Plan Review Details - Permit 05110308
Plan Review Stops For Permit 05110308
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-03-09 Cont ID  
Sent By shill Date 2006-03-09 Time 09:51 Rev Time 0.00
Received By shill Date 2006-03-09 Time 09:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-02-01 Cont ID  
Sent By shill Date 2006-02-01 Time 16:24 Rev Time 0.00
Received By shill Date 2006-02-01 Time 16:17 Sent To  
Notes
2006-02-01 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 FROM PREVIOUS LIST:
  
 1.)SEE FAC61G15-23.
  
 A. ORIGINAL "WET" SIGNATURE REQUIRED.
 THE SIGNATURE ON THE PLAN IS A
 PHOTOCOPY.
  
 2ND REVIEW - PHOTOCOPIED SIGNATURES
 SUBMITTED.WET SIGNATURE REQUIRED PER
 FLORIDA BOARD OF PROFESSIONAL ENGINEERS.
  
 B. CERTIFICATE OF AUTHORIZATION REQUIRED
 FOR BPI INTERNATIONAL IF THIS COMPANY IS
 PRACTICING ENGINEERING.
  
 2ND REVIEW - A TITLE BLOCK FOR FERRARA
 ENGINEERING, INC. PROVIDED.CERTIFICATE
 OF AUTHORIZATION (ENGINEERING BUSINESS)
 NUMBER REQUIRED TO BE ON THE PLAN
 FAC61G15-23.002.
  
  
 NOTE - "QUICK REMOVAL" DETAIL APPROVED
 BY BUILDING OFFICIAL 2/1/06SMH

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-12-22 Cont ID  
Sent By shill Date 2005-12-22 Time 15:27 Rev Time 1.00
Received By shill Date 2005-12-22 Time 14:12 Sent To PC
Notes
2005-12-22 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)SEE FAC61G15-23.
  
 A. ORIGINAL "WET" SIGNATURE REQUIRED.
 THE SIGNATURE ON THE PLAN IS A
 PHOTOCOPY.
  
 B. CERTIFICATE OF AUTHORIZATION REQUIRED
 FOR BPI INTERNATIONAL IF THIS COMPANY IS
 PRACTICING ENGINEERING.
  
 C. IF BPI INTERNATIONAL IS NOT
 PRACTICING ENGINEERING, THE ENGINEER
 SHOULD HAVE A TITLE BLOCK ON EACH SHEET
 IN COMPLIANCE WITH FAC61G15-23.002.
  
 D. THE PRINTED NAME AND LICENSE NUMBER
 OF THE PERSON SEALING THE DOCUMENT IS TO
 BE ON EACH SHEET.THE IMPRESSION OF THE
 RAISED SEAL DOES NOT SATISFY THIS
 REQUIREMENT.
  
 2.)DECLARE GOVERNING CODE (FBC2004).
  
 3.) THE REMOVABLE FABRIC CANOPY IS TO
 COMPLY WITH FBC3105.3.IT IS UNCLEAR AS
 TO WHETHER OR NOT THE REQUIREMENT OF
 FLAME RESISTANCE (NFPA701) IS SATISFIED
 BY A FLAME SPREAD INDEX OF CLASS A (ASTM
 E84).EITHER PROVIDE THIS INFORMATION
 TO ME (TO SHOW THAT ASTM E84, CLASS A
 MEETS OR EXCEEDS NFPA701) OR ADD THIS
 CRITERIA TO YOUR GENERAL NOTES.
  
 4.)YOU HAVE DECLARED AN IMPORTANCE
 FACTOR OF 1.0.SEE FBC3105.4.2.2(2).A
 REMOVABLE FABRIC IS ALLOWED ONLY WITH AN
 IMPORTANCE FACTOR OF .77.ADDRESS.
  
 5.)INDICATE ON THE PLAN THAT THE
 STRUCTURE HAS BEEN DESIGNED FOR THE
 FABRIC TO BE REMOVED AT 75 MPH.
  
 6.)SHOW COMPLIANCE WITH FBC3105.4.2.1,
 QUICK REMOVAL.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-01-22 Cont ID  
Sent By adarroug Date 2006-01-22 Time 13:51 Rev Time 0.00
Received By adarroug Date 2006-01-22 Time 13:51 Sent To B
Notes
2006-01-22 00:00:00TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-12-22 Cont ID  
Sent By shill Date 2005-12-22 Time 15:28 Rev Time 0.00
Received By shill Date 2005-11-15 Time 18:52 Sent To  
Notes
2005-11-30 00:00:00TO "COMM" BD#7
2005-11-15 00:00:00WAITING FOR "COMM" BD

Review Stop Z ZONING
Rev No 1 Status P Date 2005-12-22 Cont ID  
Sent By mmclean Date 2005-12-22 Time 11:03 Rev Time 0.00
Received By mmclean Date 2005-12-22 Time 11:03 Sent To  
Notes
***NONE***