| Plan Review Stops For Permit 05110390 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2006-05-03 |
|
|
Cont ID |
|
| Sent By |
lursu |
Date |
2006-05-03 |
Time |
16:13 |
Rev Time |
0.00 |
| Received By |
lursu |
Date |
2006-05-03 |
Time |
16:13 |
Sent To |
|
|
| Notes |
| 2006-05-03 00:00:00 | JOB TO BE DONE AT THE FS#6 ,ADDRESS HAS | | | BEEN CORRECTED :3033 CUMBERLAND DR. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2006-05-10 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2006-05-10 |
Time |
10:49 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2006-05-10 |
Time |
10:49 |
Sent To |
|
|
| Notes |
| 2006-04-26 00:00:00 | NEEDS BUIDLING REVIEW FOR NEW SLAB/ ETC |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2006-02-12 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2006-02-12 |
Time |
13:29 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2006-02-12 |
Time |
13:29 |
Sent To |
P |
|
| Notes |
| 2006-02-12 00:00:00 | | | | | | | ADDRESS AND PLANS DON'T MATCH, CLARIFY | | | IF GENERATOR WILL BE INSTALLED AT 500 | | | N.DIXIE OR CUMBERLAND DR. | | | | | | COMPLY WITH THE MECHANICAL REVIEWERS | | | NOTES AS TO FOUNDATION AND TIE-DOWN | | | REQUIREMENTS. | | | | | | | | | | | | L.MARTINEZ | | | 805-6710 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2006-11-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-11-17 |
Time |
12:01 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-11-17 |
Time |
11:14 |
Sent To |
PC |
|
| Notes |
| 2006-11-17 12:03:31 | REVISED CONDUCTORS TO PARALLEL 3/0'S. | | | | | | REDLINED 230.76/230.79 AND 110.27 FOR THE PROPOSED SE | | | RATED ATS. | | | THE MODELS AS SHOWN IN SPECS DO NOT INDICATE SPECIFIC | | | UNIT. | | | MUST MEET CODES ABOVE. | | | | | | | | | ** PLACED NOTES ON SHEETS AS CONTRACTOR DID NOT PRINT | | | AND SIGN NAME. NEEDS BEFORE PICKING UP. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2006-05-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-05-18 |
Time |
12:23 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-05-18 |
Time |
12:23 |
Sent To |
PC |
|
| Notes |
| 2006-05-18 00:00:00 | ***** PROVSIO ******** | | | | | | | | | ** NOTES REDLINED, THE SERVICE ENT RATED | | | ATS, MUST MEET 230.76,230.76, | | | 225.31-225.39 | | | THIS WILL BE VEERIFIED BY THIS OFFICE. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2006-04-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-04-26 |
Time |
19:55 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-04-26 |
Time |
19:52 |
Sent To |
|
|
| Notes |
| 2006-04-26 00:00:00 | **********UNSAT 2ND REVIEW ********** | | | | | | 1) NOTE: PLEASE SEE PLANS ARE STILL | | | BEING SUBMITTED INDICATING FIRE STATION | | | #6 WHICH IS LOCATED ON CUMBERLAND DR, | | | YET , PERMIT APPLICATION AND RESUB | | | SHEETS STILL INDICATES FIRE STATION #1, | | | WHICH IS LOCATED AT 500 N. DIXIE HWY. | | | PLEASE CORRELATE AND DECIDE WHICH | | | LOCATION THIS INSTALLATION IS TAKING | | | PLACE AND ADJUST ALL PAPER WORK | | | ACCORDINGLY. | | | | | | 2) NOTE: PLEASE SEE NOTES FROM PREVIOUS | | | REVIEW, PLEASE SEE NOW TWO DIFFERENT | | | ELECTRICAL RISERS ARE BEING SUBMITTED | | | FOR REVIEW. | | | PLEASE SEE RISERS SUBMITTED DO NOT MEET | | | MIN NEC CODE COMPLIANCE FOR | | | INSTALLATIONS. | | | PLEASE SEE MANY COMMENTS FROM PREVIOUS | | | REVIEW STILL REMAIN AND NEW COMMENTS AS | | | INFORMATION ON RISERS ARE NOT COMPLETE | | | OR DO NOT CORRELATE. | | | 215.5 | | | | | | 3) NOTE: PLEASE SEE PLANS SUBMITTED DO | | | NOT CONTAIN THE PRINTED NAME AND THE | | | SIGNATURE OF THE "DESIGN | | | PROFESSIONAL"/CONTRACTOR WHO IS TAKING | | | RESPONSIBILITY FOR PLANS AND DESIGN. | | | FBC 104.2.1 ADMINISTRATIVE SECTION AS | | | ADMENDED BY THE CITY OF WEST PALM BEACH. | | | | | | 4) NOTE: PLEASE SEE RESPONSE LETTER | | | MENTIONS GEN WILL BE SEPARATELY DERIVED | | | , HOWEVER PLANS HAVE NOT BEEN REVISED TO | | | MEET CODE COMPLIANCE FOR THIS AND THE | | | SPECS FOR THE ATS DO NOT MENTIONS | | | 4-POLE. | | | 250.30,215.5 | | | | | | 5) NOTE: PLEASE SEE 250.6,250.24B AND | | | 250.122 FOR MISSING EQUIPMENT GROUNDS. | | | | | | 6) NOTE: PLEASE SEE RISER(S) ARE MISSING | | | CONDUCTORS, OCP AND INFORMATION | | | REQUESTED FOR ITEMS ON FIRST REVIEW.\ | | | PLEASE SEE ONE SHEET MENTIONS | | | DISCONNECT, THE OTHER DISTRIBUTION? | | | 215.5 | | | | | | 7) NOTE: PLEASE SEE FLORIDA STATUES | | | 553.80(2)(B) WITH RESPECT TO THE "DESIGN | | | PROFESSIONAL" AND REPEAT COMMENTS FOR | | | CODE COMPLIANCE. | | | PLEASE KNOW, DUE TO THE EXTREME TIME | | | SENSATIVE NATURE OF THIS PROJECT IT IS | | | STRONGLY RECOMMENDED A MEETING BE HELD | | | WITH CITY'S PROJECT REPRESENTATIVE, AND | | | PLANS EXAMINER TO GO OVER NOTES AND | | | COMMENTS IN ORDER TO HELP ALLEAVIATE ANY | | | FURTHER DELAYS. | | | | | | PLEASE CALL TO SET UP A TIME TO GO OVER | | | PLANS AND FOR NEW PLANS TO BE SUBMITTED | | | ONCE ALL REVIEWS ARE COMPLETE. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-02-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-02-06 |
Time |
08:40 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-02-03 |
Time |
21:56 |
Sent To |
|
|
| Notes |
| 2006-02-06 00:00:00 | ********* UNSAT *********** | | | | | | | | | 1)NOTE: PLEASE CORRECT PLANS FOR | | | ADDRESSINGAND STATION IN WHICH WORK IS | | | BEING DONE. | | | PLEASE KNOW, THE STATION LOCATED AT 500 | | | N. DIXIE, IS FIRE STATION #1. | | | PLEASE ADJUST PAPERWORK AS NEEDED. | | | ** PLEASE ALSO SEE THE SITE/ELEVATION | | | PLANS SUBMITTED INDICAT THE STATION | | | LOCATED OFF CUMBERLAND DR?? | | | PLEASE CORRELATE ALL PAPERWORK FO THE | | | JOBSITE LOCATION IN WHICH WORK IS BEING | | | PERFORMED. | | | | | | 2)NOTE: PLEASE PROVIDE PLANS TO BE DONE | | | MINIMUM BY AN ARCHITETC AS REQUIRED | | | UNDER FS 481.229. PLANS MAY ALSO BE DONE | | | BY AND PE AS LISTED UNDER FS | | | 471.003(2)H). | | | PLEASE SEE THE FOLLOWING COMMENT AS | | | PLANS MAY BE REQUIRED TO BE DONE BY A PE | | | AS VALUE MAY BE ADJUSTED. (IF $50K OR | | | MORE, THEN A PE WILL BE REQUIRED FOR | | | PLANS. | | | | | | 3)NOTE: PLEASE SEE FBC ADMINISTRATIVE | | | SECTION 108.3 WHICH REQUIRES VALUE BASED | | | ON COMPLETE SCOPE WORK TO INCLUDE ALL | | | LABOR AND MATERIALS, EVEN IF EQUIPMENT | | | IS OWNER SUPPLIED. | | | PLEASE SEE VALUE IS SHOWN AS THE SAME | | | FOR ALL THREE PERMITTED JOBS. | | | | | | 4)NOTE: PLEASE SUBMIT ALL MANUFACTURES | | | CUT/SPEC SHEETS FOR THE NEW GENERATOR, | | | ATS AND FUEL TANK. | | | 215.5 | | | | | | 5)NOTE: PLEASE SEE NFPA-209.6.2.2 | | | WHICH REQUIRED A MIN OF 8HRS FUEL SUPPLY | | | FOR FIRE PUMP (IF APPLICABLE). IT IS NOT | | | KNOW IF THIS BLDG CONTAIN ANY FIRE PUMP. | | | PLEAS PROVIDE MIN FUEL FOR ALL LIFE | | | SAFETY DEVICES. | | | PLEASE ALSO SEE FIRE REVIEW COMMENTS. | | | | | | 6)NOTE: PLEASE SEE ATS IS SHOWN WITH AN | | | EQUIPMENT GROUNDING CONDUCTOR FROM ATS | | | TO GUTTER, ? PLEASE VERIFY IF THERE IS A | | | MAIN LOCATED ON THE LINE SIDE OF OF THIS | | | ATS. PLEASE SEE 250.24, 250.6 | | | THE GROUNDING OF ELECTRICAL SYSTEMS, | | | CIRCUIT CONDUCTORS, SURGE ARRESTERS, AND | | | CONDUCTIVE NON?CURRENT-CARRYING | | | MATERIALS AND EQUIPMENT SHALL BE | | | INSTALLED AND ARRANGED IN A MANNER THAT | | | WILL PREVENT OBJECTIONABLE CURRENT OVER | | | THE GROUNDING CONDUCTORS OR GROUNDING | | | PATHS. | | | | | | 7)NOTE: PLEASE DECLARE WHETHER OR NOT | | | THE GENERATOR WILL OR WILL NOT BE A | | | SEPARATEY DERVIED SYSTEM. PLEASE ADJUST | | | AS NEEDED. | | | 215.5 | | | | | | 8)NOTE: PLEASE SEE 445.13 FOR MIN SIZING | | | OF CONDUCTORS FROM GENERATOR TO ATS, | | | FIRST MEANS OF OCP. | | | 215.5, 240.4,310.16 | | | | | | 9)NOTE: PLEASE SEE NO OCP IS SHOWN AT | | | GENERATOR.? | | | 215.5 | | | | | | 10)NOTE: PLEASE SUBMIT PLANS INDICATION | | | LOCATION OF GENERATOR AT SITE. | | | PLEASW SHOW DETAIL OF WHERE BOLLARDS MAY | | | BE REQUIRED DEPENDING ON THE LOCATION OF | | | GENERATOR ETC. | | | | | | 11)NOTE: PLEASE SEE BLDG REVIEW ,AS NO | | | SLAB/FOOTER DETAILS WERE SUBMITTED. | | | | | | 12)NOTE: PLEASE SEE EXISTING GROUNDING | | | ELECTRODE LOCATION IS BEING SHOWN AT CT | | | CAN, PLEASE VERIFY. | | | 250.24. | | | | | | 13)NOTE: PLEASE SEE NO OCP IS INDICATED | | | FOR NEW FEED TO PANEL EM? | | | CAN NOT VERIFY FEEDERS ETC AT THIS TIME. | | | 215.5,310.16 | | | | | | ** PLEASE SEE COMMENTS FROM OTHER | | | REVIEWER(S) WHICH MAY AFFECT ELECTRICAL | | | PLANS. | | | | | | ** PLEASE SUBMIT THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY | | | QUESTIONS,PLEASE DO NOT HESITATE IN | | | CONTACTING THIS OFFICE. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | PLANS GIVEN ABCK TO LUIS M. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2006-05-02 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-05-02 |
Time |
14:47 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-05-02 |
Time |
14:47 |
Sent To |
|
|
| Notes |
| 2006-05-02 00:00:00 | ******PROVISO****** | | | | | | 1) PLEASE CORRULATE PLANS AND PERMIT | | | APPLICATION REGARDING LOCATION OF THIS | | | WORK. | | | | | | 2) WORK SHALL COMPLY WITH NFPA 110, | | | STANDARD FOR EMERGENCY AND STANDBY POWER | | | SYSTEMS. | | | | | | PLANS WILL BE STAMPED WHEN RETURNED FOR | | | OTHER REVIEW COMMENTS. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2006-02-07 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-02-07 |
Time |
14:57 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-02-07 |
Time |
14:57 |
Sent To |
|
|
| Notes |
| 2006-02-07 00:00:00 | ******DENIED****** | | | | | | 1) PLEASE NOTE THAT PERMIT APPLICATION | | | INDICATES FIRE STATION #1, WHICH IS | | | ADDRESSED 500 N. DIXIE HIGHWAY. PLANS | | | SHOW LAYOUT FOR FIRE STATION #6. PLEASE | | | MAKE CORRECTION. | | | | | | 2) PLEASE ILLUSTRATE LOCATION OF | | | GENERATOR IN RELATION TO BUILDING AND | | | PROPERTY LINES. | | | | | | 3) WORK TO COMPLY WITH NFPA 110. | | | | | | 4) PLEASE INCLUDE MANUFACTURER SPEC | | | SHEETS FOR GENERATOR. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLANS REVIEW (561) 805-6722 |
|
|
| Review Stop |
FUEL |
DIESEL GENERATOR |
| Rev No |
1 |
Status |
N |
Date |
2006-02-13 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-02-13 |
Time |
07:39 |
Rev Time |
|
| Received By |
jleech |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
N |
Date |
2006-08-28 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-08-28 |
Time |
08:21 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-08-28 |
Time |
08:21 |
Sent To |
|
|
| Notes |
| 2006-08-28 00:00:00 | GAS COMPANY TO PROVIDE PLANS WITH | | | PERMIT. | | 2006-06-26 00:00:00 | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
N |
Date |
2006-04-29 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-04-29 |
Time |
13:16 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-04-29 |
Time |
13:15 |
Sent To |
|
|
| Notes |
| 2006-04-29 00:00:00 | UNSAT | | | NO PLANS, CONTRACTOR TO SUBMITT PLANS AT | | | TIME OF PERMIT. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2006-02-13 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-02-13 |
Time |
07:10 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-02-13 |
Time |
07:10 |
Sent To |
M |
|
| Notes |
| 2006-02-13 00:00:00 | DENIED; | | | PERMIT APPLICATION WITH PLANS FROM A | | | LICENSED L.P. CONTRACTOR REQUIRED. SHOW | | | LOCATION OF TANK AND GENERATOR. | | | NEED MANUFATURE'S SPECIFICATIONS ON | | | GENERATOR. | | | GAS REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-04-26 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-04-26 |
Time |
13:11 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-04-26 |
Time |
13:11 |
Sent To |
|
|
| Notes |
| 2006-04-26 00:00:00 | WAITING FOR "COMM" BD | | | TO "COMM" BD#48 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-01-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-01-28 |
Time |
15:07 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-01-28 |
Time |
15:07 |
Sent To |
|
|
| Notes |
| 2006-01-28 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-02-13 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2006-02-13 |
Time |
16:35 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2006-01-22 |
Time |
12:23 |
Sent To |
|
|
| Notes |
| 2006-01-22 00:00:00 | TO "Z" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
N |
Date |
2006-05-01 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-05-01 |
Time |
15:29 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-05-01 |
Time |
15:29 |
Sent To |
|
|
| Notes |
| 2006-05-01 00:00:00 | PROVISO: | | | ADDITIONAL PERMIT REQUIRED FOR GAS. | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | WITH GAS PERMIT APPLICATION: | | | | | | - DEVELOPED LENGTH | | | - ISOMETRIC OF GAS PIPING | | | - PIPE SIZING | | | - PIPE MATERIAL |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2006-02-07 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-02-07 |
Time |
08:50 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-02-07 |
Time |
08:39 |
Sent To |
|
|
| Notes |
| 2006-02-07 00:00:00 | DENIED: | | | 1.PLEASE PROVIDE MANUFACTURER | | | SUBMITTAL DATA FOR THE GENERATOR. | | | | | | 2.PLEASE PROVIDE SITE PLANS INDICATING | | | LOCATION OF THE GENERATOR.SHOW | | | DISTANCE FROM BUILDING STRUCTURE, | | | WINDOWS, DOORS, LOUVERS, ETC.PLEASE | | | INDICATE DISTANCE FROM PROPERTY LINES. | | | | | | 3.PERMIT APPLICATION INDICATES NATURAL | | | GAS BUT A SUBMITTAL FOR AN LP TANK IS | | | ALSO PROVIDED.WILL THIS BE A "DUEL | | | TYPE OF FUEL SORCE"?PLEASE CLARIFY. | | | | | | 4.ADDITIONAL PERMIT REQUIRED FOR GAS | | | INSTALLATION. | | | | | | 5.PLEASE PROVIDE DETAIL FOR THE | | | GENERATOR SLAB & ANCHORING OF THE | | | GENERATOR.SHOW COMPLIANCE WITH 2004 | | | FMC 301.13. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
N |
Date |
2006-04-29 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-04-29 |
Time |
13:14 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-04-29 |
Time |
13:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2006-02-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-02-01 |
Time |
15:55 |
Rev Time |
|
| Received By |
jleech |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2006-05-03 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-05-03 |
Time |
14:01 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-05-03 |
Time |
11:48 |
Sent To |
|
|
| Notes |
| 2006-05-03 00:00:00 | PROVISO: MUST PROVIDE FENCING ALONG | | | SOUTHERN EDGE OF PROPERTY AND SHIFT TWO | | | PARKING DOWN. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2006-01-28 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-01-28 |
Time |
13:54 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-01-28 |
Time |
13:54 |
Sent To |
I |
|
| Notes |
| 2006-01-28 00:00:00 | DENIED, | | | 1. NEED TO SHOW THE LOCATION OF | | | GENERATOR AND SETBACK FROM PROPERTY | | | LINE. | | | | | | | | | MICHELLE MCLEAN | | | ZONING TECHNICIAN | | | 805-6720 |
|
|