| 2005-12-22 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | 1.)SEE FAC61G15-23. |
| | |
| | A. ORIGINAL "WET" SIGNATURE REQUIRED. |
| | THE SIGNATURE ON THE PLAN IS A |
| | PHOTOCOPY. |
| | |
| | B. CERTIFICATE OF AUTHORIZATION REQUIRED |
| | FOR BPI INTERNATIONAL IF THIS COMPANY IS |
| | PRACTICING ENGINEERING. |
| | |
| | C. IF BPI INTERNATIONAL IS NOT |
| | PRACTICING ENGINEERING, THE ENGINEER |
| | SHOULD HAVE A TITLE BLOCK ON EACH SHEET |
| | IN COMPLIANCE WITH FAC61G15-23.002. |
| | |
| | D. THE PRINTED NAME AND LICENSE NUMBER |
| | OF THE PERSON SEALING THE DOCUMENT IS TO |
| | BE ON EACH SHEET.THE IMPRESSION OF THE |
| | RAISED SEAL DOES NOT SATISFY THIS |
| | REQUIREMENT. |
| | |
| | 2.)DECLARE GOVERNING CODE (FBC2004). |
| | |
| | 3.) THE REMOVABLE FABRIC CANOPY IS TO |
| | COMPLY WITH FBC3105.3.IT IS UNCLEAR AS |
| | TO WHETHER OR NOT THE REQUIREMENT OF |
| | FLAME RESISTANCE (NFPA701) IS SATISFIED |
| | BY A FLAME SPREAD INDEX OF CLASS A (ASTM |
| | E84).EITHER PROVIDE THIS INFORMATION |
| | TO ME (TO SHOW THAT ASTM E84, CLASS A |
| | MEETS OR EXCEEDS NFPA701) OR ADD THIS |
| | CRITERIA TO YOUR GENERAL NOTES. |
| | |
| | 4.)YOU HAVE DECLARED AN IMPORTANCE |
| | FACTOR OF 1.0.SEE FBC3105.4.2.2(2).A |
| | REMOVABLE FABRIC IS ALLOWED ONLY WITH AN |
| | IMPORTANCE FACTOR OF .77.ADDRESS. |
| | |
| | 5.)INDICATE ON THE PLAN THAT THE |
| | STRUCTURE HAS BEEN DESIGNED FOR THE |
| | FABRIC TO BE REMOVED AT 75 MPH. |
| | |
| | 6.)SHOW COMPLIANCE WITH FBC3105.4.2.1, |
| | QUICK REMOVAL. |