390
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-05-03 Cont ID  
Sent By lursu Date 2006-05-03 Time 16:13 Rev Time 0.00
Received By lursu Date 2006-05-03 Time 16:13 Sent To  
Notes
2006-05-03 00:00:00JOB TO BE DONE AT THE FS#6 ,ADDRESS HAS
 BEEN CORRECTED :3033 CUMBERLAND DR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-05-10 Cont ID  
Sent By lmartine Date 2006-05-10 Time 10:49 Rev Time 0.00
Received By lmartine Date 2006-05-10 Time 10:49 Sent To  
Notes
2006-04-26 00:00:00NEEDS BUIDLING REVIEW FOR NEW SLAB/ ETC

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-02-12 Cont ID  
Sent By lmartine Date 2006-02-12 Time 13:29 Rev Time 0.00
Received By lmartine Date 2006-02-12 Time 13:29 Sent To P
Notes
2006-02-12 00:00:00 
  
 ADDRESS AND PLANS DON'T MATCH, CLARIFY
 IF GENERATOR WILL BE INSTALLED AT 500
 N.DIXIE OR CUMBERLAND DR.
  
 COMPLY WITH THE MECHANICAL REVIEWERS
 NOTES AS TO FOUNDATION AND TIE-DOWN
 REQUIREMENTS.
  
  
  
 L.MARTINEZ
 805-6710

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-11-17 Cont ID  
Sent By dpalmer Date 2006-11-17 Time 12:01 Rev Time 0.00
Received By dpalmer Date 2006-11-17 Time 11:14 Sent To PC
Notes
2006-11-17 12:03:31REVISED CONDUCTORS TO PARALLEL 3/0'S.
  
 REDLINED 230.76/230.79 AND 110.27 FOR THE PROPOSED SE
 RATED ATS.
 THE MODELS AS SHOWN IN SPECS DO NOT INDICATE SPECIFIC
 UNIT.
 MUST MEET CODES ABOVE.
  
  
 ** PLACED NOTES ON SHEETS AS CONTRACTOR DID NOT PRINT
 AND SIGN NAME. NEEDS BEFORE PICKING UP.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-05-18 Cont ID  
Sent By dpalmer Date 2006-05-18 Time 12:23 Rev Time 0.00
Received By dpalmer Date 2006-05-18 Time 12:23 Sent To PC
Notes
2006-05-18 00:00:00***** PROVSIO ********
  
  
 ** NOTES REDLINED, THE SERVICE ENT RATED
 ATS, MUST MEET 230.76,230.76,
 225.31-225.39
 THIS WILL BE VEERIFIED BY THIS OFFICE.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-04-26 Cont ID  
Sent By dpalmer Date 2006-04-26 Time 19:55 Rev Time 0.00
Received By dpalmer Date 2006-04-26 Time 19:52 Sent To  
Notes
2006-04-26 00:00:00**********UNSAT 2ND REVIEW **********
  
 1) NOTE: PLEASE SEE PLANS ARE STILL
 BEING SUBMITTED INDICATING FIRE STATION
 #6 WHICH IS LOCATED ON CUMBERLAND DR,
 YET , PERMIT APPLICATION AND RESUB
 SHEETS STILL INDICATES FIRE STATION #1,
 WHICH IS LOCATED AT 500 N. DIXIE HWY.
 PLEASE CORRELATE AND DECIDE WHICH
 LOCATION THIS INSTALLATION IS TAKING
 PLACE AND ADJUST ALL PAPER WORK
 ACCORDINGLY.
  
 2) NOTE: PLEASE SEE NOTES FROM PREVIOUS
 REVIEW, PLEASE SEE NOW TWO DIFFERENT
 ELECTRICAL RISERS ARE BEING SUBMITTED
 FOR REVIEW.
 PLEASE SEE RISERS SUBMITTED DO NOT MEET
 MIN NEC CODE COMPLIANCE FOR
 INSTALLATIONS.
 PLEASE SEE MANY COMMENTS FROM PREVIOUS
 REVIEW STILL REMAIN AND NEW COMMENTS AS
 INFORMATION ON RISERS ARE NOT COMPLETE
 OR DO NOT CORRELATE.
 215.5
  
 3) NOTE: PLEASE SEE PLANS SUBMITTED DO
 NOT CONTAIN THE PRINTED NAME AND THE
 SIGNATURE OF THE "DESIGN
 PROFESSIONAL"/CONTRACTOR WHO IS TAKING
 RESPONSIBILITY FOR PLANS AND DESIGN.
 FBC 104.2.1 ADMINISTRATIVE SECTION AS
 ADMENDED BY THE CITY OF WEST PALM BEACH.
  
 4) NOTE: PLEASE SEE RESPONSE LETTER
 MENTIONS GEN WILL BE SEPARATELY DERIVED
 , HOWEVER PLANS HAVE NOT BEEN REVISED TO
 MEET CODE COMPLIANCE FOR THIS AND THE
 SPECS FOR THE ATS DO NOT MENTIONS
 4-POLE.
 250.30,215.5
  
 5) NOTE: PLEASE SEE 250.6,250.24B AND
 250.122 FOR MISSING EQUIPMENT GROUNDS.
  
 6) NOTE: PLEASE SEE RISER(S) ARE MISSING
 CONDUCTORS, OCP AND INFORMATION
 REQUESTED FOR ITEMS ON FIRST REVIEW.\
 PLEASE SEE ONE SHEET MENTIONS
 DISCONNECT, THE OTHER DISTRIBUTION?
 215.5
  
 7) NOTE: PLEASE SEE FLORIDA STATUES
 553.80(2)(B) WITH RESPECT TO THE "DESIGN
 PROFESSIONAL" AND REPEAT COMMENTS FOR
 CODE COMPLIANCE.
 PLEASE KNOW, DUE TO THE EXTREME TIME
 SENSATIVE NATURE OF THIS PROJECT IT IS
 STRONGLY RECOMMENDED A MEETING BE HELD
 WITH CITY'S PROJECT REPRESENTATIVE, AND
 PLANS EXAMINER TO GO OVER NOTES AND
 COMMENTS IN ORDER TO HELP ALLEAVIATE ANY
 FURTHER DELAYS.
  
 PLEASE CALL TO SET UP A TIME TO GO OVER
 PLANS AND FOR NEW PLANS TO BE SUBMITTED
 ONCE ALL REVIEWS ARE COMPLETE.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-02-06 Cont ID  
Sent By dpalmer Date 2006-02-06 Time 08:40 Rev Time 0.00
Received By dpalmer Date 2006-02-03 Time 21:56 Sent To  
Notes
2006-02-06 00:00:00********* UNSAT ***********
  
  
 1)NOTE: PLEASE CORRECT PLANS FOR
 ADDRESSINGAND STATION IN WHICH WORK IS
 BEING DONE.
 PLEASE KNOW, THE STATION LOCATED AT 500
 N. DIXIE, IS FIRE STATION #1.
 PLEASE ADJUST PAPERWORK AS NEEDED.
 ** PLEASE ALSO SEE THE SITE/ELEVATION
 PLANS SUBMITTED INDICAT THE STATION
 LOCATED OFF CUMBERLAND DR??
 PLEASE CORRELATE ALL PAPERWORK FO THE
 JOBSITE LOCATION IN WHICH WORK IS BEING
 PERFORMED.
  
 2)NOTE: PLEASE PROVIDE PLANS TO BE DONE
 MINIMUM BY AN ARCHITETC AS REQUIRED
 UNDER FS 481.229. PLANS MAY ALSO BE DONE
 BY AND PE AS LISTED UNDER FS
 471.003(2)H).
 PLEASE SEE THE FOLLOWING COMMENT AS
 PLANS MAY BE REQUIRED TO BE DONE BY A PE
 AS VALUE MAY BE ADJUSTED. (IF $50K OR
 MORE, THEN A PE WILL BE REQUIRED FOR
 PLANS.
  
 3)NOTE: PLEASE SEE FBC ADMINISTRATIVE
 SECTION 108.3 WHICH REQUIRES VALUE BASED
 ON COMPLETE SCOPE WORK TO INCLUDE ALL
 LABOR AND MATERIALS, EVEN IF EQUIPMENT
 IS OWNER SUPPLIED.
 PLEASE SEE VALUE IS SHOWN AS THE SAME
 FOR ALL THREE PERMITTED JOBS.
  
 4)NOTE: PLEASE SUBMIT ALL MANUFACTURES
 CUT/SPEC SHEETS FOR THE NEW GENERATOR,
 ATS AND FUEL TANK.
 215.5
  
 5)NOTE: PLEASE SEE NFPA-209.6.2.2
 WHICH REQUIRED A MIN OF 8HRS FUEL SUPPLY
 FOR FIRE PUMP (IF APPLICABLE). IT IS NOT
 KNOW IF THIS BLDG CONTAIN ANY FIRE PUMP.
 PLEAS PROVIDE MIN FUEL FOR ALL LIFE
 SAFETY DEVICES.
 PLEASE ALSO SEE FIRE REVIEW COMMENTS.
  
 6)NOTE: PLEASE SEE ATS IS SHOWN WITH AN
 EQUIPMENT GROUNDING CONDUCTOR FROM ATS
 TO GUTTER, ? PLEASE VERIFY IF THERE IS A
 MAIN LOCATED ON THE LINE SIDE OF OF THIS
 ATS. PLEASE SEE 250.24, 250.6
 THE GROUNDING OF ELECTRICAL SYSTEMS,
 CIRCUIT CONDUCTORS, SURGE ARRESTERS, AND
 CONDUCTIVE NON?CURRENT-CARRYING
 MATERIALS AND EQUIPMENT SHALL BE
 INSTALLED AND ARRANGED IN A MANNER THAT
 WILL PREVENT OBJECTIONABLE CURRENT OVER
 THE GROUNDING CONDUCTORS OR GROUNDING
 PATHS.
  
 7)NOTE: PLEASE DECLARE WHETHER OR NOT
 THE GENERATOR WILL OR WILL NOT BE A
 SEPARATEY DERVIED SYSTEM. PLEASE ADJUST
 AS NEEDED.
 215.5
  
 8)NOTE: PLEASE SEE 445.13 FOR MIN SIZING
 OF CONDUCTORS FROM GENERATOR TO ATS,
 FIRST MEANS OF OCP.
 215.5, 240.4,310.16
  
 9)NOTE: PLEASE SEE NO OCP IS SHOWN AT
 GENERATOR.?
 215.5
  
 10)NOTE: PLEASE SUBMIT PLANS INDICATION
 LOCATION OF GENERATOR AT SITE.
 PLEASW SHOW DETAIL OF WHERE BOLLARDS MAY
 BE REQUIRED DEPENDING ON THE LOCATION OF
 GENERATOR ETC.
  
 11)NOTE: PLEASE SEE BLDG REVIEW ,AS NO
 SLAB/FOOTER DETAILS WERE SUBMITTED.
  
 12)NOTE: PLEASE SEE EXISTING GROUNDING
 ELECTRODE LOCATION IS BEING SHOWN AT CT
 CAN, PLEASE VERIFY.
 250.24.
  
 13)NOTE: PLEASE SEE NO OCP IS INDICATED
 FOR NEW FEED TO PANEL EM?
 CAN NOT VERIFY FEEDERS ETC AT THIS TIME.
 215.5,310.16
  
 ** PLEASE SEE COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY
 QUESTIONS,PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  
 PLANS GIVEN ABCK TO LUIS M.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-05-02 Cont ID  
Sent By mwennerg Date 2006-05-02 Time 14:47 Rev Time 0.00
Received By mwennerg Date 2006-05-02 Time 14:47 Sent To  
Notes
2006-05-02 00:00:00******PROVISO******
  
 1) PLEASE CORRULATE PLANS AND PERMIT
 APPLICATION REGARDING LOCATION OF THIS
 WORK.
  
 2) WORK SHALL COMPLY WITH NFPA 110,
 STANDARD FOR EMERGENCY AND STANDBY POWER
 SYSTEMS.
  
 PLANS WILL BE STAMPED WHEN RETURNED FOR
 OTHER REVIEW COMMENTS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-02-07 Cont ID  
Sent By mwennerg Date 2006-02-07 Time 14:57 Rev Time 0.00
Received By mwennerg Date 2006-02-07 Time 14:57 Sent To  
Notes
2006-02-07 00:00:00******DENIED******
  
 1) PLEASE NOTE THAT PERMIT APPLICATION
 INDICATES FIRE STATION #1, WHICH IS
 ADDRESSED 500 N. DIXIE HIGHWAY. PLANS
 SHOW LAYOUT FOR FIRE STATION #6. PLEASE
 MAKE CORRECTION.
  
 2) PLEASE ILLUSTRATE LOCATION OF
 GENERATOR IN RELATION TO BUILDING AND
 PROPERTY LINES.
  
 3) WORK TO COMPLY WITH NFPA 110.
  
 4) PLEASE INCLUDE MANUFACTURER SPEC
 SHEETS FOR GENERATOR.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLANS REVIEW (561) 805-6722

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status N Date 2006-02-13 Cont ID  
Sent By jleech Date 2006-02-13 Time 07:39 Rev Time  
Received By jleech Date   Time   Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status N Date 2006-08-28 Cont ID  
Sent By jleech Date 2006-08-28 Time 08:21 Rev Time 0.00
Received By jleech Date 2006-08-28 Time 08:21 Sent To  
Notes
2006-08-28 00:00:00GAS COMPANY TO PROVIDE PLANS WITH
 PERMIT.
2006-06-26 00:00:00 
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2006-04-29 Cont ID  
Sent By pschmitz Date 2006-04-29 Time 13:16 Rev Time 0.00
Received By pschmitz Date 2006-04-29 Time 13:15 Sent To  
Notes
2006-04-29 00:00:00UNSAT
 NO PLANS, CONTRACTOR TO SUBMITT PLANS AT
 TIME OF PERMIT.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-02-13 Cont ID  
Sent By jleech Date 2006-02-13 Time 07:10 Rev Time 0.00
Received By jleech Date 2006-02-13 Time 07:10 Sent To M
Notes
2006-02-13 00:00:00DENIED;
 PERMIT APPLICATION WITH PLANS FROM A
 LICENSED L.P. CONTRACTOR REQUIRED. SHOW
 LOCATION OF TANK AND GENERATOR.
 NEED MANUFATURE'S SPECIFICATIONS ON
 GENERATOR.
 GAS REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-04-26 Cont ID  
Sent By adarroug Date 2006-04-26 Time 13:11 Rev Time 0.00
Received By adarroug Date 2006-04-26 Time 13:11 Sent To  
Notes
2006-04-26 00:00:00WAITING FOR "COMM" BD
 TO "COMM" BD#48

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-01-28 Cont ID  
Sent By adarroug Date 2006-01-28 Time 15:07 Rev Time 0.00
Received By adarroug Date 2006-01-28 Time 15:07 Sent To  
Notes
2006-01-28 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-02-13 Cont ID  
Sent By lmartine Date 2006-02-13 Time 16:35 Rev Time 0.00
Received By lmartine Date 2006-01-22 Time 12:23 Sent To  
Notes
2006-01-22 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2006-05-01 Cont ID  
Sent By pkrauss Date 2006-05-01 Time 15:29 Rev Time 0.00
Received By pkrauss Date 2006-05-01 Time 15:29 Sent To  
Notes
2006-05-01 00:00:00PROVISO:
 ADDITIONAL PERMIT REQUIRED FOR GAS.
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 WITH GAS PERMIT APPLICATION:
  
 - DEVELOPED LENGTH
 - ISOMETRIC OF GAS PIPING
 - PIPE SIZING
 - PIPE MATERIAL

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-02-07 Cont ID  
Sent By pkrauss Date 2006-02-07 Time 08:50 Rev Time 0.00
Received By pkrauss Date 2006-02-07 Time 08:39 Sent To  
Notes
2006-02-07 00:00:00DENIED:
 1.PLEASE PROVIDE MANUFACTURER
 SUBMITTAL DATA FOR THE GENERATOR.
  
 2.PLEASE PROVIDE SITE PLANS INDICATING
 LOCATION OF THE GENERATOR.SHOW
 DISTANCE FROM BUILDING STRUCTURE,
 WINDOWS, DOORS, LOUVERS, ETC.PLEASE
 INDICATE DISTANCE FROM PROPERTY LINES.
  
 3.PERMIT APPLICATION INDICATES NATURAL
 GAS BUT A SUBMITTAL FOR AN LP TANK IS
 ALSO PROVIDED.WILL THIS BE A "DUEL
 TYPE OF FUEL SORCE"?PLEASE CLARIFY.
  
 4.ADDITIONAL PERMIT REQUIRED FOR GAS
 INSTALLATION.
  
 5.PLEASE PROVIDE DETAIL FOR THE
 GENERATOR SLAB & ANCHORING OF THE
 GENERATOR.SHOW COMPLIANCE WITH 2004
 FMC 301.13.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 2 Status N Date 2006-04-29 Cont ID  
Sent By pschmitz Date 2006-04-29 Time 13:14 Rev Time 0.00
Received By pschmitz Date 2006-04-29 Time 13:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-02-13 Cont ID  
Sent By adarroug Date 2006-02-01 Time 15:55 Rev Time  
Received By jleech Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2006-05-03 Cont ID  
Sent By mmclean Date 2006-05-03 Time 14:01 Rev Time 0.00
Received By mmclean Date 2006-05-03 Time 11:48 Sent To  
Notes
2006-05-03 00:00:00PROVISO: MUST PROVIDE FENCING ALONG
 SOUTHERN EDGE OF PROPERTY AND SHIFT TWO
 PARKING DOWN.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-01-28 Cont ID  
Sent By mmclean Date 2006-01-28 Time 13:54 Rev Time 0.00
Received By mmclean Date 2006-01-28 Time 13:54 Sent To I
Notes
2006-01-28 00:00:00DENIED,
 1. NEED TO SHOW THE LOCATION OF
 GENERATOR AND SETBACK FROM PROPERTY
 LINE.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720