 |
Plan Review Details - Permit 05110263
| Plan Review Stops For Permit 05110263 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2006-03-02 |
|
|
Cont ID |
|
| Sent By |
lursu |
Date |
2006-03-02 |
Time |
11:57 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-09-01 |
Time |
16:41 |
Sent To |
|
|
| Notes |
| 2006-03-02 00:00:00 | NEW ADDRESS HAS BEEN ASSIGNED : 1611 | | | WORTHINGTON RD.WITH A NEW | | | PCN = 74434329220000020 ( UNIT B) | | 2006-01-24 00:00:00 | 1647 WORTHINGHTON RD. ( FOR THE 4 STORY | | | HILTON HOTEL ) PCN =74434329160020071 | | | ( PERMIT # 05110263) | | | JOHN COSTAS @561-523-3699 TO E-MAIL | | | ;DONE ON DEC 28 /05 -- HEWILL E-MAIL | | | BACK WITH PCN .LU | | 2005-12-26 00:00:00 | NEEDS: | | | | | | SEE SITE PLAN. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
10 |
Status |
P |
Date |
2007-01-02 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-01-02 |
Time |
14:08 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2007-01-02 |
Time |
14:08 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
9 |
Status |
F |
Date |
2006-12-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-12-06 |
Time |
10:28 |
Rev Time |
0.55 |
| Received By |
jwitmer |
Date |
2006-12-06 |
Time |
10:28 |
Sent To |
|
|
| Notes |
| 2006-12-06 10:32:45 | BUILDING PLAN REVIEW | | | PERMIT: 05110263 | | | ADD: 1611 WORTHINGTON RD | | | CONT: NCY CONSTRUCTION | | | TEL: (561)797-3225 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1ST REVISIONREVIEW | | | ACTION: DENIED | | | | | | 1) THE STTRUCTURAL PLANS ARE DENIED, THERE IS NO | | | CERTIFICATE OF AUTHORIZATION FOR GRW ARCHITECTURE, | | | PLEASE REMOVE FROM THE TITLEBLOCK. | | | 481.219 F.S. | | | CERTIFICATE OF AUTHORIZATION.THE TITLE BLOCK FOR ANY | | | SHEET BEARING THE NAME OF AN ARCHITECT | | | PRACTICING UNDER A FICTITIOUS NAME, A | | | CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL | | | SERVICES, SHALL INCLUDE | | | THE CERTIFICATE OF AUTHORIZATION | | | NUMBER.ADD THE NUMBER TO EACH SHEET. | | | THIS MAY BE ADDED BY HAND. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
8 |
Status |
P |
Date |
2006-12-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-12-06 |
Time |
10:23 |
Rev Time |
1.55 |
| Received By |
jwitmer |
Date |
2006-12-06 |
Time |
09:38 |
Sent To |
|
|
| Notes |
| 2006-12-06 10:28:07 | REVISIONS A.01,A.05, A.06, A.10, A1.1, A1.15, A1.17, | | | A1.18, A1.19, | | | A2.0, A2.5, A2.6, A2.7, A2.8 OK |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
P |
Date |
2006-09-29 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-09-29 |
Time |
12:19 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2006-09-29 |
Time |
12:19 |
Sent To |
PC |
|
| Notes |
| 2006-09-29 00:00:00 | ALPINE METAL TRUSSESOK |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2006-08-31 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-08-31 |
Time |
09:34 |
Rev Time |
1.11 |
| Received By |
jwitmer |
Date |
2006-08-31 |
Time |
09:34 |
Sent To |
PC |
|
| Notes |
| 2006-08-31 00:00:00 | DAILY REPORTS 7-24-06/ 7-30-06 | | | 2ND FLOOR RESHORE DIAGRAM |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2006-07-11 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-07-11 |
Time |
16:53 |
Rev Time |
5.55 |
| Received By |
jwitmer |
Date |
2006-07-11 |
Time |
14:59 |
Sent To |
PC |
|
| Notes |
| 2006-07-11 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 05110263 | | | ADD: 1611 WORTHINGTON RD | | | CONT: NCY CONSTRUCTION INC | | | JOHN COSTAS | | | TEL: (561)523-3699 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | BUILDING PROVISO: | | | 109.3.10* IMPACT OF CONSTRUCTION. ALL | | | CONSTRUCTION ACTIVITY REGULATED BY THIS | | | CODE SHALL BE PERMORMED IN A MANNER SO | | | AS NOT TO ADVERSLY IMPACT THE CONDITION | | | OF ADJACENT PROPERTY, UNLESS SUCH | | | ACTIVITY IS PERMITTED TO AFFECT SAID | | | PROPERTY PURSUANT TO A CONSENT BY THE | | | APPLICABLE PROPERTY OWNER, UNDER TERMS & | | | CONDITIONS AGREEABLE TO THE APPLICABLE | | | PROPERTY OWNER.THIS INCLUDES BUT IS NOT | | | LIMITED TO THE CONTROL OF DUST, NOISE, | | | WATER OR DRAINAGE RUN-OFF, DEBRIS, AND | | | THE STORAGE OF CONSTRUCTION MATERIALS. | | | NEW CONSTRUCTION ACTIVITY SHALL NOT | | | ADVERSELY IMPACT HISTORICSURFACE WATER | | | DRAINAGE FLOWS SERVING ADJACENT | | | PROPERTIES, & MAY REQUIRE SPECIAL | | | DRAINAGE DESIGNCOMPLYING WITH | | | ENGINEERING STANDARDS TO PRESERVE THE | | | POSITIVE PATTERNS OF THE AFFECTED | | | SITES.ACCORDINGLY, DEVELOPERS, | | | CONTRACTORS, AND OWNERS OF ALL NEW | | | RESIDENTIAL DEVELOPMENET, INCLUDING | | | ADDITIONS, POOLS, PATIOS, DRIVEWAYS, | | | DECKS, OR SIMILAR ITEMS, ON EXISTING | | | PROPERTIES RESULTING IN A DECREASE IN | | | EXCESS OF 800SQ FT OF PERMEABLE LAND | | | AREA ON ANY PARCELL SHALL AS A PERMIT | | | CONDITION, PROVIDE A PROFESSIONALY | | | PREPARED DRAINAGE PLAN CLEARLY | | | INDICATING COMPLIANCE WITH THIS | | | PARAGRAPH. UPON COMPLETION OF THE | | | IMPROVEMENT, A CERTIFICATE FROM A | | | LICENSED ENGINEER SHALL BE SUBMITTED TO | | | THE INSPECTOR IN ORDER TO RECEIVE | | | APPROVAL OF THE FINAL INSPECTION. | | | | | | 109.3.10.1 HURICANE PROTECTION. | | | IT SHALL BE UNLAWFUL FOR ANY PERSON TO | | | ALLOW CONSTRUCTION RELATED MATERIALS | | | EQUIPMENET AND DEBRIS TO REMAIN LOOSE OR | | | OTHERWISE UNSECURED AT A CONSTRUCTION | | | SITE FROM 24 HRS. AFTER A HURRICANE | | | WATCH HAS BEEN ISSUED UNTIL THE | | | HURRICANE WATCH OR WARNING HAS BEEN | | | LIFTED. ALL SUCH CONSTRUCTION MATERIALS, | | | EQUIPMENT AND DEBRIS SHALL BE EITHER | | | REMOVED FROM THE CONSTRUCTION SITE OR | | | SECURED IN SUCH A MANNER AS TO MINIMIZE | | | THE DANGER OF SUCH CONSTRUCTION | | | MATERIALS, EQUIPMENT AND DEBRIS CAUSING | | | DAMAGE TO PERSONS OR PROPERTY FROM | | | HIGHWINDS. | | | ANY PERSONS WHO FAILS TO COMPLY TO | | | REMOVE OR SECURE THE CONSTRUCTION | | | MATERIALS EQUIPMENT AND DEBRIS WITHIN | | | 24 HRS AFTER A HURRICANE WATCH HAS BEEN | | | ISSUED SHALL BE SUBJECT TO A FINE NOT TO | | | EXCEED $500.00. | | | IN ADDITION TO THE ABOVE, A LICENSED | | | CONTRACTOR WHO VIOLATES THIS SECTION | | | SHALL BE SUBJECT TO DISCIPLINE PURSUANT | | | TO SECTION 113 OF THIS CHAPTER. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2006-07-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-07-07 |
Time |
15:01 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-07-07 |
Time |
15:01 |
Sent To |
|
|
| Notes |
| 2006-07-07 00:00:00 | ** PAID PALM BEACH COUNTY IMPACT FEES | | | OK TO ISSUE PER JIM WITMER'S NOTES. | | | | | | SEE PROVISO IS STILL IN EFFECT FOR NOA | | | FORARCHED ALUM WINDOW ETC FROM | | | PREVIOUS NOTES. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2006-06-19 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-06-19 |
Time |
14:41 |
Rev Time |
8.88 |
| Received By |
jwitmer |
Date |
2006-06-15 |
Time |
16:42 |
Sent To |
|
|
| Notes |
| 2006-06-19 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 05110263 | | | ADD: 1611 WORTHINGTON RD | | | CONT: NCY CONSTRUCTION INC | | | JOHN COSTAS | | | TEL: (561)523-3699 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 3RD REVIEW | | | ACTION: DENIED | | | | | | PLANS APPEAR TO BE CODE COMPLIANT WHEN | | | IMPACT FEES ARE PAID BLDG WILL BE ABLE | | | TO STAMP PLANS. | | | | | | 1) COMMENT# 3 FROM THE PREVIOUS REVIEW, | | | DEALS WITH COUNTY IMPACT FEES. PULLED | | | THE FOUNDATION PLANS, NO FEES WERE PAID | | | ON THE FOUNDATION (06011052), NO COUNTY | | | STAMP OR RECEIPT. | | | BEFORE A PERMIT TO CONSTRUCT, MAY | | | BE ISSUED, IMPACT FEES MUST BE PAID TO | | | PALM BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | PROVISO: A) ARCH ALUMINIUM- SUBMITTED | | | THE WRONG NOA FOR FLORIDA COVERSHEET | | | SUBMITTED. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2006-04-13 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-04-13 |
Time |
10:51 |
Rev Time |
5.55 |
| Received By |
jwitmer |
Date |
2006-04-13 |
Time |
07:30 |
Sent To |
|
|
| Notes |
| 2006-04-13 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 05110263 | | | ADD: LOT# 7 CENTERPARK WEST | | | CONT: "PLAN REVIEW" HILTON | | | JOHN COSTAS | | | TEL: (561)523-3699 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2ND REVIEW | | | ACTION: DENIED | | | | | | | | | ***IMPORTANT*** | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | | | | | | | 1) PROVIDE NOC RECORDED WITH THE CLERK | | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | | NOTE NOC WILL BE NULL & VOID 90 DAYS | | | AFTER RECORDING AT THE CLERK OF THE | | | COURTS OFFICE IF WORK HAS NOT STARTED. | | | FL S S 713.13(2). | | | | | | 2) 2ND REQUEST FOR THIS INFORMATION, | | | RESPONCE INDICATED A PERMIT 06011019 | | | SUPPLIED THIS INFORMATION. THIS PERMIT | | | IS A SITE PREP PERMIT. | | | A FOUNDATION PERMIT WAS APPLIED FOR | | | UNDER 06011052. | | | BOTH THE S0.1 & S1.1 HAVE NOTES | | | ABOUT THE SOILS AND FOUNDATION BUT THE | | | ENGINEER DOESN'T STATE WHAT THE SAFE | | | MINIMUM DESIGN FOR THE FOUNDATION WAS | | | DESIGNED TO? | | | THIS IS A STAND ALONE PERMIT | | | REQUESTING (3) SIGNED/SEALED SOILS | | | REPORTS AS PER, | | | FL BLD CODE 1804.2.2 QUESTIONABLE | | | SOILS, WHERE THE BEARING CAPACITY IS | | | NOT DEFINETLY KNOWN OR IS IN QUESTION. | | | WHERE THE BEARING CAPACITY OF THE SOIL | | | IS NOT DEFINITLY KNOWN OR IS IN QUESTION | | | THE BUILDING OFFICIAL MAY REQUIRE EXPLOR | | | ATIONS, TEST OR OTHER ADEQUATE PROOF AS | | | TO THE PERMISSIBLE SAFE BEARING | | | CAPACITY. REQUIRED TEST AND RECOMMENDA- | | | TIONS SUBMITTED TO VERIFY BEARING CAPA- | | | CITY SHALL BE CERTIFIED BY A GEOTECH- | | | NICALREPORT FROM A DESIGN PROFESSIONAL | | | PROPERLY LICENSED IN THE STATE OF | | | FLORIDA. | | | | | | 3) COMMENT# 3 FROM THE PREVIOUS REVIEW, | | | BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 4)COMPLIED. | | | | | | 5)COMPLIED, HAROLD PISKURA, HAS THE | | | NECESSARY DOCUMENTS. | | | | | | 6) W.P.B. AMENDMENT 105.13.4.4 ALL PLANS | | | FOR THE BUILDING WHICH ARE REQUIRED TO | | | BE SIGNED AND SEALED BY THE ARCHITECT OR | | | ENGINEER OF RECORD CONTAIN A STATEMENT | | | THAT, TO THE BEST OF THE ARCHITECT'S OR | | | ENGINEER'S KNOWLEDGE, THE PLANS AND | | | SPECIFICATIONS COMPLY WITH THE | | | APPLICABLE FIRE-SAFETY STANDARDS AS | | | DETERMINED BY THE LOCAL AUTHORITY IN | | | ACCORDANCE WITH THIS SECTION AND 633 | | | FLORIDA STATUTE. | | | THIS STATEMENT IS FOUND ON THE | | | STRUCTURAL SHEETS BUT NOT THE | | | ARCHITECTURAL SHEETS. | | | | | | 7A)COMPLIED. | | | | | | 7B)2ND REQUEST, A SITE PLAN WAS | | | SUBMITTED ONLY, THIS REQUEST IS MADE AS | | | REQUEST (7D) TO DETERMINE LOT LINE, AND | | | TABLE 503, TABLE 601 ISSUES, PLANS DO | | | NOT PROVIDE MINIMUM BLDG TYPE! | | | PROVIDE A COPY OF THE NEW PLAT, SHEET | | | SP.01 APPEARS TO HAVE BEEN SUBDIVIDED | | | WITH ADDITIONAL BUILDINGS TO BE ON THE | | | SAME LOT. | | | | | | 7C)NOTE, TO BE COMPLETED AT TIME OF | | | PERMIT APPLICATION. PLEASE FILL OUT AN | | | ACTUAL APPLICATION SHEET PROVIDING THE | | | PROPERTY | | | CONTROL NUMBER FOR ADDRESSING. | | | | | | 7D)2ND REQUEST,SAME AS ISSUES AS 7B, | | | PROVIDE A SURVEY OF THE SITE. | | | | | | 8) 2ND REQUEST,ADDITIONAL INFORMATION | | | REQUIRED FOR | | | RECORD KEEPING PURPOSES 106.1.2*: | | | 8)A) FLOOD ZONE | | | 8)B) FLOOD ELEVATION (IF A ZONE) | | | 8)C) LOMAR (IF A ZONE) | | | 8)D) COMPLIED | | | 8)E) COMPLIED | | | 8)F)COMPLIED | | | 8)G)COMPLIED | | | 8)H)COMPLIED | | | 8)I) COMPLIED | | | 8)J) COMPLIED | | | 8)K) COMPLIED | | | | | | 9)THIS COMMENT WILL STAY UNTIL A | | | CONTRACTOR IS SIGNED ON AND ACKNOWLEDGES | | | STATEMENT. | | | 109.3.10* IMPACT OF CONSTRUCTION. ALL | | | CONSTRUCTION ACTIVITY REGULATED BY THIS | | | CODE SHALL BE PERMORMED IN A MANNER SO | | | AS NOT TO ADVERSLY IMPACT THE CONDITION | | | OF ADJACENT PROPERTY, UNLESS SUCH | | | ACTIVITY IS PERMITTED TO AFFECT SAID | | | PROPERTY PURSUANT TO A CONSENT BY THE | | | APPLICABLE PROPERTY OWNER, UNDER TERMS & | | | CONDITIONS AGREEABLE TO THE APPLICABLE | | | PROPERTY OWNER.THIS INCLUDES BUT IS NOT | | | LIMITED TO THE CONTROL OF DUST, NOISE, | | | WATER OR DRAINAGE RUN-OFF, DEBRIS, AND | | | THE STORAGE OF CONSTRUCTION MATERIALS. | | | NEW CONSTRUCTION ACTIVITY SHALL NOT | | | ADVERSELY IMPACT HISTORICSURFACE WATER | | | DRAINAGE FLOWS SERVING ADJACENT | | | PROPERTIES, & MAY REQUIRE SPECIAL | | | DRAINAGE DESIGNCOMPLYING WITH | | | ENGINEERING STANDARDS TO PRESERVE THE | | | POSITIVE PATTERNS OF THE AFFECTED | | | SITES.ACCORDINGLY, DEVELOPERS, | | | CONTRACTORS, AND OWNERS OF ALL NEW | | | RESIDENTIAL DEVELOPMENET, INCLUDING | | | ADDITIONS, POOLS, PATIOS, DRIVEWAYS, | | | DECKS, OR SIMILAR ITEMS, ON EXISTING | | | PROPERTIES RESULTING IN A DECREASE IN | | | EXCESS OF 800SQ FT OF PERMEABLE LAND | | | AREA ON ANY PARCELL SHALL AS A PERMIT | | | CONDITION, PROVIDE A PROFESSIONALY | | | PREPARED DRAINAGE PLAN CLEARLY | | | INDICATING COMPLIANCE WITH THIS | | | PARAGRAPH. UPON COMPLETION OF THE | | | IMPROVEMENT, A CERTIFICATE FROM A | | | LICENSED ENGINEER SHALL BE SUBMITTED TO | | | THE INSPECTOR IN ORDER TO RECEIVE | | | APPROVAL OF THE FINAL INSPECTION. | | | | | | 10) WILL REMAIN UNTIL ALL PERTINENT | | | INFORMATION REQUIRED FOR PERMIT HAS BEEN | | | REVIEWED, | | | SINCE THISWILL BE A THRESHOLD | | | PROJECT (3) SETS OF ALL INFORMATION | | | SUBMITTED WILL BE REQUIRED. | | | | | | 11)2ND REQUEST, 1609.1.4 PROTECTION OF | | | OPENINGS. | | | IN WIND-BORNE DEBRIS REGIONS, EXTERIOR | | | GLAZING THAT RECEIVES POSITIVE PRESSURE | | | IN THE LOWER 60 FEET (18.3 M) IN | | | BUILDINGS SHALL BE ASSUMED TO BE | | | OPENINGS AND THE BALANCE OF GLAZED | | | OPENINGS IN THE REST OF THE BUILDING | | | SHALL BE ASSUMED TO BE ZERO UNLESS SUCH | | | GLAZING THAT RECEIVES POSITIVE PRESSURE | | | IS IMPACT RESISTANT OR PROTECTED WITH AN | | | IMPACT RESISTANT COVERING MEETING THE | | | REQUIREMENTS OF SSTD 12, ASTM E 1886 AND | | | ASTM E 1996, OR MIAMI-DADE TAS 201, 202 | | | AND 203 REFERENCED THEREIN AS FOLLOWS: | | | 1.GLAZED OPENINGS LOCATED WITHIN 30 | | | FEET (9.1 M) OF GRADE SHALL MEET THE | | | REQUIREMENTS OF THE LARGE MISSILE TEST. | | | 2.GLAZED OPENINGS LOCATED MORE THAN | | | 30 FEET (9.1 M) ABOVE GRADE SHALL MEET | | | THE PROVISIONS OF THE SMALL MISSILE | | | TEST. | | | | | | 12)2ND REQUEST, NONE OF THE PRODUCT | | | APPROVALS SUBMITTED HAVE FLORIDA | | | COVERSHEETS, | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 13) FL BLD CODE 1606.1.5: COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | | TESTING REPORTS,MISSING REPORTS ARE AS | | | FOLLOWS: | | | A) WINDOWS MISSING FL COVERSHEET | | | SHEET | | | B) EXTERIOR DOORS, SOLID MISSING FL | | | COVER SHEET | | | C) EXTERIOR DOORS GLAZED NOT SUBMITED | | | D) EXTERIOR DOORS BYPASS, EXTERIOR AUTO | | | SLIDERS, USUALLY TRANSOM NOT INCLUDED | | | E) MULLIONS- NOT SUBMITTED- HORIZONTAL | | | TO SEPERATE THE AUTO SLIDERS FROM FIXED | | | STOREFRONT | | | F) LOUVERS NOT SUBMITTED | | | G) TRUSS ANCHORS NOT SUBMITTED | | | H1) ROOF ASSEMBLIES, FLAT ROOF: | | | ) THIS ROOF IS MISSING OR NOT IN | | | COMPLIANCE WITH THE FOLLOW ITEMS: | | | | | | _X__ CONTRACTOR DID NOT PROVIDE THE MEAN | | | | | | ROOF HEIGHT. | | | | | | ___ CONTRACTOR DID NOT INDICATE THE ROOF | | | PITCH. | | | | | | _X__ CONTRACTOR FAILED TO INDICATE WHICH | | | SYSTEM TO BE USED.HIGHLIGHT THE ACTUALL | | | SUBSYSTEM AND ANY OPTIONS AS FASTENER | | | TYPES! | | | | | | _X THIS MAY BE THE SITUATION SINCE NO | | | SYSTEM WAS HIGHLIGHTED,__ THE SYSTEM | | | PROVIDED HAS A LOW | | | PRESSURE FOR ZONE ___ . | | | | | | ___ THE SYSTEM PROVIDED STATES | | | LIMITATION# 7, SHOULD THE FASTENER | | | RESISTANCE BE LESS THAN THAT | | | REQUIRED, AS DETERMINED BY THE | | | BUILDING OFFICIAL, A REVISED | | | FASTENER SPACING, PREPARED , SIGNED | | | AND SEALED BY A FLORIDA REGISTERED | | | PROFESSIONAL ENGINEER, REGISTERED | | | ARCHITECT OR REGISTERED ROOF | | | CONSULTANT MAY BE SUBMITTED. | | | | | | ___THE SYSTEM PROVIDED INDICATES | | | LIMITATION# 9, NO ENHANCED | | | FASTENING ALLOWED. | | | H2) ROOF TILE OR SHINGLES NOT SUBMITTED | | | I) PREMANUFACTURED A/C STANDS NOT | | | SUBMITTED | | | | | | 14)2ND REQUEST REVERTS BACK TO 13E: | | | 1707.4.5.1 MULLIONS OCCURRING | | | BETWEEN INDIVIDUAL WINDOW AND GLASS | | | DOOR ASSEMBLIES. TESTING REPORTS ARE | | | REQUIRED BY AN APPROVED TESTING | | | LABORATORY OR BE ENGINEERED. | | | | | | 15) 2ND REQUEST REVERTS BACK TO 13E: | | | 1707.4.5.2 MULLIONS SHALL BE DESIGN- | | | ED TO TRANSFER THE DESIGN PRESSURE LOADS | | | APPLIED BY THE WINDOW OR DOOR ASSEMBLIES | | | TO THE ROUGH OPENING SUBTRATE. | | | | | | 16) 2ND REQUEST, SHEET SP. 01 | | | 16A) INDICATES THAT THE TOTAL REQUIRED | | | PARKING SPACES OF 118 PARKING SPOTS. | | | PLANS NOW INDICATE (5) ACCESSIBLE | | | PARKING STALLS, 5.11-4.6.2 LOCATION. | | | ACCESSIBLE PARKING SPACES SERVING A | | | PARTICULAR BUILDING SHALL BE LOCATED ON | | | THE SHORTEST SAFELY ACCESSIBLE ROUTE OF | | | TRAVEL FROM ADJACENT PARKING TO AN | | | ACCESSIBLE ENTRANCE. THE NEW ACCESSIBLE | | | PARKING SPACE SHALL BE AS CLOSE TO THE | | | ENTRANCE AS POSSIBLE. | | | | | | 16B)2ND REQUEST, THIS SHEET NOR A.01 | | | INDICATE CLEARLY THE PASSENGER LOADING | | | ZONE UNDER THE CANOPY PLEASE CLARIFY THE | | | PASSENGER LOADING ZONE, 11-4.6.6 | | | PASSENGER LOADING ZONES. | | | PASSENGER LOADING ZONES SHALL PROVIDE AN | | | ACCESS AISLE AT LEAST 60 INCHES (1525 | | | MM) WIDE AND 20 FEET (6096 MM) LONG | | | ADJACENT AND PARALLEL TO THE VEHICLE | | | PULL-UP SPACE (SEE FIGURE 11-10 ). IF | | | THERE ARE CURBS BETWEEN THE ACCESS AISLE | | | AND THE VEHICLE PULL-UP SPACE, THEN A | | | CURB RAMP COMPLYING WITH SECTION 11-4.7 | | | SHALL BE PROVIDED. VEHICLE STANDING | | | SPACES AND ACCESS AISLES SHALL BE LEVEL | | | WITH SURFACE SLOPES NOT EXCEEDING 1:50 | | | (2 PERCENT) IN ALL DIRECTIONS. | | | | | | 17) COMPLIED. | | | | | | 18)NOTE, REQUIREMENT FOR C. O. | | | SHEET SP.03, NOTE: POOL, | | | SEE DEPARTMENT OF HEALTH FOR REGULATIONS | | | FOR POOL SAFETY FENCE, RULE 64E-9. | | | | | | 19)SHEET A.01: | | | | | | 19A)2ND REQUEST, | | | NEITHER A.01 OR A 4.17 PROVIDE WALL | | | DETAILS INDICATING A 1 HR WALL RATING. | | | THE DOOR 48A DOES NOT INDICATE ANY FIRE | | | RATING ON A.25 OF THE DOOR SCHEDULE. | | | LAUNDRY CHUTE TERMINATION ROOM & | | | DOOR 48ATO MEET THE REQUIREMENTS OF , | | | 707.13.4 TERMINATION ROOM. | | | REFUSE AND LAUNDRY CHUTES SHALL | | | DISCHARGE INTO AN ENCLOSED ROOM | | | COMPLETELY SEPARATED FROM THE REMAINDER | | | OF THE BUILDING BY CONSTRUCTION THAT HAS | | | A FIRE-RESISTANCE RATING OF NOT LESS | | | THAN 1 HOUR AND OPENINGS INTO THE | | | TERMINATION ROOM SHALL BE PROTECTED BY | | | OPENING PROTECTIVES HAVING A FIRE | | | PROTECTION RATING OF NOT LESS THAN ? | | | HOUR AND SHALL BE SELF-CLOSING OR | | | AUTOMATIC-CLOSING UPON THE DETECTION OF | | | SMOKE. REFUSE CHUTES SHALL NOT TERMINATE | | | IN AN INCINERATOR ROOM. REFUSE AND | | | LAUNDRY ROOMS THAT ARE NOT PROVIDED WITH | | | CHUTES NEED ONLY COMPLY WITH TABLE | | | 302.1.1 . | | | | | | 19B)2ND REQUEST, A.02-.04 PLANS ARE | | | TOTALLY MISSING AN ACCESS ROOM FOR THE | | | LAUNDRY CHUTE. | | | 707.13.3 REFUSE AND LAUNDRY CHUTE | | | ACCESS ROOMS. | | | ACCESS OPENINGS FOR REFUSE AND LAUNDRY | | | CHUTES SHALL BE LOCATED IN ROOMS OR | | | COMPARTMENTS COMPLETELY ENCLOSED BY | | | CONSTRUCTION THAT HAS A FIRE-RESISTANCE | | | RATING OF NOT LESS THAN 1 HOUR AND | | | OPENINGS INTO THE ACCESS ROOMS SHALL BE | | | PROTECTED BY OPENING PROTECTIVES HAVING | | | A FIRE PROTECTION RATING OF NOT LESS | | | THAN ? HOUR AND SHALL BE SELF-CLOSING OR | | | AUTOMATIC-CLOSING UPON THE DETECTION OF | | | SMOKE. | | | | | | 19C)2ND REQUEST, | | | PROVIDE A 2 HR SHAFT TO SURROUND | | | THE LAUNDRY CHUTE, 707.4 FIRE-RESISTANCE | | | RATING. SHAFT ENCLOSURES SHALL HAVE A | | | FIRE-RESISTANCE RATING OF NOT LESS THAN | | | 2 HOURS WHERE CONNECTING FOUR STORIES OR | | | MORE AND NOT LESS THAN1 HOUR WHERE | | | CONNECTING LESS THAN FOUR STORIES. THE | | | NUMBER OF STORIES CONNECTED BY THE SHAFT | | | ENCLOSURE SHALL INCLUDE ANY BASEMENTS | | | BUT NOT ANY MEZZANINES. SHAFT ENCLOSURES | | | SHALL BE CONSTRUCTED AS FIRE BARRIERS IN | | | ACCORDANCE WITH SECTION 706 . SHAFT | | | ENCLOSURES SHALL HAVE A FIRE-RESISTANCE | | | RATING NOT LESS THAN THE FLOOR ASSEMBLY | | | PENETRATED, BUT NEED NOT EXCEED 2 HOURS. | | | | | | | | | 19D)2ND REQUEST MISSING FIRE SPRINKLERS | | | LOCATED 707.13.6 AUTOMATIC FIRE | | | SPRINKLER SYSTEM. AN APPROVED AUTOMATIC | | | FIRE SPRINKLER SYSTEM SHALL BE INSTALLED | | | IN ACCORDANCE WITH SECTION 903.2.10.2 . | | | 903.2.10.2 RUBBISH AND LINEN CHUTES. | | | AN AUTOMATIC SPRINKLER SYSTEM SHALL BE | | | INSTALLED AT THE TOP OF RUBBISH AND | | | LINEN CHUTES AND IN THEIR TERMINAL | | | ROOMS. CHUTES EXTENDING THROUGH THREE OR | | | MORE FLOORS SHALL HAVE ADDITIONAL | | | SPRINKLER HEADS INSTALLED WITHIN SUCH | | | CHUTES AT ALTERNATE FLOORS. CHUTE | | | SPRINKLERS SHALL BE ACCESSIBLE FOR | | | SERVICING. | | | | | | 19E)2ND REQUEST, | | | PROVIDE A LIFE SAFETY PLAN FOR | | | EXITING. PROVIDE THE LOADS FROM THE | | | FLOORS ABOVE AS WELL AS THE FIRST FLOOR. | | | TABLE 1004.1.2/ TABLE 1005.1. | | | | | | | | | 19F)COMPLIES. | | | | | | 19G)COMPLIES. | | | . | | | | | | 19H)2ND REQUEST, INDICATE COMPLIANCE | | | WITH,BREAKFAST AREA, THIS SHEET AND | | | A.15 TO INDICATE COMPLIANCE WITH: | | | 11-5.1- 11-5.6. | | | | | | 11-5.2 COUNTERS AND BARS. | | | WHERE FOOD OR DRINK IS SERVED AT | | | COUNTERS EXCEEDING 34 INCHES (865 MM) IN | | | HEIGHT FOR CONSUMPTION BY CUSTOMERS | | | SEATED ON STOOLS OR STANDING AT THE | | | COUNTER, A PORTION OF THE MAIN COUNTER | | | WHICH IS 60 INCHES (1525 MM) IN LENGTH | | | MINIMUM SHALL BE PROVIDED IN COMPLIANCE | | | WITH SECTION 11-4.32 OR SERVICE SHALL BE | | | AVAILABLE AT ACCESSIBLE TABLES WITHIN | | | THE SAME AREA. | | | | | | 11-5.3 ACCESS AISLES. | | | ALL ACCESSIBLE FIXED TABLES SHALL BE | | | ACCESSIBLE BY MEANS OF AN ACCESS AISLE | | | AT LEAST 36 INCHES (915 MM) CLEAR | | | BETWEEN PARALLEL EDGES OF TABLES OR | | | BETWEEN A WALL AND THE TABLE EDGES. | | | | | | 11-5.5 FOOD SERVICE LINES. | | | FOOD SERVICE LINES SHALL HAVE A MINIMUM | | | CLEAR WIDTH OF 36 INCHES (915 MM), WITH | | | A PREFERRED CLEAR WIDTH OF 42 INCHES | | | (1065 MM) TO ALLOW PASSAGE AROUND A | | | PERSON USING A WHEELCHAIR. TRAY SLIDES | | | SHALL BE MOUNTED NO HIGHER THAN 34 | | | INCHES (865 MM) ABOVE THE FLOOR (SEE | | | FIGURE 11-53 ). IF SELF-SERVICE SHELVES | | | ARE PROVIDED, AT LEAST 50 PERCENT OF | | | EACH TYPE MUST BE WITHIN REACH RANGES | | | SPECIFIED IN SECTIONS 11-4.2.5 AND | | | 11-4.2.6 . | | | | | | 11-5.6 TABLEWARE AND CONDIMENT AREAS. | | | SELF-SERVICE SHELVES AND DISPENSING | | | DEVICES FOR TABLEWARE, DISHWARE, | | | CONDIMENTS, FOOD AND BEVERAGES SHALL BE | | | INSTALLED TO COMPLY WITH SECTION 11-4.2 | | | (SEE FIGURE 11-54 ). | | | | | | 19I)2ND REQUEST, PROVIDE WHERE I CAN | | | FIND THIS INFORMATION? INDICATE | | | COMPLIANCE WITH: 11-9.3 | | | VISUAL ALARMS, NOTIFICATION DEVICES AND | | | TELEPHONES. 11-9.3.1 GENERAL. | | | IN SLEEPING ROOMS REQUIRED TO COMPLY | | | WITH THIS SECTION, AUXILIARY VISUAL | | | ALARMS SHALL BE PROVIDED AND SHALL | | | COMPLY WITH SECTION 11-4.28.4 . VISUAL | | | NOTIFICATION DEVICES SHALL ALSO BE | | | PROVIDED IN UNITS, SLEEPING ROOMS AND | | | SUITES TO ALERT ROOM OCCUPANTS OF | | | INCOMING TELEPHONE CALLS AND A DOOR | | | KNOCK OR BELL. | | | NOTIFICATION DEVICES SHALL NOT BE | | | CONNECTED TO AUXILIARY VISUAL ALARM | | | SIGNAL APPLIANCES. PERMANENTLY INSTALLED | | | TELEPHONES SHALL HAVE VOLUME CONTROLS | | | COMPLYING WITH SECTION 11-4.31.5 ; AN | | | ACCESSIBLE ELECTRICAL OUTLET WITHIN 4 | | | FEET (1219 MM) OF A TELEPHONE CONNECTION | | | SHALL BE PROVIDED TO FACILITATE THE USE | | | OF A TEXT TELEPHONE. | | | | | | 20) SHEET A.02- A.04: | | | | | | 20A) 2ND REQUEST PLANS INDICATE NEXT TO | | | THE ELEVATOR A SHAFT BUT NO DETAILS TO | | | HR CONSTRUCTION, 707.4. | | | | | | 20B) REPEAT OF 20A. | | | | | | 21)2ND REQUEST.THE PLANS INDICATE A | | | DETAIL A.15 DETAIL# 5 FOR HANDRAILS, | | | THE DETAIL IS NOT FOR HANDRAILS OR | | | EXTENTIONS. THE OTHER ISSUE IS A NOTE | | | EXTEND STAIR RAIL EAST STAIR ONLY, NO | | | INFORMATION IS PROVIDED FOR THE BOTTOM | | | OF HANDRAILS NOR EXTENTIONS. | | | SHEET A.20 & A.21 BOTH INDICATE | | | STAIR TOWERS BUT NO DETAIL SHEET | | | INDICATING THE HANDRAIL GUARD RAIL | | | COMPLYING WITH 11-4.9.4(2)IF | | | HANDRAILS ARE NOT CONTINUOUS, THEY SHALL | | | EXTEND AT LEAST 12 INCHES (305 MM) | | | BEYOND THE TOP RISER AND AT LEAST 12 | | | INCHES (305 MM) PLUS THE WIDTH OF ONE | | | TREAD BEYOND THE BOTTOM RISER. AT THE | | | TOP, THE EXTENSION SHALL BE PARALLEL | | | WITH THE FLOOR OR GROUND SURFACE. AT THE | | | BOTTOM, THE HANDRAIL SHALL CONTINUE TO | | | SLOPE FOR A DISTANCE OF THE WIDTH OF ONE | | | TREAD FROM THE BOTTOM RISER; THE | | | REMAINDER OF THE EXTENSION SHALL BE | | | HORIZONTAL [SEE FIGURE 11-19 (C) AND | | | FIGURE 11-19 (D)]. HANDRAIL EXTENSIONS | | | SHALL COMPLY WITH SECTION 11-4.4 . | | | DETAILS ON A.15 ARE MISSING. | | | | | | 22) SHEET A.23: | | | | | | 22A) RESPONCE FIREPLACE DELETED, SEE | | | A.05 PLAANS INDICATE CHIMNEY. PLEASE | | | CORRECT. | | | | | | 22B)2ND REQUEST. | | | MISSING SECTIONS ON A.24A DETAILS | | | 1-4. | | | NOTE DETAIL 3 IS USED IN THE | | | CLEARSTORY AS WELL AS COMMEON TRUSS | | | DETAIL FOR HIP END. CORRECT. | | | | | | 22C) COMPLIED. | | | | | | 22D) 2ND REQUEST.THIS IS A FOUR STORY | | | BUILDING, SHOW PRODUCT APPROVAL REPORT | | | WHERE SHINGLES WILL BE ABLE TO BE USED | | | WITH A MEAN ROOF HEIGTH OF OVER 40'-0"? | | | SHEET A.23 @ CLEARSTORY, DARK GREEN | | | ASPHALT SHINGLES. | | | | | | 23) SHEET A.25 DOOR SCHEDULE: | | | | | | 23A)2ND REQUEST.INDICATE ON HARDWARE | | | SCHEDULE. DOOR SCHEDULE DOESN,T INDICATE | | | ANY HARDWARE FOR FIRE RATED DOORS, | | | PLEASE SEE SECTION:715.3.3 FOR REQUIRED | | | HARDWARE INCLUDING CLOSERS AND | | | ARTIFICIAL BOTTOM SEAL INSTALLED ACROSS | | | THE BOTTOM OF THE DOOR TESTED IN | | | ACCORDANCE WITH UL 1784. | | | | | | B)NOTE: LOUVERS ARE PROHIBITED IN FIRE | | | RATED DOORS. THE ELEVATIONS DO NOT | | | INDICATE THE BOILERE ROOM DOORS ON THE | | | ELEVATION. WHEN LOOKING AT THE | | | MECHANICAL PLANS IT APPEARS THAT THERE | | | MAY NOT BE ENOUGH MAKE UP AIR, FOR THIS | | | REASON THE COMMENT WAS MADE. | | | | | | 24) COMPLIED. | | | | | | 25) COMPLIED. | | | | | | 26) 2ND REQUEST, PLANS DO NOT PROVIDE | | | MINIMUM BLDG TYPE! S3.1, A.23 NO DETAILS | | | INDICATE THE TYPE OF MATERIAL TO BE USED | | | FOR ROOF SHEATHING. PLANS ALSO DO NOT | | | PROVIDE THE MINIMUM BUILDING DESIGN | | | TABLE 503/ 601. | | | | | | NEW COMMENTS: | | | | | | 27)1207.2 AIR-BORNE SOUND. | | | WALLS, PARTITIONS AND FLOOR/CEILING | | | ASSEMBLIES SEPARATING DWELLING UNITS | | | FROM EACH OTHER OR FROM PUBLIC OR | | | SERVICE AREAS SHALL HAVE A SOUND | | | TRANSMISSION CLASS (STC) OF NOT LESS | | | THAN 50 (45 IF FIELD TESTED) FOR | | | AIR-BORNE NOISE WHEN TESTED IN | | | ACCORDANCE WITH ASTM E 90. PENETRATIONS | | | OR OPENINGS IN CONSTRUCTION ASSEMBLIES | | | FOR PIPING; ELECTRICAL DEVICES; RECESSED | | | CABINETS; BATHTUBS; SOFFITS; OR HEATING, | | | VENTILATING OR EXHAUST DUCTS SHALL BE | | | SEALED, LINED, INSULATED OR OTHERWISE | | | TREATED TO MAINTAIN THE REQUIRED | | | RATINGS. THIS REQUIREMENT SHALL NOT | | | APPLY TO DWELLING UNIT ENTRANCE DOORS; | | | HOWEVER, SUCH DOORS SHALL BE TIGHT | | | FITTING TO THE FRAME AND SILL. | | | | | | 28) 1207.3 STRUCTURE-BORNE SOUND. | | | FLOOR/CEILING ASSEMBLIES BETWEEN | | | DWELLING UNITS OR BETWEEN A DWELLING | | | UNIT AND A PUBLIC OR SERVICE AREA WITHIN | | | THE STRUCTURE SHALL HAVE AN IMPACT | | | INSULATION CLASS (IIC) RATING OF NOT | | | LESS THAN 50 (45 IF FIELD TESTED) WHEN | | | TESTED IN ACCORDANCE WITH ASTM E 492. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-02-28 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-02-28 |
Time |
11:55 |
Rev Time |
8.88 |
| Received By |
jwitmer |
Date |
2006-02-28 |
Time |
11:55 |
Sent To |
|
|
| Notes |
| 2006-02-28 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 05110263 | | | ADD: LOT# 7 CENTERPARK WEST | | | CONT: "PLAN REVIEW" HILTON | | | JOHN COSTAS | | | TEL: (561)523-3699 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | | | | ***IMPORTANT*** | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | | | | | | | 1) PROVIDE NOC RECORDED WITH THE CLERK | | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | | NOTE NOC WILL BE NULL & VOID 90 DAYS | | | AFTER RECORDING AT THE CLERK OF THE | | | COURTS OFFICE IF WORK HAS NOT STARTED. | | | FL S S 713.13(2). | | | | | | 2) FL BLD CODE 1804.2.2 QUESTIONABLE | | | SOILS, WHERE THE BEARING CAPACITY IS | | | NOT DEFINETLY KNOWN OR IS IN QUESTION. | | | WHERE THE BEARING CAPACITY OF THE SOIL | | | IS NOT DEFINITLY KNOWN OR IS IN QUESTION | | | THE BUILDING OFFICIAL MAY REQUIRE EXPLOR | | | ATIONS, TEST OR OTHER ADEQUATE PROOF AS | | | TO THE PERMISSIBLE SAFE BEARING | | | CAPACITY. REQUIRED TEST AND RECOMMENDA- | | | TIONS SUBMITTED TO VERIFY BEARING CAPA- | | | CITY SHALL BE CERTIFIED BY A GEOTECH- | | | NICALREPORT FROM A DESIGN PROFESSIONAL | | | PROPERLY LICENSED IN THE STATE OF | | | FLORIDA. | | | | | | 3)BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 4)FL S. S. 553.71(7) " THRESHOLD | | | BUILDING" MEANING ANY BUILDING WHICH IS | | | GREATER THAN (3) STORIES OR 50 FT IN | | | HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN | | | CY CLASSIFICATION AS DEINED IN THE | | | FLORIDA BUILDING CODE WHICH EXCEEDS | | | 5,000 SQ FT IN AREA AND AN OCCUPANT | | | CONTENT OF GREATER THAN 500 PERSONS. | | | | | | 105.13.1 THE ENFORCING AGENCY SHALL | | | REQUIRE A SPECIAL INSPECTOR TO PERFORM | | | SRUCTURAL INSPECTIONS ON A THRESHOLD | | | BUILDING PURSUANT TO A STRUCTURAL INSPEC | | | TION PLAN PREPARED BY THE ENGINEER OF | | | RECORD. THE STRUCTURAL INSPECTION PLAN | | | MUST BE SUBMITTED TO THE ENFORCING AGEN- | | | CY PRIOR TO THE ISSUANCE OF A BUILDING | | | PERMIT FOR THE CONSTRUCTION OF A THRESH- | | | OLD BUILDING. THE PURPOSE OF THE SRUCTUR | | | AL INSPECTION PLAN IS TO PROVIDE SPECIF- | | | IC INSPECTION PROCEDURES AND SCHEDULES | | | SO THAT THE BUILDING CAN BE ADEQUATELY | | | INSPECTED FOR COMPLIANCE WITH THE | | | PERMITTED DOCUMENTS. | | | | | | 5) WPB AMENDMENT 105.13.6. W.P.B. | | | CONSTRUCTION SERVICES DEPARTMENT | | | REQUEST FOR THRESHOLD BUILDINGS A | | | SPECIAL INSPECTOR AS REQUIRED BY S. | | | 553.79(5) FLORIDA STATUTES TO THE MIN- | | | IMUM INSPECTIONS REQUIRED BY THIS CODE. | | | CONTACT HAROLD PISKURA MANAGER OF THE | | | SPECIAL INSPECTOR PROGRAM AT (561) | | | 805-6711 FOR FURTHER INFORMATION BEFORE | | | THE PERMIT MAY BE ISSUED. | | | | | | 6) W.P.B. AMENDMENT 105.13.4.4 ALL PLANS | | | FOR THE BUILDING WHICH ARE REQUIRED TO | | | BE SIGNED AND SEALED BY THE ARCHITECT OR | | | ENGINEER OF RECORD CONTAIN A STATEMENT | | | THAT, TO THE BEST OF THE ARCHITECT'S OR | | | ENGINEER'S KNOWLEDGE, THE PLANS AND | | | SPECIFICATIONS COMPLY WITH THE | | | APPLICABLE FIRE-SAFETY STANDARDS AS | | | DETERMINED BY THE LOCAL AUTHORITY IN | | | ACCORDANCE WITH THIS SECTION AND 633 | | | FLORIDA STATUTE. | | | THIS STATEMENT IS FOUND ON THE | | | STRUCTURAL SHEETS BUT NOT THE | | | ARCHITECTURAL SHEETS. | | | | | | 7A) CONTACT LILI URSA FOR ADDRESSING | | | REQUIREMENTS @ (561)822-1239 | | | | | | 7B)PROVIDE A COPY OF THE NEW PLAT, SHEET | | | SP.01 APPEARS TO HAVE BEEN SUBDIVIDED | | | WITH ADDITIONAL BUILDINGS TO BE ON THE | | | SAME LOT. | | | | | | 7C) PLEASE FILL OUT AN ACTUAL | | | APPLICATION SHEET PROVIDING THE PROPERTY | | | CONTROL NUMBER FOR ADDRESSING. | | | | | | 7D) PROVIDE A SURVEY OF THE SITE. | | | | | | 8) ADDITIONAL INFORMATION REQUIRED FOR | | | RECORD KEEPING PURPOSES 106.1.2*: | | | 8)A) FLOOD ZONE | | | 8)B) FLOOD ELEVATION (IF A ZONE) | | | 8)C) LOMAR (IF A ZONE) | | | 8)D) NUMBER OF UNITS | | | 8)E) NUMBER OF FLOORS | | | 8)F) NUMBER OF BEDROOMS | | | 8)G) NUMBER OF ROOMS | | | 8)H) NUMBER OF BATHROOM | | | 88)I) SQ FT LIVING SPACE(TOTAL) | | | 8)J) SQ FT FOOT PRINT | | | 8)K) SQ FT UNDER ROOF (TOTAL) | | | | | | 9) 109.3.10* IMPACT OF CONSTRUCTION. ALL | | | CONSTRUCTION ACTIVITY REGULATED BY THIS | | | CODE SHALL BE PERMORMED IN A MANNER SO | | | AS NOT TO ADVERSLY IMPACT THE CONDITION | | | OF ADJACENT PROPERTY, UNLESS SUCH | | | ACTIVITY IS PERMITTED TO AFFECT SAID | | | PROPERTY PURSUANT TO A CONSENT BY THE | | | APPLICABLE PROPERTY OWNER, UNDER TERMS & | | | CONDITIONS AGREEABLE TO THE APPLICABLE | | | PROPERTY OWNER.THIS INCLUDES BUT IS NOT | | | LIMITED TO THE CONTROL OF DUST, NOISE, | | | WATER OR DRAINAGE RUN-OFF, DEBRIS, AND | | | THE STORAGE OF CONSTRUCTION MATERIALS. | | | NEW CONSTRUCTION ACTIVITY SHALL NOT | | | ADVERSELY IMPACT HISTORICSURFACE WATER | | | DRAINAGE FLOWS SERVING ADJACENT | | | PROPERTIES, & MAY REQUIRE SPECIAL | | | DRAINAGE DESIGNCOMPLYING WITH | | | ENGINEERING STANDARDS TO PRESERVE THE | | | POSITIVE PATTERNS OF THE AFFECTED | | | SITES.ACCORDINGLY, DEVELOPERS, | | | CONTRACTORS, AND OWNERS OF ALL NEW | | | RESIDENTIAL DEVELOPMENET, INCLUDING | | | ADDITIONS, POOLS, PATIOS, DRIVEWAYS, | | | DECKS, OR SIMILAR ITEMS, ON EXISTING | | | PROPERTIES RESULTING IN A DECREASE IN | | | EXCESS OF 800SQ FT OF PERMEABLE LAND | | | AREA ON ANY PARCELL SHALL AS A PERMIT | | | CONDITION, PROVIDE A PROFESSIONALY | | | PREPARED DRAINAGE PLAN CLEARLY | | | INDICATING COMPLIANCE WITH THIS | | | PARAGRAPH. UPON COMPLETION OF THE | | | IMPROVEMENT, A CERTIFICATE FROM A | | | LICENSED ENGINEER SHALL BE SUBMITTED TO | | | THE INSPECTOR IN ORDER TO RECEIVE | | | APPROVAL OF THE FINAL INSPECTION. | | | | | | 10) SINCE THISWILL BE A THRESHOLD | | | PROJECT (3) SETS OF ALL INFORMATION | | | SUBMITTED WILL BE REQUIRED. | | | | | | 11) 1609.1.4 PROTECTION OF OPENINGS. | | | IN WIND-BORNE DEBRIS REGIONS, EXTERIOR | | | GLAZING THAT RECEIVES POSITIVE PRESSURE | | | IN THE LOWER 60 FEET (18.3 M) IN | | | BUILDINGS SHALL BE ASSUMED TO BE | | | OPENINGS AND THE BALANCE OF GLAZED | | | OPENINGS IN THE REST OF THE BUILDING | | | SHALL BE ASSUMED TO BE ZERO UNLESS SUCH | | | GLAZING THAT RECEIVES POSITIVE PRESSURE | | | IS IMPACT RESISTANT OR PROTECTED WITH AN | | | IMPACT RESISTANT COVERING MEETING THE | | | REQUIREMENTS OF SSTD 12, ASTM E 1886 AND | | | ASTM E 1996, OR MIAMI-DADE TAS 201, 202 | | | AND 203 REFERENCED THEREIN AS FOLLOWS: | | | 1.GLAZED OPENINGS LOCATED WITHIN 30 | | | FEET (9.1 M) OF GRADE SHALL MEET THE | | | REQUIREMENTS OF THE LARGE MISSILE TEST. | | | 2.GLAZED OPENINGS LOCATED MORE THAN | | | 30 FEET (9.1 M) ABOVE GRADE SHALL MEET | | | THE PROVISIONS OF THE SMALL MISSILE | | | TEST. | | | | | | 12) PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 13) FL BLD CODE 1606.1.5: COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | | TESTING REPORTS,MISSING REPORTS ARE AS | | | FOLLOWS: | | | A) WINDOWS NO WINDOW SCHEDULE ON INDEX | | | SHEET | | | B) EXTERIOR DOORS, SOLID | | | C) EXTERIOR DOORS GLAZED | | | D) EXTERIOR DOORS BYPASS | | | E) MULLIONS | | | F) LOUVERS | | | G) TRUSS ANCHORS | | | H) ROOF ASSEMBLIES, FLAT AND TILE | | | I) PREMANUFACTURED A/C STANDS | | | | | | 14) 1707.4.5.1 MULLIONS OCCURRING | | | BETWEEN INDIVIDUAL WINDOW AND GLASS | | | DOOR ASSEMBLIES. TESTING REPORTS ARE | | | REQUIRED BY AN APPROVED TESTING | | | LABORATORY OR BE ENGINEERED. | | | | | | 15) 1707.4.5.2 MULLIONS SHALL BE DESIGN- | | | ED TO TRANSFER THE DESIGN PRESSURE LOADS | | | APPLIED BY THE WINDOW OR DOOR ASSEMBLIES | | | TO THE ROUGH OPENING SUBTRATE. | | | | | | 16) SHEET SP. 01 | | | 16A) INDICATES THAT THE TOTAL REQUIRED | | | PARKING SPACES OF 118 PARKING SPOTS. | | | PLANS ONLY INDICATE (4) | | | ACCESSIBLE PARKING STALLS, 11-4.1.2(5) | | | IF TOTAL PARKING SPOTS ARE BETWEEN 101 | | | TO 150 THEN THE MINIMUM NUMBER ODF | | | ACCESSIBLE SPACES ARE 5. | | | | | | 16B) THIS SHEET NOR A.01 INDICATE | | | CLEARLY THE PASSENGER LOADING ZONE UNDER | | | THE CANOPY PLEASE CLARIFY THE PASSENGER | | | LOADING ZONE, 11-4.6.6 PASSENGER LOADING | | | ZONES. | | | PASSENGER LOADING ZONES SHALL PROVIDE AN | | | ACCESS AISLE AT LEAST 60 INCHES (1525 | | | MM) WIDE AND 20 FEET (6096 MM) LONG | | | ADJACENT AND PARALLEL TO THE VEHICLE | | | PULL-UP SPACE (SEE FIGURE 11-10 ). IF | | | THERE ARE CURBS BETWEEN THE ACCESS AISLE | | | AND THE VEHICLE PULL-UP SPACE, THEN A | | | CURB RAMP COMPLYING WITH SECTION 11-4.7 | | | SHALL BE PROVIDED. VEHICLE STANDING | | | SPACES AND ACCESS AISLES SHALL BE LEVEL | | | WITH SURFACE SLOPES NOT EXCEEDING 1:50 | | | (2 PERCENT) IN ALL DIRECTIONS. | | | | | | 17) SHEET SP.02 REFLECTING POOL PROVIDE | | | A CROSS SECTION OF THIS SITE AMENITY, | | | 11-4.29.6 DETECTABLE WARNINGS AT | | | REFLECTING POOLS. THE EDGES OF | | | REFLECTING POOLS SHALL BE PROTECTED BY | | | RAILINGS, WALLS, CURBS, OR DETECTABLE | | | WARNINGS COMPLYING WITH 11-4.29.2. | | | | | | 18)SHEET SP.03, NOTE: POOL, | | | SEE DEPARTMENT OF HEALTH FOR REGULATIONS | | | FOR POOL SAFETY FENCE, RULE 64E-9. | | | | | | 19)SHEET A.01: | | | | | | 19A) LAUNDRY CHUTE TERMINATION ROOM & | | | DOOR 48ATO MEET THE REQUIREMENTS OF , | | | 707.13.4 TERMINATION ROOM. | | | REFUSE AND LAUNDRY CHUTES SHALL | | | DISCHARGE INTO AN ENCLOSED ROOM | | | COMPLETELY SEPARATED FROM THE REMAINDER | | | OF THE BUILDING BY CONSTRUCTION THAT HAS | | | A FIRE-RESISTANCE RATING OF NOT LESS | | | THAN 1 HOUR AND OPENINGS INTO THE | | | TERMINATION ROOM SHALL BE PROTECTED BY | | | OPENING PROTECTIVES HAVING A FIRE | | | PROTECTION RATING OF NOT LESS THAN ? | | | HOUR AND SHALL BE SELF-CLOSING OR | | | AUTOMATIC-CLOSING UPON THE DETECTION OF | | | SMOKE. REFUSE CHUTES SHALL NOT TERMINATE | | | IN AN INCINERATOR ROOM. REFUSE AND | | | LAUNDRY ROOMS THAT ARE NOT PROVIDED WITH | | | CHUTES NEED ONLY COMPLY WITH TABLE | | | 302.1.1 . | | | | | | 19B) 707.13.3 REFUSE AND LAUNDRY CHUTE | | | ACCESS ROOMS. | | | ACCESS OPENINGS FOR REFUSE AND LAUNDRY | | | CHUTES SHALL BE LOCATED IN ROOMS OR | | | COMPARTMENTS COMPLETELY ENCLOSED BY | | | CONSTRUCTION THAT HAS A FIRE-RESISTANCE | | | RATING OF NOT LESS THAN 1 HOUR AND | | | OPENINGS INTO THE ACCESS ROOMS SHALL BE | | | PROTECTED BY OPENING PROTECTIVES HAVING | | | A FIRE PROTECTION RATING OF NOT LESS | | | THAN ? HOUR AND SHALL BE SELF-CLOSING OR | | | AUTOMATIC-CLOSING UPON THE DETECTION OF | | | SMOKE. | | | | | | 19C) PROVIDE A 2 HR SHAFT TO SURROUND | | | THE LAUNDRY CHUTE, 707.4 FIRE-RESISTANCE | | | RATING. SHAFT ENCLOSURES SHALL HAVE A | | | FIRE-RESISTANCE RATING OF NOT LESS THAN | | | 2 HOURS WHERE CONNECTING FOUR STORIES OR | | | MORE AND NOT LESS THAN1 HOUR WHERE | | | CONNECTING LESS THAN FOUR STORIES. THE | | | NUMBER OF STORIES CONNECTED BY THE SHAFT | | | ENCLOSURE SHALL INCLUDE ANY BASEMENTS | | | BUT NOT ANY MEZZANINES. SHAFT ENCLOSURES | | | SHALL BE CONSTRUCTED AS FIRE BARRIERS IN | | | ACCORDANCE WITH SECTION 706 . SHAFT | | | ENCLOSURES SHALL HAVE A FIRE-RESISTANCE | | | RATING NOT LESS THAN THE FLOOR ASSEMBLY | | | PENETRATED, BUT NEED NOT EXCEED 2 HOURS. | | | | | | | | | 19D) 707.13.6 AUTOMATIC FIRE SPRINKLER | | | SYSTEM. AN APPROVED AUTOMATIC FIRE | | | SPRINKLER SYSTEM SHALL BE INSTALLED IN | | | ACCORDANCE WITH SECTION 903.2.10.2 . | | | | | | 19E) PROVIDE A LIFE SAFETY PLAN FOR | | | EXITING. PROVIDE THE LOADS FROM THE | | | FLOORS ABOVE AS WELL AS THE FIRST FLOOR. | | | TABLE 1004.1.2/ TABLE 1005.1. | | | | | | 19F) MEETING ROOM # 34 OCC LOAD OF 96, | | | 24X28=672/7= 96 OCC LOAD.1014.1 EXIT OR | | | EXIT ACCESS DOORWAYS REQUIRED. | | | | | | 19G)TWO EXITS OR EXIT ACCESS DOORWAYS | | | FROM ANY SPACE SHALL BE PROVIDED WHERE | | | ONE OF THE FOLLOWING CONDITIONS EXISTS: | | | 1014.1.(1)THE OCCUPANT LOAD OF THE | | | SPACE EXCEEDS THE VALUES IN TABLE 1014.1 | | | . | | | | | | 19H) BREAAKFAST AREA, THIS SHEET AND | | | A.15 TO INDICATE COMPLIANCE WITH: | | | 11-5.1- 11-5.6. | | | | | | 19I) INDICATE COMPLIANCE WITH: 11-9.3 | | | VISUAL ALARMS, NOTIFICATION DEVICES AND | | | TELEPHONES. 11-9.3.1 GENERAL. | | | IN SLEEPING ROOMS REQUIRED TO COMPLY | | | WITH THIS SECTION, AUXILIARY VISUAL | | | ALARMS SHALL BE PROVIDED AND SHALL | | | COMPLY WITH SECTION 11-4.28.4 . VISUAL | | | NOTIFICATION DEVICES SHALL ALSO BE | | | PROVIDED IN UNITS, SLEEPING ROOMS AND | | | SUITES TO ALERT ROOM OCCUPANTS OF | | | INCOMING TELEPHONE CALLS AND A DOOR | | | KNOCK OR BELL. | | | NOTIFICATION DEVICES SHALL NOT BE | | | CONNECTED TO AUXILIARY VISUAL ALARM | | | SIGNAL APPLIANCES. PERMANENTLY INSTALLED | | | TELEPHONES SHALL HAVE VOLUME CONTROLS | | | COMPLYING WITH SECTION 11-4.31.5 ; AN | | | ACCESSIBLE ELECTRICAL OUTLET WITHIN 4 | | | FEET (1219 MM) OF A TELEPHONE CONNECTION | | | SHALL BE PROVIDED TO FACILITATE THE USE | | | OF A TEXT TELEPHONE. | | | | | | 20) SHEET A.02- A.04: | | | | | | 20A) PLANS INDICATE NEXT TO THE ELEVATOR | | | A SHAFT BUT NO DETAILS TO HR | | | CONSTRUCTION OR WHAT IT WILL BE USED | | | FOR?707.4. | | | | | | 20B) PLANS ALSO INDICATE A SHAFT NEXT TO | | | THE ELEVATOR SHAFT NO CUT SECTION? | | | USAGE? | | | | | | 21) SHEET A.20 & A.21 BOTH INDICATE | | | STAIR TOWWERS BUT NO DETAIL SHEET | | | INDICATING THE HANDRAIL GUARD RAIL | | | COMPLYING WITH 11-4.9.4(2)IF | | | HANDRAILS ARE NOT CONTINUOUS, THEY SHALL | | | EXTEND AT LEAST 12 INCHES (305 MM) | | | BEYOND THE TOP RISER AND AT LEAST 12 | | | INCHES (305 MM) PLUS THE WIDTH OF ONE | | | TREAD BEYOND THE BOTTOM RISER. AT THE | | | TOP, THE EXTENSION SHALL BE PARALLEL | | | WITH THE FLOOR OR GROUND SURFACE. AT THE | | | BOTTOM, THE HANDRAIL SHALL CONTINUE TO | | | SLOPE FOR A DISTANCE OF THE WIDTH OF ONE | | | TREAD FROM THE BOTTOM RISER; THE | | | REMAINDER OF THE EXTENSION SHALL BE | | | HORIZONTAL [SEE FIGURE 11-19 (C) AND | | | FIGURE 11-19 (D)]. HANDRAIL EXTENSIONS | | | SHALL COMPLY WITH SECTION 11-4.4 . | | | DETAILS ON A.15 ARE MISSING. | | | | | | 22) SHEET A.23: | | | | | | 22A) PLANS INDICATE THE USE OF A PREFAB | | | FIREPLACE AND FLUE SUBMIT ADDITIONAL | | | INFORMATION: | | | | | | 22B) MISSING SECTIONS ON A.24A DETAILS | | | 1-4. NOTE DETAIL 3 IS USED IN THE | | | CLEARSTORY AS WELL AS COMMEON TRUSS | | | DETAIL FOR HIP END. CORRECT. | | | | | | 22C) SUBMIT STRUCTURAL PLANS INDICATING | | | HOW TO BUILD THE SURROUND AROUND THE | | | PREFAB FLUE? | | | | | | 22D) THIS IS A FOUR STORY BUILDING, SHOW | | | | | | PRODUCT APPROVAL REPORT WHERE SHINGLES | | | WILL BE ABLE TO BE USED WITH A MEAN ROOF | | | HEIGTH OF OVER 40'-0"? | | | | | | 23) SHEET A.25 DOOR SCHEDULE: | | | | | | 23A) DOOR SCHEDULE DOESN,T INDICATE ANY | | | HARDWARE FOR FIRE RATED DOORS, PLEASE | | | SEE SECTION:715.3.3 FOR REQUIRED | | | HARDWARE INCLUDING CLOSERS AND | | | ARTIFICIAL BOTTOM SEAL INSTALLED ACROSS | | | THE BOTTOM OF THE DOOR TESTED IN | | | ACCORDANCE WITH UL 1784. | | | | | | B) LOUVERS ARE OROHIBITED IN FIRE RATED | | | DOORS. | | | | | | 24) A.27WALL TYPE 11A PROVIDE A DESIGN | | | NUMBER FOR 2 HR RATED SHAFT DESIGN | | | | | | 25) A.34 PUBLIC RESTROOMS:1210.2 WALLS. | | | WALLS WITHIN 2 FEET (610 MM) OF URINALS | | | AND WATER CLOSETS SHALL HAVE A SMOOTH, | | | HARD, NONABSORBENT SURFACE, TO A HEIGHT | | | OF 4 FEET (1219 MM) ABOVE THE FLOOR, AND | | | EXCEPT FOR STRUCTURAL ELEMENTS, THE | | | MATERIALS USED IN SUCH WALLS SHALL BE OF | | | A TYPE THAT IS NOT ADVERSELY AFFECTED BY | | | MOISTURE. | | | | | | 26) S3.1, A.23 NO DETAILS INDICATE THE | | | TYPE OF MATERIAL TO BE USED FOR ROOF | | | SHEATHING. PLANS ALSO DO NOT PROVIDE THE | | | MINIMUM BUILDING DESIGN TABLE 503/ 601. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2007-01-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-01-14 |
Time |
14:35 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-01-14 |
Time |
13:32 |
Sent To |
|
|
| Notes |
| 2007-01-14 14:35:28 | REV'S E1-E15 OK. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2006-08-23 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-08-23 |
Time |
13:32 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-08-23 |
Time |
20:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2006-06-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-06-08 |
Time |
20:56 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-06-08 |
Time |
20:33 |
Sent To |
|
|
| Notes |
| 2006-06-08 00:00:00 | IN ELEC FOR REVIEW, REVIEW IN PROGRESS. | | | ** ELECTRICAL SHEETS STAMPED IN ALL | | | 3-SETS. | | | | | | ALL NOTES ADDRESSED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2006-04-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-04-14 |
Time |
16:39 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-04-13 |
Time |
15:42 |
Sent To |
|
|
| Notes |
| 2006-04-14 00:00:00 | ************ UNSAT 2ND REVIEW ********* | | | | | | HILTON GARDENS INN | | | | | | ** PLEASE KNOW, PLANS TO DATE HAVE STILL | | | NOT BEEN SUBMITTED FOR PERMIT FOR | | | BUILDING AND PLANS ARE ONLY SUBMITTED | | | FOR "PLAN REVIEW". | | | | | | ** PLEASE SEE MANY NOTES FROM PREVIOUS | | | REVIEW WHICH ARE IN NEED OF BEING | | | ADDRESSED AND SOME NEW NOTES FOR ITEMS | | | CHANGED AND/OR NOW SUBMITTED FOR REVIEW> | | | PLEASE SEE NOTES BELOW ARE TAKEN | | | DIRECTLY FROM PREVIOUS REVIEW. | | | | | | | | | 1A) NOTE: NO, PLEASE SEE NO INFORMATION | | | WAS SUBMITTED AND NO CHANGES OR | | | ADJUSTMENTS COULD BE LOCATED ON PLANS | | | FOR COMPLIANCE TO THE 2004 FBC CHAPTER | | | 13. 13-413.1ABC.1.1,13-415.1.ABC.1.1, | | | 13-415.1.ABC.1.2,13-415.1.ABC.1.4 ETC. | | | PLEAS KNOW, IN THE RESPONSE PACKAGE FROM | | | DESIGN PROFESSIONALNO RESPONSE WAS | | | INDICATED. | | | | | | ** PREVIOUS NOTE** | | | PLEASE SEE 2004 FCB CHAPTER 13 | | | HOTELS, ROOM OCCUPANCY CONTROLS FOR AND | | | OTHER CONTROL FOR COMMON AREAS. | | | | | | | | | | | | 1)NOTE: NO, PLEASE SEE THESE COULD NOT | | | BE LOCATED ON PLANS FOR ADDED CODES AND | | | RESPONSE LETTER DOES NOT RESPONSED TO | | | THIS NOTE. | | | | | | ** PREVIOUS NOTE** | | | PLEASE BE SURE PLANS REFERENCE | | | CURRENT CODES IN EFFECT. | | | 2002 NFPA-70 (NEC), 2003 NFPA-101, 2002 | | | NFPA-72 ETC | | | | | | 2)NOTE:OK, HOWEVER PLEASE SEE | | | ARCHITECTURAL PLANS DO NOT CORRELATE | | | WITH DOOR SWINGS AND PLEASE ALSO SEE | | | POSSIBLE CONFLICT WIHT THE SWING OF | | | OTHER DOOR ON PLANS. PLEASE SEE IF ONE | | | DOOR IS BEING OPENED AND THE SINGLE DOOR | | | FROM MAIN ELECTRICAL ROOM ALSO OPENS | | | THESE WILL INTERSECT IN THE CENTER OF | | | HALL EGRESS AREA. PLEASE SEE DOOR | | | HINGE/SWING SIDE MAY NEED TO BE REVERSED | | | TO AVOIDE THIS INTERFERENCE. | | | | | | ** PREVVIOUS NOTE ** | | | PLEASE SEE MAIN ELECTRICAL ROOM | | | DOORS WILL BE REQUIRED TO OPEN OUTWARD | | | AND SHALL HAVE PANIC HARDWARE. | | | 110.26 | | | | | | 3)NOTE:OK, HOWEVER SEE NEW NOTES FOR | | | CORRELATION OF FIXTURES ETC. | | | | | | ** PREVIOUS NOTE** | | | PLEASE BE SURE ALL ELECTRICAL RMS, | | | ELEVATOR EQUIPMENT RMS CONTAIN A | | | BATTERY BACK UP LIGHT OF SOME SORT. | | | LS101 7.8,7.9, 700.16 | | | | | | 4)NOTE: OK. | | | | | | | | | 5)NOTE: OK. | | | | | | 6)NOTE:NO, PLEASE SEE SOME AREAS/ITEMS | | | ON PLANS ARE REDLINED WHERE FIXTURES AND | | | EQUIPMENT IS NOT CIRCUITED. PLEASE ALSO | | | PLEASE SEE GUEST ROOMS DO NOT INDICATE | | | THE CIRCUITING. PLEASE SEE RESPONSE LTR | | | MENTIONS THESE WERE ALL DONE, HOWEVER | | | PLEASE SEE PLANS. | | | | | | ** PREVIOUS NOTE ** | | | PLEASE COMPLETE ALL OTHER CIRCUITING, | | | GUEST RMS ETC. 215.5 | | | | | | 7)NOTE: OK. | | | | | | 8)NOTE: OK. | | | | | | 9)NOTE:OK, HOWEVER PLEASE SEE | | | DESCREPANCIES IN THE PHOTO-METRICS, AND | | | FIXTURE TYPES. PLEASE SEE THE | | | PHOTO-METRICS SEEM TO BE REVERSED, THE | | | LEVEL OF LIGHTING UNDER NORMAL LIGHTING | | | CONDITION IS LOWER THAN UNDER EMERGENCY? | | | PLEASE SEE PERHAPS EACH SUDY WAS | | | REVERSED IN LABLEING? | | | PLEASE ALSO CORRELATE STAIR AREAS AND | | | FIXTURE TYOE WITH FIXTURES LISTED ON | | | FIXTURE SCHEDULE. PLEASE SEE FIXTURE | | | SCHEDULE AND ORIGINAL PLANS FOR LIGHTING | | | ON EACH FLR INDICATES A FIXTURE "H".THIS | | | FIXTURE IS SHOWN AS WALL MOUNTED AND | | | MENTIONED AS CEILING MOUNTED ON | | | SCHEDULE? | | | PLEASE CORRELATE. | | | | | | ** PREVIOUS NOTE** | | | PLEASE SUBMIT COMPLETE PHOTOMETRICS FOR | | | ALL COMMON AREAS, AND STAIR TOWERS. | | | PLEASE SEE 2003 NFPA-1017.8.1.3 WHICH | | | REQUIRES A MIN OF 1 FT CANDLEAND A MIN | | | OF 10FT CANDLES ON THE WALKING SURFACE | | | UNDER NORMAL POWER. PLEASE SEE7.9.2.1 | | | WHICH REQUIRES A MIN OF 1FT CANDLE OF | | | LIGHTING ON ALL WALKING SURFACES UNDER | | | EMERGENCY CONDITIONS. | | | | | | 10)NOTE: NO, PLEASE SEE RESPONSE LTR | | | MENTIONS TO SEE ARCHITECTURAL PLANS, | | | HOWEVER NONE OF THE A-SHEETS CONTAIN THE | | | INFORMATION NEED AND REQUESTED. | | | | | | ** PREVIOUS REVIEW ** | | | PLEASE SEE PHOTOMETRICS SHOWN | | | FOR POOL AREA SHALL BE SUBMITTED TO PALM | | | BEACH COUNTY HEATH DEPARTMENT FOR ANY | | | AFTER DUSK SWIMMMING. | | | IF THERE IS NOT GOING TO BE ANY SWIMMING | | | FROM DUSK TO DAWN, PLEASE PROVIDE A NOTE | | | ON PLAN FOR REQUIRED SIGNAGE TO BE PLACE | | | AT AND IN POOL AREA. | | | ** PLEASE KNOW, THE SWIMMING POOL ITSELF | | | WILL BE REQUIRED TO BE UNDER A SEPARATE | | | PERMIT. | | | | | | 11)NOTE:NO, SAME NOTE. SEE CIRCUITING | | | NOTE. | | | RESPONSE LTR MENTIONS TO SEE ROOM TYOE | | | ADDED?? THIS DOES NOT CORRELATE FOR THE | | | COMMENT WHICH WAS MADE. | | | | | | ** PREVIOUS NOTE ** | | | PLEASE CLARIFY NOTE ON PLANS FOR THE | | | REQUIREMENTS OF GUEST BATH GFI. | | | THIS CAN NOT BE VERIFIED AT THIS TIME | | | DUE TO MISSING CIRCUITING. | | | | | | 12)NOTE: OK. | | | | | | 13)NOTE: NO, PLEASE SEE LTTR MENTIONS NO | | | PROTECTION PER OWNER? PLEASE SEE | | | PREVIOUS NOTE::: | | | | | | ** PREVIOUS NOTE** | | | PLEASE PROVIDE A NOTE ON THE ROOOFTOP | | | PLAN WHICH SHOULD NOTE/MENTION: | | | ANY PROPOSED LIGHTNING PROTECTION SYSTEM | | | SHALL MEET NFPA-780, OR WORDS TO THAT | | | AFFECT. | | | IT IS NOTED THAT NO SYSTEM IS SHOWN AT | | | THIS TIME, AND ANY FUTURE WOULD BE UNDER | | | A SEPARATE PERMIT, HOWEVER A NOTE IS | | | REQUIRED AT THIS TIME. | | | | | | 14)NOTE: OK. | | | | | | 15)NOTE: OK. | | | | | | 16)NOTE: OK. | | | | | | 17)NOTE:OK, HOWEVER PLEASE SEE WHAT | | | APPEARS TO BE A MISPRINT FOR 3RD FLR | | | PANEL "3R3" WHICH READS "2R3" | | | | | | ** PREVIOUS NOTE** | | | PLEASE SEE RISER AND MSB SHOWS ALL 1H1, | | | 2H2, 3H3 ETC AS 1H, 2H, 3H ETC ON PANEL | | | SCHEDULES FOR THESE. | | | PLEASE CORRELATE THE IDENTIFICATION OF | | | THESE. | | | 215.5 | | | | | | 18)NOTE: NO, PLEASE SEE RESPONSE | | | MENTIONS "800A CHILLER HAS BEEN | | | ELIMINATED" ETC, PLEASE KNOW, THIS | | | RESPONSE WAS NOT FOR COMMENT MADE? | | | PLEASE SEE RISER AND NEW LOAD | | | CALCULATIONS NOW SUBMITTED. PLEASE SEE | | | NOTE #2 ON RISER WAS ADDRESSED IN FEEDER | | | SCHEDULE, HOWEVER SAME SHEET STILL | | | MENTIONS CONDUITRS, AND CONDUCTORS NOT | | | RATED FOR THE 3000A MAIN BEING ISTALLED. | | | PLEASE SEEREDLINED PLANS. | | | | | | **PREVIOUS NOTE ** | | | PLEASE SEE 240.4C, WHICH REQUIRES THE | | | CONDUCTOR FEEDING DEVICES RATED OVER | | | 800A'S TO MEET OR EXCEED RAITNG OF SUCH | | | DEVICE. | | | PLEASE SEE MSB OS SHOWN AS A 3000A MAIN | | | , HOWEVER CONDUCTORS ARE ONLY RATED FOR | | | 2100 A'S? | | | 5-SETS OF 600MCM, RATED @420A'S EACH.(75 | | | DEGREE COL). | | | 110.14, 215.5,215.3 | | | PLEASE ADJUST ON MORE THAN ONE SHEET, | | | SEE 13,14. | | | | | | 19)NOTE: OK, CHILLER REMOVED, HOWEVER | | | PLEASE SEE PLANS NOW INDICATE NEW CU'S | | | LOCATED ON SITE WITHOUT SERVICE RECEPTS | | | 210.63 AND PLEASE SEE MECH PLANS | | | INDICATE "P-TAC" UNITS AT THE END OF | | | THE HALLS FOR EACH FLR, HOWEVER THESE | | | ARE NOT SHOWN ON ELECTRICAL PLANS , | | | HOWEVER THEY ARE INDICATED ON PANEL | | | SCHEDULES.?? | | | | | | **PREVIOUS NOTE** | | | PLEASE ALSO SEE CONDUCTORS FOR MAIN | | | FEEDERS TO CHILLER FROM MSB. | | | PLEASE SEE MSB SHOWS 3-300 MCM, HOWEVER | | | PLEASE SEE CALCUALTIONS FOR CHILLER | | | WHICH INDICATE 2-600'S. | | | PLEASE CORRELARE. 215.5 | | | | | | 20)NOTE: NO, PLEASE SEE RESPONSE LTR | | | MENTIONS TO SEE REVISED DETAIL, HOWEVER | | | DETAIL WAS NOT REVISED AND SHOW THE | | | SAME. | | | | | | ** PREVIOUS ** | | | PLEASE SEE RISER INDICATES "BLDG STEEL" | | | AS PART OF THE GROUNDING ELECTRODE | | | SYSTEM, WHICHIS OK AND IS REQUIRED IF | | | "BLDG STEEL" IS PRESENT. | | | PLEASE ALSO INCLUDE THE REQUIRED "FOOTER | | | STEEL" IN DETAIL. | | | 250.50 | | | | | | 21)NOTE: NO?? RESPONSE MENTIONS | | | "INFORMATION TO FOLLOW" , WHAT IS MEANT | | | BY THIS?????? | | | PLEASE KNOW, THIS INFORMATION IS NEEDED | | | AND REQUIRED ATTHIS TIME AND SHALL BE | | | ON PLANS BEFORE PERMITTING. | | | | | | ** PREVIOUS NOTE** | | | PLEASE KNOW, THE REQUIRED WIND LOAD | | | CALCULATIONS FOR LT POLES WITH FIXTURES | | | ON THEM ARE REQUIRED AT THIS TIME. | | | PLEASE KNOW, THESE WILL BE REVIEWED BY A | | | STRUCTUAL PLANS REVIEWER. | | | IF THIS INFORMATION IS NOT SUBMITTED AT | | | THIS TIME, ALL SITE LIGHTING WOULD BE | | | REQUIRED TO BE UNDER A SEPARATE PERMIT, | | | WITH SEPARATE PLANS AND FEES. | | | | | | | | | ** PLEASE KNOW, ONE SET OF PLANS ARE | | | BEING RETAINED FOR FILE AND RECORD OF | | | PLAN REVIEWS FOR REPEAT COMMENTS. | | | | | | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM | | | OTHER REVIEWERS WHICH MAY AFFECT | | | ELECTRICAL PLANS. | | | | | | ** PLEASE SEE ONE SET OF ELECTRICAL | | | PLANS HAVE MANY OF THE ABOVE ITMES | | | REDLINED IN LOCATIONS FOR NOTES. | | | IE,FLR ELEC RMS, RECEPTS ETC. | | | | | | **BEFORE RESUBMITTING PLANS, PLEASE | | | REMOVE ALL OLD/VOIDED ELECTRICAL PAGES | | | AND ONLY INSERT NEW REVISED SHEETS INTO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | | | | 19)NOTE: PLEAS | | 2006-04-13 00:00:00 | IN ELEC FOR REVIEW. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-12-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-12-27 |
Time |
06:11 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2005-12-26 |
Time |
14:03 |
Sent To |
|
|
| Notes |
| 2006-02-01 00:00:00 | *** PLEASE SEE 2004 FBC CHAPETR 13. | | | HOTELS, ROOM OCCUPANCY CONTROLS FOR | | | ROOMS AND OTHER CONTROL FOR COMMON AREAS | | | ETC. | | 2005-12-27 00:00:00 | *************************************** | | | ************** UNSAT *************** | | | | | | ** HILTON GARDENS ** | | | | | | ** PLEASE KNOW, PLANS ONLY SUBMITTED FOR | | | "PLAN REVIEW ONLY" AND HAVE NOT BEEN | | | SUBMITTED FOR PERMIT. | | | | | | ** PLEASE SEE BLDG REVIEW COMMENTS AS | | | THIS PROJECT MAY REQUIRE A THIRD SET OF | | | PLANS | | | | | | | | | 1)NOTE: PLEASE BE SURE PLANS REFERENCE | | | CURRENT CODES IN EFFECT. | | | 2002 NFPA-70 (NEC), 2003 NFPA-101, 2002 | | | NFPA-72 ETC | | | | | | 2)NOTE: PLEASE SEE MAIN ELECTRICAL ROOM | | | DOORS WILL BE REQUIRED TO OPEN OUTWARD | | | AND SHALL HAVE PANIC HARDWARE. | | | 110.26 | | | | | | 3)NOTE: PLEASE BE SURE ALL ELECTRICAL | | | RMS, ELEVATOR EQUIPMENT RMS CONTAIN A | | | BATTERY BACK UP LIGHT OF SOME SORT. | | | LS101 7.8,7.9, 700.16 | | | | | | 4)NOTE: PLEASE SEE ELECTRICAL RMS ON | | | EACH FLOOR MAY NOT CONTAIN AREA FOR | | | "HOUSEKEEPING/STORAGE. | | | PLEASE SEE SHEETS E-5- E7 WHICH WOULD BE | | | ACCEPTABLE BY PLACING A WALL BETWEEN | | | THIS AREA ELECTRICAL ROOM WITH A | | | SEPARATE ENTRANCE/DOOR. | | | 110.26, 407.7, 240.24 | | | | | | 5)NOTE: PLEASE SEE FIRST FLR CIRCUTING | | | FOR HALL RECEPTS, SOME SHOWN AND SOME | | | MISSING. PLEASE COMPLETE. | | | THERE IS A NOTE ON PLANS, WHICH MENTIONS | | | HALL RECEPTS TO BE CIRCUITED TO NEAREST | | | GUEST RM, HOWEVER THIS CIRCUIT NEEDS TO | | | BE SHOWN. | | | | | | 6)NOTE: PLEASE COMPLETE ALL OTHER | | | CIRCUITING, GUEST RMS ETC. | | | 215.5 | | | | | | 7)NOTE: PLEASE SEE ELECTRICAL EQUIPMENT | | | LOCATED ON WALL NEXT TO POOL APEARS TO | | | BE LOCATED TOO CLOSE WHICH DOES NOT MEET | | | MIN CLEARENCES PER 680.22 | | | | | | 8)NOTE: PLEASE SEE 620.23, 620.24 WHICH | | | REQUIRES A DEDICATED BRANCH CIRCUIT FOR | | | RECEPTS AND LTS FOR ELEVATOR EQUIPMENT | | | RMS AND ANY ELEVATOR PITS. | | | | | | 9)NOTE: PLEASE SUBMIT COMPLETE | | | PHOTOMETRICS FOR ALL COMMON AREAS, AND | | | STAIR TOWERS. | | | PLEASE SEE 2003 NFPA-1017.8.1.3 WHICH | | | REQUIRES A MIN OF 1 FT CANDLEAND A MIN | | | OF 10FT CANDLES ON THE WALKING SURFACE | | | UNDER NORMAL POWER. PLEASE SEE7.9.2.1 | | | WHICH REQUIRES A MIN OF 1FT CANDLE OF | | | LIGHTING ON ALL WALKING SURFACES UNDER | | | EMERGENCY CONDITIONS. | | | | | | 10)NOTE: PLEASE SEE PHOTOMETRICS SHOWN | | | FOR POOL AREA SHALL BE SUBMITTED TO PALM | | | BEACH COUNTY HEATH DEPARTMENT FOR ANY | | | AFTER DUSK SWIMMMING. | | | IF THERE IS NOT GOING TO BE ANY SWIMMING | | | FROM DUSK TO DAWN, PLEASE PROVIDE A NOTE | | | ON PLAN FOR REQUIRED SIGNAGE TO BE PLACE | | | AT AND IN POOL AREA. | | | ** PLEASE KNOW, THE SWIMMING POOL ITSELF | | | WILL BE REQUIRED TO BE UNDER A SEPARATE | | | PERMIT. | | | | | | 11)NOTE: PLEASE CLARIFY NOTE ON PLANS | | | FOR THE REQUIREMENTS OF GUEST BATH GFI. | | | THIS CAN NOT BE VERIFIED AT THIS TIME | | | DUE TO MISSING CIRCUITING. | | | | | | 12)NOTE: PLEASE SEE 210.60 FOR REQUIRED | | | RECEPT SPACING FOR GUEST RMS OF HOTELS | | | WHICH REFERENCES 210.52 FOR MIN SPACING. | | | PLEASE SEE THERE IS AN EXCEPTION TO THE | | | MIN SPACING AS TO PROVIDE RECEPTS FOR | | | FURNITURE PLANS, HOWEVER THE NUMBER OF | | | RECEPTS TO BE PROVIDED SHALL MEET THE | | | SAME NUMBER OF RECEPTS IF THEEY WERE | | | INSTALLED PER 210.52 | | | PLEASE SEE MANY GUEST RM TYPES WHICH ARE | | | MISSING THE REQUIRED NUMBER. | | | PLEASE SEE MOSTOF THESE UNTIS ARE | | | REDLINED ON ONE SET OF PLANS. | | | KING,2,5 6,7,KING SUITE ETC. PLEASE KNOW | | | THAT NOT ALL UNITS WERE REDLINED, PLEASE | | | BE SURE TO GO OVER THE MIN. | | | PLEASE KNOW THAT A MIN OF TWO RECEPTS | | | SHALL BE READILY ACCESSIBLE AT ALL | | | TIMES. | | | MOST UNITS MEET THIS , HOWEVER A COUPLE | | | ARE MISSING. | | | | | | 13)NOTE: PLEASE PROVIDE A NOTE ON THE | | | ROOOFTOP PLAN WHICH SHOULD NOTE/MENTION: | | | ANY PROPOSED LIGHTNING PROTECTION SYSTEM | | | SHALL MEET NFPA-780, OR WORDS TO THAT | | | AFFECT. | | | IT IS NOTED THAT NO SYSTEM IS SHOWN AT | | | THIS TIME, AND ANY FUTURE WOULD BE UNDER | | | A SEPARATE PERMIT, HOWEVER A NOTE IS | | | REQUIRED AT THIS TIME. | | | | | | 14)NOTE:PLEASE SEE PANEL "K" IS SHOWN | | | LISTING A 125A OCP TO FEED TO PANEL | | | "KA", HOWEVER PANEL "KA" IS ONLY REATED | | | AT 100A'S? | | | PLEASE CORRELATE AND ADJUST. | | | 215.5, | | | | | | 15)NOTE: PLEASE SEE PANEL "LDY" IS SHOWN | | | AS A 100A MLO, YET MSB SHOWS A 225A | | | BRKR/OCP FEEDING THIS PANEL. | | | PLEASE ADJUST AND CORRELATE. | | | 215.5 | | | | | | 16)NOTE: PLEASE SEE PANEL "L" IS SHOWN | | | AS 100A MLO, WITH MSB SHWOING 150A OCP | | | FEEDING THIS PANEL. | | | PLEASE ADJUST AND CORRELATE. | | | 215.5 | | | | | | 17)NOTE: PLEASE SEE RISER AND MSB SHOWS | | | ALL 1H1, 2H2, 3H3 ETC AS 1H, 2H, 3H ETC | | | ON PANEL SCHEDULES FOR THESE. | | | PLEASE CORRELATE THE IDENTIFICATION OF | | | THESE. | | | 215.5 | | | | | | 18)NOTE: PLEASE SEE 240.4C, WHICH | | | REQUIRES THE CONDUCTOR FEEDING DEVICES | | | RATED OVER 800A'S TO MEET OR EXCEED | | | RAITNG OF SUCH DEVICE. | | | PLEASE SEE MSB OS SHOWN AS A 3000A MAIN | | | , HOWEVER CONDUCTORS ARE ONLY RATED FOR | | | 2100 A'S? | | | 5-SETS OF 600MCM, RATED @420A'S EACH.(75 | | | DEGREE COL). | | | 110.14, 215.5,215.3 | | | PLEASE ADJUST ON MORE THAN ONE SHEET, | | | SEE 13,14. | | | | | | 19)NOTE: PLEASE ALSO SEE CONDUCTORS FOR | | | MAIN FEEDERS TO CHILLER FROM MSB. | | | PLEASE SEE MSB SHOWS 3-300 MCM, HOWEVER | | | PLEASE SEE CALCUALTIONS FOR CHILLER | | | WHICH INDICATE 2-600'S. | | | PLEASE CORRELARE. 215.5 | | | | | | 20)NOTE: PLEASE SEE RISER INDICATES | | | "BLDG STEEL" AS PART OF THE GROUNDING | | | ELECTRODE SYSTEM, WHICHIS OK AND IS | | | REQUIRED IF "BLDG STEEL" IS PRESENT. | | | PLEASE ALSO INCLUDE THE REQUIRED "FOOTER | | | STEEL" IN DETAIL. | | | 250.50 | | | | | | 21)NOTE: PLEASE KNOW, THE REQUIRED WIND | | | LOAD CALCULATIONS FOR LT POLES WITH | | | FIXTURES ON THEM ARE REQUIRED AT THIS | | | TIME. | | | PLEASE KNOW, THESE WILL BE REVIEWED BY A | | | STRUCTUAL PLANS REVIEWER. | | | IF THIS INFORMATION IS NOT SUBMITTED AT | | | THIS TIME, ALL SITE LIGHTING WOULD BE | | | REQUIRED TO BE UNDER A SEPARATE PERMIT, | | | WITH SEPARATE PLANS AND FEES. | | | | | | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM | | | OTHER REVIEWERS WHICH MAY AFFECT | | | ELECTRICAL PLANS. | | | | | | ** PLEASE SEE ONE SET OF ELECTRICAL | | | PLANS HAVE MANY OF THE ABOVE ITMES | | | REDLINED IN LOCATIONS FOR NOTES. | | | IE,FLR ELEC RMS, RECEPTS ETC. | | | | | | ** PLEASE REMOVE ALL OLD/VOIDED | | | ELECTRICAL PAGES AND ONLY INSERT NEW | | | REVISED SHEETS INTO COMPLETE SETS FOR | | | REVIEW AND STAMPING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | | | | 19)NOTE: PLEAS | | 2005-12-26 00:00:00 | ONE ROLL IN ELECTRIC FOR REVIEW. | | | PLANS WILL GO INTO "F" STATUS. | | | REVIEW IN PROGRESS, NOTES TO FOLLOW. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
P |
Date |
2006-06-29 |
|
|
Cont ID |
|
| Sent By |
|
Date |
2006-06-29 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
2006-06-29 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
F |
Date |
2006-04-07 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2006-04-07 |
Time |
11:40 |
Rev Time |
0.50 |
| Received By |
mamini |
Date |
2006-04-07 |
Time |
11:40 |
Sent To |
|
|
| Notes |
| 2006-04-07 00:00:00 | FAILED: | | | | | | 1. PLEASE SEE PREVIOUS REVIEW COMMENTS | | | DATED 1-20-06. | | | | | | IF ANY QUESTION PLEASE CONTACT 805-6723 | | | MOHAMMAD R. AMINI. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2006-01-20 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2006-01-20 |
Time |
15:46 |
Rev Time |
1.00 |
| Received By |
mamini |
Date |
2006-01-20 |
Time |
15:46 |
Sent To |
|
|
| Notes |
| 2006-01-20 00:00:00 | FAILED: | | | | | | 1. PLEASE SUBMIT A COPY OF MODIFIED | | | SFWMD PERMIT. | | | 2. PLEASE PROVIDE CALCULATION FOR STORM | | | WATER POST DEVELOPMENT. | | | 3. PLEASE STATE AS WHERE RAIN LEADERS | | | BEING CONNECTED. | | | 4. A CLEAN OUT IN ALL SEWER LATERAL IS | | | REQUIRED. | | | PLEASE SHOW THE LOCATIONS FOR BACKFLOWS | | | FOR DOMMESTIC AND FIRE LINE. | | | 5. AN OIL WATER SEPARATOR IN SEWER LINE | | | FOR THIS FACILITY IS REQUIRED. | | | 6. IS THERE A SEPARATE METER FOR THIS | | | FACILITY? | | | 7. DUMPSTER ENCLOSURE SHOULD BE SIZED | | | PER CITY OF WEST PALM BEACH REQUIREMENTS | | | IF TO BE PICKED UP BY THE CITY, 12'-6" | | | BETWEEN THE GATE POSTS, 12'-6" DEEP. | | | 8. ANY INLET IN THE PROPOSED ASPHALT | | | DRIVEWAY? PLEASE VERIFY. | | | IF ANY QUESTION PLEASE CONTACT 805-6723 | | | MOHAMMAD R. AMINI |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2007-01-17 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-01-17 |
Time |
14:15 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-01-17 |
Time |
14:14 |
Sent To |
|
|
| Notes |
| 2007-01-17 14:17:37 | *****APPROVED***** | | | | | | | | | REVISED PLAN SHEETS E-4, E-5, E-6, AND E-7 WERE | | | STAMPED, INITIALED, AND DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2006-12-22 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2006-12-22 |
Time |
14:46 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2006-12-22 |
Time |
14:46 |
Sent To |
|
|
| Notes |
| 2006-12-22 15:01:23 | *****PROVISO***** | | | | | | | | | | | | 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 2.THE IMPACT OF THE PROPOSED CONSTRUCTION (FUTURE | | | POOL) SHALL NOT INTERFERE OR HINDER EMERGENCY RESPONDER | | | ACCESS TO THE SAID PROPERTY OR VICINITY THEREOF | | | (INCLUDING FIRE LANES). | | | | | | 3.SHOW/DISPLAY THE NUMERICAL ADDRESS FRONTING THE | | | BUILDING.AS PER WEST PALM BEACH CODE, THOSE NUMBERS | | | SHALL BE NO LESS THAN 6" IN HEIGHT AND 1" IN WIDTH.IF | | | THE NUMERICAL ADDRESS IS NOT PLAINLY VISIBLE FROM | | | WORTHINGTON ROAD, A MONUMENT SIGN OR MARKEE WITH THE | | | POSTED NUMERICAL ADDRESS WILL BE REQUIRED. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2006-06-28 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-06-28 |
Time |
14:35 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-06-28 |
Time |
14:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2006-05-05 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-05-05 |
Time |
13:16 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-05-05 |
Time |
13:16 |
Sent To |
|
|
| Notes |
| 2006-05-05 00:00:00 | ******DENIED****** | | | | | | PLEASE BE ADVISED THAT RESPONSES HAVE | | | BEEN PROVIDED, HOWEVER SOME ADDITIONS, | | | DELETIONS OR CHANGES ARE NOT ILLUSTRATED | | | ON THE PLANS. | | | | | | 1) COMMENT 5- RESPONSE STATES THAT A 2ND | | | FIRE HYDRANT IS SHOWN ON FP-16. ONLY (8) | | | FP SHEETS HAVE BEEN SUBMITTED. | | | | | | 2) COMMENT 7- RESPONSE REFERS TO A.20, | | | HOWEVER NO SUCH NOTE WAS FOUND. | | | | | | 3) COMMENT 11- CERTIFICATION OR APPROVED | | | COPY OF CERTIFICATE SHALL BE AVAILABLE | | | PRIOR TO OR AT THE TIME OF THE FIRE | | | ALARM FINAL. | | | | | | 4) COMMENT 13- PLEASE PROVIDE NOTE TO | | | DRAWINGS. | | | | | | 5) COMMENT 15- PLEASE ADD ADDRESS NOTE | | | TO ELEVATIONS. | | | | | | 6) COMMENT 18- PLEASE NOTE THAT | | | INCORRECT CHAPTER IS STILL REFERENCED ON | | | A.20. PLEASE MAKE CORRECTION. | | | | | | 7) COMMENT 20- PLEASE PROVIDE NOTE TO | | | PLANS. NO SUCH NOTE WAS FOUND ON A.25. | | | | | | 8) COMMENT 24- RESPONSE INDICATES THAT | | | THE FIRE DEPARTMENT CONNECTION | | | ARRANGEMENT ON DCDA WAS ELEIMINATED. | | | THIS ARRANGEMENT IS STILL BEING SHOWN ON | | | FP-6. | | | | | | 9) COMMENT 27- PLEASE BE AWARE THAT FIRE | | | SPRINKLER COVERAGE SHALL BE IN | | | ACCORDANCE WITH NFPA 13. IF SUCH AN | | | EXCEPTION EXISTS, PLEASE PROVIDE WITH | | | RESPONSE INDICATING THAT SECTION. | | | | | | 10) COMMENT 33- PLEASE NOTE THAT A | | | DIMENSION OF 13'-6" WAS NOT FOUND ON | | | A.24. | | | | | | | | | PLEASE BE SURE WHEN RESUBMITTING, TO | | | REFLECT ANY CHANGES TO PLANS THAT | | | CORRULATE WITH APPROPRIATE RESPONSE. | | | THIS WILL ASSIST IN EXPEDITING THIS | | | PROCESS. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2005-12-19 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2005-12-19 |
Time |
14:13 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2005-12-19 |
Time |
14:13 |
Sent To |
|
|
| Notes |
| 2005-12-19 00:00:00 | 1. CONSTRUCTION, DEMOLITION, AND | | | RENOVATION TO COMPLY WITH NFPA 241. | | | | | | 2. SUITABLE ROADS ARE TO BE PROVIDED | | | DURING CONSTRUCTION FOR FIRE AND | | | PARAMEDICAL EQUIPMENT. | | | | | | 3. EXIT STAIRS ARE TO BE KEPT UP WITH | | | CONSTRUCTION. | | | | | | 4. THE AUTOMATIC SLIDING DOOR SHALL | | | COMPLY WITH POWERED OPERATED DOOR | | | REQUIREMENTS PER THE LIFE SAFETY CODE, | | | 2003 EDITION. | | | | | | 5. THE SITE PLAN APPEARS TO ONLY DISPLAY | | | ONE FIRE HYDRANT. IF THIS HYDRANT IS | | | USED TO CONNECT TO THE FIRE DEPARTMENT | | | SPRINKLER CONNECTION NO OTHERS ARE | | | AVAILABLE FOR USE. | | | | | | 6. FIRE HOSE VALVES SHALL BE PRESENT | | | WITHIN THE STAIRWELLS WHERE A TWO HOUR | | | RATED FIRE PROTECTION IS PROVIDED NOT | | | OUTSIDE THE STAIRWELLS AS SHOWN. | | | PORTABLE FIRE EXTINGUISHER CABINETS CAN | | | REMAIN OUTSIDE THE STAIRWELLS BUT THE | | | STANDPIPE CONNECTIONS SHOULD BE LOCATED | | | IN THE STAIRWELLS. | | | | | | 7. PLEASE PROVIDE PRESCRIPTIVE | | | REQUIREMENTS FOR ALL HANDRAILS AND | | | GUARDRAILS. | | | | | | 8. ELEVATOR WARNING SIGNS WILL BE | | | REQUIRED IN THE ELEVATOR LOBBIES. | | | | | | 9. SEPERATE PLANS AND PERMITS REQUIRED | | | FOR ANY HOOD, DUCT, AND FIRE SUPPRESSION | | | SYSTEMS PLANNED. | | | | | | 10. SEPERATE PLANS AND PERMITS REQUIRED | | | FOR FIRE SPRINKLER SYSTEM INSTALLATION. | | | | | | 11. SEPERATE PLANS AND PERMITS REQUIRED | | | FOR FIRE ALARM SYSTEM. FIRE ALARM SYSTEM | | | SHALL BE MONITORED BY A LICENSED UL | | | LISTED CENTRAL STATION APPROVED FOR | | | CENTRAL STATION SERVICE. | | | | | | 12. WILL THE PROPOSED FIREPLACE BE | | | OPERATIONAL OR IS IT DECORATIVE. | | | | | | 13. PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATIONS FOR ALL WALLS AND | | | CEILINGS. | | | | | | 14. NO SOFFITS SHALL INTERFERE WITH THE | | | OPERATION OF ANY FIRE SPRINKLER HEADS. | | | | | | 15. BUILDING ADDRESS IS REQUIRED ON | | | PROPER ELEVATION. A MINIMUM OF AT LEAST | | | 6" HIGH NUMBERS ARE REQUIRED. | | | | | | 16. GAS DRYERS ARE TO BE INSTALLED IN | | | ACCORDANCE WITH RECOGNIZED NFPA | | | STANDARDS AND RECOGNIZED SAFETY | | | STANDARDS. | | | | | | 17. ALL COOLERS AND FREEZERS SHALL HAVE | | | FIRE SPRINKLER PROTECTION. | | | | | | 18. STAIR SECTION 1, ON PAGE A.20 | | | REFERENCES CHAPTER 5. IT SHOULD READ | | | CHAPTER 7. | | | | | | 19. ON PAGE A.22 NOTES INDICATE A TWO | | | HOUR RATING BUT NO UL NUMBER IS | | | PROVIDED. UL NUMBERS LOCATED ON A.27. | | | | | | 20. PLEASE INDICATE ON THE PLANS THAT | | | ALL FIRE RATED DOORS SHALL BE EQUIPPED | | | WITH SELF-CLOSING DEVICES AND SHALL | | | POSITIVELY LATCH WHEN CLOSED. | | | | | | 21. HOW WILL CARD READERS INTERFACE WITH | | | EXITING REQUIREMENTS. | | | | | | 22. ALL SMOKE DETECTORS SHALL BE LOCATED | | | A MINIMUM OF AT LEAST THREE FEET FROM | | | AIR CONDITIONING DIFFUSERS. PLEASE | | | PROVIDE NOTE ON PLANS. | | | | | | 23. PLEASE INDICATE WHAT REQUIRED | | | INFORMATION WILL BE PLACED WITHIN THE | | | HOTEL ROOMS ON THE INTERIOR SIDE DOORS. | | | | | | 24. FP-1 APPEARS TO ILLUSTRATE TWO FIRE | | | HYDRANTS BUT NO CALL-OUTS ARE PROVIDED. | | | PLEASE REVISE. | | | | | | 25. FP-1 SEEMS TO SUGGEST TWO FIRE | | | DEPARTMENT CONENCTIONS. DUE TO THE SIZE | | | AND OCCUPANCY TYPE, ONLY ONE FDC IS | | | REQUIRED. | | | | | | 26. FIRE LINE BACKFLOW DEVICE SHALL BE | | | EQUIPPED WITH FLOW SWITCHES, CHAINS AND | | | LOCKS. | | | | | | 27. NO FIRE SPRINKLER HEADS SHOWN IN | | | MAIN ELECTRICAL ROOM. | | | | | | 28. RISER # 2 ON PAGE FP-6 APPEARS TO | | | DISPLAY CONTROL VALVES BEHIND THE FIRE | | | DEPARTMENT CONNECTION. | | | | | | 29. PLEASE EXPLAIN FOUR INCH UNDERGROUND | | | FIRE LINE. TYPICALLY, THE MINIMUM SHALL | | | BE AT LEAST 6" UNLESS HYDRAULIC | | | CALCULATIONS SUGGEST SOMETHING | | | OTHERWISE. | | | | | | 30. PLANS MENTION EXHAUST DUCT WRAP. | | | PLEASE PROVIDE PRODUCT APPROVALS | | | REGARDING THE DUCT WRAP STATED IN THE | | | PLANS. | | | | | | 31. DIFFERENT SHEETS SEEM TO SUGGEST | | | DIFFERENT NUMBERS OF FIRE HYDRANTS. | | | PLEASE REVISE ALL SHEETS AND ENSURE THAT | | | THE CORRECT NUMBER OF FIRE HYDRANTS ARE | | | SHOWN. | | | | | | 32. FLOOR PLANS SHALL ILLUSTRATE ALL | | | RATED WALLS AND LOCATIONS OF RATED | | | SHAFTS. RATED WALLS IN COMMON AND | | | BETWEEN GUEST ROOMS SHALL BE SHOWN. | | | | | | 33. PLEASE PROVIDE HEIGHT OF PORTA | | | CACHERE FROM FINISHED ELEVATION. | | | | | | 34. TACTILE SIGNAGE REQUIRED AT EXIT | | | DOORS. | | | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | | OFFICER | | | | | | 804-4709 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
6 |
Status |
F |
Date |
2007-02-09 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-02-09 |
Time |
18:55 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-02-09 |
Time |
18:55 |
Sent To |
|
|
| Notes |
| 2007-02-09 18:55:40 | | | | REVISION DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | FBC-2004 CHAPTER 1 | | | | | | | | | 1. SHT P-15THE GAS RISER DIAGRAM BETWEEN SECTIONS (1) | | | & (2) DO NOT REFLECT THE GAS EQUIPMENT SCHEDULE. THE | | | RISER SHOWS TWO ITEM 45'S AND THE SCHEDULE ONLY SHOWS | | | ONE ITEM 45. THIS WOULD CHANGE THE TOTAL CONNECTED GAS | | | LOAD BY 140,900 BTU'S. PLEASE CORRELATE THE RISER | | | DIAGRAM WITH THE GAS EQUIPMENT SCHEDULE. SECTION | | | 106.1.1. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
5 |
Status |
P |
Date |
2007-01-16 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2007-01-16 |
Time |
09:44 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2007-01-16 |
Time |
09:44 |
Sent To |
|
|
| Notes |
| 2007-01-16 09:46:17 | SEE GAS PERMIT #06120002 FOR REVIEWED PLANS |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
4 |
Status |
F |
Date |
2006-09-01 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-09-01 |
Time |
16:45 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-09-01 |
Time |
16:45 |
Sent To |
|
|
| Notes |
| 2006-09-01 00:00:00 | REVISION DENIED | | | | | | A. SHT P-15 SUBMIT THE FOLLOWING: | | | | | | 1. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | INDICATE THE MODEL NUMBER FOR EACH GAS | | | APPLIANCE, AND EACH APPLIANCE MANUF. | | | SPECIFICATION SHEET SHALL SHOW LISTING. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
N |
Date |
2006-07-07 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-07-07 |
Time |
13:45 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-07-07 |
Time |
13:44 |
Sent To |
|
|
| Notes |
| 2006-07-07 00:00:00 | | | | | | | PASSED/PROVISO | | | | | | REVISIONS REQUIRED FOR SHEETS P1, P-5, & | | | P-10 FLOOR PLANS SHOWING THE HAND SINKS | | | REQUIRED BY DBPR PLAN REVIEW. REVISION | | | IS ALSO REQUIRED FORSHEET P-8 WATER | | | RISER DIAGRAM AND SHT P-15 FPR THE | | | GREASE ISOMETRIC RISER DIAGRAM | | | REFLECTING THESE CHANGES. | | | | | | REVISION IS ALSO REQUIRED FOR THE GAS | | | ISOMETRIC RISER DIAGRAM, WHICH SHALL | | | CORRELATE WITH THE GAS | | | EQUIPMENT/CONNECTED LOAD AND THE MANUF. | | | SPECIFICATION SHEETS INDICATING THE BTU | | | LOAD FOR EACH GAS APPLIANCE. | | | | | | GAS ISOMETRIC NOT APPROVED AT THIS TIME. | | | PLUMBING ONLY APPROVED. SEPARATE GAS | | | PERMIT REQUIRED. | | | | | | | | | | | | | | | . |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2006-07-05 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-07-05 |
Time |
18:57 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-07-05 |
Time |
18:57 |
Sent To |
|
|
| Notes |
| 2006-07-05 00:00:00 | DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | | | | 32. P-15 THE FOLLOWING INFORMATION IS | | | REQUIRED FOR GAS PLAN APPROVAL: | | | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS. | | | ***RESPONSE NOTED, BUT THERE ARE SOME | | | CUT SECTIONS THAT DO NOT SHOW THE | | | LENGTH. | | | ****RESPONSE NOTED, BUT THERE IS NO | | | LENGTHS FOR THE PIPING TO THE POOL/SPA | | | HEATERS. THERE ARE 3 WATER HEATERS | | | INDICATED, BUT ONLY TWO SHOWN ON THE | | | ISOMETRIC RISER DIAGRAM. PLEASE | | | CORRELATE THE APPLIANCES WITH THE RISER | | | DIAGRAM. | | | | | | F. SUBMIT MANUFACTURE SHEETS FOR ALL | | | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | ***NO RESPONSE, NOT ADDRESSED. | | | ****RESPONSE NOTED, BUT MANUF. | | | SPECIFICATION SHEET ARE REQUIRED FOR ALL | | | GAS APPLIANCES. | | | | | | G. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. BYPASS | | | PIPING SHALL BE CONNECTED DOWNSTREAM OF | | | THE EMERGENCY HOOD SHUT OFF VALVE. | | | ***NO RESPONSE, NOT ADDRESSED. EMERGENCY | | | HOOD SHUT DOWN SHUT OFF VALVE SHALL BE | | | INSTALLED BETWEEN 42" AND 48" PER | | | NFPA-96 SECTION 10.5.1 AND NFPA-1 | | | SECTION 50.4.7.1. INDICATE ON GAS RISER. | | | ****RESPONSE NOTED, BUT NO MANUAL GAS | | | SHUT OFF VALVE IS SHOWN ON RISER | | | DIAGRAM. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2006-04-29 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-04-29 |
Time |
19:54 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-04-29 |
Time |
19:54 |
Sent To |
|
|
| Notes |
| 2006-04-29 00:00:00 | DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | NFPA-96 | | | NFPA-1 | | | | | | FROM PLUMBING REVIEW NOTES: | | | | | | 32. P-15 THE FOLLOWING INFORMATION IS | | | REQUIRED FOR GAS PLAN APPROVAL: | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS. | | | ***RESPONSE NOTED, BUT THERE ARE SOME | | | CUT SECTIONS THAT DO NOT SHOW THE LENGTH | | | | | | B. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES,- | | | SPECIFICATIONS NOT SUBMITTED. INDICATE | | | IF PIPING WILL BE SCREW PIPE OR WELDED | | | PIPE. | | | ***RESPONSE NOTED, BUT NO INFORMATION | | | FOUND. | | | | | | D. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2004 FUEL GAS CODE SEC. | | | 402.4(2). NATURAL GAS SPECIFY .5 PSI OR | | | 2 PSI. | | | ***RESPONSE NOTED, BUT DELIVERY PRESSURE | | | HAS NOT BEEN ADDRESSED. | | | | | | F. SUBMIT MANUFACTURE SHEETS FOR ALL | | | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | ***NO RESPONSE, NOT ADDRESSED. | | | | | | G. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. BYPASS | | | PIPING SHALL BE CONNECTED DOWNSTREAM OF | | | THE EMERGENCY HOOD SHUT OFF VALVE. | | | ***NO RESPONSE, NOT ADDRESSED. EMERGENCY | | | HOOD SHUT DOWN SHUT OFF VALVE SHALL BE | | | INSTALLED BETWEEN 42" AND 48" PER | | | NFPA-96 SECTION 10.5.1 AND NFPA-1 | | | SECTION 50.4.7.1. INDICATE ON GAS RISER. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | RESUBMIT ONE SET OF ORIGINAL SHEETS FOR | | | COMPARISON. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
14 |
Status |
N |
Date |
2007-02-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-02-15 |
Time |
13:19 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-02-15 |
Time |
13:19 |
Sent To |
P |
|
| Notes |
| 2007-02-15 13:19:36 | TO "P" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
13 |
Status |
N |
Date |
2007-02-01 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-02-01 |
Time |
14:56 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-02-01 |
Time |
14:56 |
Sent To |
Z |
|
| Notes |
| 2007-02-01 14:57:14 | TO "Z" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
12 |
Status |
N |
Date |
2007-01-11 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-01-11 |
Time |
09:28 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-01-11 |
Time |
09:28 |
Sent To |
Z |
|
| Notes |
| 2007-01-11 09:29:02 | TO "Z" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
11 |
Status |
N |
Date |
2006-12-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-12-27 |
Time |
10:57 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-12-27 |
Time |
10:57 |
Sent To |
|
|
| Notes |
| 2007-01-13 12:44:35 | TO "COMM" BD#57 | | 2006-12-27 10:57:48 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
10 |
Status |
N |
Date |
2006-11-12 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-11-12 |
Time |
10:25 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-11-12 |
Time |
10:25 |
Sent To |
|
|
| Notes |
| 2006-11-14 09:59:21 | TO "COMM" BD#53 | | 2006-11-12 10:25:27 | WAITING FOR "COMM' BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
N |
Date |
2006-11-03 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-11-03 |
Time |
08:49 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-11-03 |
Time |
08:49 |
Sent To |
M |
|
| Notes |
| 2006-11-03 08:50:08 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2006-09-25 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-09-25 |
Time |
14:53 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-09-25 |
Time |
14:53 |
Sent To |
B |
|
| Notes |
| 2006-09-25 00:00:00 | TO "JWITMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2006-09-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-09-23 |
Time |
19:07 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-09-23 |
Time |
19:07 |
Sent To |
P |
|
| Notes |
| 2006-09-23 00:00:00 | TO "P" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2006-08-10 |
|
|
Cont ID |
|
| Sent By |
mmiller |
Date |
2006-08-10 |
Time |
16:29 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-08-10 |
Time |
10:12 |
Sent To |
E |
|
| Notes |
| 2006-08-22 00:00:00 | TO "COMM" BD#17 | | 2006-08-10 00:00:00 | WAITING FOR COMM B |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2006-08-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-08-02 |
Time |
16:47 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-08-02 |
Time |
16:47 |
Sent To |
B |
|
| Notes |
| 2006-08-02 00:00:00 | TO "JWITMER" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2006-07-20 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2006-07-20 |
Time |
19:24 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2006-07-20 |
Time |
19:24 |
Sent To |
|
|
| Notes |
| 2006-07-20 00:00:00 | SUBMITTAL FOR SHORING PLANS TO JIM | | | WITMER'S DESK. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-05-25 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-05-18 |
Time |
09:24 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2006-05-18 |
Time |
11:58 |
Sent To |
|
|
| Notes |
| 2006-06-06 00:00:00 | TO "COMM" BD#44 | | 2006-05-25 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-04-03 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-03-15 |
Time |
14:28 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-03-15 |
Time |
14:27 |
Sent To |
|
|
| Notes |
| 2006-04-03 00:00:00 | TO "COMM" BD#38 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-03-01 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-03-01 |
Time |
12:47 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2005-11-18 |
Time |
17:24 |
Sent To |
|
|
| Notes |
| 2005-12-09 00:00:00 | ON COMM BOARD SPACE # 43 | | 2005-11-18 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
8 |
Status |
P |
Date |
2007-02-09 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-02-09 |
Time |
15:01 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-02-09 |
Time |
10:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
7 |
Status |
P |
Date |
2007-02-07 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2007-02-07 |
Time |
08:38 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2007-02-07 |
Time |
08:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
P |
Date |
2006-12-06 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-12-06 |
Time |
10:55 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-12-06 |
Time |
10:55 |
Sent To |
|
|
| Notes |
| 2006-12-07 07:20:21 | REVISIONS TO SHEET M-1 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
F |
Date |
2006-11-30 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-11-30 |
Time |
09:39 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-11-30 |
Time |
09:36 |
Sent To |
|
|
| Notes |
| 2006-11-30 10:02:10 | DENIED: | | | REVISION IS SUPERCEDED BY PLAN DATED 11/7/06.THIS | | | REVISION WAS ISSUED 10/29/06. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS | | | AT (561)805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2006-11-21 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-11-21 |
Time |
09:09 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-11-21 |
Time |
08:57 |
Sent To |
|
|
| Notes |
| 2006-11-21 09:59:48 | DENIED: | | | REVISED SHEET M-1 IS MISSING FIRE DAMPERS IN THE | | | FOLLOWING AREAS: | | | | | | 1.SUPPLY & RETURN AIR DUCTS FROM AHU-3, PLAN SHEET | | | A.01 INDICATES MECHANICAL CLOSET HAS A 1 HR RATING, | | | FIRE DAMPERS ARE REQUIRED. | | | | | | 2.S/A & R/A FROM AHU-3 INTO THE CORRIDOR AREA AND | | | DUCTS PENETRATING INTO THE FOLLOWING ROOMS;47,48, 46, | | | 50, 51, PLEASE NOTE, PER 2004 FMC 603.5.5, FLEXIBLE AIR | | | DUCTS & FLEX CONNECTORS SHALL NOT PASS THROUGH ANY | | | FIRE-RESISTANCE-RATED ASSEMBLY.PLANS INDICATE FLEX | | | DUCT PENETRATING RATED CORRIDOR.PLEASE ALSO SEE | | | EXCEPTIONS IN 607.5.3, SHOULD PENETRATIONS COMPLY WITH | | | THE AFOREMENTIONED SECTION, PLEASE ANNOTATE THIS | | | SECTION ON THE PLAN. | | | | | | 3. PLEASE CLARIFY THE PENETRATION BETWEEN THE GUEST | | | LAUNDRY ROOM AND THE LOCKER AREA. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS | | | AT (561)805-6719 OR E-MAIL [email protected] | | | | | | *****************REVIEW IN | | | PROGRESS************************ |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2006-07-03 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-06-30 |
Time |
13:57 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-06-21 |
Time |
10:41 |
Sent To |
|
|
| Notes |
| 2006-06-30 00:00:00 | ALL COMMENTS ADDRESSED: | | | RESPONSE TO COMMENTS DATED 5/3/06 | | | | | | COMMENT #1 - INDICATES SUPPLY DUCT SHALL | | | BE IN A RATED CHASE.OK | | | | | | COMMENT #3 - SUBDUCT DETAIL ON PLAN | | | SHEET M-10 | | | | | | COMMENT #5 - RESPONSE INDICATES PLAN | | | SHEETS M-15 & M-16 (CHILLED WATER | | | PIPING) WERE REMOVED.PLANS ARE STILL | | | IN FOR RE-SUBMITTAL.PLEASE REMOVE. | | | | | | NEW COMMENTS | | | COMMENT #1 - OK | | | COMMENT #2 - PLANS STILL IN SUBMITTAL | | | THAT ARE NOT PERTINENT. | | | COMMENT #3 - OK | | | | | | PLEASE NOTE, BTU'S USED FOR COMBUSTION | | | AIR CALUCALTIONS ARE NOT CORRECT.PLAN | | | SHOWS 165,000 BTU'S PER DRYER AND THE | | | MANUFACTURE SUBMITTAL DATA INDICATE | | | 215,000 BTU'S. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2006-05-03 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-05-03 |
Time |
07:50 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-05-03 |
Time |
06:51 |
Sent To |
|
|
| Notes |
| 2006-05-03 00:00:00 | DENIED: | | | RESPONSE TO COMMENT #1 FROM REVIEW DATED | | | 1-24-06 INDICATES THE OUTDOOR SHAFT WAS | | | ELIMINATED.RTU #1 SUPPLY AIR FOR THE | | | COMMON AREA OF FLOORS ONE THROUGH 4. | | | THIS DUCT SHALL BE BE IN A RATED CHASE | | | IN ACCORDANCE WITH 2004 FMC 607.6. | | | | | | COMMENT #3:RESPONSE INDICATES SUB-DUCT | | | DETAIL IS NO LONGER ON PLAN SHEET M-11 | | | BUT IS NOW ON PLAN SHEET M-9, THIS IS | | | INCORRECT.PLAN SHEET M-9 IS THE FIRE | | | SUPPRESSION FOR THE GREASE HOOD. | | | SUB-DUCT IS DETAILED ON PLAN SHEET M-11. | | | | | | COMMENT #5:REPONSE INDICATES CHILLED | | | WATER SYSTEM HAS BEEN ELIMINATED.PLAN | | | SHEETS M-15, M-16 & DETAIL ON PLAN SHEET | | | M-14, STILL INDICATE A CHILLED WATER | | | SYSTEM.PLEASE REMOVE DETAILS AND PLANS | | | THAT DO NOT PERTAIN TO THIS JOB. | | | | | | | | | NEW COMMENTS: | | | 1.PLAN SHEET M-1 RETURN AIR FROM THE | | | MAIN ELECTRICAL ROOM IS MISSING A FIRE | | | DAMPER/ACCESS DOOR.PLEASE CLARIFY. | | | | | | 2.PLEASE CLARIFY PLAN SHEET M-6 & M-8. | | | PLAN SHEET M-6 APPEARS TO REPLACE M-8. | | | PLEASE REMOVE ALL PAGES THAT ARE NOT | | | PERTINENT. | | | | | | 3.PLAN SHEET M-6 THE FRESH AIR | | | CALCULATION INDICATES FRESH PROVIDED | | | FROM AHU-1 & BY VTAC UNITS.PLEASE | | | INDICATE WHERE THE VTAC UNITS ARE | | | LOCATED.PLEASE NOTE THE VTAC UNITS ARE | | | NOT INDICATED ON THE EQUIPMENT SCHEDULE | | | OR ON THE PLAN.PLEASE CLARIFY HOW | | | AHU-1 IS ABLE TO PROVIDE OUTSIDE AIR | | | WHEN THERE IS NO OUTSIDE AIR DUCTED INTO | | | AHU-1.IT APPREARS THAT AHU-3, 4, 5 & | | | POSSIBLY AHU-2 HAVE OUTSIDE AIR PROVIDED | | | VIA RTU-1.AHU-1, 6, & 7 DO NOT APPEAR | | | TO HAVE FRESH AIR INTRODUCED INTO THE | | | SYSTEM. | | | | | | ADDITIONAL PERMITS REQUIRED FOR HOOD, | | | FIRE SUPPRESSION & WALK-IN COOLERS. | | | HOOD & SUPPRESSION PLANS SUBMITTED WITH | | | BUILDING PERMIT.PLEASE PROVIDE | | | MANUFACTURE SUBMITTAL DATA FOR THE | | | WALK-IN COOLER WITH MECHANICAL PERMIT | | | APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. | | | | | | | | | | | | **************REVIEW IN PROGRESS******* |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2006-01-24 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-01-24 |
Time |
09:57 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-01-23 |
Time |
16:46 |
Sent To |
|
|
| Notes |
| 2006-01-24 00:00:00 | DENIED:********PLAN CHECK ONLY******* | | | | | | 1.PLAN SHEET M-2 DETAIL OF THE FAN | | | COIL UNITS INDICATE A FIRE DAMPER AT THE | | | FLOOR PENETRATIONS.PER 2004 FMC | | | 607.6.1,FIRE DAMPERS ARE PERMITTED THE | | | FLOOR CEILING PENETRATIONS WHEN | | | CONNECTING NOT MORE THAN TWO STORIES.A | | | SHAFT ENCLOSURE WILL BE REQUIRED FOR THE | | | OUTSIDE AIR DUCT THAT PENETRATES 3 FIRE | | | RATED FLOOR/CEILING & 1 CEILING ROOF | | | ASSEMBLY. | | | | | | 2.PLAN SHEET M-2 TERMINATION OF GREASE | | | DUCT.PER 2004 FMC 506.3.12.3, EXHAUST | | | OUTLETS SHALL BE LOCATED NOT LESS THAN | | | 10 FT HORIZONTALLY FROM PARTS OF THE | | | SAME OR CONTIGUOUS BUILDINGS.THE | | | EXCEPTION TO THE 10 FT CLEARANCE IS, 5FT | | | PROVIDED THAT THE EXHAUST DISCHARAGES | | | AWAY FROM SUCH LOCATIONS. | | | | | | 3.PLEASE CLARIFY IF THE TOILET EXHAUST | | | WILL BE IN A SUB-DUCT AS INDICATED ON | | | PLAN SHEET M-11. | | | | | | 4.PLAN SHEET M-2 PLEASE CLARIFY THE | | | FLUE THAT TERMINATES ON THE ROOFAT THE | | | SECOND FLOOR.PLEASE PROVIDE DETAIL. | | | | | | 5.PLEASE INDICATE PIPING MATERIAL & | | | METHOD OF JOING THE PIPE (WELD, | | | VICTALIC, THREADED, ETC).PLEASE NOTE, | | | UNDER GROUND PIPING TO BE PRESSURE | | | TESTED AND INSPECTED PRIOR TO COVERING | | | IN ACCORDANCE WITH 2004 FMC 1208. | | | | | | 6.PLEASE PROVIDE SUBMITTAL DATA FOR | | | ALL COMPONENTS OF THE SYSTEM. | | | | | | 8.ADDITIONAL PERMITS REQUIRED FOR THE | | | HOOD, FIRE SUPPRESSION AND WALK-IN | | | COOLER/FREEZER.PLEASE PROVIDE | | | MANUFACTURER SUBMITTAL WITH PERMIT | | | APPLICATION. | | | | | | 9.PLEASE INDICATE CLEARANCE TO | | | COMBUSTIBLES AS REQUIRED IN 2004 FMC | | | 506.3.6. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
9 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2007-02-16 |
Time |
09:49 |
Sent To |
PC |
|
| Notes |
| 2007-02-16 09:51:38 | REVISION DELETING SINKS IN RM# 210,310,410. | | | PLUMBING PIPES CAPPED OFF AT WALL |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
8 |
Status |
F |
Date |
2007-02-09 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-02-09 |
Time |
18:39 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-02-09 |
Time |
18:39 |
Sent To |
|
|
| Notes |
| 2007-02-09 18:54:53 | REVISION DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 FUEL GAS | | | FBC-2004 CHAPTER 1 | | | | | | 1. SHT P-1 HAND DRAWN CHANGES AND WHITE OUT ARE NOT | | | APPROVED FOR REVISIONS. SECTION 106.1.3.--NO CHANGE | | | NOTED ON ONE REVISION #5< (BETWEEN COL. LINE 11 & 12). | | | --PLEASE TURN OFF THE CLOUDS AND NUMBERED TRIANGLES | | | FROM PREVIOUS REVISIONS TO EXPEDITE REVIEW OF THE | | | REVISIONS. SECTION 106.1.1. | | | | | | 2. SHT P-5 HAND DRAWN CHANGES AND WHITE OUT ARE NOT | | | APPROVED FOR REVISIONS. SECTION 106.1.3.--PLEASE | | | TURN OFF THE CLOUDS AND NUMBERED TRIANGLES FROM | | | PREVIOUS REVISIONS TO EXPEDITE REVIEW OF THE REVISIONS. | | | SECTION 106.1.1. | | | | | | 3. SHT P-8WHITE OUT IS NOT APPROVED FOR REVISIONS. | | | SECTION 106.1.3.--PLEASE TURN OFF THE CLOUDS AND | | | NUMBERED TRIANGLES FROM PREVIOUS REVISIONS TO EXPEDITE | | | REVIEW OF THE REVISIONS. SECTION 106.1.1. | | | | | | 4. SHT P-9WHITE OUT IS NOT APPROVED FOR REVISIONS. | | | SECTION 106.1.3.--PLEASE TURN OFF THE CLOUDS AND | | | NUMBERED TRIANGLES FROM PREVIOUS REVISIONS TO EXPEDITE | | | REVIEW OF THE REVISIONS. SECTION 106.1.1. | | | | | | 5. SHT P-10 SHOWS THE DRAINAGE FROM (L-11) 4" ROOF | | | DRAIN 824 SQ FT BEING ROUTED TWO DIFFERENT WAYS TO THE | | | RISER. PLEASE CLARIFY. SECTIONS 106.1.1 AND 706.3. | | | | | | 6. SHT P-15THE GAS RISER DIAGRAM BETWEEN SECTIONS (1) | | | & (2) DO NOT REFLECT THE GAS EQUIPMENT SCHEDULE. THE | | | RISER SHOWS TWO ITEM 45'S AND THE SCHEDULE ONLY SHOWS | | | ONE ITEM 45. THIS WOULD CHANGE THE TOTAL CONNECTED GAS | | | LOAD BY 140,900 BTU'S. PLEASE CORRELATE THE RISER | | | DIAGRAM WITH THE GAS EQUIPMENT SCHEDULE. SECTION | | | 106.1.1. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
7 |
Status |
F |
Date |
2006-12-19 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-12-19 |
Time |
17:50 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-12-19 |
Time |
17:50 |
Sent To |
|
|
| Notes |
| 2006-12-19 18:16:08 | REVISION DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | | | | 1. SHT P-1.AS INDICATED ON PREVIOUS REVISION REVIEW, | | | MAKE SURE THE CLOUDS ARE BOLD ENOUGH TO SEE. THE | | | REVISION FOR NUMBER 5 IS FAINT & HARD TO SEE. A NEW | | | REVISION WAS FOUND ON THE PLAN. THIS NUMBER 6 REVISION | | | IS NOT CLOUDED AND NOT INDICATED IN THE REVISION INDEX. | | | PLEASE CLOUD ALL REVISIONS WITH A HEAVY CLOUD, AND SHOW | | | ALL REVISIONS ON THE REVISION INDEX. | | | | | | 2. SHT P-5. REVISION #6 NOT CLOUDED. PLEASE CLOUD ALL | | | REVISIONS. IT APPEARS THAT THERE IS A NEW TOILET ROOM. | | | IF SO PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE WITH | | | SECTIONS 11-4.16, 11-4.18, 11-4.19, & 11-4.22 AND ALL | | | SUBSECTIONS. SUBMIT A REVISION FOR THE SANITARY RISER | | | DIAGRAM THAT REFLECTS THE FLOOR PLAN, SHOWING THE NEW | | | TOILET ROOM PIPING AND INDICATING ALL PIPE SIZES, | | | TRAPS, VENTS ETC. SECTION 106.3.5.1.3. | | | | | | 3. SHT P-8REVISION 5 NOT SHOWN ON THE REVISION INDEX, | | | NOR IS THE REVISION CLOUDED. PLEASE CLOUD ALL REVISIONS | | | AND INDICATED THE REVISION NUMBER ON THE REVISION | | | INDEX. SECTION 106.1.1. - REVISION 3 IS NOT CLOUDED, | | | NOR DOES IT INDICATE WHAT CHANGE HAS BEEN MADE. PLEASE | | | CLARIFY. SECTION 106.1.1. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
F |
Date |
2006-11-01 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-11-01 |
Time |
13:52 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-11-01 |
Time |
13:52 |
Sent To |
|
|
| Notes |
| 2006-11-01 14:01:13 | REVISIONDENIED | | | REFERENCE: | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. SHTS P-1, P-5, P-8 PLUMBING TECHNICAL CODES OK, BUT | | | THE TITLE BLOCK FOR THE ARCHITECT DOES NOT HAVE THE | | | REQUIRED BUSINESS NUMBER, (CERTIFICATE OF | | | AUTHORIZATION), IN THE TITLE BLOCK. THIS HAS BEEN | | | COMMENTED ON SINCE FEB. 06 IN THE FIRST PLAN REVIEW FOR | | | PLUMBING. EIGHT MONTHS IS SUFFICIENT TIME TO APPLY FOR | | | A CERTIFICATE OF AUTHORIZTION. EITHER REMOVE "GRW | | | ARCHITECTS" FROM THE SHEETS, OR INDICATE THE BUSINESS | | | NUMBER IN THE TITLE BLOCK AS REQUIRED IN FAC | | | 61G1-16.004(2) & FS 481.219. | | | | | | 2. WHEN RESUBMITTING REVISIONS, DISABLE ALL REVISION | | | CLOUDS FROM PREVIOUS REVISIONS AND ONLY SHOW THE | | | CLOUDED REVISIONS BEING SUBMITTED FOR THE PRESENT | | | REVISION. ALSO MAKE SURE THE CLOUDS ARE BOLD ENOUGH TO | | | SEE. THE LAST REVISIONS WERE DIFFICULT TO FIND. SECTION | | | 104.2.1. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
F |
Date |
2006-09-01 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-09-01 |
Time |
16:41 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-09-01 |
Time |
16:41 |
Sent To |
|
|
| Notes |
| 2006-09-01 00:00:00 | REVISION DENIED | | | SHEETS P-8 & P-15 | | | | | | 1. SHT P-8 WATER LINES DO NOT REFLECT | | | THE FLOOR PLAN NEAR FIXTURES P-15 & | | | P-16. | | | | | | 2. SHT P-15 GAS REVISION NOT APPROVED. | | | SEE GAS REVISION NOTES | | | | | | | | | REVISION OK SHTS P-1, P-5, & P-17 | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2006-07-07 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-07-07 |
Time |
13:35 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-07-07 |
Time |
13:35 |
Sent To |
|
|
| Notes |
| 2006-07-07 00:00:00 | | | | | | | PASSED/PROVISO | | | | | | REVISIONS REQUIRED FOR SHEETS P1, P-5, & | | | P-10 FLOOR PLANS SHOWING THE HAND SINKS | | | REQUIRED BY DBPR PLAN REVIEW. REVISION | | | IS ALSO REQUIRED FORSHEET P-8 WATER | | | RISER DIAGRAM AND SHT P-15 FPR THE | | | GREASE ISOMETRIC RISER DIAGRAM | | | REFLECTING THESE CHANGES. | | | | | | REVISION IS ALSO REQUIRED FOR THE GAS | | | ISOMETRIC RISER DIAGRAM, WHICH SHALL | | | CORRELATE WITH THE GAS | | | EQUIPMENT/CONNECTED LOAD AND THE MANUF. SPECIFICATION | | | SHEETS INDICATING THE BTU | | | LOAD FOR EACH GAS APPLIANCE. | | | | | | GAS ISOMETRIC NOT APPROVED AT THIS TIME. | | | PLUMBING ONLY APPROVED. SEPARATE GAS | | | PERMIT REQUIRED. | | | | | | | | | | | | | | | . |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2006-07-05 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-07-05 |
Time |
18:23 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-07-05 |
Time |
18:23 |
Sent To |
|
|
| Notes |
| 2006-07-05 00:00:00 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | WPB CITY CODE/ORDINENCES | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | A. FROM PREVIOUS REVIEW: THE COMMENT | | | NUMBERS WILL REMAIN THE SAME. | | | | | | 5. SHT A.01 ROUTE PLANS TO DBPR, | | | DIVISION OF HOTEL & RESTURANT FOR REVIEW | | | PRIOR TO RESUBMITTING. MINIMUM 3 SETS OF | | | PLANS SHALL BE REVIEWED, STAMPED AND TWO | | | SHEET "WORKSHEETS" SHALL BE ATTACHED TO | | | EACH SET OF PLANS SUBMITTED FOR REVIEW. | | | SECTION 102.2.1. | | | ***NO RESPONSE, NOT ADDRESSED. | | | ***RESPONSE NOTED, BUT NEW SHEETS SHALL | | | BE INSERTED INTO THE PLANS, AND ALL | | | VOIDED SHEETS REMOVED. ATTACH 2 PAGE | | | "SPECIFICATION WORKSHEETS" TO EACH SET | | | OF PLANS. REMOVE BUSINESS NAME FROM THE | | | TITLE BLOCK, OR INDICATE CERTIFICATE OF | | | AUTHORIZATION NUMBER ON TITLE BLOCK. THE | | | SIGNED SEALED SHALL BE DATED WHEN SEAL | | | IS AFFIXED TO DRAWINGS. FAC 61G1-16.003 | | | & 61G1-16.004(5) - FS 481.219. | | | | | | 10. SHT A.01 ADA ROOMS MATRIX INDICATES | | | 5 ROOMS FOR THE HEARING IMPAIRED ROOMS. | | | ONE ROOM (226) IS NOT SHOWN ON THE FLOOR | | | PLAN. (4 OTHER ROOMS SHOWN AS HEARING | | | IMPAIRED ACCOMODATIONS). PLEASE CLARIFY. | | | SECTION 11-9.1.3. | | | ***NO RESPONSE, NOT ADDRESSED. | | | ****RESPONSE NOTED, BUT HEARING IMPAIRED | | | ROOMS SHALL BE IN ADDITION TO THOSE | | | ACCESSIBLE SLEEPING ROOMS AND SUITES | | | REQUIRED BY 11-9.1.2. ONLY ROOMS 307 & | | | 407 MEET THIS REQUIREMENT. 2 OTHER | | | HEARING IMPAIRED ACCOMMODATION ROOMS | | | REQUIRED. | | | | | | 11. SHT A.01 1 ROOM SHALL COMPLY WITH | | | SECTION 11-9.2.3 PLEASE INDICATE THE | | | ROOM NUMBER THAT SHALL COMPLY WITH THIS | | | REQUIREMENT. | | | ***NO RESPONSE, NOT ADDRESSED. | | | ****RESPONSE NOTED, BUT THE ROOM IN | | | QUESTION HAS NOT BEEN INDICATED ON THE | | | MATRIX. | | | | | | 13. SHT A.17 BREAK SINK TO COMPLY WITH | | | SECTION 11-4.24 AND ALL SUBSECTIONS. | | | SUBMIT A DETAIL. | | | ***NO RESPONSE, NOT ADDRESSED. | | | ****RESPONSE NOTED, BUT NO DETAIL FOR | | | THE SINK IS LOCATED ON SHT A.17. | | | | | | 14. SHT A.17 PLAN KEY NOTES: SHOW THE | | | LOCATIONS OF NUMBER 2 & 10. SECTION | | | 106.1.1. | | | ***NO RESPONSE, NOT ADDRESSED. | | | ****RESPONSE NOTED, BUT DO NOT | | | UNDERSTAND THE RESPONSE. KEY NOTES HAVE | | | BEEN DELETED, AND THE EYE WASH AND THE | | | ICE MACHINE AS INDICATED PREVIOUSLY ARE | | | NOT SHOWN. PLEASE CLARIFY. | | | | | | 17. SHT A.34 PUBLIC TOILETS, PROVIDE A | | | DETAIL SHOWING COMPLIANCE WITH 11-4.16, | | | 11-4.18, 11-4.19, & 11-4.22 AND ALL | | | SUBSECTIONS. SECTION 106.1.1. | | | ***NO RESPONSE, NOT ADDRESSED. | | | ****RESPONSE NOTED, BUT THE FOLLOWING | | | INFORMATION IS NOT SHOWN: | | | FOR THE UNINAL: | | | A. 11-4.18.2 HEIGHT | | | B. 11-4.18.4 FLUSH CONTROLS | | | FOR THE LAV'S: | | | A. 11-4.19.2 HEIGHT & CLEARANCES | | | B. 11-4.19.5 FAUCETS. | | | | | | 32. P-15 THE FOLLOWING INFORMATION IS | | | REQUIRED FOR GAS PLAN APPROVAL: | | | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS. | | | ***RESPONSE NOTED, BUT THERE ARE SOME | | | CUT SECTIONS THAT DO NOT SHOW THE | | | LENGTH. | | | ****RESPONSE NOTED, BUT THERE IS NO | | | LENGTHS FOR THE PIPING TO THE POOL/SPA | | | HEATERS. THERE ARE 3 WATER HEATERS | | | INDICATED, BUT ONLY TWO SHOWN ON THE | | | ISOMETRIC RISER DIAGRAM. PLEASE | | | CORRELATE THE APPLIANCES WITH THE RISER | | | DIAGRAM. | | | | | | F. SUBMIT MANUFACTURE SHEETS FOR ALL | | | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | ***NO RESPONSE, NOT ADDRESSED. | | | ****RESPONSE NOTED, BUT MANUF. | | | SPECIFICATION SHEET ARE REQUIRED FOR ALL | | | GAS APPLIANCES. | | | | | | G. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. BYPASS | | | PIPING SHALL BE CONNECTED DOWNSTREAM OF | | | THE EMERGENCY HOOD SHUT OFF VALVE. | | | ***NO RESPONSE, NOT ADDRESSED. EMERGENCY | | | HOOD SHUT DOWN SHUT OFF VALVE SHALL BE | | | INSTALLED BETWEEN 42" AND 48" PER | | | NFPA-96 SECTION 10.5.1 AND NFPA-1 | | | SECTION 50.4.7.1. INDICATE ON GAS RISER. | | | ****RESPONSE NOTED, BUT NO MANUAL GAS | | | SHUT OFF VALVE IS SHOWN ON RISER | | | DIAGRAM. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | RESUBMIT ONE SET OF ORIGINAL SHEETS FOR | | | COMPARISON. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2006-04-29 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-04-29 |
Time |
19:07 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-04-29 |
Time |
19:07 |
Sent To |
|
|
| Notes |
| 2006-04-29 00:00:00 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | WPB CITY CODE/ORDINENCES | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | A. FROM PREVIOUS REVIEW: THE COMMENT | | | NUMBERS WILL REMAIN THE SAME. | | | | | | 2. ALL ARCHITECTURAL SHEETS SHALL SHOW | | | THE DATE THAT THE SEAL WAS AFFIXED TO | | | THE PLANS. FAC 61G1-16.003 & | | | 61G1-16.004(5) AND FS 481.219 & | | | 481.2055. MANY SHEETS HAVE NO DATE ON | | | THE SEAL AND THE CERTIFICATE OF | | | AUTHORIZATION NUMBER SHALL BE IN THE | | | TITLE BLOCK OF EACH SHEET. | | | ***NO RESPONSE: ID SHEETS HAVE PREPARED | | | BY THE ARCHITECT HAVE NO DATE ON THE | | | SEAL AND NO SHEETS HAVE THE CERTIFICATE | | | OF AUTHORIZATION NUMBER ON EACH SHEET. | | | | | | 3. POOL PLAN: SEPARATE PERMIT/PLANS | | | REQUIRED FOR THE POOL. MINIMUM 2 SETS OF | | | PLANS SHALL BE REVIEWED AND STAMPED BY | | | THE PBC HEALTH DEPT. PRIOR TO SUBMITTING | | | TO THE CITY WPB FOR REVIEW. | | | ***NO RESPONSE: THIS WAS INFORMATIONAL. | | | | | | 5. SHT A.01 ROUTE PLANS TO DBPR, | | | DIVISION OF HOTEL & RESTURANT FOR REVIEW | | | PRIOR TO RESUBMITTING. MINIMUM 3 SETS OF | | | PLANS SHALL BE REVIEWED, STAMPED AND TWO | | | SHEET "WORKSHEETS" SHALL BE ATTACHED TO | | | EACH SET OF PLANS SUBMITTED FOR REVIEW. | | | SECTION 102.2.1. | | | ***NO RESPONSE, NOT ADDRESSED. | | | | | | 7. SHT A.01 INDICATES ROOM TYPES K4, K5, | | | K6, K7, KING HI, KING, KS, K2, K3, KING | | | 2, KING 3, KING 8, QQ, QQ HI, BUT ONLY | | | K4, K7, KS, KE, KING 2, OFFER | | | ACCESSIBLITY. PLEASE INDICATE HOW THIS | | | COMPLYS WITH SECTION 11-9.1.4 CLASSES OF | | | SLEEPING ACCOMMODATIONS. | | | ***NO RESPONSE, NOT ADDRESSED. | | | | | | 8. SHT A.01 PLAN KEY NOTES: UNABLE TO | | | LOCATE KEY PLAN NUMBERS 7 AND 10. PLEASE | | | SHOW NUMBERS ON FLOOR PLAN. SECTION | | | 106.1.1. | | | ***NO RESPONSE, NOT ADDRESSED. | | | | | | 9. SHT A.01 ADA ROOMS MATRIX INDICATES | | | ROOM 121 AS HAVING A SHOWER. TABLE | | | INDICATING NUMBER OF ACCESSIBLE ROOMS | | | INDICATE 4 ARE REQUIRED WITH ONE ROOM | | | WITH A ROLL IN SHOWER REQUIRED. PLEASE | | | INDICATE IF ROOM 121 IS ONE OF THE FOUR | | | REQUIRED ACCESSIBLE ROOMS. SECTION | | | 11-9.1.2. | | | ***NO RESPONSE, NOT ADDRESSED. | | | | | | 10. SHT A.01 ADA ROOMS MATRIX INDICATES | | | 5 ROOMS FOR THE HEARING IMPAIRED ROOMS. | | | ONE ROOM (226) IS NOT SHOWN ON THE FLOOR | | | PLAN. (4 OTHER ROOMS SHOWN AS HEARING | | | IMPAIRED ACCOMODATIONS). PLEASE CLARIFY. | | | SECTION 11-9.1.3. | | | ***NO RESPONSE, NOT ADDRESSED. | | | | | | 11. SHT A.01 1 ROOM SHALL COMPLY WITH | | | SECTION 11-9.2.3 PLEASE INDICATE THE | | | ROOM NUMBER THAT SHALL COMPLY WITH THIS | | | REQUIREMENT. | | | ***NO RESPONSE, NOT ADDRESSED. | | | | | | 12. SHT A.05 SUBMIT A DETAIL FOR | | | SCUPPERS. ALL DOWNSPOUTS ARE NOT SHOWN | | | ON THE ELEVATIONS. PLEASE CLARIFY. | | | SECTION 106.1.1. | | | ***NO RESPONSE, NOT ADDRESSED. | | | | | | 13. SHT A.17 BREAK SINK TO COMPLY WITH | | | SECTION 11-4.24 AND ALL SUBSECTIONS. | | | SUBMIT A DETAIL. | | | ***NO RESPONSE, NOT ADDRESSED. | | | | | | 14. SHT A.17 PLAN KEY NOTES: SHOW THE | | | LOCATIONS OF NUMBER 2 & 10. SECTION | | | 106.1.1. | | | ***NO RESPONSE, NOT ADDRESSED. | | | | | | 15. SHT A.32 SHOW CENTER OF FIXTURE OFF | | | THE WALL AT 18" FOR THE WATER CLOSET. | | | (FIG. 28). SHOW THE FLUSH CONTROLS AS | | | REQUIRED IN SECTION 11-4.16.5. | | | ***NO RESPONSE, NOT ADDRESSED. | | | | | | 16. SHT A.33A LAV CLEARANCE TO BE 29" | | | PER 11-4.19.2. (27" SHOWN). - SHOW THE | | | FAUCET REQUIREMENT PER SECTION 11-4.19.5 | | | - SHOW CONTROL REQUIREMENTS FOR TUB & | | | SHOWERS PER 11-4.20.5 (FIG. 11-34) AND | | | 11-4.21.5 (FIG. 11-37). | | | ***NO RESPONSE, NOT ADDRESSED. | | | | | | 17. SHT A.34 PUBLIC TOILETS PROVIDE A | | | DETAIL SHOWING COMPLIANCE WITH 11-4.16, | | | 11-4.18, 11-4.19, & 11-4.22 AND ALL | | | SUBSECTIONS. SECTION 106.1.1. | | | ***NO RESPONSE, NOT ADDRESSED. | | | | | | 18. SHT P-1 NOTE INDICATES 24 GAUGE | | | GALVINIZED PAN ABOVE THE ELECTRICAL | | | EQUIPMENT ROOM WITH A 1" DRAIN TO FLOOR | | | DRAIN. PER PLUMBING NOTES ON SHT P-12, | | | NO WATER, SANITARY, OR DRAINAGE PIPING | | | PERMITTED IN ELECTRICAL OR ELEVATOR | | | EQUIPMENT ROOMS. (ALSO SEE NEC SECTION | | | 110.26(F)A.D. - IF SOMEHOW APPROVED, AN | | | EXPLANATION WILL BE REQUIRED TO EXPLAIN | | | HOW A 1" DRAIN LINE WILL BE ABLE TO | | | DRAIN THE 4" SOIL STACK #13, 1" HOT | | | WATER & 1-1/4" COLD WATER IF THESE LINES | | | HAPPEN TO FAIL. SECTION 106.1.1. | | | ***RESPONSE NOTED, BUT PLAN STILL SHOWS | | | A 1" DRAIN FROM METAL PAN, AND STILL | | | SHOWS STACK 13 9TYPE A) SOIL STACK IN | | | THE MAIN ELECTRIC ROOM. | | | | | | 19. SUBMIT A KITCHEN FIXTURE I.D. SHEET | | | INDICATING THE LOCATION AND I.D. NUMBER | | | FOR EACH FIXTURE. INDICATE ALL SANT., | | | GREASE, GAS, AND WATER SUPPLY PIPE SIZE | | | FOR EACH FIXTURE/APPLIANCE. SECTION | | | 106.3.5.1.3. | | | ***RESPONSE NOTED, BUT NO KITCHEN | | | FIXTURE ID SHEET SUBMITTED. (SEE SHT | | | A-19 FOR ALL KITCHEN FIXTURES). | | | | | | 21. SHT P-4 BATH GROUP "E" ITEM D | | | INDIRECT WASTE FROM THE ICE MACHINE NOT | | | APPROVED AS SHOWN. SEE ICE MACHINE | | | DETAIL SHEET P-14 FOR CORRECT | | | INSTALLATION OF THE INDIRECT WASTE. | | | SECTIONS 802.3 & 802.3.2. PLEASE CHANGE | | | DETAIL ON BATH GROUP "E" | | | ***RESONSE NOTED, BUT NO CHANGED NOTED | | | ON PLANS | | | | | | 22. SHT P-5 3" RPZV BACKFLOW REQUIRED | | | DOWNSTREAM OF THE METERS. SECTIONS 603.1 | | | FOOTNOTE D, AND608.13.2. - ALSO MAKE | | | CHANGE TO WATER ISOMETRIC DIAGRAM ON | | | SHEET P-8. | | | ***RESPONSE NOTED, BUT DOUBLE CHECK | | | VALVES ARE NOT APPROVED. 3" RPCV | | | BACKFLOW REQUIRED. | | | | | | 23. SHT P-6 ALL WATER RISER DIAGRAMS, | | | WATER HAMMER ARRESTORS SHALL BE LOCATED | | | NEAR THE FIXTURE IN AN "EFFECTIVE RANGE" | | | NOT IN THE CEILING AS SHOWN. PDI-WH 201 | | | AND MANUF. INSTALLATION INSTRUCTIONS. | | | CHANGE NOTE 3 OF THE WATER ISOMETRIC | | | RISERS NOTES TO REFLECT THIS. SECTION | | | 106.1.1. | | | ***RESPONSE NOTED, BUT WATER HAMMER | | | ARRESTORS ARE STILL SHOWN IN THE CEILING | | | FOR THE SHOWERS AND TUBS. | | | | | | 24. SHT P-7 STACK TYPE "A1" NOTE | | | INDICATES A SHOWER FOR THE BATHROOM | | | GROUPS, BUT A TUB IS SHOWN ON THE FLOOR | | | PLAN. PLEASE CORRELATE FLOOR PLAN AND | | | NOTE. - STACK TYPE "C" A TUB ON THE BATH | | | GROUP, BUT ISOMETRIC SHOWS SHOWERS. | | | PLEASE CORRELATE. - STACK TYPE "E" SHOWS | | | A SAFEWASTE FOR THE INDIRECT WASTE FOR | | | THE ICE MAKER. SHEET P-14 SHOWS THE | | | CORRECT INDIRECT WASTE ON THE ICE MAKER | | | DETAIL. PLEASE CHANGE RISER ISOMETRIC TO | | | REFLECT THE ICE MAKER DETAIL FOR | | | INDIRECT WASTE. SECTION 106.1.1. | | | ***RESPONSE NOTED, BUT STACK A1 NOT | | | CHANGED, STACK C SHOULD SHOW 1 TUB & 1 | | | SHOWER AND FLOOR PLAN ONLY SHOWN ONE | | | LAV, AND STACK E REQUIRES A FLOOR SINK, | | | NOT A FLOOR DRAIN. | | | | | | 25. SHT P-8 BACKFLOW PROTECTION IS | | | REQUIRED FOR SUPPLY LINE TO THE | | | FOUNTAIN. PLEASE INDICATE METHOD OF | | | BACKFLOW PROTECTION. SECTION 608. | | | ***RESPONSE NOTED, BUT DOUBLE CHECK | | | VALVES ARE NOT APPROVED. | | | | | | 27. SHT P-13 WATER HEATER DETAIL STATES | | | "SEE PROJECT DOCUMENTS AND SPECIFICTION | | | FOR ADDITIONAL INFORMATION AND WORK | | | REQUIRED FOR A CODE APPROVED AND | | | ARCHITECT ACCEPTED INSTALLATION". ALSO | | | STATESIN PIPING ARRANGEMENT AT WATER | | | HEATERS (E) "REFER TO MANUFACTURE | | | RECOMMENDATIONS AND CODE REQUIREMENTS | | | FOR INSTALLATIONS AND LOCATIONS OF | | | INTAKE AND EXHAUST VENT TERMINALS". | | | THESE HAVE NOT BEEN SUBMITTED. SECTION | | | 106.1.1. | | | ***RESPONSE NOTED, BUT NO SPECIFICATIONS | | | HAVE BEEN LOCATED. | | | | | | 29. SHT P-14 NOTES REFER TO PROJECT | | | SPECIFICATIONS THAT WERE NOT SUBMITTED. | | | PLEASE SUBMIT ALL REFERENCED | | | SPECIFICATIONS. SECTION 106.1.1. | | | ***RESPONSE NOTED, BUT NO SPECIFICATION | | | HAVE BEEN LOCATED. | | | | | | 30. SHT P-14 ICE MACHINE DETAIL. | | | SEPARATE DRAIN LINES REQUIRED FOR THE | | | ICE CUBER AND THE ICE BIN. | | | ***RESPONSE NOTED, BUT DETAIL HAS NOT | | | BEEN CHANGED. | | | | | | 31. SHT P-15 GREASE WASTE ISOMETRIC | | | DIAGRAM DOES NOT REFLECT THE FLOOR PLAN. | | | NO LINE TO THE CAN WASH IS SHOWN. P-5 | | | BEHIND THE ELECTRICAL ROOM IS SHOWN AS A | | | FLOOR SINK ON THE FLOOR PLAN AND AS A | | | FLOOR DRAIN ON THE RISER DIAGRAM. | | | (SHOULD BE A FLOOR SINK ON BOTH) SECTION | | | 106.1.1. - UNDER GREASE WASTE DIAGRAM | | | THE NOTESTATES "SEE KITCHEN DOCUMENTS, | | | SPECIFICATIONS, AND DATA SHEETS FOR | | | ADDITIONAL INFORMATION AND REQUIREMENTS | | | OF PLUMBING WORK ETC.". THESE WERE NOT | | | SUBMITTED. | | | ***RESPONSE NOTED, BUT NO CHANGES ARE | | | SHOWN AND COMMENT HAS NOT BEEN | | | ADDRESSED. | | | | | | 32. P-15 THE FOLLOWING INFORMATION IS | | | REQUIRED FOR GAS PLAN APPROVAL: | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS. | | | ***RESPONSE NOTED, BUT THERE ARE SOME | | | CUT SECTIONS THAT DO NOT SHOW THE LENGTH | | | | | | B. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES,- | | | SPECIFICATIONS NOT SUBMITTED. INDICATE | | | IF PIPING WILL BE SCREW PIPE OR WELDED | | | PIPE. | | | ***RESPONSE NOTED, BUT NO INFORMATION | | | FOUND. | | | | | | D. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2004 FUEL GAS CODE SEC. | | | 402.4(2). NATURAL GAS SPECIFY .5 PSI OR | | | 2 PSI. | | | ***RESPONSE NOTED, BUT DELIVERY PRESSURE | | | HAS NOT BEEN ADDRESSED. | | | | | | F. SUBMIT MANUFACTURE SHEETS FOR ALL | | | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | ***NO RESPONSE, NOT ADDRESSED. | | | | | | G. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. BYPASS | | | PIPING SHALL BE CONNECTED DOWNSTREAM OF | | | THE EMERGENCY HOOD SHUT OFF VALVE. | | | ***NO RESPONSE, NOT ADDRESSED. EMERGENCY | | | HOOD SHUT DOWN SHUT OFF VALVE SHALL BE | | | INSTALLED BETWEEN 42" AND 48" PER | | | NFPA-96 SECTION 10.5.1 AND NFPA-1 | | | SECTION 50.4.7.1. INDICATE ON GAS RISER. | | | | | | *************NEW COMMENT**************** | | | 1B. SHT P-9 SANITARY RISER DIAGRAM DOES | | | NOT REFLECT THE FLOOR PLAN. NEW FLOOR | | | PLAN SHOWS THE LAV CHANGED TO THE | | | OPPOSITE WALL BY STACK 1 WHERE AS THE | | | RISER DOES NOT REFLECT THIS CHANGE. THE | | | BATHROOM AT STACK 2 SHOWS A TUB ON THE | | | FLOOR PLAN, BUT A SHOWER ON THE RISER | | | DIAGRAM. PLEASE CORRELATE RISER AND | | | FLOOR PLAN. SECTION 106.1.1. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | RESUBMIT ONE SET OF ORIGINAL SHEETS FOR | | | COMPARISON. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2006-02-21 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-02-21 |
Time |
09:30 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-02-11 |
Time |
18:55 |
Sent To |
|
|
| Notes |
| 2006-02-21 00:00:00 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | WPB CITY CODE/ORDINENCES | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. INDICATE ON PLANS THAT THE DESIGN IS | | | PER FBC-2004. | | | 2. ALL ARCHITECTURAL SHEETS SHALL SHOW | | | THE DATE THAT THE SEAL WAS AFFIXED TO | | | THE PLANS. FAC 61G1-16.003 & | | | 61G1-16.004(5) AND FS 481.219 & | | | 481.2055. MANY SHEETS HAVE NO DATE ON | | | THE SEAL AND THE CERTIFICATE OF | | | AUTHORIZATION NUMBER SHALL BE IN THE | | | TITLE BLOCK OF EACH SHEET. | | | 3. POOL PLAN: SEPARATE PERMIT/PLANS | | | REQUIRED FOR THE POOL. MINIMUM 2 SETS OF | | | PLANS SHALL BE REVIEWED AND STAMPED BY | | | THE PBC HEALTH DEPT. PRIOR TO SUBMITTING | | | TO THE CITY WPB FOR REVIEW. | | | 4. SHT A.01 GREASE INTECEPTOR SHALL BE | | | SIZED BY LYNN MASSON, ENVIRONMENTAL | | | COMPLIANCE. PLEASE CONTACT HER AT (561) | | | 822-2271, OR FAX (561) 822-2279, OR | | | E-MAIL HER AT [email protected]. SUBMIT A | | | COPY OF HER REQUIREMENTS/DETERMINATION | | | WITH PLANS WHEN RESUBMITTING. WASTE ORD. | | | 90-124(7)(B). | | | 5. SHT A.01 ROUTE PLANS TO DBPR, | | | DIVISION OF HOTEL & RESTURANT FOR REVIEW | | | PRIOR TO RESUBMITTING. MINIMUM 3 SETS OF | | | PLANS SHALL BE REVIEWED, STAMPED AND TWO | | | SHEET "WORKSHEETS" SHALL BE ATTACHED TO | | | EACH SET OF PLANS SUBMITTED FOR REVIEW. | | | SECTION 102.2.1. | | | 6. SHT A.01 SHOW THE TURNING AREA IN THE | | | TOILET ROOMS 32 & 33, NOT IN THE | | | ACCESSIBLE STALL. SECTION 11-4.22.3 | | | 7. SHT A.01 INDICATES ROOM TYPES K4, K5, | | | K6, K7, KING HI, KING, KS, K2, K3, KING | | | 2, KING 3, KING 8, QQ, QQ HI, BUT ONLY | | | K4, K7, KS, KE, KING 2, OFFER | | | ACCESSIBLITY. PLEASE INDICATE HOW THIS | | | COMPLYS WITH SECTION 11-9.1.4 CLASSES OF | | | SLEEPING ACCOMMODATIONS. | | | 8. SHT A.01 PLAN KEY NOTES: UNABLE TO | | | LOCATE KEY PLAN NUMBERS 7 AND 10. PLEASE | | | SHOW NUMBERS ON PLAN. SECTION 106.1.1. | | | 9. SHT A.01 ADA ROOMS MATRIX INDICATES | | | ROOM 121 AS HAVING A SHOWER. TABLE | | | INDICATING NUMBER OF ACCESSIBLE ROOMS | | | INDICATE 4 ARE REQUIRED WITH ONE ROOM | | | WITH A ROLL IN SHOWER REQUIRED. PLEASE | | | INDICATE IF ROOM 121 IS ONE OF THE FOUR | | | REQUIRED ACCESSIBLE ROOMS. SECTION | | | 11-9.1.2. | | | 10. SHT A.01 ADA ROOMS MATRIX INDICATES | | | 5 ROOMS FOR THE HEARING IMPAIRED ROOMS. | | | ONE ROOM (226) IS NOT SHOWN ON THE FLOOR | | | PLAN. (4 OTHER ROOMS SHOWN AS HEARING | | | IMPAIRED ACCOMODATIONS). PLEASE CLARIFY. | | | SECTION 11-9.1.3. | | | 11. SHT A.01 1 ROOM SHALL COMPLY WITH | | | SECTION 11-9.2.3 PLEASE INDICATE THE | | | ROOM NUMBER THAT SHALL COMPLY WITH THIS | | | REQUIREMENT. | | | 12. SHT A.05 SUBMIT A DETAIL FOR | | | SCUPPERS. ALL DOWNSPOUTS ARE NOT SHOWN | | | ON THE ELEVATIONS. PLEASE CLARIFY. | | | SECTION 106.1.1. | | | 13. SHT A.17 BREAK SINK TO COMPLY WITH | | | SECTION 11-4.24 AND ALL SUBSECTIONS. | | | SUBMIT A DETAIL. | | | 14. SHT A.17 PLAN KEY NOTES: SHOW THE | | | LOCATIONS OF NUMBER 2 & 10. SECTION | | | 106.1.1. | | | 15. SHT A.32 SHOW CENTER OF FIXTURE OFF | | | THE WALL AT 18" FOR THE WATER CLOSET. | | | (FIG. 28). SHOW THE FLUSH CONTROLS AS | | | REQUIRED IN SECTION 11-4.16.5. | | | 16. SHT A.33A LAV CLEARANCE TO BE 29" | | | PER 11-4.19.2. (27" SHOWN). - SHOW THE | | | FAUCET REQUIREMENT PER SECTION 11-4.19.5 | | | - SHOW CONTROL REQUIREMENTS FOR TUB & | | | SHOWERS PER 11-4.20.5 (FIG. 11-34) AND | | | 11-4.21.5 (FIG. 11-37). | | | 17. SHT A.34 PUBLIC TOILETS PROVIDE A | | | DETAIL SHOWING COMPLIANCE WITH 11-4.16, | | | 11-4.18, 11-4.19, & 11-4.22 AND ALL | | | SUBSECTIONS. SECTION 106.1.1. | | | 18. SHT P-1 NOTE INDICATES 24 GAUGE | | | GALVINIZED PAN ABOVE THE ELECTRICAL | | | EQUIPMENT ROOM WITH A 1" DRAIN TO FLOOR | | | DRAIN. PER PLUMBING NOTES ON SHT P-12, | | | NO WATER, SANITARY, OR DRAINAGE PIPING | | | PERMITTED IN ELECTRICAL OR ELEVATOR | | | EQUIPMENT ROOMS. (ALSO SEE NEC SECTION | | | 110.26(F)A.D. - IF SOMEHOW APPROVED, AN | | | EXPLANATION WILL BE REQUIRED TO EXPLAIN | | | HOW A 1" DRAIN LINE WILL BE ABLE TO | | | DRAIN THE 4" SOIL STACK #13, 1" HOT | | | WATER & 1-1/4" COLD WATER IF THESE LINES | | | HAPPEN TO FAIL. SECTION 106.1.1. | | | 19. SUBMIT A KITCHEN FIXTURE I.D. SHEET | | | INDICATING THE LOCATION AND I.D. NUMBER | | | FOR EACH FIXTURE. INDICATE ALL SANT., | | | GREASE, GAS, AND WATER SUPPLY PIPE SIZE | | | FOR EACH FIXTURE/APPLIANCE. SECTION | | | 106.3.5.1.3. | | | 20. SHT P-1 DISHWASHER SHALL DRAIN INTO | | | THE SANITARY SYSTEM, NOT THE GREASE | | | SYSTEM PER CITY CODE 90-124(7)(B). | | | 21. SHT P-4 BATH GROUP "E" ITEM D | | | INDIRECT WASTE FROM THE ICE MACHINE NOT | | | APPROVED AS SHOWN. SEE ICE MACHINE | | | DETAIL SHEET P-14 FOR CORRECT | | | INSTALLATION OF THE INDIRECT WASTE. | | | SECTIONS 802.3 & 802.3.2. PLEASE CHANGE | | | DETAIL ON BATH GROUP "E" | | | 22. SHT P-5 3" RPZV BACKFLOW REQUIRED | | | DOWNSTREAM OF THE METERS. SECTIONS 603.1 | | | FOOTNOTE D, AND608.13.2. - ALSO MAKE | | | CHANGE TO WATER ISOMETRIC DIAGRAM ON | | | SHEET P-8. | | | 23. SHT P-6 ALL WATER RISER DIAGRAMS, | | | WATER HAMMER ARRESTORS SHALL BE LOCATED | | | NEAR THE FIXTURE IN AN "EFFECTIVE RANGE" | | | NOT IN THE CEILING AS SHOWN. PDI-WH 201 | | | AND MANUF. INSTALLATION INSTRUCTIONS. | | | CHANGE NOTE 3 OF THE WATER ISOMETRIC | | | RISERS NOTES TO REFLECT THIS. SECTION | | | 106.1.1. | | | 24. SHT P-7 STACK TYPE "A1" NOTE | | | INDICATES A SHOWER FOR THE BATHROOM | | | GROUPS, BUT A TUB IS SHOWN ON THE FLOOR | | | PLAN. PLEASE CORRELATE FLOOR PLAN AND | | | NOTE. - STACK TYPE "C" A TUB ON THE BATH | | | GROUP, BUT ISOMETRIC SHOWS SHOWERS. | | | PLEASE CORRELATE. - STACK TYPE "E" SHOWS | | | A SAFEWASTE FOR THE INDIRECT WASTE FOR | | | THE ICE MAKER. SHEET P-14 SHOWS THE | | | CORRECT INDIRECT WASTE ON THE ICE MAKER | | | DETAIL. PLEASE CHANGE RISER ISOMETRIC TO | | | REFLECT THE ICE MAKER DETAIL FOR | | | INDIRECT WASTE. SECTION 106.1.1. | | | 25. SHT P-8 BACKFLOW PROTECTION IS | | | REQUIRED FOR SUPPLY LINE TO THE | | | FOUNTAIN. PLEASE INDICATE METHOD OF | | | BACKFLOW PROTECTION. SECTION 608. | | | 26. SHT P-10 INDICATE THE PIPE SIZE AND | | | SQUARE FOOTAGE BEING DRAINED DOWNSTREAM | | | OF STORM RISER L-5. - PIPING DOWNSTREAM | | | OF STORM RISER L-2 IS INDICATED AS BEING | | | 2% SLOPE. THIS IS NOT REQUIRED AS THE | | | RAINFALL RATE IS 4.5 INCHES PER HR. IF | | | THE PIPE IS TO BE 2% THEN THE ENTIRE RUN | | | FROM L-8 TO THE OUTSIDE OF THE BLDG | | | SHALL BE 2% PER SECTION 704.1. - PER | | | TABLE 1106.3THE MAXIMUM SQUARE FOOTAGE | | | FOR 4" PIPE @ 4.5 PER INCH RANIFALL RATE | | | IS 1600SF. L-10 & L-11 ADD UP TO 1646SF. | | | 5" HORIZONTAL PIPING REQUIRED. PLEASE | | | CLARIFY. | | | 27. SHT P-13 WATER HEATER DETAIL STATES | | | "SEE PROJECT DOCUMENTS AND SPECIFICTION | | | FOR ADDITIONAL INFORMATION AND WORK | | | REQUIRED FOR A CODE APPROVED AND | | | ARCHITECT ACCEPTED INSTALLATION". ALSO | | | STATESIN PIPING ARRANGEMENT AT WATER | | | HEATERS (E) "REFER TO MANUFACTURE | | | RECOMMENDATIONS AND CODE REQUIREMENTS | | | FOR INSTALLATIONS AND LOCATIONS OF | | | INTAKE AND EXHAUST VENT TERMINALS". | | | THESE HAVE NOT BEEN SUBMITTED. SECTION | | | 106.1.1. | | | 28. SHT P-14 STORM ISOMETRIC DIAGRAM | | | DOES NOT REFLECT THE PIPING SHOWING ON | | | SHEET P-10. THE RISER TO L-10 & L-11 IS | | | SHOWN AS 5" ON SHT P-10, BUT NO PIPE | | | SIZE IS SHOWN ON RISER. - INDICATE THE | | | PIPE SIZE AND SQUARE FOOTAGE DOWNSTREAM | | | OF RISER L-5. - 2% SLOPE SHOWN | | | DOWNSTREAM OF RISER L-2. (SEE COMMENT | | | 26) SECTION 106.1.1 AND TABLE 1106.3. | | | 29. SHT P-14 NOTES REFER TO PROJECT | | | SPECIFICATIONS THAT WERE NOT SUBMITTED. | | | PLEASE SUBMIT ALL REFERENCED | | | SPECIFICATIONS. SECTION 106.1.1. | | | 30. SHT P-14 ICE MACHINE DETAIL. | | | SEPARATE DRAIN LINES REQUIRED FOR THE | | | ICE CUBER AND THE ICE BIN. | | | 31. SHT P-15 GREASE WASTE ISOMETRIC | | | DIAGRAM DOES NOT REFLECT THE FLOOR PLAN. | | | NO LINE TO THE CAN WASH IS SHOWN. P-5 | | | BEHIND THE ELECTRICAL ROOM IS SHOWN AS A | | | FLOOR SINK ON THE FLOOR PLAN AND AS A | | | FLOOR DRAIN ON THE RISER DIAGRAM. | | | (SHOULD BE A FLOOR SINK ON BOTH) SECTION | | | 106.1.1. - UNDER GREASE WASTE DIAGRAM | | | THE NOTESTATES "SEE KITCHEN DOCUMENTS, | | | SPECIFICATIONS, AND DATA SHEETS FOR | | | ADDITIONAL INFORMATION AND REQUIREMENTS | | | OF PLUMBING WORK ETC.". THESE WERE NOT | | | SUBMITTED. | | | 32. P-15 THE FOLLOWING INFORMATION IS | | | REQUIRED FOR GAS PLAN APPROVAL: | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS. | | | B. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES,- | | | SPECIFICATIONS NOT SUBMITTED. INDICATE | | | IF PIPING WILL BE SCREW PIPE OR WELDED | | | PIPE. | | | C. SUBMIT CALCULATIONS FOR COMBUSTION | | | AIR (IF APPLICABLE) PER FBC-2004 FUEL | | | GAS CODE SECTION 304. | | | D. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2004 FUEL GAS CODE SEC. | | | 402.4(2). NATURAL GAS SPECIFY .5 PSI OR | | | 2 PSI. | | | E. SUBMIT A DETAIL SHOWING THE TYPE, | | | LOCATION, SIZE AND TERMINATION OF THE | | | GAS VENTS PER FBC-2004 FUEL GAS CODE | | | SECS. 502 THRU 505. | | | F. SUBMIT MANUFACTURE SHEETS FOR ALL | | | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | G. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. BYPASS | | | PIPING SHALL BE CONNECTED DOWNSTREAM OF | | | THE EMERGENCY HOOD SHUT OFF VALVE. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | RESUBMIT ONE SET OF ORIGINAL SHEETS FOR | | | COMPARISON. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
6 |
Status |
P |
Date |
2007-02-06 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2007-02-06 |
Time |
22:28 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2007-02-06 |
Time |
22:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
5 |
Status |
F |
Date |
2007-01-17 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2007-01-17 |
Time |
13:55 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2007-01-17 |
Time |
13:53 |
Sent To |
|
|
| Notes |
| 2007-01-17 13:55:23 | 1/17/07 ***LANDSCAPE REVISIONS FAILED*** | | | | | | 1) MINOR PD AMENDMENT SHALL BE SUBMITTED AND APPROVED | | | BY THE PLANNING DEPARTMENT PRIOR TO APPROVAL OF A | | | BUILDING PERMIT. | | | | | | 2) PROPOSED LANDSCAPE REVISIONS WILL NOT BE SUPPORTED | | | BY THIS OFFICE BASED ON CONCERNS BY THE LANDSCAPE | | | PLANNER AS WELL AS MYSELF. | | | | | | QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER, | | | AT (561) 822-1435. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2006-11-20 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2006-11-20 |
Time |
11:52 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2006-11-20 |
Time |
11:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2006-05-25 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2006-05-25 |
Time |
21:10 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2006-05-25 |
Time |
21:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2006-04-01 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2006-04-01 |
Time |
10:57 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2006-04-01 |
Time |
10:57 |
Sent To |
|
|
| Notes |
| 2006-04-01 00:00:00 | 4/1/2006 ***FAILED*** | | | | | | 1) ALL PLANS NEED TO BE CONSISTENT!!! | | | SOME INSTANCES ARE INDICATED IN THE | | | FOLLOWING COMMENTS. | | | | | | 2) LETTER OF APPROVAL FROM THE MASTER | | | DEVELOPMENT SHALL BE INCLUDED IN THE | | | PERMIT PACKAGE INDICATING ACCEPTANCE OF | | | THE SITE PLAN, LANDSCAPE PLAN, | | | ELEVATIONS, MATERIALS, COLORS, ETC. | | | | | | 3) THE PAVING/GRADING PLAN DOES NOT | | | MATCH THE SITE PLAN WITH RESPECT TO THE | | | LOCATION OF THE BUILDING, THE ADDITONAL | | | HC PARKING SPACE, ETC. | | | | | | 4) THE LANDSCAPE PLANS DO NOT MATCH THE | | | SITE PLAN WITH RESPECT TO THE LOCATION | | | OF THE BUILDING, THE ADDITIONAL HC | | | PARKING SPACE, THE SWIMMING POOL, THE | | | REFLECTING POOL. | | | | | | 5) THE WALLS/FENCES AROUND THE TWO POOLS | | | ARE NOT SHOWN ON THE LANDSCAPE PLAN AND | | | THE PROPOSED LANDSCAPING APPEARS TO | | | INTERFERE WITH THEIR LOCATION. | | | | | | 6) THE SCREENING OF THE POOL EQUIPMENT | | | IS NOT SHOWN ON THE SITE OR LANDSCAPE | | | PLANS...THE LOCATION OF THE POOL | | | EQUIPMENT IS NOT EVEN SHOWN ON THE | | | LANDSCAPE PLAN. | | | | | | 7) THE LANDSCAPING AT THE NORTHEAST | | | CORNER OF THE PROPERTY INTERFERES WITH | | | THE EXISTING ASPHALT PATH THAT GOES | | | AROUND THE BELLSOUTH EASEMENT...IS THE | | | PATH BEING RELOCATED?IF SO, IS | | | BELLSOUTH ACCEPTABLE OF THIS AND NO | | | OTHER PLANS INDICATE IT BEING RELOCATED. | | | | | | 8) ON SHEET SP.02, PROVIDE THE OUTLINE | | | OF THE BUILDING.NO DETAIL WAS PROVIDED | | | ON THE PROPOSED ALUMINUM FENCE AND THE | | | LANDSCAPE PLAN DOES NOT MATCH THE | | | PLANTING BEDS THAT ARE INDICATED HERE. | | | | | | 9) ON SHEET SP.03, THE LABEL NEAR THE | | | POOL INDICATES A FOUNTAIN FEATURE, BUT | | | NONE IS SHOWN, SCREENING OF THE POOL | | | EQUIPMENT IS NOT SHOWN, NO DETAIL OF THE | | | PROPOSED BIKE RACK HAS BEEN PROVIDED, | | | THE LANDSCAPE PLAN DOES NOT MATCH THE | | | PLANTING BEDS THAT ARE INDICATED HERE. | | | | | | 10) PROVIDE MORE DETAIL REGARDING THE | | | CANOPIES THAT ARE INDICATED ON SHEETS | | | SP.02 AND SP.03.THESE CANOPIES ALSO | | | ARE NOT SHOWN ON THE ELEVATIONS. | | | | | | 11) THE LOCATION OF THE KITCHEN EXHAUST | | | FAN IS NOT CONSISTENT BETWEEN ALL | | | ELEVATIONS NOR THE ROOF PLAN. | | | | | | 12) PLEASE PROVIDE MORE DETAIL OF THE | | | SCREENING OF THE KITCHEN EXHAUST FAN. | | | | | | QUESTIONS/COMMENTS, CONTACT JOHN ROACH, | | | SENIOR PLANNER AT (561) 822-1435. | | | | | | ----------------- | | | | | | THE FOLLOWING COMMENTS ARE FROM ALAN | | | BARATTA, LANDSCAPE PLANNER.... | | | | | | 1) THE TREE PLANTING DIAGRAM NEEDS TO BE | | | MODIFIED TO ACTUALLY SHOW A PLANTING | | | HOLE 3 TIMES THE SIZE OF THE ROOT BALL, | | | AS INDICATED IN THE VERBAGE. | | | | | | 2) ADD A STATEMENT THAT THE TRUNK FLARE | | | OR TOP ROOT WILL BE VISIBLE ON THE | | | SURFACE. | | | | | | 3) ADD A CONTAINER SPECIFIICATION THAT | | | CONTAINER-GROWN TREES WILL BE CHECKED | | | FOR CIRCLING ROOTS PRIOR TO PLANTING. | | | IF FOUND, THE MATERIAL MUST BE REJECTED | | | OF IF THE ROOTS ARE LESS THAN 1/3 THE | | | TRUNK DIAMETER, THEY CAN BE CUT IN AN | | | AREA WHERE THEY ARE GROWNING RADIALLY | | | FROM THE TRUNK. | | | | | | 4) ADD A COMMENT THAT ALL TREES SHALL | | | HAVE THE BURLAP FOLDED BACK TO THE | | | BOTTOM 1/3 OF THE ROOT BALL. | | | | | | 5) METAL BASKETS SHALL BE REMOVED FROM | | | THE 1/2 FO THE ROOT BALL. | | | | | | QUESTIONS/COMMENTS, CONTACT ALAN | | | BARATTA, LANDSCAPE PLANNER AT (561) | | | 822-1435. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2007-01-17 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2006-01-26 |
Time |
15:51 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2006-01-26 |
Time |
15:51 |
Sent To |
|
|
| Notes |
| 2006-01-26 00:00:00 | 1/26/2005 ***FAILED*** | | | | | | 1) THE WALL/FENCE AROUND THE POOL AND | | | REFLECTING POOL IS NOT CONSISTENT | | | AMONGST ALL PLANS.SHEET SP.01 SHOWS 6' | | | BLOCK WALL.SECTION E ON SP.04 SHOWS 6' | | | BLOCK WALL.LEGEND ON SP.02 AND SP.03 | | | INDICATE 5' ALUMINUM FENCE.NOTES ON | | | SP.03 INDICATE 5' ALUMINUM FENCE AND 6' | | | BLOCK WALL.PROVIDE MORE DETAILS ON | | | PLANS AND MAKE THEM CONSISTENT. | | | | | | 2)THE POOL EQUIPMENT IS NOT SHOWN ON | | | THE LANDSCAPE PLANS.MAKE SURE ALL | | | MECHANICAL EQUIPMENT IS SHOWN AND IS | | | PROPERLY SCREENED. | | | | | | 3) SIGNS SHALL BE REVIEWED UNDER A | | | SEPARATE PERMIT.REMOVE FROM THE PLANS | | | OR NOTE THAT IT WILL BE PERMITTED BY | | | OTHERS. | | | | | | 4) PER THE CONDITION OF SITE PLAN | | | APPROVAL, THE LANDSCAPE BUFFER SHALL BE | | | PROVIDED BETWEEN THE SIDEWALK AND THE | | | WEST WALL/FENCE SURROUNDING THE | | | REFLECTING POOL. | | | | | | 5) LETTER OF APPROVAL FROM THE MASTER | | | DEVELOPER INDICATING APPROVAL OF THE | | | SITE PLAN, LANDSCAPE PLAN, ELEVATIONS, | | | COLORS, MATERIALS, SIGNS, ETC. SHALL BE | | | PROVIDED. | | | | | | 6) PLEASE IDENTIFY AND CLARIFY THE 7'4 | | | 3/4" TOWER THAT IS SHOWN ON THE SOUTH | | | END OF THE PAVILLION. | | | | | | 7) PLEASE EXPLORE ALTERNATIVES TO SHIELD | | | THE KITCHEN EXHAUST ON TOP OF THE | | | PAVILLION. | | | | | | 8) THE LANDSCAPE PLANS DO NOT SHOW THE | | | WALLS/FENCES AROUND THE POOL AND | | | REFLECTING POOL. | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT JOHN | | | ROACH, PLANNER AT (561) 822-1435. | | | | | | COMMENTS FROM ALAN BARATTA, LANDSCAPE | | | PLANNER... | | | | | | 1) CHANGE THE EAST PALATKA HOLLY TO | | | DAHOON HOLLY. | | | | | | 2) THE TREE PLANTING DIAGRAM NEEDS TO | | | SHOW A PLANTING HOLE 3 TIMES THE SIZE AS | | | INDICATED IN THE VERBAGE. | | | | | | 3) ADD A STATEMENT THAT THE TRUNK FLARE | | | OR TOP ROOT WILL BE VISIBLE ON THE | | | SURFACE. | | | | | | 4) ADD TO THE CONTAINER SPECS THAT | | | CONTAINER-GROWN TREES WILL BE CHECK FOR | | | CIRCLING ROOTS PRIOR TO PLANTING.IF | | | FOUND, THE MATERIAL MUST BE REJECTED OR | | | IF THE ROOTS ARE LESS THAN 1/3 THE TRUNK | | | DIAMETER, THEY CAN BE CUT IN AN AREA | | | WHERE THEY ARE GROWING RADIALLY TO THE | | | TRUNK. | | | | | | 5) ADD A COMMENT THAT ALL TREES SHALL | | | HAVE THE BURLAP FOLDED BACK TO THE | | | BOTTOM 1/3 OF THE ROOT BALL. | | | | | | 6) METAL BASKETS SHALL BE REMOVED FROM | | | THE TOP 1/2 OF THE ROOT BALL. | | | | | | QUESTIONS/COMMENTS, CONTACT ALAN | | | BARATTA, LANDSCAPE PLANNER AT (561) | | | 822-1435. |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |