Plan Review Details - Permit 05110320
Plan Review Stops For Permit 05110320
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-09-06 Cont ID  
Sent By mjacobs Date 2006-09-06 Time 16:54 Rev Time 0.00
Received By mjacobs Date 2006-09-06 Time 16:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-01-20 Cont ID  
Sent By mjacobs Date 2006-01-20 Time 18:32 Rev Time 1.00
Received By mjacobs Date 2006-01-20 Time 16:49 Sent To M
Notes
2006-01-20 00:00:00 
 PROVISO
 1005.2 DOOR ENCROACHMENT.
 DOORS OPENING INTO THE PATH OF EGRESS
 TRAVEL SHALL NOT REDUCE THE REQUIRED
 WIDTH TO LESS THAN ONE-HALF DURING THE
 COURSE OF THE SWING. WHEN FULLY OPEN,
 THE DOOR SHALL NOT PROJECT MORE THAN 7
 INCHES (178 MM) INTO THE REQUIRED WIDTH.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-11-21 Cont ID  
Sent By mjacobs Date 2005-11-21 Time 13:05 Rev Time 1.50
Received By mjacobs Date 2005-11-21 Time 11:50 Sent To  
Notes
2005-11-21 00:00:001) SHEETS GSA 1 THROUGH 4 NEEDS TO BE
 SIGNED/DATED AND SEALED BY THE ARCHITECT
 OR ENGINEER RESPONSIBLE FOR THE
 DRAWINGS.SEE F.S 472.025 AND
 F.A.C. 61G15.23.002.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL (561)805-6726
 FAX (561) 659-8026
 [email protected].

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-09-07 Cont ID  
Sent By dpalmer Date 2006-09-07 Time 09:42 Rev Time 0.00
Received By dpalmer Date 2006-09-07 Time 09:42 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-01-20 Cont ID  
Sent By dpalmer Date 2006-01-20 Time 13:53 Rev Time 0.00
Received By dpalmer Date 2006-01-20 Time 13:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-11-17 Cont ID  
Sent By dpalmer Date 2005-11-17 Time 12:24 Rev Time 0.00
Received By dpalmer Date 2005-11-17 Time 12:24 Sent To  
Notes
2005-11-17 00:00:00********* UNSAT **********
  
  
 1)NOTE: PLEASE CORRELATE NEW
 CONDUCTOR/FEEDER SIZES FROM PANEL "6HB"
 TO NEW 45KVA TRANSFORMER. PLEASE SEE
 RISER SHOWS 1/0'S AND PANEL SCHEDULE
 SHOWS #4.
  
  
 2)NOTE: PLEASE SHOW GROUNDING FOR
 TRANSFORMER PER 250.30 FOR SEPARATELY
 DERIVED SYSTEMS.
 PLEASE ALSO SEE 250.66 FOR SIZING.
  
 PLEASE SEE PLANS ARE COMING BACK, PLEASE
 MAKE THE ABOVE CORRECTIONS AT THIS TIME.
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETED SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD VOIDED SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-09-06 Cont ID  
Sent By mawillia Date 2006-09-06 Time 11:21 Rev Time 0.00
Received By mawillia Date 2006-09-06 Time 11:13 Sent To B
Notes
2006-09-06 00:00:00*****APPROVED*****
  
  
  
  
 1.) STRUCTURES UNDERGOING CONSTRUCTION,
 ALTERATION, OF DEMOLITION OPERATIONS
 SHALL COMPLY WITH NFPA 241.
  
 2.) ACCUMULATIONS OF COMBUSTIBLE WASTE
 MATERIAL, DUST, AND DEBRIS SHALL BE
 REMOVED FROM THE VICINITY AT THE END OF
 EACH SHIFT OR MORE FREQUENTLY AS
 NECESSARY FOR SAFE OPERATIONS.
  
 3.) WHERE THE BUILDING IS PROTECTED BY
 FIRE PROTECTED SYSTEMS, SUCH SYSTEMS
 SHALL BE MAINTAINED OPERATIONAL AT ALL
 TIMES.
  
  
  
  
  
  
 LT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-01-20 Cont ID  
Sent By mwennerg Date 2006-01-20 Time 14:53 Rev Time 0.00
Received By mwennerg Date 2006-01-20 Time 14:53 Sent To  
Notes
2006-01-20 00:00:00PLANS APPROVED PRIOR AND STAMPED ON THIS
 DATE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-11-21 Cont ID  
Sent By mwennerg Date 2005-11-21 Time 15:48 Rev Time 0.00
Received By mwennerg Date 2005-11-21 Time 15:48 Sent To  
Notes
2005-11-21 00:00:00******PASSED******
  
 ANY PROPOSED SPECIAL LOCKING
 ARRANGEMENTS SHALL COMPLY WITH NFPA 101,
 SEC. 7.2.1.6, 2003 EDITION. ACCESS
 CONTROLLED EGRESS DOORS SHALL BE IN
 COMPLIANCE WITH SEC. 7.2.1.6.2.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-08-15 Cont ID  
Sent By adarroug Date 2006-08-15 Time 11:25 Rev Time 0.00
Received By adarroug Date 2006-08-15 Time 11:25 Sent To  
Notes
2006-09-05 00:00:00TO "BOB"#2
2006-08-15 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-03-24 Cont ID  
Sent By dpalmer Date 2006-03-24 Time 14:36 Rev Time 0.00
Received By dpalmer Date 2006-03-24 Time 14:36 Sent To M
Notes
2006-03-24 00:00:00TO MECH INBOX.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-01-17 Cont ID  
Sent By adarroug Date 2006-01-17 Time 14:28 Rev Time 0.00
Received By adarroug Date 2006-01-17 Time 14:28 Sent To  
Notes
2006-01-17 00:00:00TO "BOB"#9

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2005-11-29 Time   Rev Time 0.00
Received By adarroug Date 2005-11-15 Time 18:45 Sent To  
Notes
2005-11-15 00:00:00TO "BOB"#9

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-09-06 Cont ID  
Sent By tgordon Date 2006-09-06 Time 14:37 Rev Time 0.25
Received By tgordon Date 2006-09-06 Time 14:37 Sent To  
Notes
2006-09-06 00:00:00MECH. REVISION TO PAGES M-1 & M-2 .

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-03-27 Cont ID  
Sent By tgordon Date 2006-03-27 Time 11:49 Rev Time 0.20
Received By tgordon Date 2006-03-27 Time 11:49 Sent To  
Notes
2006-03-27 00:00:00REVISION TO MECH. PLAN PAGE M-2 .

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-01-21 Cont ID  
Sent By pkrauss Date 2006-01-21 Time 08:23 Rev Time 0.00
Received By pkrauss Date 2006-01-21 Time 08:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-11-29 Cont ID  
Sent By hmoser Date 2005-11-29 Time 08:12 Rev Time 0.00
Received By hmoser Date 2005-11-29 Time 08:12 Sent To  
Notes
2005-11-29 00:00:00PLAN DENIED
 CAN NOT READ PLANS.PLEASE REFER TO
 SECTION 603.5.6.6 FLEXIBLE DUCT
 INSTALLATION AND SUPPORT #1 2004 FBC(M)
 PLAN REVIEW BY HAROLD MOSER 561-805-6732