Plan Review Details - Permit 05110263
Plan Review Stops For Permit 05110263
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-03-02 Cont ID  
Sent By lursu Date 2006-03-02 Time 11:57 Rev Time 0.00
Received By kstevens Date 2006-09-01 Time 16:41 Sent To  
Notes
2006-03-02 00:00:00NEW ADDRESS HAS BEEN ASSIGNED : 1611
 WORTHINGTON RD.WITH A NEW
 PCN = 74434329220000020 ( UNIT B)
2006-01-24 00:00:001647 WORTHINGHTON RD. ( FOR THE 4 STORY
 HILTON HOTEL ) PCN =74434329160020071
 ( PERMIT # 05110263)
 JOHN COSTAS @561-523-3699 TO E-MAIL
 ;DONE ON DEC 28 /05 -- HEWILL E-MAIL
 BACK WITH PCN .LU
2005-12-26 00:00:00NEEDS:
  
 SEE SITE PLAN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2007-01-02 Cont ID  
Sent By jwitmer Date 2007-01-02 Time 14:08 Rev Time 0.77
Received By jwitmer Date 2007-01-02 Time 14:08 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status F Date 2006-12-06 Cont ID  
Sent By jwitmer Date 2006-12-06 Time 10:28 Rev Time 0.55
Received By jwitmer Date 2006-12-06 Time 10:28 Sent To  
Notes
2006-12-06 10:32:45BUILDING PLAN REVIEW
 PERMIT: 05110263
 ADD: 1611 WORTHINGTON RD
 CONT: NCY CONSTRUCTION
 TEL: (561)797-3225
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVISIONREVIEW
 ACTION: DENIED
  
 1) THE STTRUCTURAL PLANS ARE DENIED, THERE IS NO
 CERTIFICATE OF AUTHORIZATION FOR GRW ARCHITECTURE,
 PLEASE REMOVE FROM THE TITLEBLOCK.
 481.219 F.S.
 CERTIFICATE OF AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL
 SERVICES, SHALL INCLUDE
 THE CERTIFICATE OF AUTHORIZATION
 NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2006-12-06 Cont ID  
Sent By jwitmer Date 2006-12-06 Time 10:23 Rev Time 1.55
Received By jwitmer Date 2006-12-06 Time 09:38 Sent To  
Notes
2006-12-06 10:28:07REVISIONS A.01,A.05, A.06, A.10, A1.1, A1.15, A1.17,
 A1.18, A1.19,
 A2.0, A2.5, A2.6, A2.7, A2.8 OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2006-09-29 Cont ID  
Sent By jwitmer Date 2006-09-29 Time 12:19 Rev Time 0.77
Received By jwitmer Date 2006-09-29 Time 12:19 Sent To PC
Notes
2006-09-29 00:00:00ALPINE METAL TRUSSESOK

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2006-08-31 Cont ID  
Sent By jwitmer Date 2006-08-31 Time 09:34 Rev Time 1.11
Received By jwitmer Date 2006-08-31 Time 09:34 Sent To PC
Notes
2006-08-31 00:00:00DAILY REPORTS 7-24-06/ 7-30-06
 2ND FLOOR RESHORE DIAGRAM

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-07-11 Cont ID  
Sent By jwitmer Date 2006-07-11 Time 16:53 Rev Time 5.55
Received By jwitmer Date 2006-07-11 Time 14:59 Sent To PC
Notes
2006-07-11 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05110263
 ADD: 1611 WORTHINGTON RD
 CONT: NCY CONSTRUCTION INC
 JOHN COSTAS
 TEL: (561)523-3699
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING PROVISO:
 109.3.10* IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS
 CODE SHALL BE PERMORMED IN A MANNER SO
 AS NOT TO ADVERSLY IMPACT THE CONDITION
 OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS &
 CONDITIONS AGREEABLE TO THE APPLICABLE
 PROPERTY OWNER.THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE,
 WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS.
 NEW CONSTRUCTION ACTIVITY SHALL NOT
 ADVERSELY IMPACT HISTORICSURFACE WATER
 DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, & MAY REQUIRE SPECIAL
 DRAINAGE DESIGNCOMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED
 SITES.ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENET, INCLUDING
 ADDITIONS, POOLS, PATIOS, DRIVEWAYS,
 DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN
 EXCESS OF 800SQ FT OF PERMEABLE LAND
 AREA ON ANY PARCELL SHALL AS A PERMIT
 CONDITION, PROVIDE A PROFESSIONALY
 PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENET AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM
 HIGHWINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-07-07 Cont ID  
Sent By dpalmer Date 2006-07-07 Time 15:01 Rev Time 0.00
Received By dpalmer Date 2006-07-07 Time 15:01 Sent To  
Notes
2006-07-07 00:00:00** PAID PALM BEACH COUNTY IMPACT FEES
 OK TO ISSUE PER JIM WITMER'S NOTES.
  
 SEE PROVISO IS STILL IN EFFECT FOR NOA
 FORARCHED ALUM WINDOW ETC FROM
 PREVIOUS NOTES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-06-19 Cont ID  
Sent By jwitmer Date 2006-06-19 Time 14:41 Rev Time 8.88
Received By jwitmer Date 2006-06-15 Time 16:42 Sent To  
Notes
2006-06-19 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05110263
 ADD: 1611 WORTHINGTON RD
 CONT: NCY CONSTRUCTION INC
 JOHN COSTAS
 TEL: (561)523-3699
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW
 ACTION: DENIED
  
 PLANS APPEAR TO BE CODE COMPLIANT WHEN
 IMPACT FEES ARE PAID BLDG WILL BE ABLE
 TO STAMP PLANS.
  
 1) COMMENT# 3 FROM THE PREVIOUS REVIEW,
 DEALS WITH COUNTY IMPACT FEES. PULLED
 THE FOUNDATION PLANS, NO FEES WERE PAID
 ON THE FOUNDATION (06011052), NO COUNTY
 STAMP OR RECEIPT.
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 PROVISO: A) ARCH ALUMINIUM- SUBMITTED
 THE WRONG NOA FOR FLORIDA COVERSHEET
 SUBMITTED.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-04-13 Cont ID  
Sent By jwitmer Date 2006-04-13 Time 10:51 Rev Time 5.55
Received By jwitmer Date 2006-04-13 Time 07:30 Sent To  
Notes
2006-04-13 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05110263
 ADD: LOT# 7 CENTERPARK WEST
 CONT: "PLAN REVIEW" HILTON
 JOHN COSTAS
 TEL: (561)523-3699
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
  
 ***IMPORTANT***
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
 NOTE NOC WILL BE NULL & VOID 90 DAYS
 AFTER RECORDING AT THE CLERK OF THE
 COURTS OFFICE IF WORK HAS NOT STARTED.
 FL S S 713.13(2).
  
 2) 2ND REQUEST FOR THIS INFORMATION,
 RESPONCE INDICATED A PERMIT 06011019
 SUPPLIED THIS INFORMATION. THIS PERMIT
 IS A SITE PREP PERMIT.
 A FOUNDATION PERMIT WAS APPLIED FOR
 UNDER 06011052.
 BOTH THE S0.1 & S1.1 HAVE NOTES
 ABOUT THE SOILS AND FOUNDATION BUT THE
 ENGINEER DOESN'T STATE WHAT THE SAFE
 MINIMUM DESIGN FOR THE FOUNDATION WAS
 DESIGNED TO?
 THIS IS A STAND ALONE PERMIT
 REQUESTING (3) SIGNED/SEALED SOILS
 REPORTS AS PER,
 FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 3) COMMENT# 3 FROM THE PREVIOUS REVIEW,
 BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 4)COMPLIED.
  
 5)COMPLIED, HAROLD PISKURA, HAS THE
 NECESSARY DOCUMENTS.
  
 6) W.P.B. AMENDMENT 105.13.4.4 ALL PLANS
 FOR THE BUILDING WHICH ARE REQUIRED TO
 BE SIGNED AND SEALED BY THE ARCHITECT OR
 ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S OR
 ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
 THIS STATEMENT IS FOUND ON THE
 STRUCTURAL SHEETS BUT NOT THE
 ARCHITECTURAL SHEETS.
  
 7A)COMPLIED.
  
 7B)2ND REQUEST, A SITE PLAN WAS
 SUBMITTED ONLY, THIS REQUEST IS MADE AS
 REQUEST (7D) TO DETERMINE LOT LINE, AND
 TABLE 503, TABLE 601 ISSUES, PLANS DO
 NOT PROVIDE MINIMUM BLDG TYPE!
 PROVIDE A COPY OF THE NEW PLAT, SHEET
 SP.01 APPEARS TO HAVE BEEN SUBDIVIDED
 WITH ADDITIONAL BUILDINGS TO BE ON THE
 SAME LOT.
  
 7C)NOTE, TO BE COMPLETED AT TIME OF
 PERMIT APPLICATION. PLEASE FILL OUT AN
 ACTUAL APPLICATION SHEET PROVIDING THE
 PROPERTY
 CONTROL NUMBER FOR ADDRESSING.
  
 7D)2ND REQUEST,SAME AS ISSUES AS 7B,
 PROVIDE A SURVEY OF THE SITE.
  
 8) 2ND REQUEST,ADDITIONAL INFORMATION
 REQUIRED FOR
 RECORD KEEPING PURPOSES 106.1.2*:
 8)A) FLOOD ZONE
 8)B) FLOOD ELEVATION (IF A ZONE)
 8)C) LOMAR (IF A ZONE)
 8)D) COMPLIED
 8)E) COMPLIED
 8)F)COMPLIED
 8)G)COMPLIED
 8)H)COMPLIED
 8)I) COMPLIED
 8)J) COMPLIED
 8)K) COMPLIED
  
 9)THIS COMMENT WILL STAY UNTIL A
 CONTRACTOR IS SIGNED ON AND ACKNOWLEDGES
 STATEMENT.
 109.3.10* IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS
 CODE SHALL BE PERMORMED IN A MANNER SO
 AS NOT TO ADVERSLY IMPACT THE CONDITION
 OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS &
 CONDITIONS AGREEABLE TO THE APPLICABLE
 PROPERTY OWNER.THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE,
 WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS.
 NEW CONSTRUCTION ACTIVITY SHALL NOT
 ADVERSELY IMPACT HISTORICSURFACE WATER
 DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, & MAY REQUIRE SPECIAL
 DRAINAGE DESIGNCOMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED
 SITES.ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENET, INCLUDING
 ADDITIONS, POOLS, PATIOS, DRIVEWAYS,
 DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN
 EXCESS OF 800SQ FT OF PERMEABLE LAND
 AREA ON ANY PARCELL SHALL AS A PERMIT
 CONDITION, PROVIDE A PROFESSIONALY
 PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 10) WILL REMAIN UNTIL ALL PERTINENT
 INFORMATION REQUIRED FOR PERMIT HAS BEEN
 REVIEWED,
 SINCE THISWILL BE A THRESHOLD
 PROJECT (3) SETS OF ALL INFORMATION
 SUBMITTED WILL BE REQUIRED.
  
 11)2ND REQUEST, 1609.1.4 PROTECTION OF
 OPENINGS.
 IN WIND-BORNE DEBRIS REGIONS, EXTERIOR
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IN THE LOWER 60 FEET (18.3 M) IN
 BUILDINGS SHALL BE ASSUMED TO BE
 OPENINGS AND THE BALANCE OF GLAZED
 OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IS IMPACT RESISTANT OR PROTECTED WITH AN
 IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND
 ASTM E 1996, OR MIAMI-DADE TAS 201, 202
 AND 203 REFERENCED THEREIN AS FOLLOWS:
 1.GLAZED OPENINGS LOCATED WITHIN 30
 FEET (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN
 30 FEET (9.1 M) ABOVE GRADE SHALL MEET
 THE PROVISIONS OF THE SMALL MISSILE
 TEST.
  
 12)2ND REQUEST, NONE OF THE PRODUCT
 APPROVALS SUBMITTED HAVE FLORIDA
 COVERSHEETS,
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 13) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS MISSING FL COVERSHEET
 SHEET
 B) EXTERIOR DOORS, SOLID MISSING FL
 COVER SHEET
 C) EXTERIOR DOORS GLAZED NOT SUBMITED
 D) EXTERIOR DOORS BYPASS, EXTERIOR AUTO
 SLIDERS, USUALLY TRANSOM NOT INCLUDED
 E) MULLIONS- NOT SUBMITTED- HORIZONTAL
 TO SEPERATE THE AUTO SLIDERS FROM FIXED
 STOREFRONT
 F) LOUVERS NOT SUBMITTED
 G) TRUSS ANCHORS NOT SUBMITTED
 H1) ROOF ASSEMBLIES, FLAT ROOF:
 ) THIS ROOF IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
  
 _X__ CONTRACTOR DID NOT PROVIDE THE MEAN
  
 ROOF HEIGHT.
  
 ___ CONTRACTOR DID NOT INDICATE THE ROOF
 PITCH.
  
 _X__ CONTRACTOR FAILED TO INDICATE WHICH
 SYSTEM TO BE USED.HIGHLIGHT THE ACTUALL
 SUBSYSTEM AND ANY OPTIONS AS FASTENER
 TYPES!
  
 _X THIS MAY BE THE SITUATION SINCE NO
 SYSTEM WAS HIGHLIGHTED,__ THE SYSTEM
 PROVIDED HAS A LOW
 PRESSURE FOR ZONE ___ .
  
 ___ THE SYSTEM PROVIDED STATES
 LIMITATION# 7, SHOULD THE FASTENER
 RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THE
 BUILDING OFFICIAL, A REVISED
 FASTENER SPACING, PREPARED , SIGNED
 AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF
 CONSULTANT MAY BE SUBMITTED.
  
 ___THE SYSTEM PROVIDED INDICATES
 LIMITATION# 9, NO ENHANCED
 FASTENING ALLOWED.
 H2) ROOF TILE OR SHINGLES NOT SUBMITTED
 I) PREMANUFACTURED A/C STANDS NOT
 SUBMITTED
  
 14)2ND REQUEST REVERTS BACK TO 13E:
 1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 15) 2ND REQUEST REVERTS BACK TO 13E:
 1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 16) 2ND REQUEST, SHEET SP. 01
 16A) INDICATES THAT THE TOTAL REQUIRED
 PARKING SPACES OF 118 PARKING SPOTS.
 PLANS NOW INDICATE (5) ACCESSIBLE
 PARKING STALLS, 5.11-4.6.2 LOCATION.
 ACCESSIBLE PARKING SPACES SERVING A
 PARTICULAR BUILDING SHALL BE LOCATED ON
 THE SHORTEST SAFELY ACCESSIBLE ROUTE OF
 TRAVEL FROM ADJACENT PARKING TO AN
 ACCESSIBLE ENTRANCE. THE NEW ACCESSIBLE
 PARKING SPACE SHALL BE AS CLOSE TO THE
 ENTRANCE AS POSSIBLE.
  
 16B)2ND REQUEST, THIS SHEET NOR A.01
 INDICATE CLEARLY THE PASSENGER LOADING
 ZONE UNDER THE CANOPY PLEASE CLARIFY THE
 PASSENGER LOADING ZONE, 11-4.6.6
 PASSENGER LOADING ZONES.
 PASSENGER LOADING ZONES SHALL PROVIDE AN
 ACCESS AISLE AT LEAST 60 INCHES (1525
 MM) WIDE AND 20 FEET (6096 MM) LONG
 ADJACENT AND PARALLEL TO THE VEHICLE
 PULL-UP SPACE (SEE FIGURE 11-10 ). IF
 THERE ARE CURBS BETWEEN THE ACCESS AISLE
 AND THE VEHICLE PULL-UP SPACE, THEN A
 CURB RAMP COMPLYING WITH SECTION 11-4.7
 SHALL BE PROVIDED. VEHICLE STANDING
 SPACES AND ACCESS AISLES SHALL BE LEVEL
 WITH SURFACE SLOPES NOT EXCEEDING 1:50
 (2 PERCENT) IN ALL DIRECTIONS.
  
 17) COMPLIED.
  
 18)NOTE, REQUIREMENT FOR C. O.
 SHEET SP.03, NOTE: POOL,
 SEE DEPARTMENT OF HEALTH FOR REGULATIONS
 FOR POOL SAFETY FENCE, RULE 64E-9.
  
 19)SHEET A.01:
  
 19A)2ND REQUEST,
 NEITHER A.01 OR A 4.17 PROVIDE WALL
 DETAILS INDICATING A 1 HR WALL RATING.
 THE DOOR 48A DOES NOT INDICATE ANY FIRE
 RATING ON A.25 OF THE DOOR SCHEDULE.
 LAUNDRY CHUTE TERMINATION ROOM &
 DOOR 48ATO MEET THE REQUIREMENTS OF ,
 707.13.4 TERMINATION ROOM.
 REFUSE AND LAUNDRY CHUTES SHALL
 DISCHARGE INTO AN ENCLOSED ROOM
 COMPLETELY SEPARATED FROM THE REMAINDER
 OF THE BUILDING BY CONSTRUCTION THAT HAS
 A FIRE-RESISTANCE RATING OF NOT LESS
 THAN 1 HOUR AND OPENINGS INTO THE
 TERMINATION ROOM SHALL BE PROTECTED BY
 OPENING PROTECTIVES HAVING A FIRE
 PROTECTION RATING OF NOT LESS THAN ?
 HOUR AND SHALL BE SELF-CLOSING OR
 AUTOMATIC-CLOSING UPON THE DETECTION OF
 SMOKE. REFUSE CHUTES SHALL NOT TERMINATE
 IN AN INCINERATOR ROOM. REFUSE AND
 LAUNDRY ROOMS THAT ARE NOT PROVIDED WITH
 CHUTES NEED ONLY COMPLY WITH TABLE
 302.1.1 .
  
 19B)2ND REQUEST, A.02-.04 PLANS ARE
 TOTALLY MISSING AN ACCESS ROOM FOR THE
 LAUNDRY CHUTE.
 707.13.3 REFUSE AND LAUNDRY CHUTE
 ACCESS ROOMS.
 ACCESS OPENINGS FOR REFUSE AND LAUNDRY
 CHUTES SHALL BE LOCATED IN ROOMS OR
 COMPARTMENTS COMPLETELY ENCLOSED BY
 CONSTRUCTION THAT HAS A FIRE-RESISTANCE
 RATING OF NOT LESS THAN 1 HOUR AND
 OPENINGS INTO THE ACCESS ROOMS SHALL BE
 PROTECTED BY OPENING PROTECTIVES HAVING
 A FIRE PROTECTION RATING OF NOT LESS
 THAN ? HOUR AND SHALL BE SELF-CLOSING OR
 AUTOMATIC-CLOSING UPON THE DETECTION OF
 SMOKE.
  
 19C)2ND REQUEST,
 PROVIDE A 2 HR SHAFT TO SURROUND
 THE LAUNDRY CHUTE, 707.4 FIRE-RESISTANCE
 RATING. SHAFT ENCLOSURES SHALL HAVE A
 FIRE-RESISTANCE RATING OF NOT LESS THAN
 2 HOURS WHERE CONNECTING FOUR STORIES OR
 MORE AND NOT LESS THAN1 HOUR WHERE
 CONNECTING LESS THAN FOUR STORIES. THE
 NUMBER OF STORIES CONNECTED BY THE SHAFT
 ENCLOSURE SHALL INCLUDE ANY BASEMENTS
 BUT NOT ANY MEZZANINES. SHAFT ENCLOSURES
 SHALL BE CONSTRUCTED AS FIRE BARRIERS IN
 ACCORDANCE WITH SECTION 706 . SHAFT
 ENCLOSURES SHALL HAVE A FIRE-RESISTANCE
 RATING NOT LESS THAN THE FLOOR ASSEMBLY
 PENETRATED, BUT NEED NOT EXCEED 2 HOURS.
  
  
 19D)2ND REQUEST MISSING FIRE SPRINKLERS
 LOCATED 707.13.6 AUTOMATIC FIRE
 SPRINKLER SYSTEM. AN APPROVED AUTOMATIC
 FIRE SPRINKLER SYSTEM SHALL BE INSTALLED
 IN ACCORDANCE WITH SECTION 903.2.10.2 .
 903.2.10.2 RUBBISH AND LINEN CHUTES.
 AN AUTOMATIC SPRINKLER SYSTEM SHALL BE
 INSTALLED AT THE TOP OF RUBBISH AND
 LINEN CHUTES AND IN THEIR TERMINAL
 ROOMS. CHUTES EXTENDING THROUGH THREE OR
 MORE FLOORS SHALL HAVE ADDITIONAL
 SPRINKLER HEADS INSTALLED WITHIN SUCH
 CHUTES AT ALTERNATE FLOORS. CHUTE
 SPRINKLERS SHALL BE ACCESSIBLE FOR
 SERVICING.
  
 19E)2ND REQUEST,
 PROVIDE A LIFE SAFETY PLAN FOR
 EXITING. PROVIDE THE LOADS FROM THE
 FLOORS ABOVE AS WELL AS THE FIRST FLOOR.
 TABLE 1004.1.2/ TABLE 1005.1.
  
  
 19F)COMPLIES.
  
 19G)COMPLIES.
 .
  
 19H)2ND REQUEST, INDICATE COMPLIANCE
 WITH,BREAKFAST AREA, THIS SHEET AND
 A.15 TO INDICATE COMPLIANCE WITH:
 11-5.1- 11-5.6.
  
 11-5.2 COUNTERS AND BARS.
 WHERE FOOD OR DRINK IS SERVED AT
 COUNTERS EXCEEDING 34 INCHES (865 MM) IN
 HEIGHT FOR CONSUMPTION BY CUSTOMERS
 SEATED ON STOOLS OR STANDING AT THE
 COUNTER, A PORTION OF THE MAIN COUNTER
 WHICH IS 60 INCHES (1525 MM) IN LENGTH
 MINIMUM SHALL BE PROVIDED IN COMPLIANCE
 WITH SECTION 11-4.32 OR SERVICE SHALL BE
 AVAILABLE AT ACCESSIBLE TABLES WITHIN
 THE SAME AREA.
  
 11-5.3 ACCESS AISLES.
 ALL ACCESSIBLE FIXED TABLES SHALL BE
 ACCESSIBLE BY MEANS OF AN ACCESS AISLE
 AT LEAST 36 INCHES (915 MM) CLEAR
 BETWEEN PARALLEL EDGES OF TABLES OR
 BETWEEN A WALL AND THE TABLE EDGES.
  
 11-5.5 FOOD SERVICE LINES.
 FOOD SERVICE LINES SHALL HAVE A MINIMUM
 CLEAR WIDTH OF 36 INCHES (915 MM), WITH
 A PREFERRED CLEAR WIDTH OF 42 INCHES
 (1065 MM) TO ALLOW PASSAGE AROUND A
 PERSON USING A WHEELCHAIR. TRAY SLIDES
 SHALL BE MOUNTED NO HIGHER THAN 34
 INCHES (865 MM) ABOVE THE FLOOR (SEE
 FIGURE 11-53 ). IF SELF-SERVICE SHELVES
 ARE PROVIDED, AT LEAST 50 PERCENT OF
 EACH TYPE MUST BE WITHIN REACH RANGES
 SPECIFIED IN SECTIONS 11-4.2.5 AND
 11-4.2.6 .
  
 11-5.6 TABLEWARE AND CONDIMENT AREAS.
 SELF-SERVICE SHELVES AND DISPENSING
 DEVICES FOR TABLEWARE, DISHWARE,
 CONDIMENTS, FOOD AND BEVERAGES SHALL BE
 INSTALLED TO COMPLY WITH SECTION 11-4.2
 (SEE FIGURE 11-54 ).
  
 19I)2ND REQUEST, PROVIDE WHERE I CAN
 FIND THIS INFORMATION? INDICATE
 COMPLIANCE WITH: 11-9.3
 VISUAL ALARMS, NOTIFICATION DEVICES AND
 TELEPHONES. 11-9.3.1 GENERAL.
 IN SLEEPING ROOMS REQUIRED TO COMPLY
 WITH THIS SECTION, AUXILIARY VISUAL
 ALARMS SHALL BE PROVIDED AND SHALL
 COMPLY WITH SECTION 11-4.28.4 . VISUAL
 NOTIFICATION DEVICES SHALL ALSO BE
 PROVIDED IN UNITS, SLEEPING ROOMS AND
 SUITES TO ALERT ROOM OCCUPANTS OF
 INCOMING TELEPHONE CALLS AND A DOOR
 KNOCK OR BELL.
 NOTIFICATION DEVICES SHALL NOT BE
 CONNECTED TO AUXILIARY VISUAL ALARM
 SIGNAL APPLIANCES. PERMANENTLY INSTALLED
 TELEPHONES SHALL HAVE VOLUME CONTROLS
 COMPLYING WITH SECTION 11-4.31.5 ; AN
 ACCESSIBLE ELECTRICAL OUTLET WITHIN 4
 FEET (1219 MM) OF A TELEPHONE CONNECTION
 SHALL BE PROVIDED TO FACILITATE THE USE
 OF A TEXT TELEPHONE.
  
 20) SHEET A.02- A.04:
  
 20A) 2ND REQUEST PLANS INDICATE NEXT TO
 THE ELEVATOR A SHAFT BUT NO DETAILS TO
 HR CONSTRUCTION, 707.4.
  
 20B) REPEAT OF 20A.
  
 21)2ND REQUEST.THE PLANS INDICATE A
 DETAIL A.15 DETAIL# 5 FOR HANDRAILS,
 THE DETAIL IS NOT FOR HANDRAILS OR
 EXTENTIONS. THE OTHER ISSUE IS A NOTE
 EXTEND STAIR RAIL EAST STAIR ONLY, NO
 INFORMATION IS PROVIDED FOR THE BOTTOM
 OF HANDRAILS NOR EXTENTIONS.
 SHEET A.20 & A.21 BOTH INDICATE
 STAIR TOWERS BUT NO DETAIL SHEET
 INDICATING THE HANDRAIL GUARD RAIL
 COMPLYING WITH 11-4.9.4(2)IF
 HANDRAILS ARE NOT CONTINUOUS, THEY SHALL
 EXTEND AT LEAST 12 INCHES (305 MM)
 BEYOND THE TOP RISER AND AT LEAST 12
 INCHES (305 MM) PLUS THE WIDTH OF ONE
 TREAD BEYOND THE BOTTOM RISER. AT THE
 TOP, THE EXTENSION SHALL BE PARALLEL
 WITH THE FLOOR OR GROUND SURFACE. AT THE
 BOTTOM, THE HANDRAIL SHALL CONTINUE TO
 SLOPE FOR A DISTANCE OF THE WIDTH OF ONE
 TREAD FROM THE BOTTOM RISER; THE
 REMAINDER OF THE EXTENSION SHALL BE
 HORIZONTAL [SEE FIGURE 11-19 (C) AND
 FIGURE 11-19 (D)]. HANDRAIL EXTENSIONS
 SHALL COMPLY WITH SECTION 11-4.4 .
 DETAILS ON A.15 ARE MISSING.
  
 22) SHEET A.23:
  
 22A) RESPONCE FIREPLACE DELETED, SEE
 A.05 PLAANS INDICATE CHIMNEY. PLEASE
 CORRECT.
  
 22B)2ND REQUEST.
 MISSING SECTIONS ON A.24A DETAILS
 1-4.
 NOTE DETAIL 3 IS USED IN THE
 CLEARSTORY AS WELL AS COMMEON TRUSS
 DETAIL FOR HIP END. CORRECT.
  
 22C) COMPLIED.
  
 22D) 2ND REQUEST.THIS IS A FOUR STORY
 BUILDING, SHOW PRODUCT APPROVAL REPORT
 WHERE SHINGLES WILL BE ABLE TO BE USED
 WITH A MEAN ROOF HEIGTH OF OVER 40'-0"?
 SHEET A.23 @ CLEARSTORY, DARK GREEN
 ASPHALT SHINGLES.
  
 23) SHEET A.25 DOOR SCHEDULE:
  
 23A)2ND REQUEST.INDICATE ON HARDWARE
 SCHEDULE. DOOR SCHEDULE DOESN,T INDICATE
 ANY HARDWARE FOR FIRE RATED DOORS,
 PLEASE SEE SECTION:715.3.3 FOR REQUIRED
 HARDWARE INCLUDING CLOSERS AND
 ARTIFICIAL BOTTOM SEAL INSTALLED ACROSS
 THE BOTTOM OF THE DOOR TESTED IN
 ACCORDANCE WITH UL 1784.
  
 B)NOTE: LOUVERS ARE PROHIBITED IN FIRE
 RATED DOORS. THE ELEVATIONS DO NOT
 INDICATE THE BOILERE ROOM DOORS ON THE
 ELEVATION. WHEN LOOKING AT THE
 MECHANICAL PLANS IT APPEARS THAT THERE
 MAY NOT BE ENOUGH MAKE UP AIR, FOR THIS
 REASON THE COMMENT WAS MADE.
  
 24) COMPLIED.
  
 25) COMPLIED.
  
 26) 2ND REQUEST, PLANS DO NOT PROVIDE
 MINIMUM BLDG TYPE! S3.1, A.23 NO DETAILS
 INDICATE THE TYPE OF MATERIAL TO BE USED
 FOR ROOF SHEATHING. PLANS ALSO DO NOT
 PROVIDE THE MINIMUM BUILDING DESIGN
 TABLE 503/ 601.
  
 NEW COMMENTS:
  
 27)1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING
 ASSEMBLIES SEPARATING DWELLING UNITS
 FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND
 TRANSMISSION CLASS (STC) OF NOT LESS
 THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN
 ACCORDANCE WITH ASTM E 90. PENETRATIONS
 OR OPENINGS IN CONSTRUCTION ASSEMBLIES
 FOR PIPING; ELECTRICAL DEVICES; RECESSED
 CABINETS; BATHTUBS; SOFFITS; OR HEATING,
 VENTILATING OR EXHAUST DUCTS SHALL BE
 SEALED, LINED, INSULATED OR OTHERWISE
 TREATED TO MAINTAIN THE REQUIRED
 RATINGS. THIS REQUIREMENT SHALL NOT
 APPLY TO DWELLING UNIT ENTRANCE DOORS;
 HOWEVER, SUCH DOORS SHALL BE TIGHT
 FITTING TO THE FRAME AND SILL.
  
 28) 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING
 UNIT AND A PUBLIC OR SERVICE AREA WITHIN
 THE STRUCTURE SHALL HAVE AN IMPACT
 INSULATION CLASS (IIC) RATING OF NOT
 LESS THAN 50 (45 IF FIELD TESTED) WHEN
 TESTED IN ACCORDANCE WITH ASTM E 492.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-02-28 Cont ID  
Sent By jwitmer Date 2006-02-28 Time 11:55 Rev Time 8.88
Received By jwitmer Date 2006-02-28 Time 11:55 Sent To  
Notes
2006-02-28 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05110263
 ADD: LOT# 7 CENTERPARK WEST
 CONT: "PLAN REVIEW" HILTON
 JOHN COSTAS
 TEL: (561)523-3699
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
  
 ***IMPORTANT***
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
 NOTE NOC WILL BE NULL & VOID 90 DAYS
 AFTER RECORDING AT THE CLERK OF THE
 COURTS OFFICE IF WORK HAS NOT STARTED.
 FL S S 713.13(2).
  
 2) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 3)BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 4)FL S. S. 553.71(7) " THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN
 CY CLASSIFICATION AS DEINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
  
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 SRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL INSPEC
 TION PLAN PREPARED BY THE ENGINEER OF
 RECORD. THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO THE ENFORCING AGEN-
 CY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESH-
 OLD BUILDING. THE PURPOSE OF THE SRUCTUR
 AL INSPECTION PLAN IS TO PROVIDE SPECIF-
 IC INSPECTION PROCEDURES AND SCHEDULES
 SO THAT THE BUILDING CAN BE ADEQUATELY
 INSPECTED FOR COMPLIANCE WITH THE
 PERMITTED DOCUMENTS.
  
 5) WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 6) W.P.B. AMENDMENT 105.13.4.4 ALL PLANS
 FOR THE BUILDING WHICH ARE REQUIRED TO
 BE SIGNED AND SEALED BY THE ARCHITECT OR
 ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S OR
 ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
 THIS STATEMENT IS FOUND ON THE
 STRUCTURAL SHEETS BUT NOT THE
 ARCHITECTURAL SHEETS.
  
 7A) CONTACT LILI URSA FOR ADDRESSING
 REQUIREMENTS @ (561)822-1239
  
 7B)PROVIDE A COPY OF THE NEW PLAT, SHEET
 SP.01 APPEARS TO HAVE BEEN SUBDIVIDED
 WITH ADDITIONAL BUILDINGS TO BE ON THE
 SAME LOT.
  
 7C) PLEASE FILL OUT AN ACTUAL
 APPLICATION SHEET PROVIDING THE PROPERTY
 CONTROL NUMBER FOR ADDRESSING.
  
 7D) PROVIDE A SURVEY OF THE SITE.
  
 8) ADDITIONAL INFORMATION REQUIRED FOR
 RECORD KEEPING PURPOSES 106.1.2*:
 8)A) FLOOD ZONE
 8)B) FLOOD ELEVATION (IF A ZONE)
 8)C) LOMAR (IF A ZONE)
 8)D) NUMBER OF UNITS
 8)E) NUMBER OF FLOORS
 8)F) NUMBER OF BEDROOMS
 8)G) NUMBER OF ROOMS
 8)H) NUMBER OF BATHROOM
 88)I) SQ FT LIVING SPACE(TOTAL)
 8)J) SQ FT FOOT PRINT
 8)K) SQ FT UNDER ROOF (TOTAL)
  
 9) 109.3.10* IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS
 CODE SHALL BE PERMORMED IN A MANNER SO
 AS NOT TO ADVERSLY IMPACT THE CONDITION
 OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS &
 CONDITIONS AGREEABLE TO THE APPLICABLE
 PROPERTY OWNER.THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE,
 WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS.
 NEW CONSTRUCTION ACTIVITY SHALL NOT
 ADVERSELY IMPACT HISTORICSURFACE WATER
 DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, & MAY REQUIRE SPECIAL
 DRAINAGE DESIGNCOMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED
 SITES.ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENET, INCLUDING
 ADDITIONS, POOLS, PATIOS, DRIVEWAYS,
 DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN
 EXCESS OF 800SQ FT OF PERMEABLE LAND
 AREA ON ANY PARCELL SHALL AS A PERMIT
 CONDITION, PROVIDE A PROFESSIONALY
 PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 10) SINCE THISWILL BE A THRESHOLD
 PROJECT (3) SETS OF ALL INFORMATION
 SUBMITTED WILL BE REQUIRED.
  
 11) 1609.1.4 PROTECTION OF OPENINGS.
 IN WIND-BORNE DEBRIS REGIONS, EXTERIOR
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IN THE LOWER 60 FEET (18.3 M) IN
 BUILDINGS SHALL BE ASSUMED TO BE
 OPENINGS AND THE BALANCE OF GLAZED
 OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IS IMPACT RESISTANT OR PROTECTED WITH AN
 IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND
 ASTM E 1996, OR MIAMI-DADE TAS 201, 202
 AND 203 REFERENCED THEREIN AS FOLLOWS:
 1.GLAZED OPENINGS LOCATED WITHIN 30
 FEET (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN
 30 FEET (9.1 M) ABOVE GRADE SHALL MEET
 THE PROVISIONS OF THE SMALL MISSILE
 TEST.
  
 12) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 13) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS NO WINDOW SCHEDULE ON INDEX
 SHEET
 B) EXTERIOR DOORS, SOLID
 C) EXTERIOR DOORS GLAZED
 D) EXTERIOR DOORS BYPASS
 E) MULLIONS
 F) LOUVERS
 G) TRUSS ANCHORS
 H) ROOF ASSEMBLIES, FLAT AND TILE
 I) PREMANUFACTURED A/C STANDS
  
 14) 1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 15) 1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 16) SHEET SP. 01
 16A) INDICATES THAT THE TOTAL REQUIRED
 PARKING SPACES OF 118 PARKING SPOTS.
 PLANS ONLY INDICATE (4)
 ACCESSIBLE PARKING STALLS, 11-4.1.2(5)
 IF TOTAL PARKING SPOTS ARE BETWEEN 101
 TO 150 THEN THE MINIMUM NUMBER ODF
 ACCESSIBLE SPACES ARE 5.
  
 16B) THIS SHEET NOR A.01 INDICATE
 CLEARLY THE PASSENGER LOADING ZONE UNDER
 THE CANOPY PLEASE CLARIFY THE PASSENGER
 LOADING ZONE, 11-4.6.6 PASSENGER LOADING
 ZONES.
 PASSENGER LOADING ZONES SHALL PROVIDE AN
 ACCESS AISLE AT LEAST 60 INCHES (1525
 MM) WIDE AND 20 FEET (6096 MM) LONG
 ADJACENT AND PARALLEL TO THE VEHICLE
 PULL-UP SPACE (SEE FIGURE 11-10 ). IF
 THERE ARE CURBS BETWEEN THE ACCESS AISLE
 AND THE VEHICLE PULL-UP SPACE, THEN A
 CURB RAMP COMPLYING WITH SECTION 11-4.7
 SHALL BE PROVIDED. VEHICLE STANDING
 SPACES AND ACCESS AISLES SHALL BE LEVEL
 WITH SURFACE SLOPES NOT EXCEEDING 1:50
 (2 PERCENT) IN ALL DIRECTIONS.
  
 17) SHEET SP.02 REFLECTING POOL PROVIDE
 A CROSS SECTION OF THIS SITE AMENITY,
 11-4.29.6 DETECTABLE WARNINGS AT
 REFLECTING POOLS. THE EDGES OF
 REFLECTING POOLS SHALL BE PROTECTED BY
 RAILINGS, WALLS, CURBS, OR DETECTABLE
 WARNINGS COMPLYING WITH 11-4.29.2.
  
 18)SHEET SP.03, NOTE: POOL,
 SEE DEPARTMENT OF HEALTH FOR REGULATIONS
 FOR POOL SAFETY FENCE, RULE 64E-9.
  
 19)SHEET A.01:
  
 19A) LAUNDRY CHUTE TERMINATION ROOM &
 DOOR 48ATO MEET THE REQUIREMENTS OF ,
 707.13.4 TERMINATION ROOM.
 REFUSE AND LAUNDRY CHUTES SHALL
 DISCHARGE INTO AN ENCLOSED ROOM
 COMPLETELY SEPARATED FROM THE REMAINDER
 OF THE BUILDING BY CONSTRUCTION THAT HAS
 A FIRE-RESISTANCE RATING OF NOT LESS
 THAN 1 HOUR AND OPENINGS INTO THE
 TERMINATION ROOM SHALL BE PROTECTED BY
 OPENING PROTECTIVES HAVING A FIRE
 PROTECTION RATING OF NOT LESS THAN ?
 HOUR AND SHALL BE SELF-CLOSING OR
 AUTOMATIC-CLOSING UPON THE DETECTION OF
 SMOKE. REFUSE CHUTES SHALL NOT TERMINATE
 IN AN INCINERATOR ROOM. REFUSE AND
 LAUNDRY ROOMS THAT ARE NOT PROVIDED WITH
 CHUTES NEED ONLY COMPLY WITH TABLE
 302.1.1 .
  
 19B) 707.13.3 REFUSE AND LAUNDRY CHUTE
 ACCESS ROOMS.
 ACCESS OPENINGS FOR REFUSE AND LAUNDRY
 CHUTES SHALL BE LOCATED IN ROOMS OR
 COMPARTMENTS COMPLETELY ENCLOSED BY
 CONSTRUCTION THAT HAS A FIRE-RESISTANCE
 RATING OF NOT LESS THAN 1 HOUR AND
 OPENINGS INTO THE ACCESS ROOMS SHALL BE
 PROTECTED BY OPENING PROTECTIVES HAVING
 A FIRE PROTECTION RATING OF NOT LESS
 THAN ? HOUR AND SHALL BE SELF-CLOSING OR
 AUTOMATIC-CLOSING UPON THE DETECTION OF
 SMOKE.
  
 19C) PROVIDE A 2 HR SHAFT TO SURROUND
 THE LAUNDRY CHUTE, 707.4 FIRE-RESISTANCE
 RATING. SHAFT ENCLOSURES SHALL HAVE A
 FIRE-RESISTANCE RATING OF NOT LESS THAN
 2 HOURS WHERE CONNECTING FOUR STORIES OR
 MORE AND NOT LESS THAN1 HOUR WHERE
 CONNECTING LESS THAN FOUR STORIES. THE
 NUMBER OF STORIES CONNECTED BY THE SHAFT
 ENCLOSURE SHALL INCLUDE ANY BASEMENTS
 BUT NOT ANY MEZZANINES. SHAFT ENCLOSURES
 SHALL BE CONSTRUCTED AS FIRE BARRIERS IN
 ACCORDANCE WITH SECTION 706 . SHAFT
 ENCLOSURES SHALL HAVE A FIRE-RESISTANCE
 RATING NOT LESS THAN THE FLOOR ASSEMBLY
 PENETRATED, BUT NEED NOT EXCEED 2 HOURS.
  
  
 19D) 707.13.6 AUTOMATIC FIRE SPRINKLER
 SYSTEM. AN APPROVED AUTOMATIC FIRE
 SPRINKLER SYSTEM SHALL BE INSTALLED IN
 ACCORDANCE WITH SECTION 903.2.10.2 .
  
 19E) PROVIDE A LIFE SAFETY PLAN FOR
 EXITING. PROVIDE THE LOADS FROM THE
 FLOORS ABOVE AS WELL AS THE FIRST FLOOR.
 TABLE 1004.1.2/ TABLE 1005.1.
  
 19F) MEETING ROOM # 34 OCC LOAD OF 96,
 24X28=672/7= 96 OCC LOAD.1014.1 EXIT OR
 EXIT ACCESS DOORWAYS REQUIRED.
  
 19G)TWO EXITS OR EXIT ACCESS DOORWAYS
 FROM ANY SPACE SHALL BE PROVIDED WHERE
 ONE OF THE FOLLOWING CONDITIONS EXISTS:
 1014.1.(1)THE OCCUPANT LOAD OF THE
 SPACE EXCEEDS THE VALUES IN TABLE 1014.1
 .
  
 19H) BREAAKFAST AREA, THIS SHEET AND
 A.15 TO INDICATE COMPLIANCE WITH:
 11-5.1- 11-5.6.
  
 19I) INDICATE COMPLIANCE WITH: 11-9.3
 VISUAL ALARMS, NOTIFICATION DEVICES AND
 TELEPHONES. 11-9.3.1 GENERAL.
 IN SLEEPING ROOMS REQUIRED TO COMPLY
 WITH THIS SECTION, AUXILIARY VISUAL
 ALARMS SHALL BE PROVIDED AND SHALL
 COMPLY WITH SECTION 11-4.28.4 . VISUAL
 NOTIFICATION DEVICES SHALL ALSO BE
 PROVIDED IN UNITS, SLEEPING ROOMS AND
 SUITES TO ALERT ROOM OCCUPANTS OF
 INCOMING TELEPHONE CALLS AND A DOOR
 KNOCK OR BELL.
 NOTIFICATION DEVICES SHALL NOT BE
 CONNECTED TO AUXILIARY VISUAL ALARM
 SIGNAL APPLIANCES. PERMANENTLY INSTALLED
 TELEPHONES SHALL HAVE VOLUME CONTROLS
 COMPLYING WITH SECTION 11-4.31.5 ; AN
 ACCESSIBLE ELECTRICAL OUTLET WITHIN 4
 FEET (1219 MM) OF A TELEPHONE CONNECTION
 SHALL BE PROVIDED TO FACILITATE THE USE
 OF A TEXT TELEPHONE.
  
 20) SHEET A.02- A.04:
  
 20A) PLANS INDICATE NEXT TO THE ELEVATOR
 A SHAFT BUT NO DETAILS TO HR
 CONSTRUCTION OR WHAT IT WILL BE USED
 FOR?707.4.
  
 20B) PLANS ALSO INDICATE A SHAFT NEXT TO
 THE ELEVATOR SHAFT NO CUT SECTION?
 USAGE?
  
 21) SHEET A.20 & A.21 BOTH INDICATE
 STAIR TOWWERS BUT NO DETAIL SHEET
 INDICATING THE HANDRAIL GUARD RAIL
 COMPLYING WITH 11-4.9.4(2)IF
 HANDRAILS ARE NOT CONTINUOUS, THEY SHALL
 EXTEND AT LEAST 12 INCHES (305 MM)
 BEYOND THE TOP RISER AND AT LEAST 12
 INCHES (305 MM) PLUS THE WIDTH OF ONE
 TREAD BEYOND THE BOTTOM RISER. AT THE
 TOP, THE EXTENSION SHALL BE PARALLEL
 WITH THE FLOOR OR GROUND SURFACE. AT THE
 BOTTOM, THE HANDRAIL SHALL CONTINUE TO
 SLOPE FOR A DISTANCE OF THE WIDTH OF ONE
 TREAD FROM THE BOTTOM RISER; THE
 REMAINDER OF THE EXTENSION SHALL BE
 HORIZONTAL [SEE FIGURE 11-19 (C) AND
 FIGURE 11-19 (D)]. HANDRAIL EXTENSIONS
 SHALL COMPLY WITH SECTION 11-4.4 .
 DETAILS ON A.15 ARE MISSING.
  
 22) SHEET A.23:
  
 22A) PLANS INDICATE THE USE OF A PREFAB
 FIREPLACE AND FLUE SUBMIT ADDITIONAL
 INFORMATION:
  
 22B) MISSING SECTIONS ON A.24A DETAILS
 1-4. NOTE DETAIL 3 IS USED IN THE
 CLEARSTORY AS WELL AS COMMEON TRUSS
 DETAIL FOR HIP END. CORRECT.
  
 22C) SUBMIT STRUCTURAL PLANS INDICATING
 HOW TO BUILD THE SURROUND AROUND THE
 PREFAB FLUE?
  
 22D) THIS IS A FOUR STORY BUILDING, SHOW
  
 PRODUCT APPROVAL REPORT WHERE SHINGLES
 WILL BE ABLE TO BE USED WITH A MEAN ROOF
 HEIGTH OF OVER 40'-0"?
  
 23) SHEET A.25 DOOR SCHEDULE:
  
 23A) DOOR SCHEDULE DOESN,T INDICATE ANY
 HARDWARE FOR FIRE RATED DOORS, PLEASE
 SEE SECTION:715.3.3 FOR REQUIRED
 HARDWARE INCLUDING CLOSERS AND
 ARTIFICIAL BOTTOM SEAL INSTALLED ACROSS
 THE BOTTOM OF THE DOOR TESTED IN
 ACCORDANCE WITH UL 1784.
  
 B) LOUVERS ARE OROHIBITED IN FIRE RATED
 DOORS.
  
 24) A.27WALL TYPE 11A PROVIDE A DESIGN
 NUMBER FOR 2 HR RATED SHAFT DESIGN
  
 25) A.34 PUBLIC RESTROOMS:1210.2 WALLS.
 WALLS WITHIN 2 FEET (610 MM) OF URINALS
 AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT
 OF 4 FEET (1219 MM) ABOVE THE FLOOR, AND
 EXCEPT FOR STRUCTURAL ELEMENTS, THE
 MATERIALS USED IN SUCH WALLS SHALL BE OF
 A TYPE THAT IS NOT ADVERSELY AFFECTED BY
 MOISTURE.
  
 26) S3.1, A.23 NO DETAILS INDICATE THE
 TYPE OF MATERIAL TO BE USED FOR ROOF
 SHEATHING. PLANS ALSO DO NOT PROVIDE THE
 MINIMUM BUILDING DESIGN TABLE 503/ 601.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-01-14 Cont ID  
Sent By dpalmer Date 2007-01-14 Time 14:35 Rev Time 0.00
Received By dpalmer Date 2007-01-14 Time 13:32 Sent To  
Notes
2007-01-14 14:35:28REV'S E1-E15 OK.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-08-23 Cont ID  
Sent By dpalmer Date 2006-08-23 Time 13:32 Rev Time 0.00
Received By dpalmer Date 2006-08-23 Time 20:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-06-08 Cont ID  
Sent By dpalmer Date 2006-06-08 Time 20:56 Rev Time 0.00
Received By dpalmer Date 2006-06-08 Time 20:33 Sent To  
Notes
2006-06-08 00:00:00IN ELEC FOR REVIEW, REVIEW IN PROGRESS.
 ** ELECTRICAL SHEETS STAMPED IN ALL
 3-SETS.
  
 ALL NOTES ADDRESSED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-04-14 Cont ID  
Sent By dpalmer Date 2006-04-14 Time 16:39 Rev Time 0.00
Received By dpalmer Date 2006-04-13 Time 15:42 Sent To  
Notes
2006-04-14 00:00:00************ UNSAT 2ND REVIEW *********
  
 HILTON GARDENS INN
  
 ** PLEASE KNOW, PLANS TO DATE HAVE STILL
 NOT BEEN SUBMITTED FOR PERMIT FOR
 BUILDING AND PLANS ARE ONLY SUBMITTED
 FOR "PLAN REVIEW".
  
 ** PLEASE SEE MANY NOTES FROM PREVIOUS
 REVIEW WHICH ARE IN NEED OF BEING
 ADDRESSED AND SOME NEW NOTES FOR ITEMS
 CHANGED AND/OR NOW SUBMITTED FOR REVIEW>
 PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW.
  
  
 1A) NOTE: NO, PLEASE SEE NO INFORMATION
 WAS SUBMITTED AND NO CHANGES OR
 ADJUSTMENTS COULD BE LOCATED ON PLANS
 FOR COMPLIANCE TO THE 2004 FBC CHAPTER
 13. 13-413.1ABC.1.1,13-415.1.ABC.1.1,
 13-415.1.ABC.1.2,13-415.1.ABC.1.4 ETC.
 PLEAS KNOW, IN THE RESPONSE PACKAGE FROM
 DESIGN PROFESSIONALNO RESPONSE WAS
 INDICATED.
  
 ** PREVIOUS NOTE**
 PLEASE SEE 2004 FCB CHAPTER 13
 HOTELS, ROOM OCCUPANCY CONTROLS FOR AND
 OTHER CONTROL FOR COMMON AREAS.
  
  
  
 1)NOTE: NO, PLEASE SEE THESE COULD NOT
 BE LOCATED ON PLANS FOR ADDED CODES AND
 RESPONSE LETTER DOES NOT RESPONSED TO
 THIS NOTE.
  
 ** PREVIOUS NOTE**
 PLEASE BE SURE PLANS REFERENCE
 CURRENT CODES IN EFFECT.
 2002 NFPA-70 (NEC), 2003 NFPA-101, 2002
 NFPA-72 ETC
  
 2)NOTE:OK, HOWEVER PLEASE SEE
 ARCHITECTURAL PLANS DO NOT CORRELATE
 WITH DOOR SWINGS AND PLEASE ALSO SEE
 POSSIBLE CONFLICT WIHT THE SWING OF
 OTHER DOOR ON PLANS. PLEASE SEE IF ONE
 DOOR IS BEING OPENED AND THE SINGLE DOOR
 FROM MAIN ELECTRICAL ROOM ALSO OPENS
 THESE WILL INTERSECT IN THE CENTER OF
 HALL EGRESS AREA. PLEASE SEE DOOR
 HINGE/SWING SIDE MAY NEED TO BE REVERSED
 TO AVOIDE THIS INTERFERENCE.
  
 ** PREVVIOUS NOTE **
 PLEASE SEE MAIN ELECTRICAL ROOM
 DOORS WILL BE REQUIRED TO OPEN OUTWARD
 AND SHALL HAVE PANIC HARDWARE.
 110.26
  
 3)NOTE:OK, HOWEVER SEE NEW NOTES FOR
 CORRELATION OF FIXTURES ETC.
  
 ** PREVIOUS NOTE**
 PLEASE BE SURE ALL ELECTRICAL RMS,
 ELEVATOR EQUIPMENT RMS CONTAIN A
 BATTERY BACK UP LIGHT OF SOME SORT.
 LS101 7.8,7.9, 700.16
  
 4)NOTE: OK.
  
  
 5)NOTE: OK.
  
 6)NOTE:NO, PLEASE SEE SOME AREAS/ITEMS
 ON PLANS ARE REDLINED WHERE FIXTURES AND
 EQUIPMENT IS NOT CIRCUITED. PLEASE ALSO
 PLEASE SEE GUEST ROOMS DO NOT INDICATE
 THE CIRCUITING. PLEASE SEE RESPONSE LTR
 MENTIONS THESE WERE ALL DONE, HOWEVER
 PLEASE SEE PLANS.
  
 ** PREVIOUS NOTE **
 PLEASE COMPLETE ALL OTHER CIRCUITING,
 GUEST RMS ETC. 215.5
  
 7)NOTE: OK.
  
 8)NOTE: OK.
  
 9)NOTE:OK, HOWEVER PLEASE SEE
 DESCREPANCIES IN THE PHOTO-METRICS, AND
 FIXTURE TYPES. PLEASE SEE THE
 PHOTO-METRICS SEEM TO BE REVERSED, THE
 LEVEL OF LIGHTING UNDER NORMAL LIGHTING
 CONDITION IS LOWER THAN UNDER EMERGENCY?
 PLEASE SEE PERHAPS EACH SUDY WAS
 REVERSED IN LABLEING?
 PLEASE ALSO CORRELATE STAIR AREAS AND
 FIXTURE TYOE WITH FIXTURES LISTED ON
 FIXTURE SCHEDULE. PLEASE SEE FIXTURE
 SCHEDULE AND ORIGINAL PLANS FOR LIGHTING
 ON EACH FLR INDICATES A FIXTURE "H".THIS
 FIXTURE IS SHOWN AS WALL MOUNTED AND
 MENTIONED AS CEILING MOUNTED ON
 SCHEDULE?
 PLEASE CORRELATE.
  
 ** PREVIOUS NOTE**
 PLEASE SUBMIT COMPLETE PHOTOMETRICS FOR
 ALL COMMON AREAS, AND STAIR TOWERS.
 PLEASE SEE 2003 NFPA-1017.8.1.3 WHICH
 REQUIRES A MIN OF 1 FT CANDLEAND A MIN
 OF 10FT CANDLES ON THE WALKING SURFACE
 UNDER NORMAL POWER. PLEASE SEE7.9.2.1
 WHICH REQUIRES A MIN OF 1FT CANDLE OF
 LIGHTING ON ALL WALKING SURFACES UNDER
 EMERGENCY CONDITIONS.
  
 10)NOTE: NO, PLEASE SEE RESPONSE LTR
 MENTIONS TO SEE ARCHITECTURAL PLANS,
 HOWEVER NONE OF THE A-SHEETS CONTAIN THE
 INFORMATION NEED AND REQUESTED.
  
 ** PREVIOUS REVIEW **
 PLEASE SEE PHOTOMETRICS SHOWN
 FOR POOL AREA SHALL BE SUBMITTED TO PALM
 BEACH COUNTY HEATH DEPARTMENT FOR ANY
 AFTER DUSK SWIMMMING.
 IF THERE IS NOT GOING TO BE ANY SWIMMING
 FROM DUSK TO DAWN, PLEASE PROVIDE A NOTE
 ON PLAN FOR REQUIRED SIGNAGE TO BE PLACE
 AT AND IN POOL AREA.
 ** PLEASE KNOW, THE SWIMMING POOL ITSELF
 WILL BE REQUIRED TO BE UNDER A SEPARATE
 PERMIT.
  
 11)NOTE:NO, SAME NOTE. SEE CIRCUITING
 NOTE.
 RESPONSE LTR MENTIONS TO SEE ROOM TYOE
 ADDED?? THIS DOES NOT CORRELATE FOR THE
 COMMENT WHICH WAS MADE.
  
 ** PREVIOUS NOTE **
 PLEASE CLARIFY NOTE ON PLANS FOR THE
 REQUIREMENTS OF GUEST BATH GFI.
 THIS CAN NOT BE VERIFIED AT THIS TIME
 DUE TO MISSING CIRCUITING.
  
 12)NOTE: OK.
  
 13)NOTE: NO, PLEASE SEE LTTR MENTIONS NO
 PROTECTION PER OWNER? PLEASE SEE
 PREVIOUS NOTE:::
  
 ** PREVIOUS NOTE**
 PLEASE PROVIDE A NOTE ON THE ROOOFTOP
 PLAN WHICH SHOULD NOTE/MENTION:
 ANY PROPOSED LIGHTNING PROTECTION SYSTEM
 SHALL MEET NFPA-780, OR WORDS TO THAT
 AFFECT.
 IT IS NOTED THAT NO SYSTEM IS SHOWN AT
 THIS TIME, AND ANY FUTURE WOULD BE UNDER
 A SEPARATE PERMIT, HOWEVER A NOTE IS
 REQUIRED AT THIS TIME.
  
 14)NOTE: OK.
  
 15)NOTE: OK.
  
 16)NOTE: OK.
  
 17)NOTE:OK, HOWEVER PLEASE SEE WHAT
 APPEARS TO BE A MISPRINT FOR 3RD FLR
 PANEL "3R3" WHICH READS "2R3"
  
 ** PREVIOUS NOTE**
 PLEASE SEE RISER AND MSB SHOWS ALL 1H1,
 2H2, 3H3 ETC AS 1H, 2H, 3H ETC ON PANEL
 SCHEDULES FOR THESE.
 PLEASE CORRELATE THE IDENTIFICATION OF
 THESE.
 215.5
  
 18)NOTE: NO, PLEASE SEE RESPONSE
 MENTIONS "800A CHILLER HAS BEEN
 ELIMINATED" ETC, PLEASE KNOW, THIS
 RESPONSE WAS NOT FOR COMMENT MADE?
 PLEASE SEE RISER AND NEW LOAD
 CALCULATIONS NOW SUBMITTED. PLEASE SEE
 NOTE #2 ON RISER WAS ADDRESSED IN FEEDER
 SCHEDULE, HOWEVER SAME SHEET STILL
 MENTIONS CONDUITRS, AND CONDUCTORS NOT
 RATED FOR THE 3000A MAIN BEING ISTALLED.
 PLEASE SEEREDLINED PLANS.
  
 **PREVIOUS NOTE **
 PLEASE SEE 240.4C, WHICH REQUIRES THE
 CONDUCTOR FEEDING DEVICES RATED OVER
 800A'S TO MEET OR EXCEED RAITNG OF SUCH
 DEVICE.
 PLEASE SEE MSB OS SHOWN AS A 3000A MAIN
 , HOWEVER CONDUCTORS ARE ONLY RATED FOR
 2100 A'S?
 5-SETS OF 600MCM, RATED @420A'S EACH.(75
 DEGREE COL).
 110.14, 215.5,215.3
 PLEASE ADJUST ON MORE THAN ONE SHEET,
 SEE 13,14.
  
 19)NOTE: OK, CHILLER REMOVED, HOWEVER
 PLEASE SEE PLANS NOW INDICATE NEW CU'S
 LOCATED ON SITE WITHOUT SERVICE RECEPTS
 210.63 AND PLEASE SEE MECH PLANS
 INDICATE "P-TAC" UNITS AT THE END OF
 THE HALLS FOR EACH FLR, HOWEVER THESE
 ARE NOT SHOWN ON ELECTRICAL PLANS ,
 HOWEVER THEY ARE INDICATED ON PANEL
 SCHEDULES.??
  
 **PREVIOUS NOTE**
 PLEASE ALSO SEE CONDUCTORS FOR MAIN
 FEEDERS TO CHILLER FROM MSB.
 PLEASE SEE MSB SHOWS 3-300 MCM, HOWEVER
 PLEASE SEE CALCUALTIONS FOR CHILLER
 WHICH INDICATE 2-600'S.
 PLEASE CORRELARE. 215.5
  
 20)NOTE: NO, PLEASE SEE RESPONSE LTR
 MENTIONS TO SEE REVISED DETAIL, HOWEVER
 DETAIL WAS NOT REVISED AND SHOW THE
 SAME.
  
 ** PREVIOUS **
 PLEASE SEE RISER INDICATES "BLDG STEEL"
 AS PART OF THE GROUNDING ELECTRODE
 SYSTEM, WHICHIS OK AND IS REQUIRED IF
 "BLDG STEEL" IS PRESENT.
 PLEASE ALSO INCLUDE THE REQUIRED "FOOTER
 STEEL" IN DETAIL.
 250.50
  
 21)NOTE: NO?? RESPONSE MENTIONS
 "INFORMATION TO FOLLOW" , WHAT IS MEANT
 BY THIS??????
 PLEASE KNOW, THIS INFORMATION IS NEEDED
 AND REQUIRED ATTHIS TIME AND SHALL BE
 ON PLANS BEFORE PERMITTING.
  
 ** PREVIOUS NOTE**
 PLEASE KNOW, THE REQUIRED WIND LOAD
 CALCULATIONS FOR LT POLES WITH FIXTURES
 ON THEM ARE REQUIRED AT THIS TIME.
 PLEASE KNOW, THESE WILL BE REVIEWED BY A
 STRUCTUAL PLANS REVIEWER.
 IF THIS INFORMATION IS NOT SUBMITTED AT
 THIS TIME, ALL SITE LIGHTING WOULD BE
 REQUIRED TO BE UNDER A SEPARATE PERMIT,
 WITH SEPARATE PLANS AND FEES.
  
  
 ** PLEASE KNOW, ONE SET OF PLANS ARE
 BEING RETAINED FOR FILE AND RECORD OF
 PLAN REVIEWS FOR REPEAT COMMENTS.
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWERS WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 ** PLEASE SEE ONE SET OF ELECTRICAL
 PLANS HAVE MANY OF THE ABOVE ITMES
 REDLINED IN LOCATIONS FOR NOTES.
 IE,FLR ELEC RMS, RECEPTS ETC.
  
 **BEFORE RESUBMITTING PLANS, PLEASE
 REMOVE ALL OLD/VOIDED ELECTRICAL PAGES
 AND ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-805-6717
 [email protected]
  
  
  
  
 19)NOTE: PLEAS
2006-04-13 00:00:00IN ELEC FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-12-27 Cont ID  
Sent By dpalmer Date 2005-12-27 Time 06:11 Rev Time 0.00
Received By dpalmer Date 2005-12-26 Time 14:03 Sent To  
Notes
2006-02-01 00:00:00*** PLEASE SEE 2004 FBC CHAPETR 13.
 HOTELS, ROOM OCCUPANCY CONTROLS FOR
 ROOMS AND OTHER CONTROL FOR COMMON AREAS
 ETC.
2005-12-27 00:00:00***************************************
 ************** UNSAT ***************
  
 ** HILTON GARDENS **
  
 ** PLEASE KNOW, PLANS ONLY SUBMITTED FOR
 "PLAN REVIEW ONLY" AND HAVE NOT BEEN
 SUBMITTED FOR PERMIT.
  
 ** PLEASE SEE BLDG REVIEW COMMENTS AS
 THIS PROJECT MAY REQUIRE A THIRD SET OF
 PLANS
  
  
 1)NOTE: PLEASE BE SURE PLANS REFERENCE
 CURRENT CODES IN EFFECT.
 2002 NFPA-70 (NEC), 2003 NFPA-101, 2002
 NFPA-72 ETC
  
 2)NOTE: PLEASE SEE MAIN ELECTRICAL ROOM
 DOORS WILL BE REQUIRED TO OPEN OUTWARD
 AND SHALL HAVE PANIC HARDWARE.
 110.26
  
 3)NOTE: PLEASE BE SURE ALL ELECTRICAL
 RMS, ELEVATOR EQUIPMENT RMS CONTAIN A
 BATTERY BACK UP LIGHT OF SOME SORT.
 LS101 7.8,7.9, 700.16
  
 4)NOTE: PLEASE SEE ELECTRICAL RMS ON
 EACH FLOOR MAY NOT CONTAIN AREA FOR
 "HOUSEKEEPING/STORAGE.
 PLEASE SEE SHEETS E-5- E7 WHICH WOULD BE
 ACCEPTABLE BY PLACING A WALL BETWEEN
 THIS AREA ELECTRICAL ROOM WITH A
 SEPARATE ENTRANCE/DOOR.
 110.26, 407.7, 240.24
  
 5)NOTE: PLEASE SEE FIRST FLR CIRCUTING
 FOR HALL RECEPTS, SOME SHOWN AND SOME
 MISSING. PLEASE COMPLETE.
 THERE IS A NOTE ON PLANS, WHICH MENTIONS
 HALL RECEPTS TO BE CIRCUITED TO NEAREST
 GUEST RM, HOWEVER THIS CIRCUIT NEEDS TO
 BE SHOWN.
  
 6)NOTE: PLEASE COMPLETE ALL OTHER
 CIRCUITING, GUEST RMS ETC.
 215.5
  
 7)NOTE: PLEASE SEE ELECTRICAL EQUIPMENT
 LOCATED ON WALL NEXT TO POOL APEARS TO
 BE LOCATED TOO CLOSE WHICH DOES NOT MEET
 MIN CLEARENCES PER 680.22
  
 8)NOTE: PLEASE SEE 620.23, 620.24 WHICH
 REQUIRES A DEDICATED BRANCH CIRCUIT FOR
 RECEPTS AND LTS FOR ELEVATOR EQUIPMENT
 RMS AND ANY ELEVATOR PITS.
  
 9)NOTE: PLEASE SUBMIT COMPLETE
 PHOTOMETRICS FOR ALL COMMON AREAS, AND
 STAIR TOWERS.
 PLEASE SEE 2003 NFPA-1017.8.1.3 WHICH
 REQUIRES A MIN OF 1 FT CANDLEAND A MIN
 OF 10FT CANDLES ON THE WALKING SURFACE
 UNDER NORMAL POWER. PLEASE SEE7.9.2.1
 WHICH REQUIRES A MIN OF 1FT CANDLE OF
 LIGHTING ON ALL WALKING SURFACES UNDER
 EMERGENCY CONDITIONS.
  
 10)NOTE: PLEASE SEE PHOTOMETRICS SHOWN
 FOR POOL AREA SHALL BE SUBMITTED TO PALM
 BEACH COUNTY HEATH DEPARTMENT FOR ANY
 AFTER DUSK SWIMMMING.
 IF THERE IS NOT GOING TO BE ANY SWIMMING
 FROM DUSK TO DAWN, PLEASE PROVIDE A NOTE
 ON PLAN FOR REQUIRED SIGNAGE TO BE PLACE
 AT AND IN POOL AREA.
 ** PLEASE KNOW, THE SWIMMING POOL ITSELF
 WILL BE REQUIRED TO BE UNDER A SEPARATE
 PERMIT.
  
 11)NOTE: PLEASE CLARIFY NOTE ON PLANS
 FOR THE REQUIREMENTS OF GUEST BATH GFI.
 THIS CAN NOT BE VERIFIED AT THIS TIME
 DUE TO MISSING CIRCUITING.
  
 12)NOTE: PLEASE SEE 210.60 FOR REQUIRED
 RECEPT SPACING FOR GUEST RMS OF HOTELS
 WHICH REFERENCES 210.52 FOR MIN SPACING.
 PLEASE SEE THERE IS AN EXCEPTION TO THE
 MIN SPACING AS TO PROVIDE RECEPTS FOR
 FURNITURE PLANS, HOWEVER THE NUMBER OF
 RECEPTS TO BE PROVIDED SHALL MEET THE
 SAME NUMBER OF RECEPTS IF THEEY WERE
 INSTALLED PER 210.52
 PLEASE SEE MANY GUEST RM TYPES WHICH ARE
 MISSING THE REQUIRED NUMBER.
 PLEASE SEE MOSTOF THESE UNTIS ARE
 REDLINED ON ONE SET OF PLANS.
 KING,2,5 6,7,KING SUITE ETC. PLEASE KNOW
 THAT NOT ALL UNITS WERE REDLINED, PLEASE
 BE SURE TO GO OVER THE MIN.
 PLEASE KNOW THAT A MIN OF TWO RECEPTS
 SHALL BE READILY ACCESSIBLE AT ALL
 TIMES.
 MOST UNITS MEET THIS , HOWEVER A COUPLE
 ARE MISSING.
  
 13)NOTE: PLEASE PROVIDE A NOTE ON THE
 ROOOFTOP PLAN WHICH SHOULD NOTE/MENTION:
 ANY PROPOSED LIGHTNING PROTECTION SYSTEM
 SHALL MEET NFPA-780, OR WORDS TO THAT
 AFFECT.
 IT IS NOTED THAT NO SYSTEM IS SHOWN AT
 THIS TIME, AND ANY FUTURE WOULD BE UNDER
 A SEPARATE PERMIT, HOWEVER A NOTE IS
 REQUIRED AT THIS TIME.
  
 14)NOTE:PLEASE SEE PANEL "K" IS SHOWN
 LISTING A 125A OCP TO FEED TO PANEL
 "KA", HOWEVER PANEL "KA" IS ONLY REATED
 AT 100A'S?
 PLEASE CORRELATE AND ADJUST.
 215.5,
  
 15)NOTE: PLEASE SEE PANEL "LDY" IS SHOWN
 AS A 100A MLO, YET MSB SHOWS A 225A
 BRKR/OCP FEEDING THIS PANEL.
 PLEASE ADJUST AND CORRELATE.
 215.5
  
 16)NOTE: PLEASE SEE PANEL "L" IS SHOWN
 AS 100A MLO, WITH MSB SHWOING 150A OCP
 FEEDING THIS PANEL.
 PLEASE ADJUST AND CORRELATE.
 215.5
  
 17)NOTE: PLEASE SEE RISER AND MSB SHOWS
 ALL 1H1, 2H2, 3H3 ETC AS 1H, 2H, 3H ETC
 ON PANEL SCHEDULES FOR THESE.
 PLEASE CORRELATE THE IDENTIFICATION OF
 THESE.
 215.5
  
 18)NOTE: PLEASE SEE 240.4C, WHICH
 REQUIRES THE CONDUCTOR FEEDING DEVICES
 RATED OVER 800A'S TO MEET OR EXCEED
 RAITNG OF SUCH DEVICE.
 PLEASE SEE MSB OS SHOWN AS A 3000A MAIN
 , HOWEVER CONDUCTORS ARE ONLY RATED FOR
 2100 A'S?
 5-SETS OF 600MCM, RATED @420A'S EACH.(75
 DEGREE COL).
 110.14, 215.5,215.3
 PLEASE ADJUST ON MORE THAN ONE SHEET,
 SEE 13,14.
  
 19)NOTE: PLEASE ALSO SEE CONDUCTORS FOR
 MAIN FEEDERS TO CHILLER FROM MSB.
 PLEASE SEE MSB SHOWS 3-300 MCM, HOWEVER
 PLEASE SEE CALCUALTIONS FOR CHILLER
 WHICH INDICATE 2-600'S.
 PLEASE CORRELARE. 215.5
  
 20)NOTE: PLEASE SEE RISER INDICATES
 "BLDG STEEL" AS PART OF THE GROUNDING
 ELECTRODE SYSTEM, WHICHIS OK AND IS
 REQUIRED IF "BLDG STEEL" IS PRESENT.
 PLEASE ALSO INCLUDE THE REQUIRED "FOOTER
 STEEL" IN DETAIL.
 250.50
  
 21)NOTE: PLEASE KNOW, THE REQUIRED WIND
 LOAD CALCULATIONS FOR LT POLES WITH
 FIXTURES ON THEM ARE REQUIRED AT THIS
 TIME.
 PLEASE KNOW, THESE WILL BE REVIEWED BY A
 STRUCTUAL PLANS REVIEWER.
 IF THIS INFORMATION IS NOT SUBMITTED AT
 THIS TIME, ALL SITE LIGHTING WOULD BE
 REQUIRED TO BE UNDER A SEPARATE PERMIT,
 WITH SEPARATE PLANS AND FEES.
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWERS WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 ** PLEASE SEE ONE SET OF ELECTRICAL
 PLANS HAVE MANY OF THE ABOVE ITMES
 REDLINED IN LOCATIONS FOR NOTES.
 IE,FLR ELEC RMS, RECEPTS ETC.
  
 ** PLEASE REMOVE ALL OLD/VOIDED
 ELECTRICAL PAGES AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-805-6717
 [email protected]
  
  
  
  
 19)NOTE: PLEAS
2005-12-26 00:00:00ONE ROLL IN ELECTRIC FOR REVIEW.
 PLANS WILL GO INTO "F" STATUS.
 REVIEW IN PROGRESS, NOTES TO FOLLOW.

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2006-06-29 Cont ID  
Sent By   Date 2006-06-29 Time   Rev Time 0.00
Received By   Date 2006-06-29 Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2006-04-07 Cont ID  
Sent By mamini Date 2006-04-07 Time 11:40 Rev Time 0.50
Received By mamini Date 2006-04-07 Time 11:40 Sent To  
Notes
2006-04-07 00:00:00FAILED:
  
 1. PLEASE SEE PREVIOUS REVIEW COMMENTS
 DATED 1-20-06.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2006-01-20 Cont ID  
Sent By mamini Date 2006-01-20 Time 15:46 Rev Time 1.00
Received By mamini Date 2006-01-20 Time 15:46 Sent To  
Notes
2006-01-20 00:00:00FAILED:
  
 1. PLEASE SUBMIT A COPY OF MODIFIED
 SFWMD PERMIT.
 2. PLEASE PROVIDE CALCULATION FOR STORM
 WATER POST DEVELOPMENT.
 3. PLEASE STATE AS WHERE RAIN LEADERS
 BEING CONNECTED.
 4. A CLEAN OUT IN ALL SEWER LATERAL IS
 REQUIRED.
 PLEASE SHOW THE LOCATIONS FOR BACKFLOWS
 FOR DOMMESTIC AND FIRE LINE.
 5. AN OIL WATER SEPARATOR IN SEWER LINE
 FOR THIS FACILITY IS REQUIRED.
 6. IS THERE A SEPARATE METER FOR THIS
 FACILITY?
 7. DUMPSTER ENCLOSURE SHOULD BE SIZED
 PER CITY OF WEST PALM BEACH REQUIREMENTS
 IF TO BE PICKED UP BY THE CITY, 12'-6"
 BETWEEN THE GATE POSTS, 12'-6" DEEP.
 8. ANY INLET IN THE PROPOSED ASPHALT
 DRIVEWAY? PLEASE VERIFY.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2007-01-17 Cont ID  
Sent By mawillia Date 2007-01-17 Time 14:15 Rev Time 0.00
Received By mawillia Date 2007-01-17 Time 14:14 Sent To  
Notes
2007-01-17 14:17:37*****APPROVED*****
  
  
 REVISED PLAN SHEETS E-4, E-5, E-6, AND E-7 WERE
 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2006-12-22 Cont ID  
Sent By mawillia Date 2006-12-22 Time 14:46 Rev Time 0.00
Received By mawillia Date 2006-12-22 Time 14:46 Sent To  
Notes
2006-12-22 15:01:23*****PROVISO*****
  
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.THE IMPACT OF THE PROPOSED CONSTRUCTION (FUTURE
 POOL) SHALL NOT INTERFERE OR HINDER EMERGENCY RESPONDER
 ACCESS TO THE SAID PROPERTY OR VICINITY THEREOF
 (INCLUDING FIRE LANES).
  
 3.SHOW/DISPLAY THE NUMERICAL ADDRESS FRONTING THE
 BUILDING.AS PER WEST PALM BEACH CODE, THOSE NUMBERS
 SHALL BE NO LESS THAN 6" IN HEIGHT AND 1" IN WIDTH.IF
 THE NUMERICAL ADDRESS IS NOT PLAINLY VISIBLE FROM
 WORTHINGTON ROAD, A MONUMENT SIGN OR MARKEE WITH THE
 POSTED NUMERICAL ADDRESS WILL BE REQUIRED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-06-28 Cont ID  
Sent By mwennerg Date 2006-06-28 Time 14:35 Rev Time 0.00
Received By mwennerg Date 2006-06-28 Time 14:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-05-05 Cont ID  
Sent By mwennerg Date 2006-05-05 Time 13:16 Rev Time 0.00
Received By mwennerg Date 2006-05-05 Time 13:16 Sent To  
Notes
2006-05-05 00:00:00******DENIED******
  
 PLEASE BE ADVISED THAT RESPONSES HAVE
 BEEN PROVIDED, HOWEVER SOME ADDITIONS,
 DELETIONS OR CHANGES ARE NOT ILLUSTRATED
 ON THE PLANS.
  
 1) COMMENT 5- RESPONSE STATES THAT A 2ND
 FIRE HYDRANT IS SHOWN ON FP-16. ONLY (8)
 FP SHEETS HAVE BEEN SUBMITTED.
  
 2) COMMENT 7- RESPONSE REFERS TO A.20,
 HOWEVER NO SUCH NOTE WAS FOUND.
  
 3) COMMENT 11- CERTIFICATION OR APPROVED
 COPY OF CERTIFICATE SHALL BE AVAILABLE
 PRIOR TO OR AT THE TIME OF THE FIRE
 ALARM FINAL.
  
 4) COMMENT 13- PLEASE PROVIDE NOTE TO
 DRAWINGS.
  
 5) COMMENT 15- PLEASE ADD ADDRESS NOTE
 TO ELEVATIONS.
  
 6) COMMENT 18- PLEASE NOTE THAT
 INCORRECT CHAPTER IS STILL REFERENCED ON
 A.20. PLEASE MAKE CORRECTION.
  
 7) COMMENT 20- PLEASE PROVIDE NOTE TO
 PLANS. NO SUCH NOTE WAS FOUND ON A.25.
  
 8) COMMENT 24- RESPONSE INDICATES THAT
 THE FIRE DEPARTMENT CONNECTION
 ARRANGEMENT ON DCDA WAS ELEIMINATED.
 THIS ARRANGEMENT IS STILL BEING SHOWN ON
 FP-6.
  
 9) COMMENT 27- PLEASE BE AWARE THAT FIRE
 SPRINKLER COVERAGE SHALL BE IN
 ACCORDANCE WITH NFPA 13. IF SUCH AN
 EXCEPTION EXISTS, PLEASE PROVIDE WITH
 RESPONSE INDICATING THAT SECTION.
  
 10) COMMENT 33- PLEASE NOTE THAT A
 DIMENSION OF 13'-6" WAS NOT FOUND ON
 A.24.
  
  
 PLEASE BE SURE WHEN RESUBMITTING, TO
 REFLECT ANY CHANGES TO PLANS THAT
 CORRULATE WITH APPROPRIATE RESPONSE.
 THIS WILL ASSIST IN EXPEDITING THIS
 PROCESS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-12-19 Cont ID  
Sent By mcarsill Date 2005-12-19 Time 14:13 Rev Time 0.00
Received By mcarsill Date 2005-12-19 Time 14:13 Sent To  
Notes
2005-12-19 00:00:001. CONSTRUCTION, DEMOLITION, AND
 RENOVATION TO COMPLY WITH NFPA 241.
  
 2. SUITABLE ROADS ARE TO BE PROVIDED
 DURING CONSTRUCTION FOR FIRE AND
 PARAMEDICAL EQUIPMENT.
  
 3. EXIT STAIRS ARE TO BE KEPT UP WITH
 CONSTRUCTION.
  
 4. THE AUTOMATIC SLIDING DOOR SHALL
 COMPLY WITH POWERED OPERATED DOOR
 REQUIREMENTS PER THE LIFE SAFETY CODE,
 2003 EDITION.
  
 5. THE SITE PLAN APPEARS TO ONLY DISPLAY
 ONE FIRE HYDRANT. IF THIS HYDRANT IS
 USED TO CONNECT TO THE FIRE DEPARTMENT
 SPRINKLER CONNECTION NO OTHERS ARE
 AVAILABLE FOR USE.
  
 6. FIRE HOSE VALVES SHALL BE PRESENT
 WITHIN THE STAIRWELLS WHERE A TWO HOUR
 RATED FIRE PROTECTION IS PROVIDED NOT
 OUTSIDE THE STAIRWELLS AS SHOWN.
 PORTABLE FIRE EXTINGUISHER CABINETS CAN
 REMAIN OUTSIDE THE STAIRWELLS BUT THE
 STANDPIPE CONNECTIONS SHOULD BE LOCATED
 IN THE STAIRWELLS.
  
 7. PLEASE PROVIDE PRESCRIPTIVE
 REQUIREMENTS FOR ALL HANDRAILS AND
 GUARDRAILS.
  
 8. ELEVATOR WARNING SIGNS WILL BE
 REQUIRED IN THE ELEVATOR LOBBIES.
  
 9. SEPERATE PLANS AND PERMITS REQUIRED
 FOR ANY HOOD, DUCT, AND FIRE SUPPRESSION
 SYSTEMS PLANNED.
  
 10. SEPERATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER SYSTEM INSTALLATION.
  
 11. SEPERATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM SYSTEM. FIRE ALARM SYSTEM
 SHALL BE MONITORED BY A LICENSED UL
 LISTED CENTRAL STATION APPROVED FOR
 CENTRAL STATION SERVICE.
  
 12. WILL THE PROPOSED FIREPLACE BE
 OPERATIONAL OR IS IT DECORATIVE.
  
 13. PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATIONS FOR ALL WALLS AND
 CEILINGS.
  
 14. NO SOFFITS SHALL INTERFERE WITH THE
 OPERATION OF ANY FIRE SPRINKLER HEADS.
  
 15. BUILDING ADDRESS IS REQUIRED ON
 PROPER ELEVATION. A MINIMUM OF AT LEAST
 6" HIGH NUMBERS ARE REQUIRED.
  
 16. GAS DRYERS ARE TO BE INSTALLED IN
 ACCORDANCE WITH RECOGNIZED NFPA
 STANDARDS AND RECOGNIZED SAFETY
 STANDARDS.
  
 17. ALL COOLERS AND FREEZERS SHALL HAVE
 FIRE SPRINKLER PROTECTION.
  
 18. STAIR SECTION 1, ON PAGE A.20
 REFERENCES CHAPTER 5. IT SHOULD READ
 CHAPTER 7.
  
 19. ON PAGE A.22 NOTES INDICATE A TWO
 HOUR RATING BUT NO UL NUMBER IS
 PROVIDED. UL NUMBERS LOCATED ON A.27.
  
 20. PLEASE INDICATE ON THE PLANS THAT
 ALL FIRE RATED DOORS SHALL BE EQUIPPED
 WITH SELF-CLOSING DEVICES AND SHALL
 POSITIVELY LATCH WHEN CLOSED.
  
 21. HOW WILL CARD READERS INTERFACE WITH
 EXITING REQUIREMENTS.
  
 22. ALL SMOKE DETECTORS SHALL BE LOCATED
 A MINIMUM OF AT LEAST THREE FEET FROM
 AIR CONDITIONING DIFFUSERS. PLEASE
 PROVIDE NOTE ON PLANS.
  
 23. PLEASE INDICATE WHAT REQUIRED
 INFORMATION WILL BE PLACED WITHIN THE
 HOTEL ROOMS ON THE INTERIOR SIDE DOORS.
  
 24. FP-1 APPEARS TO ILLUSTRATE TWO FIRE
 HYDRANTS BUT NO CALL-OUTS ARE PROVIDED.
 PLEASE REVISE.
  
 25. FP-1 SEEMS TO SUGGEST TWO FIRE
 DEPARTMENT CONENCTIONS. DUE TO THE SIZE
 AND OCCUPANCY TYPE, ONLY ONE FDC IS
 REQUIRED.
  
 26. FIRE LINE BACKFLOW DEVICE SHALL BE
 EQUIPPED WITH FLOW SWITCHES, CHAINS AND
 LOCKS.
  
 27. NO FIRE SPRINKLER HEADS SHOWN IN
 MAIN ELECTRICAL ROOM.
  
 28. RISER # 2 ON PAGE FP-6 APPEARS TO
 DISPLAY CONTROL VALVES BEHIND THE FIRE
 DEPARTMENT CONNECTION.
  
 29. PLEASE EXPLAIN FOUR INCH UNDERGROUND
 FIRE LINE. TYPICALLY, THE MINIMUM SHALL
 BE AT LEAST 6" UNLESS HYDRAULIC
 CALCULATIONS SUGGEST SOMETHING
 OTHERWISE.
  
 30. PLANS MENTION EXHAUST DUCT WRAP.
 PLEASE PROVIDE PRODUCT APPROVALS
 REGARDING THE DUCT WRAP STATED IN THE
 PLANS.
  
 31. DIFFERENT SHEETS SEEM TO SUGGEST
 DIFFERENT NUMBERS OF FIRE HYDRANTS.
 PLEASE REVISE ALL SHEETS AND ENSURE THAT
 THE CORRECT NUMBER OF FIRE HYDRANTS ARE
 SHOWN.
  
 32. FLOOR PLANS SHALL ILLUSTRATE ALL
 RATED WALLS AND LOCATIONS OF RATED
 SHAFTS. RATED WALLS IN COMMON AND
 BETWEEN GUEST ROOMS SHALL BE SHOWN.
  
 33. PLEASE PROVIDE HEIGHT OF PORTA
 CACHERE FROM FINISHED ELEVATION.
  
 34. TACTILE SIGNAGE REQUIRED AT EXIT
 DOORS.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
  
 804-4709

Review Stop G GAS REVIEW
Rev No 6 Status F Date 2007-02-09 Cont ID  
Sent By kstevens Date 2007-02-09 Time 18:55 Rev Time 0.00
Received By kstevens Date 2007-02-09 Time 18:55 Sent To  
Notes
2007-02-09 18:55:40 
 REVISION DENIED
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
  
 1. SHT P-15THE GAS RISER DIAGRAM BETWEEN SECTIONS (1)
 & (2) DO NOT REFLECT THE GAS EQUIPMENT SCHEDULE. THE
 RISER SHOWS TWO ITEM 45'S AND THE SCHEDULE ONLY SHOWS
 ONE ITEM 45. THIS WOULD CHANGE THE TOTAL CONNECTED GAS
 LOAD BY 140,900 BTU'S. PLEASE CORRELATE THE RISER
 DIAGRAM WITH THE GAS EQUIPMENT SCHEDULE. SECTION
 106.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 5 Status P Date 2007-01-16 Cont ID  
Sent By pschmitz Date 2007-01-16 Time 09:44 Rev Time 0.00
Received By pschmitz Date 2007-01-16 Time 09:44 Sent To  
Notes
2007-01-16 09:46:17SEE GAS PERMIT #06120002 FOR REVIEWED PLANS

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2006-09-01 Cont ID  
Sent By kstevens Date 2006-09-01 Time 16:45 Rev Time 0.00
Received By kstevens Date 2006-09-01 Time 16:45 Sent To  
Notes
2006-09-01 00:00:00REVISION DENIED
  
 A. SHT P-15 SUBMIT THE FOLLOWING:
  
 1. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 INDICATE THE MODEL NUMBER FOR EACH GAS
 APPLIANCE, AND EACH APPLIANCE MANUF.
 SPECIFICATION SHEET SHALL SHOW LISTING.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 3 Status N Date 2006-07-07 Cont ID  
Sent By kstevens Date 2006-07-07 Time 13:45 Rev Time 0.00
Received By kstevens Date 2006-07-07 Time 13:44 Sent To  
Notes
2006-07-07 00:00:00 
  
 PASSED/PROVISO
  
 REVISIONS REQUIRED FOR SHEETS P1, P-5, &
 P-10 FLOOR PLANS SHOWING THE HAND SINKS
 REQUIRED BY DBPR PLAN REVIEW. REVISION
 IS ALSO REQUIRED FORSHEET P-8 WATER
 RISER DIAGRAM AND SHT P-15 FPR THE
 GREASE ISOMETRIC RISER DIAGRAM
 REFLECTING THESE CHANGES.
  
 REVISION IS ALSO REQUIRED FOR THE GAS
 ISOMETRIC RISER DIAGRAM, WHICH SHALL
 CORRELATE WITH THE GAS
 EQUIPMENT/CONNECTED LOAD AND THE MANUF.
 SPECIFICATION SHEETS INDICATING THE BTU
 LOAD FOR EACH GAS APPLIANCE.
  
 GAS ISOMETRIC NOT APPROVED AT THIS TIME.
 PLUMBING ONLY APPROVED. SEPARATE GAS
 PERMIT REQUIRED.
  
  
  
  
 .

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2006-07-05 Cont ID  
Sent By kstevens Date 2006-07-05 Time 18:57 Rev Time 0.00
Received By kstevens Date 2006-07-05 Time 18:57 Sent To  
Notes
2006-07-05 00:00:00DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 32. P-15 THE FOLLOWING INFORMATION IS
 REQUIRED FOR GAS PLAN APPROVAL:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS.
 ***RESPONSE NOTED, BUT THERE ARE SOME
 CUT SECTIONS THAT DO NOT SHOW THE
 LENGTH.
 ****RESPONSE NOTED, BUT THERE IS NO
 LENGTHS FOR THE PIPING TO THE POOL/SPA
 HEATERS. THERE ARE 3 WATER HEATERS
 INDICATED, BUT ONLY TWO SHOWN ON THE
 ISOMETRIC RISER DIAGRAM. PLEASE
 CORRELATE THE APPLIANCES WITH THE RISER
 DIAGRAM.
  
 F. SUBMIT MANUFACTURE SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ***NO RESPONSE, NOT ADDRESSED.
 ****RESPONSE NOTED, BUT MANUF.
 SPECIFICATION SHEET ARE REQUIRED FOR ALL
 GAS APPLIANCES.
  
 G. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. BYPASS
 PIPING SHALL BE CONNECTED DOWNSTREAM OF
 THE EMERGENCY HOOD SHUT OFF VALVE.
 ***NO RESPONSE, NOT ADDRESSED. EMERGENCY
 HOOD SHUT DOWN SHUT OFF VALVE SHALL BE
 INSTALLED BETWEEN 42" AND 48" PER
 NFPA-96 SECTION 10.5.1 AND NFPA-1
 SECTION 50.4.7.1. INDICATE ON GAS RISER.
 ****RESPONSE NOTED, BUT NO MANUAL GAS
 SHUT OFF VALVE IS SHOWN ON RISER
 DIAGRAM.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-04-29 Cont ID  
Sent By kstevens Date 2006-04-29 Time 19:54 Rev Time 0.00
Received By kstevens Date 2006-04-29 Time 19:54 Sent To  
Notes
2006-04-29 00:00:00DENIED
 REFERENCE: FBC-2004 FUEL GAS
 NFPA-96
 NFPA-1
  
 FROM PLUMBING REVIEW NOTES:
  
 32. P-15 THE FOLLOWING INFORMATION IS
 REQUIRED FOR GAS PLAN APPROVAL:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS.
 ***RESPONSE NOTED, BUT THERE ARE SOME
 CUT SECTIONS THAT DO NOT SHOW THE LENGTH
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES,-
 SPECIFICATIONS NOT SUBMITTED. INDICATE
 IF PIPING WILL BE SCREW PIPE OR WELDED
 PIPE.
 ***RESPONSE NOTED, BUT NO INFORMATION
 FOUND.
  
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC.
 402.4(2). NATURAL GAS SPECIFY .5 PSI OR
 2 PSI.
 ***RESPONSE NOTED, BUT DELIVERY PRESSURE
 HAS NOT BEEN ADDRESSED.
  
 F. SUBMIT MANUFACTURE SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ***NO RESPONSE, NOT ADDRESSED.
  
 G. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. BYPASS
 PIPING SHALL BE CONNECTED DOWNSTREAM OF
 THE EMERGENCY HOOD SHUT OFF VALVE.
 ***NO RESPONSE, NOT ADDRESSED. EMERGENCY
 HOOD SHUT DOWN SHUT OFF VALVE SHALL BE
 INSTALLED BETWEEN 42" AND 48" PER
 NFPA-96 SECTION 10.5.1 AND NFPA-1
 SECTION 50.4.7.1. INDICATE ON GAS RISER.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 RESUBMIT ONE SET OF ORIGINAL SHEETS FOR
 COMPARISON.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2007-02-15 Cont ID  
Sent By adarroug Date 2007-02-15 Time 13:19 Rev Time 0.00
Received By adarroug Date 2007-02-15 Time 13:19 Sent To P
Notes
2007-02-15 13:19:36TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2007-02-01 Cont ID  
Sent By adarroug Date 2007-02-01 Time 14:56 Rev Time 0.00
Received By adarroug Date 2007-02-01 Time 14:56 Sent To Z
Notes
2007-02-01 14:57:14TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2007-01-11 Cont ID  
Sent By adarroug Date 2007-01-11 Time 09:28 Rev Time 0.00
Received By adarroug Date 2007-01-11 Time 09:28 Sent To Z
Notes
2007-01-11 09:29:02TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2006-12-27 Cont ID  
Sent By adarroug Date 2006-12-27 Time 10:57 Rev Time 0.00
Received By adarroug Date 2006-12-27 Time 10:57 Sent To  
Notes
2007-01-13 12:44:35TO "COMM" BD#57
2006-12-27 10:57:48WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-11-12 Cont ID  
Sent By adarroug Date 2006-11-12 Time 10:25 Rev Time 0.00
Received By adarroug Date 2006-11-12 Time 10:25 Sent To  
Notes
2006-11-14 09:59:21TO "COMM" BD#53
2006-11-12 10:25:27WAITING FOR "COMM' BD

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-11-03 Cont ID  
Sent By adarroug Date 2006-11-03 Time 08:49 Rev Time 0.00
Received By adarroug Date 2006-11-03 Time 08:49 Sent To M
Notes
2006-11-03 08:50:08TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-09-25 Cont ID  
Sent By adarroug Date 2006-09-25 Time 14:53 Rev Time 0.00
Received By adarroug Date 2006-09-25 Time 14:53 Sent To B
Notes
2006-09-25 00:00:00TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-09-23 Cont ID  
Sent By adarroug Date 2006-09-23 Time 19:07 Rev Time 0.00
Received By adarroug Date 2006-09-23 Time 19:07 Sent To P
Notes
2006-09-23 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-08-10 Cont ID  
Sent By mmiller Date 2006-08-10 Time 16:29 Rev Time 0.00
Received By adarroug Date 2006-08-10 Time 10:12 Sent To E
Notes
2006-08-22 00:00:00TO "COMM" BD#17
2006-08-10 00:00:00WAITING FOR COMM B

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-08-02 Cont ID  
Sent By adarroug Date 2006-08-02 Time 16:47 Rev Time 0.00
Received By adarroug Date 2006-08-02 Time 16:47 Sent To B
Notes
2006-08-02 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-07-20 Cont ID  
Sent By rbrown Date 2006-07-20 Time 19:24 Rev Time 0.00
Received By rbrown Date 2006-07-20 Time 19:24 Sent To  
Notes
2006-07-20 00:00:00SUBMITTAL FOR SHORING PLANS TO JIM
 WITMER'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-05-25 Cont ID  
Sent By adarroug Date 2006-05-18 Time 09:24 Rev Time 0.00
Received By lmartine Date 2006-05-18 Time 11:58 Sent To  
Notes
2006-06-06 00:00:00TO "COMM" BD#44
2006-05-25 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-04-03 Cont ID  
Sent By adarroug Date 2006-03-15 Time 14:28 Rev Time 0.00
Received By adarroug Date 2006-03-15 Time 14:27 Sent To  
Notes
2006-04-03 00:00:00TO "COMM" BD#38

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-03-01 Cont ID  
Sent By jwitmer Date 2006-03-01 Time 12:47 Rev Time 0.00
Received By jwitmer Date 2005-11-18 Time 17:24 Sent To  
Notes
2005-12-09 00:00:00ON COMM BOARD SPACE # 43
2005-11-18 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2007-02-09 Cont ID  
Sent By rregueir Date 2007-02-09 Time 15:01 Rev Time 0.00
Received By rregueir Date 2007-02-09 Time 10:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2007-02-07 Cont ID  
Sent By hmoser Date 2007-02-07 Time 08:38 Rev Time 0.00
Received By hmoser Date 2007-02-07 Time 08:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2006-12-06 Cont ID  
Sent By pkrauss Date 2006-12-06 Time 10:55 Rev Time 0.00
Received By pkrauss Date 2006-12-06 Time 10:55 Sent To  
Notes
2006-12-07 07:20:21REVISIONS TO SHEET M-1

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2006-11-30 Cont ID  
Sent By pkrauss Date 2006-11-30 Time 09:39 Rev Time 0.00
Received By pkrauss Date 2006-11-30 Time 09:36 Sent To  
Notes
2006-11-30 10:02:10DENIED:
 REVISION IS SUPERCEDED BY PLAN DATED 11/7/06.THIS
 REVISION WAS ISSUED 10/29/06.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2006-11-21 Cont ID  
Sent By pkrauss Date 2006-11-21 Time 09:09 Rev Time 0.00
Received By pkrauss Date 2006-11-21 Time 08:57 Sent To  
Notes
2006-11-21 09:59:48DENIED:
 REVISED SHEET M-1 IS MISSING FIRE DAMPERS IN THE
 FOLLOWING AREAS:
  
 1.SUPPLY & RETURN AIR DUCTS FROM AHU-3, PLAN SHEET
 A.01 INDICATES MECHANICAL CLOSET HAS A 1 HR RATING,
 FIRE DAMPERS ARE REQUIRED.
  
 2.S/A & R/A FROM AHU-3 INTO THE CORRIDOR AREA AND
 DUCTS PENETRATING INTO THE FOLLOWING ROOMS;47,48, 46,
 50, 51, PLEASE NOTE, PER 2004 FMC 603.5.5, FLEXIBLE AIR
 DUCTS & FLEX CONNECTORS SHALL NOT PASS THROUGH ANY
 FIRE-RESISTANCE-RATED ASSEMBLY.PLANS INDICATE FLEX
 DUCT PENETRATING RATED CORRIDOR.PLEASE ALSO SEE
 EXCEPTIONS IN 607.5.3, SHOULD PENETRATIONS COMPLY WITH
 THE AFOREMENTIONED SECTION, PLEASE ANNOTATE THIS
 SECTION ON THE PLAN.
  
 3. PLEASE CLARIFY THE PENETRATION BETWEEN THE GUEST
 LAUNDRY ROOM AND THE LOCKER AREA.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719 OR E-MAIL [email protected]
  
 *****************REVIEW IN
 PROGRESS************************

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-07-03 Cont ID  
Sent By pkrauss Date 2006-06-30 Time 13:57 Rev Time 0.00
Received By pkrauss Date 2006-06-21 Time 10:41 Sent To  
Notes
2006-06-30 00:00:00ALL COMMENTS ADDRESSED:
 RESPONSE TO COMMENTS DATED 5/3/06
  
 COMMENT #1 - INDICATES SUPPLY DUCT SHALL
 BE IN A RATED CHASE.OK
  
 COMMENT #3 - SUBDUCT DETAIL ON PLAN
 SHEET M-10
  
 COMMENT #5 - RESPONSE INDICATES PLAN
 SHEETS M-15 & M-16 (CHILLED WATER
 PIPING) WERE REMOVED.PLANS ARE STILL
 IN FOR RE-SUBMITTAL.PLEASE REMOVE.
  
 NEW COMMENTS
 COMMENT #1 - OK
 COMMENT #2 - PLANS STILL IN SUBMITTAL
 THAT ARE NOT PERTINENT.
 COMMENT #3 - OK
  
 PLEASE NOTE, BTU'S USED FOR COMBUSTION
 AIR CALUCALTIONS ARE NOT CORRECT.PLAN
 SHOWS 165,000 BTU'S PER DRYER AND THE
 MANUFACTURE SUBMITTAL DATA INDICATE
 215,000 BTU'S.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-05-03 Cont ID  
Sent By pkrauss Date 2006-05-03 Time 07:50 Rev Time 0.00
Received By pkrauss Date 2006-05-03 Time 06:51 Sent To  
Notes
2006-05-03 00:00:00DENIED:
 RESPONSE TO COMMENT #1 FROM REVIEW DATED
 1-24-06 INDICATES THE OUTDOOR SHAFT WAS
 ELIMINATED.RTU #1 SUPPLY AIR FOR THE
 COMMON AREA OF FLOORS ONE THROUGH 4.
 THIS DUCT SHALL BE BE IN A RATED CHASE
 IN ACCORDANCE WITH 2004 FMC 607.6.
  
 COMMENT #3:RESPONSE INDICATES SUB-DUCT
 DETAIL IS NO LONGER ON PLAN SHEET M-11
 BUT IS NOW ON PLAN SHEET M-9, THIS IS
 INCORRECT.PLAN SHEET M-9 IS THE FIRE
 SUPPRESSION FOR THE GREASE HOOD.
 SUB-DUCT IS DETAILED ON PLAN SHEET M-11.
  
 COMMENT #5:REPONSE INDICATES CHILLED
 WATER SYSTEM HAS BEEN ELIMINATED.PLAN
 SHEETS M-15, M-16 & DETAIL ON PLAN SHEET
 M-14, STILL INDICATE A CHILLED WATER
 SYSTEM.PLEASE REMOVE DETAILS AND PLANS
 THAT DO NOT PERTAIN TO THIS JOB.
  
  
 NEW COMMENTS:
 1.PLAN SHEET M-1 RETURN AIR FROM THE
 MAIN ELECTRICAL ROOM IS MISSING A FIRE
 DAMPER/ACCESS DOOR.PLEASE CLARIFY.
  
 2.PLEASE CLARIFY PLAN SHEET M-6 & M-8.
 PLAN SHEET M-6 APPEARS TO REPLACE M-8.
 PLEASE REMOVE ALL PAGES THAT ARE NOT
 PERTINENT.
  
 3.PLAN SHEET M-6 THE FRESH AIR
 CALCULATION INDICATES FRESH PROVIDED
 FROM AHU-1 & BY VTAC UNITS.PLEASE
 INDICATE WHERE THE VTAC UNITS ARE
 LOCATED.PLEASE NOTE THE VTAC UNITS ARE
 NOT INDICATED ON THE EQUIPMENT SCHEDULE
 OR ON THE PLAN.PLEASE CLARIFY HOW
 AHU-1 IS ABLE TO PROVIDE OUTSIDE AIR
 WHEN THERE IS NO OUTSIDE AIR DUCTED INTO
 AHU-1.IT APPREARS THAT AHU-3, 4, 5 &
 POSSIBLY AHU-2 HAVE OUTSIDE AIR PROVIDED
 VIA RTU-1.AHU-1, 6, & 7 DO NOT APPEAR
 TO HAVE FRESH AIR INTRODUCED INTO THE
 SYSTEM.
  
 ADDITIONAL PERMITS REQUIRED FOR HOOD,
 FIRE SUPPRESSION & WALK-IN COOLERS.
 HOOD & SUPPRESSION PLANS SUBMITTED WITH
 BUILDING PERMIT.PLEASE PROVIDE
 MANUFACTURE SUBMITTAL DATA FOR THE
 WALK-IN COOLER WITH MECHANICAL PERMIT
 APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
  
  
 **************REVIEW IN PROGRESS*******

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-01-24 Cont ID  
Sent By pkrauss Date 2006-01-24 Time 09:57 Rev Time 0.00
Received By pkrauss Date 2006-01-23 Time 16:46 Sent To  
Notes
2006-01-24 00:00:00DENIED:********PLAN CHECK ONLY*******
  
 1.PLAN SHEET M-2 DETAIL OF THE FAN
 COIL UNITS INDICATE A FIRE DAMPER AT THE
 FLOOR PENETRATIONS.PER 2004 FMC
 607.6.1,FIRE DAMPERS ARE PERMITTED THE
 FLOOR CEILING PENETRATIONS WHEN
 CONNECTING NOT MORE THAN TWO STORIES.A
 SHAFT ENCLOSURE WILL BE REQUIRED FOR THE
 OUTSIDE AIR DUCT THAT PENETRATES 3 FIRE
 RATED FLOOR/CEILING & 1 CEILING ROOF
 ASSEMBLY.
  
 2.PLAN SHEET M-2 TERMINATION OF GREASE
 DUCT.PER 2004 FMC 506.3.12.3, EXHAUST
 OUTLETS SHALL BE LOCATED NOT LESS THAN
 10 FT HORIZONTALLY FROM PARTS OF THE
 SAME OR CONTIGUOUS BUILDINGS.THE
 EXCEPTION TO THE 10 FT CLEARANCE IS, 5FT
 PROVIDED THAT THE EXHAUST DISCHARAGES
 AWAY FROM SUCH LOCATIONS.
  
 3.PLEASE CLARIFY IF THE TOILET EXHAUST
 WILL BE IN A SUB-DUCT AS INDICATED ON
 PLAN SHEET M-11.
  
 4.PLAN SHEET M-2 PLEASE CLARIFY THE
 FLUE THAT TERMINATES ON THE ROOFAT THE
 SECOND FLOOR.PLEASE PROVIDE DETAIL.
  
 5.PLEASE INDICATE PIPING MATERIAL &
 METHOD OF JOING THE PIPE (WELD,
 VICTALIC, THREADED, ETC).PLEASE NOTE,
 UNDER GROUND PIPING TO BE PRESSURE
 TESTED AND INSPECTED PRIOR TO COVERING
 IN ACCORDANCE WITH 2004 FMC 1208.
  
 6.PLEASE PROVIDE SUBMITTAL DATA FOR
 ALL COMPONENTS OF THE SYSTEM.
  
 8.ADDITIONAL PERMITS REQUIRED FOR THE
 HOOD, FIRE SUPPRESSION AND WALK-IN
 COOLER/FREEZER.PLEASE PROVIDE
 MANUFACTURER SUBMITTAL WITH PERMIT
 APPLICATION.
  
 9.PLEASE INDICATE CLEARANCE TO
 COMBUSTIBLES AS REQUIRED IN 2004 FMC
 506.3.6.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 9 Status P Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By pschmitz Date 2007-02-16 Time 09:49 Sent To PC
Notes
2007-02-16 09:51:38REVISION DELETING SINKS IN RM# 210,310,410.
 PLUMBING PIPES CAPPED OFF AT WALL

Review Stop P PLUMBING
Rev No 8 Status F Date 2007-02-09 Cont ID  
Sent By kstevens Date 2007-02-09 Time 18:39 Rev Time 0.00
Received By kstevens Date 2007-02-09 Time 18:39 Sent To  
Notes
2007-02-09 18:54:53REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 1. SHT P-1 HAND DRAWN CHANGES AND WHITE OUT ARE NOT
 APPROVED FOR REVISIONS. SECTION 106.1.3.--NO CHANGE
 NOTED ON ONE REVISION #5< (BETWEEN COL. LINE 11 & 12).
 --PLEASE TURN OFF THE CLOUDS AND NUMBERED TRIANGLES
 FROM PREVIOUS REVISIONS TO EXPEDITE REVIEW OF THE
 REVISIONS. SECTION 106.1.1.
  
 2. SHT P-5 HAND DRAWN CHANGES AND WHITE OUT ARE NOT
 APPROVED FOR REVISIONS. SECTION 106.1.3.--PLEASE
 TURN OFF THE CLOUDS AND NUMBERED TRIANGLES FROM
 PREVIOUS REVISIONS TO EXPEDITE REVIEW OF THE REVISIONS.
 SECTION 106.1.1.
  
 3. SHT P-8WHITE OUT IS NOT APPROVED FOR REVISIONS.
 SECTION 106.1.3.--PLEASE TURN OFF THE CLOUDS AND
 NUMBERED TRIANGLES FROM PREVIOUS REVISIONS TO EXPEDITE
 REVIEW OF THE REVISIONS. SECTION 106.1.1.
  
 4. SHT P-9WHITE OUT IS NOT APPROVED FOR REVISIONS.
 SECTION 106.1.3.--PLEASE TURN OFF THE CLOUDS AND
 NUMBERED TRIANGLES FROM PREVIOUS REVISIONS TO EXPEDITE
 REVIEW OF THE REVISIONS. SECTION 106.1.1.
  
 5. SHT P-10 SHOWS THE DRAINAGE FROM (L-11) 4" ROOF
 DRAIN 824 SQ FT BEING ROUTED TWO DIFFERENT WAYS TO THE
 RISER. PLEASE CLARIFY. SECTIONS 106.1.1 AND 706.3.
  
 6. SHT P-15THE GAS RISER DIAGRAM BETWEEN SECTIONS (1)
 & (2) DO NOT REFLECT THE GAS EQUIPMENT SCHEDULE. THE
 RISER SHOWS TWO ITEM 45'S AND THE SCHEDULE ONLY SHOWS
 ONE ITEM 45. THIS WOULD CHANGE THE TOTAL CONNECTED GAS
 LOAD BY 140,900 BTU'S. PLEASE CORRELATE THE RISER
 DIAGRAM WITH THE GAS EQUIPMENT SCHEDULE. SECTION
 106.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 7 Status F Date 2006-12-19 Cont ID  
Sent By kstevens Date 2006-12-19 Time 17:50 Rev Time 0.00
Received By kstevens Date 2006-12-19 Time 17:50 Sent To  
Notes
2006-12-19 18:16:08REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SHT P-1.AS INDICATED ON PREVIOUS REVISION REVIEW,
 MAKE SURE THE CLOUDS ARE BOLD ENOUGH TO SEE. THE
 REVISION FOR NUMBER 5 IS FAINT & HARD TO SEE. A NEW
 REVISION WAS FOUND ON THE PLAN. THIS NUMBER 6 REVISION
 IS NOT CLOUDED AND NOT INDICATED IN THE REVISION INDEX.
 PLEASE CLOUD ALL REVISIONS WITH A HEAVY CLOUD, AND SHOW
 ALL REVISIONS ON THE REVISION INDEX.
  
 2. SHT P-5. REVISION #6 NOT CLOUDED. PLEASE CLOUD ALL
 REVISIONS. IT APPEARS THAT THERE IS A NEW TOILET ROOM.
 IF SO PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE WITH
 SECTIONS 11-4.16, 11-4.18, 11-4.19, & 11-4.22 AND ALL
 SUBSECTIONS. SUBMIT A REVISION FOR THE SANITARY RISER
 DIAGRAM THAT REFLECTS THE FLOOR PLAN, SHOWING THE NEW
 TOILET ROOM PIPING AND INDICATING ALL PIPE SIZES,
 TRAPS, VENTS ETC. SECTION 106.3.5.1.3.
  
 3. SHT P-8REVISION 5 NOT SHOWN ON THE REVISION INDEX,
 NOR IS THE REVISION CLOUDED. PLEASE CLOUD ALL REVISIONS
 AND INDICATED THE REVISION NUMBER ON THE REVISION
 INDEX. SECTION 106.1.1. - REVISION 3 IS NOT CLOUDED,
 NOR DOES IT INDICATE WHAT CHANGE HAS BEEN MADE. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 6 Status F Date 2006-11-01 Cont ID  
Sent By kstevens Date 2006-11-01 Time 13:52 Rev Time 0.00
Received By kstevens Date 2006-11-01 Time 13:52 Sent To  
Notes
2006-11-01 14:01:13REVISIONDENIED
 REFERENCE:
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHTS P-1, P-5, P-8 PLUMBING TECHNICAL CODES OK, BUT
 THE TITLE BLOCK FOR THE ARCHITECT DOES NOT HAVE THE
 REQUIRED BUSINESS NUMBER, (CERTIFICATE OF
 AUTHORIZATION), IN THE TITLE BLOCK. THIS HAS BEEN
 COMMENTED ON SINCE FEB. 06 IN THE FIRST PLAN REVIEW FOR
 PLUMBING. EIGHT MONTHS IS SUFFICIENT TIME TO APPLY FOR
 A CERTIFICATE OF AUTHORIZTION. EITHER REMOVE "GRW
 ARCHITECTS" FROM THE SHEETS, OR INDICATE THE BUSINESS
 NUMBER IN THE TITLE BLOCK AS REQUIRED IN FAC
 61G1-16.004(2) & FS 481.219.
  
 2. WHEN RESUBMITTING REVISIONS, DISABLE ALL REVISION
 CLOUDS FROM PREVIOUS REVISIONS AND ONLY SHOW THE
 CLOUDED REVISIONS BEING SUBMITTED FOR THE PRESENT
 REVISION. ALSO MAKE SURE THE CLOUDS ARE BOLD ENOUGH TO
 SEE. THE LAST REVISIONS WERE DIFFICULT TO FIND. SECTION
 104.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 5 Status F Date 2006-09-01 Cont ID  
Sent By kstevens Date 2006-09-01 Time 16:41 Rev Time 0.00
Received By kstevens Date 2006-09-01 Time 16:41 Sent To  
Notes
2006-09-01 00:00:00REVISION DENIED
 SHEETS P-8 & P-15
  
 1. SHT P-8 WATER LINES DO NOT REFLECT
 THE FLOOR PLAN NEAR FIXTURES P-15 &
 P-16.
  
 2. SHT P-15 GAS REVISION NOT APPROVED.
 SEE GAS REVISION NOTES
  
  
 REVISION OK SHTS P-1, P-5, & P-17
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-07-07 Cont ID  
Sent By kstevens Date 2006-07-07 Time 13:35 Rev Time 0.00
Received By kstevens Date 2006-07-07 Time 13:35 Sent To  
Notes
2006-07-07 00:00:00 
  
 PASSED/PROVISO
  
 REVISIONS REQUIRED FOR SHEETS P1, P-5, &
 P-10 FLOOR PLANS SHOWING THE HAND SINKS
 REQUIRED BY DBPR PLAN REVIEW. REVISION
 IS ALSO REQUIRED FORSHEET P-8 WATER
 RISER DIAGRAM AND SHT P-15 FPR THE
 GREASE ISOMETRIC RISER DIAGRAM
 REFLECTING THESE CHANGES.
  
 REVISION IS ALSO REQUIRED FOR THE GAS
 ISOMETRIC RISER DIAGRAM, WHICH SHALL
 CORRELATE WITH THE GAS
 EQUIPMENT/CONNECTED LOAD AND THE MANUF. SPECIFICATION
 SHEETS INDICATING THE BTU
 LOAD FOR EACH GAS APPLIANCE.
  
 GAS ISOMETRIC NOT APPROVED AT THIS TIME.
 PLUMBING ONLY APPROVED. SEPARATE GAS
 PERMIT REQUIRED.
  
  
  
  
 .

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-07-05 Cont ID  
Sent By kstevens Date 2006-07-05 Time 18:23 Rev Time 0.00
Received By kstevens Date 2006-07-05 Time 18:23 Sent To  
Notes
2006-07-05 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 WPB CITY CODE/ORDINENCES
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 A. FROM PREVIOUS REVIEW: THE COMMENT
 NUMBERS WILL REMAIN THE SAME.
  
 5. SHT A.01 ROUTE PLANS TO DBPR,
 DIVISION OF HOTEL & RESTURANT FOR REVIEW
 PRIOR TO RESUBMITTING. MINIMUM 3 SETS OF
 PLANS SHALL BE REVIEWED, STAMPED AND TWO
 SHEET "WORKSHEETS" SHALL BE ATTACHED TO
 EACH SET OF PLANS SUBMITTED FOR REVIEW.
 SECTION 102.2.1.
 ***NO RESPONSE, NOT ADDRESSED.
 ***RESPONSE NOTED, BUT NEW SHEETS SHALL
 BE INSERTED INTO THE PLANS, AND ALL
 VOIDED SHEETS REMOVED. ATTACH 2 PAGE
 "SPECIFICATION WORKSHEETS" TO EACH SET
 OF PLANS. REMOVE BUSINESS NAME FROM THE
 TITLE BLOCK, OR INDICATE CERTIFICATE OF
 AUTHORIZATION NUMBER ON TITLE BLOCK. THE
 SIGNED SEALED SHALL BE DATED WHEN SEAL
 IS AFFIXED TO DRAWINGS. FAC 61G1-16.003
 & 61G1-16.004(5) - FS 481.219.
  
 10. SHT A.01 ADA ROOMS MATRIX INDICATES
 5 ROOMS FOR THE HEARING IMPAIRED ROOMS.
 ONE ROOM (226) IS NOT SHOWN ON THE FLOOR
 PLAN. (4 OTHER ROOMS SHOWN AS HEARING
 IMPAIRED ACCOMODATIONS). PLEASE CLARIFY.
 SECTION 11-9.1.3.
 ***NO RESPONSE, NOT ADDRESSED.
 ****RESPONSE NOTED, BUT HEARING IMPAIRED
 ROOMS SHALL BE IN ADDITION TO THOSE
 ACCESSIBLE SLEEPING ROOMS AND SUITES
 REQUIRED BY 11-9.1.2. ONLY ROOMS 307 &
 407 MEET THIS REQUIREMENT. 2 OTHER
 HEARING IMPAIRED ACCOMMODATION ROOMS
 REQUIRED.
  
 11. SHT A.01 1 ROOM SHALL COMPLY WITH
 SECTION 11-9.2.3 PLEASE INDICATE THE
 ROOM NUMBER THAT SHALL COMPLY WITH THIS
 REQUIREMENT.
 ***NO RESPONSE, NOT ADDRESSED.
 ****RESPONSE NOTED, BUT THE ROOM IN
 QUESTION HAS NOT BEEN INDICATED ON THE
 MATRIX.
  
 13. SHT A.17 BREAK SINK TO COMPLY WITH
 SECTION 11-4.24 AND ALL SUBSECTIONS.
 SUBMIT A DETAIL.
 ***NO RESPONSE, NOT ADDRESSED.
 ****RESPONSE NOTED, BUT NO DETAIL FOR
 THE SINK IS LOCATED ON SHT A.17.
  
 14. SHT A.17 PLAN KEY NOTES: SHOW THE
 LOCATIONS OF NUMBER 2 & 10. SECTION
 106.1.1.
 ***NO RESPONSE, NOT ADDRESSED.
 ****RESPONSE NOTED, BUT DO NOT
 UNDERSTAND THE RESPONSE. KEY NOTES HAVE
 BEEN DELETED, AND THE EYE WASH AND THE
 ICE MACHINE AS INDICATED PREVIOUSLY ARE
 NOT SHOWN. PLEASE CLARIFY.
  
 17. SHT A.34 PUBLIC TOILETS, PROVIDE A
 DETAIL SHOWING COMPLIANCE WITH 11-4.16,
 11-4.18, 11-4.19, & 11-4.22 AND ALL
 SUBSECTIONS. SECTION 106.1.1.
 ***NO RESPONSE, NOT ADDRESSED.
 ****RESPONSE NOTED, BUT THE FOLLOWING
 INFORMATION IS NOT SHOWN:
 FOR THE UNINAL:
 A. 11-4.18.2 HEIGHT
 B. 11-4.18.4 FLUSH CONTROLS
 FOR THE LAV'S:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.5 FAUCETS.
  
 32. P-15 THE FOLLOWING INFORMATION IS
 REQUIRED FOR GAS PLAN APPROVAL:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS.
 ***RESPONSE NOTED, BUT THERE ARE SOME
 CUT SECTIONS THAT DO NOT SHOW THE
 LENGTH.
 ****RESPONSE NOTED, BUT THERE IS NO
 LENGTHS FOR THE PIPING TO THE POOL/SPA
 HEATERS. THERE ARE 3 WATER HEATERS
 INDICATED, BUT ONLY TWO SHOWN ON THE
 ISOMETRIC RISER DIAGRAM. PLEASE
 CORRELATE THE APPLIANCES WITH THE RISER
 DIAGRAM.
  
 F. SUBMIT MANUFACTURE SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ***NO RESPONSE, NOT ADDRESSED.
 ****RESPONSE NOTED, BUT MANUF.
 SPECIFICATION SHEET ARE REQUIRED FOR ALL
 GAS APPLIANCES.
  
 G. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. BYPASS
 PIPING SHALL BE CONNECTED DOWNSTREAM OF
 THE EMERGENCY HOOD SHUT OFF VALVE.
 ***NO RESPONSE, NOT ADDRESSED. EMERGENCY
 HOOD SHUT DOWN SHUT OFF VALVE SHALL BE
 INSTALLED BETWEEN 42" AND 48" PER
 NFPA-96 SECTION 10.5.1 AND NFPA-1
 SECTION 50.4.7.1. INDICATE ON GAS RISER.
 ****RESPONSE NOTED, BUT NO MANUAL GAS
 SHUT OFF VALVE IS SHOWN ON RISER
 DIAGRAM.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 RESUBMIT ONE SET OF ORIGINAL SHEETS FOR
 COMPARISON.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-04-29 Cont ID  
Sent By kstevens Date 2006-04-29 Time 19:07 Rev Time 0.00
Received By kstevens Date 2006-04-29 Time 19:07 Sent To  
Notes
2006-04-29 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 WPB CITY CODE/ORDINENCES
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 A. FROM PREVIOUS REVIEW: THE COMMENT
 NUMBERS WILL REMAIN THE SAME.
  
 2. ALL ARCHITECTURAL SHEETS SHALL SHOW
 THE DATE THAT THE SEAL WAS AFFIXED TO
 THE PLANS. FAC 61G1-16.003 &
 61G1-16.004(5) AND FS 481.219 &
 481.2055. MANY SHEETS HAVE NO DATE ON
 THE SEAL AND THE CERTIFICATE OF
 AUTHORIZATION NUMBER SHALL BE IN THE
 TITLE BLOCK OF EACH SHEET.
 ***NO RESPONSE: ID SHEETS HAVE PREPARED
 BY THE ARCHITECT HAVE NO DATE ON THE
 SEAL AND NO SHEETS HAVE THE CERTIFICATE
 OF AUTHORIZATION NUMBER ON EACH SHEET.
  
 3. POOL PLAN: SEPARATE PERMIT/PLANS
 REQUIRED FOR THE POOL. MINIMUM 2 SETS OF
 PLANS SHALL BE REVIEWED AND STAMPED BY
 THE PBC HEALTH DEPT. PRIOR TO SUBMITTING
 TO THE CITY WPB FOR REVIEW.
 ***NO RESPONSE: THIS WAS INFORMATIONAL.
  
 5. SHT A.01 ROUTE PLANS TO DBPR,
 DIVISION OF HOTEL & RESTURANT FOR REVIEW
 PRIOR TO RESUBMITTING. MINIMUM 3 SETS OF
 PLANS SHALL BE REVIEWED, STAMPED AND TWO
 SHEET "WORKSHEETS" SHALL BE ATTACHED TO
 EACH SET OF PLANS SUBMITTED FOR REVIEW.
 SECTION 102.2.1.
 ***NO RESPONSE, NOT ADDRESSED.
  
 7. SHT A.01 INDICATES ROOM TYPES K4, K5,
 K6, K7, KING HI, KING, KS, K2, K3, KING
 2, KING 3, KING 8, QQ, QQ HI, BUT ONLY
 K4, K7, KS, KE, KING 2, OFFER
 ACCESSIBLITY. PLEASE INDICATE HOW THIS
 COMPLYS WITH SECTION 11-9.1.4 CLASSES OF
 SLEEPING ACCOMMODATIONS.
 ***NO RESPONSE, NOT ADDRESSED.
  
 8. SHT A.01 PLAN KEY NOTES: UNABLE TO
 LOCATE KEY PLAN NUMBERS 7 AND 10. PLEASE
 SHOW NUMBERS ON FLOOR PLAN. SECTION
 106.1.1.
 ***NO RESPONSE, NOT ADDRESSED.
  
 9. SHT A.01 ADA ROOMS MATRIX INDICATES
 ROOM 121 AS HAVING A SHOWER. TABLE
 INDICATING NUMBER OF ACCESSIBLE ROOMS
 INDICATE 4 ARE REQUIRED WITH ONE ROOM
 WITH A ROLL IN SHOWER REQUIRED. PLEASE
 INDICATE IF ROOM 121 IS ONE OF THE FOUR
 REQUIRED ACCESSIBLE ROOMS. SECTION
 11-9.1.2.
 ***NO RESPONSE, NOT ADDRESSED.
  
 10. SHT A.01 ADA ROOMS MATRIX INDICATES
 5 ROOMS FOR THE HEARING IMPAIRED ROOMS.
 ONE ROOM (226) IS NOT SHOWN ON THE FLOOR
 PLAN. (4 OTHER ROOMS SHOWN AS HEARING
 IMPAIRED ACCOMODATIONS). PLEASE CLARIFY.
 SECTION 11-9.1.3.
 ***NO RESPONSE, NOT ADDRESSED.
  
 11. SHT A.01 1 ROOM SHALL COMPLY WITH
 SECTION 11-9.2.3 PLEASE INDICATE THE
 ROOM NUMBER THAT SHALL COMPLY WITH THIS
 REQUIREMENT.
 ***NO RESPONSE, NOT ADDRESSED.
  
 12. SHT A.05 SUBMIT A DETAIL FOR
 SCUPPERS. ALL DOWNSPOUTS ARE NOT SHOWN
 ON THE ELEVATIONS. PLEASE CLARIFY.
 SECTION 106.1.1.
 ***NO RESPONSE, NOT ADDRESSED.
  
 13. SHT A.17 BREAK SINK TO COMPLY WITH
 SECTION 11-4.24 AND ALL SUBSECTIONS.
 SUBMIT A DETAIL.
 ***NO RESPONSE, NOT ADDRESSED.
  
 14. SHT A.17 PLAN KEY NOTES: SHOW THE
 LOCATIONS OF NUMBER 2 & 10. SECTION
 106.1.1.
 ***NO RESPONSE, NOT ADDRESSED.
  
 15. SHT A.32 SHOW CENTER OF FIXTURE OFF
 THE WALL AT 18" FOR THE WATER CLOSET.
 (FIG. 28). SHOW THE FLUSH CONTROLS AS
 REQUIRED IN SECTION 11-4.16.5.
 ***NO RESPONSE, NOT ADDRESSED.
  
 16. SHT A.33A LAV CLEARANCE TO BE 29"
 PER 11-4.19.2. (27" SHOWN). - SHOW THE
 FAUCET REQUIREMENT PER SECTION 11-4.19.5
 - SHOW CONTROL REQUIREMENTS FOR TUB &
 SHOWERS PER 11-4.20.5 (FIG. 11-34) AND
 11-4.21.5 (FIG. 11-37).
 ***NO RESPONSE, NOT ADDRESSED.
  
 17. SHT A.34 PUBLIC TOILETS PROVIDE A
 DETAIL SHOWING COMPLIANCE WITH 11-4.16,
 11-4.18, 11-4.19, & 11-4.22 AND ALL
 SUBSECTIONS. SECTION 106.1.1.
 ***NO RESPONSE, NOT ADDRESSED.
  
 18. SHT P-1 NOTE INDICATES 24 GAUGE
 GALVINIZED PAN ABOVE THE ELECTRICAL
 EQUIPMENT ROOM WITH A 1" DRAIN TO FLOOR
 DRAIN. PER PLUMBING NOTES ON SHT P-12,
 NO WATER, SANITARY, OR DRAINAGE PIPING
 PERMITTED IN ELECTRICAL OR ELEVATOR
 EQUIPMENT ROOMS. (ALSO SEE NEC SECTION
 110.26(F)A.D. - IF SOMEHOW APPROVED, AN
 EXPLANATION WILL BE REQUIRED TO EXPLAIN
 HOW A 1" DRAIN LINE WILL BE ABLE TO
 DRAIN THE 4" SOIL STACK #13, 1" HOT
 WATER & 1-1/4" COLD WATER IF THESE LINES
 HAPPEN TO FAIL. SECTION 106.1.1.
 ***RESPONSE NOTED, BUT PLAN STILL SHOWS
 A 1" DRAIN FROM METAL PAN, AND STILL
 SHOWS STACK 13 9TYPE A) SOIL STACK IN
 THE MAIN ELECTRIC ROOM.
  
 19. SUBMIT A KITCHEN FIXTURE I.D. SHEET
 INDICATING THE LOCATION AND I.D. NUMBER
 FOR EACH FIXTURE. INDICATE ALL SANT.,
 GREASE, GAS, AND WATER SUPPLY PIPE SIZE
 FOR EACH FIXTURE/APPLIANCE. SECTION
 106.3.5.1.3.
 ***RESPONSE NOTED, BUT NO KITCHEN
 FIXTURE ID SHEET SUBMITTED. (SEE SHT
 A-19 FOR ALL KITCHEN FIXTURES).
  
 21. SHT P-4 BATH GROUP "E" ITEM D
 INDIRECT WASTE FROM THE ICE MACHINE NOT
 APPROVED AS SHOWN. SEE ICE MACHINE
 DETAIL SHEET P-14 FOR CORRECT
 INSTALLATION OF THE INDIRECT WASTE.
 SECTIONS 802.3 & 802.3.2. PLEASE CHANGE
 DETAIL ON BATH GROUP "E"
 ***RESONSE NOTED, BUT NO CHANGED NOTED
 ON PLANS
  
 22. SHT P-5 3" RPZV BACKFLOW REQUIRED
 DOWNSTREAM OF THE METERS. SECTIONS 603.1
 FOOTNOTE D, AND608.13.2. - ALSO MAKE
 CHANGE TO WATER ISOMETRIC DIAGRAM ON
 SHEET P-8.
 ***RESPONSE NOTED, BUT DOUBLE CHECK
 VALVES ARE NOT APPROVED. 3" RPCV
 BACKFLOW REQUIRED.
  
 23. SHT P-6 ALL WATER RISER DIAGRAMS,
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURE IN AN "EFFECTIVE RANGE"
 NOT IN THE CEILING AS SHOWN. PDI-WH 201
 AND MANUF. INSTALLATION INSTRUCTIONS.
 CHANGE NOTE 3 OF THE WATER ISOMETRIC
 RISERS NOTES TO REFLECT THIS. SECTION
 106.1.1.
 ***RESPONSE NOTED, BUT WATER HAMMER
 ARRESTORS ARE STILL SHOWN IN THE CEILING
 FOR THE SHOWERS AND TUBS.
  
 24. SHT P-7 STACK TYPE "A1" NOTE
 INDICATES A SHOWER FOR THE BATHROOM
 GROUPS, BUT A TUB IS SHOWN ON THE FLOOR
 PLAN. PLEASE CORRELATE FLOOR PLAN AND
 NOTE. - STACK TYPE "C" A TUB ON THE BATH
 GROUP, BUT ISOMETRIC SHOWS SHOWERS.
 PLEASE CORRELATE. - STACK TYPE "E" SHOWS
 A SAFEWASTE FOR THE INDIRECT WASTE FOR
 THE ICE MAKER. SHEET P-14 SHOWS THE
 CORRECT INDIRECT WASTE ON THE ICE MAKER
 DETAIL. PLEASE CHANGE RISER ISOMETRIC TO
 REFLECT THE ICE MAKER DETAIL FOR
 INDIRECT WASTE. SECTION 106.1.1.
 ***RESPONSE NOTED, BUT STACK A1 NOT
 CHANGED, STACK C SHOULD SHOW 1 TUB & 1
 SHOWER AND FLOOR PLAN ONLY SHOWN ONE
 LAV, AND STACK E REQUIRES A FLOOR SINK,
 NOT A FLOOR DRAIN.
  
 25. SHT P-8 BACKFLOW PROTECTION IS
 REQUIRED FOR SUPPLY LINE TO THE
 FOUNTAIN. PLEASE INDICATE METHOD OF
 BACKFLOW PROTECTION. SECTION 608.
 ***RESPONSE NOTED, BUT DOUBLE CHECK
 VALVES ARE NOT APPROVED.
  
 27. SHT P-13 WATER HEATER DETAIL STATES
 "SEE PROJECT DOCUMENTS AND SPECIFICTION
 FOR ADDITIONAL INFORMATION AND WORK
 REQUIRED FOR A CODE APPROVED AND
 ARCHITECT ACCEPTED INSTALLATION". ALSO
 STATESIN PIPING ARRANGEMENT AT WATER
 HEATERS (E) "REFER TO MANUFACTURE
 RECOMMENDATIONS AND CODE REQUIREMENTS
 FOR INSTALLATIONS AND LOCATIONS OF
 INTAKE AND EXHAUST VENT TERMINALS".
 THESE HAVE NOT BEEN SUBMITTED. SECTION
 106.1.1.
 ***RESPONSE NOTED, BUT NO SPECIFICATIONS
 HAVE BEEN LOCATED.
  
 29. SHT P-14 NOTES REFER TO PROJECT
 SPECIFICATIONS THAT WERE NOT SUBMITTED.
 PLEASE SUBMIT ALL REFERENCED
 SPECIFICATIONS. SECTION 106.1.1.
 ***RESPONSE NOTED, BUT NO SPECIFICATION
 HAVE BEEN LOCATED.
  
 30. SHT P-14 ICE MACHINE DETAIL.
 SEPARATE DRAIN LINES REQUIRED FOR THE
 ICE CUBER AND THE ICE BIN.
 ***RESPONSE NOTED, BUT DETAIL HAS NOT
 BEEN CHANGED.
  
 31. SHT P-15 GREASE WASTE ISOMETRIC
 DIAGRAM DOES NOT REFLECT THE FLOOR PLAN.
 NO LINE TO THE CAN WASH IS SHOWN. P-5
 BEHIND THE ELECTRICAL ROOM IS SHOWN AS A
 FLOOR SINK ON THE FLOOR PLAN AND AS A
 FLOOR DRAIN ON THE RISER DIAGRAM.
 (SHOULD BE A FLOOR SINK ON BOTH) SECTION
 106.1.1. - UNDER GREASE WASTE DIAGRAM
 THE NOTESTATES "SEE KITCHEN DOCUMENTS,
 SPECIFICATIONS, AND DATA SHEETS FOR
 ADDITIONAL INFORMATION AND REQUIREMENTS
 OF PLUMBING WORK ETC.". THESE WERE NOT
 SUBMITTED.
 ***RESPONSE NOTED, BUT NO CHANGES ARE
 SHOWN AND COMMENT HAS NOT BEEN
 ADDRESSED.
  
 32. P-15 THE FOLLOWING INFORMATION IS
 REQUIRED FOR GAS PLAN APPROVAL:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS.
 ***RESPONSE NOTED, BUT THERE ARE SOME
 CUT SECTIONS THAT DO NOT SHOW THE LENGTH
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES,-
 SPECIFICATIONS NOT SUBMITTED. INDICATE
 IF PIPING WILL BE SCREW PIPE OR WELDED
 PIPE.
 ***RESPONSE NOTED, BUT NO INFORMATION
 FOUND.
  
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC.
 402.4(2). NATURAL GAS SPECIFY .5 PSI OR
 2 PSI.
 ***RESPONSE NOTED, BUT DELIVERY PRESSURE
 HAS NOT BEEN ADDRESSED.
  
 F. SUBMIT MANUFACTURE SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ***NO RESPONSE, NOT ADDRESSED.
  
 G. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. BYPASS
 PIPING SHALL BE CONNECTED DOWNSTREAM OF
 THE EMERGENCY HOOD SHUT OFF VALVE.
 ***NO RESPONSE, NOT ADDRESSED. EMERGENCY
 HOOD SHUT DOWN SHUT OFF VALVE SHALL BE
 INSTALLED BETWEEN 42" AND 48" PER
 NFPA-96 SECTION 10.5.1 AND NFPA-1
 SECTION 50.4.7.1. INDICATE ON GAS RISER.
  
 *************NEW COMMENT****************
 1B. SHT P-9 SANITARY RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN. NEW FLOOR
 PLAN SHOWS THE LAV CHANGED TO THE
 OPPOSITE WALL BY STACK 1 WHERE AS THE
 RISER DOES NOT REFLECT THIS CHANGE. THE
 BATHROOM AT STACK 2 SHOWS A TUB ON THE
 FLOOR PLAN, BUT A SHOWER ON THE RISER
 DIAGRAM. PLEASE CORRELATE RISER AND
 FLOOR PLAN. SECTION 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 RESUBMIT ONE SET OF ORIGINAL SHEETS FOR
 COMPARISON.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-02-21 Cont ID  
Sent By kstevens Date 2006-02-21 Time 09:30 Rev Time 0.00
Received By kstevens Date 2006-02-11 Time 18:55 Sent To  
Notes
2006-02-21 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 WPB CITY CODE/ORDINENCES
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. INDICATE ON PLANS THAT THE DESIGN IS
 PER FBC-2004.
 2. ALL ARCHITECTURAL SHEETS SHALL SHOW
 THE DATE THAT THE SEAL WAS AFFIXED TO
 THE PLANS. FAC 61G1-16.003 &
 61G1-16.004(5) AND FS 481.219 &
 481.2055. MANY SHEETS HAVE NO DATE ON
 THE SEAL AND THE CERTIFICATE OF
 AUTHORIZATION NUMBER SHALL BE IN THE
 TITLE BLOCK OF EACH SHEET.
 3. POOL PLAN: SEPARATE PERMIT/PLANS
 REQUIRED FOR THE POOL. MINIMUM 2 SETS OF
 PLANS SHALL BE REVIEWED AND STAMPED BY
 THE PBC HEALTH DEPT. PRIOR TO SUBMITTING
 TO THE CITY WPB FOR REVIEW.
 4. SHT A.01 GREASE INTECEPTOR SHALL BE
 SIZED BY LYNN MASSON, ENVIRONMENTAL
 COMPLIANCE. PLEASE CONTACT HER AT (561)
 822-2271, OR FAX (561) 822-2279, OR
 E-MAIL HER AT [email protected]. SUBMIT A
 COPY OF HER REQUIREMENTS/DETERMINATION
 WITH PLANS WHEN RESUBMITTING. WASTE ORD.
 90-124(7)(B).
 5. SHT A.01 ROUTE PLANS TO DBPR,
 DIVISION OF HOTEL & RESTURANT FOR REVIEW
 PRIOR TO RESUBMITTING. MINIMUM 3 SETS OF
 PLANS SHALL BE REVIEWED, STAMPED AND TWO
 SHEET "WORKSHEETS" SHALL BE ATTACHED TO
 EACH SET OF PLANS SUBMITTED FOR REVIEW.
 SECTION 102.2.1.
 6. SHT A.01 SHOW THE TURNING AREA IN THE
 TOILET ROOMS 32 & 33, NOT IN THE
 ACCESSIBLE STALL. SECTION 11-4.22.3
 7. SHT A.01 INDICATES ROOM TYPES K4, K5,
 K6, K7, KING HI, KING, KS, K2, K3, KING
 2, KING 3, KING 8, QQ, QQ HI, BUT ONLY
 K4, K7, KS, KE, KING 2, OFFER
 ACCESSIBLITY. PLEASE INDICATE HOW THIS
 COMPLYS WITH SECTION 11-9.1.4 CLASSES OF
 SLEEPING ACCOMMODATIONS.
 8. SHT A.01 PLAN KEY NOTES: UNABLE TO
 LOCATE KEY PLAN NUMBERS 7 AND 10. PLEASE
 SHOW NUMBERS ON PLAN. SECTION 106.1.1.
 9. SHT A.01 ADA ROOMS MATRIX INDICATES
 ROOM 121 AS HAVING A SHOWER. TABLE
 INDICATING NUMBER OF ACCESSIBLE ROOMS
 INDICATE 4 ARE REQUIRED WITH ONE ROOM
 WITH A ROLL IN SHOWER REQUIRED. PLEASE
 INDICATE IF ROOM 121 IS ONE OF THE FOUR
 REQUIRED ACCESSIBLE ROOMS. SECTION
 11-9.1.2.
 10. SHT A.01 ADA ROOMS MATRIX INDICATES
 5 ROOMS FOR THE HEARING IMPAIRED ROOMS.
 ONE ROOM (226) IS NOT SHOWN ON THE FLOOR
 PLAN. (4 OTHER ROOMS SHOWN AS HEARING
 IMPAIRED ACCOMODATIONS). PLEASE CLARIFY.
 SECTION 11-9.1.3.
 11. SHT A.01 1 ROOM SHALL COMPLY WITH
 SECTION 11-9.2.3 PLEASE INDICATE THE
 ROOM NUMBER THAT SHALL COMPLY WITH THIS
 REQUIREMENT.
 12. SHT A.05 SUBMIT A DETAIL FOR
 SCUPPERS. ALL DOWNSPOUTS ARE NOT SHOWN
 ON THE ELEVATIONS. PLEASE CLARIFY.
 SECTION 106.1.1.
 13. SHT A.17 BREAK SINK TO COMPLY WITH
 SECTION 11-4.24 AND ALL SUBSECTIONS.
 SUBMIT A DETAIL.
 14. SHT A.17 PLAN KEY NOTES: SHOW THE
 LOCATIONS OF NUMBER 2 & 10. SECTION
 106.1.1.
 15. SHT A.32 SHOW CENTER OF FIXTURE OFF
 THE WALL AT 18" FOR THE WATER CLOSET.
 (FIG. 28). SHOW THE FLUSH CONTROLS AS
 REQUIRED IN SECTION 11-4.16.5.
 16. SHT A.33A LAV CLEARANCE TO BE 29"
 PER 11-4.19.2. (27" SHOWN). - SHOW THE
 FAUCET REQUIREMENT PER SECTION 11-4.19.5
 - SHOW CONTROL REQUIREMENTS FOR TUB &
 SHOWERS PER 11-4.20.5 (FIG. 11-34) AND
 11-4.21.5 (FIG. 11-37).
 17. SHT A.34 PUBLIC TOILETS PROVIDE A
 DETAIL SHOWING COMPLIANCE WITH 11-4.16,
 11-4.18, 11-4.19, & 11-4.22 AND ALL
 SUBSECTIONS. SECTION 106.1.1.
 18. SHT P-1 NOTE INDICATES 24 GAUGE
 GALVINIZED PAN ABOVE THE ELECTRICAL
 EQUIPMENT ROOM WITH A 1" DRAIN TO FLOOR
 DRAIN. PER PLUMBING NOTES ON SHT P-12,
 NO WATER, SANITARY, OR DRAINAGE PIPING
 PERMITTED IN ELECTRICAL OR ELEVATOR
 EQUIPMENT ROOMS. (ALSO SEE NEC SECTION
 110.26(F)A.D. - IF SOMEHOW APPROVED, AN
 EXPLANATION WILL BE REQUIRED TO EXPLAIN
 HOW A 1" DRAIN LINE WILL BE ABLE TO
 DRAIN THE 4" SOIL STACK #13, 1" HOT
 WATER & 1-1/4" COLD WATER IF THESE LINES
 HAPPEN TO FAIL. SECTION 106.1.1.
 19. SUBMIT A KITCHEN FIXTURE I.D. SHEET
 INDICATING THE LOCATION AND I.D. NUMBER
 FOR EACH FIXTURE. INDICATE ALL SANT.,
 GREASE, GAS, AND WATER SUPPLY PIPE SIZE
 FOR EACH FIXTURE/APPLIANCE. SECTION
 106.3.5.1.3.
 20. SHT P-1 DISHWASHER SHALL DRAIN INTO
 THE SANITARY SYSTEM, NOT THE GREASE
 SYSTEM PER CITY CODE 90-124(7)(B).
 21. SHT P-4 BATH GROUP "E" ITEM D
 INDIRECT WASTE FROM THE ICE MACHINE NOT
 APPROVED AS SHOWN. SEE ICE MACHINE
 DETAIL SHEET P-14 FOR CORRECT
 INSTALLATION OF THE INDIRECT WASTE.
 SECTIONS 802.3 & 802.3.2. PLEASE CHANGE
 DETAIL ON BATH GROUP "E"
 22. SHT P-5 3" RPZV BACKFLOW REQUIRED
 DOWNSTREAM OF THE METERS. SECTIONS 603.1
 FOOTNOTE D, AND608.13.2. - ALSO MAKE
 CHANGE TO WATER ISOMETRIC DIAGRAM ON
 SHEET P-8.
 23. SHT P-6 ALL WATER RISER DIAGRAMS,
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURE IN AN "EFFECTIVE RANGE"
 NOT IN THE CEILING AS SHOWN. PDI-WH 201
 AND MANUF. INSTALLATION INSTRUCTIONS.
 CHANGE NOTE 3 OF THE WATER ISOMETRIC
 RISERS NOTES TO REFLECT THIS. SECTION
 106.1.1.
 24. SHT P-7 STACK TYPE "A1" NOTE
 INDICATES A SHOWER FOR THE BATHROOM
 GROUPS, BUT A TUB IS SHOWN ON THE FLOOR
 PLAN. PLEASE CORRELATE FLOOR PLAN AND
 NOTE. - STACK TYPE "C" A TUB ON THE BATH
 GROUP, BUT ISOMETRIC SHOWS SHOWERS.
 PLEASE CORRELATE. - STACK TYPE "E" SHOWS
 A SAFEWASTE FOR THE INDIRECT WASTE FOR
 THE ICE MAKER. SHEET P-14 SHOWS THE
 CORRECT INDIRECT WASTE ON THE ICE MAKER
 DETAIL. PLEASE CHANGE RISER ISOMETRIC TO
 REFLECT THE ICE MAKER DETAIL FOR
 INDIRECT WASTE. SECTION 106.1.1.
 25. SHT P-8 BACKFLOW PROTECTION IS
 REQUIRED FOR SUPPLY LINE TO THE
 FOUNTAIN. PLEASE INDICATE METHOD OF
 BACKFLOW PROTECTION. SECTION 608.
 26. SHT P-10 INDICATE THE PIPE SIZE AND
 SQUARE FOOTAGE BEING DRAINED DOWNSTREAM
 OF STORM RISER L-5. - PIPING DOWNSTREAM
 OF STORM RISER L-2 IS INDICATED AS BEING
 2% SLOPE. THIS IS NOT REQUIRED AS THE
 RAINFALL RATE IS 4.5 INCHES PER HR. IF
 THE PIPE IS TO BE 2% THEN THE ENTIRE RUN
 FROM L-8 TO THE OUTSIDE OF THE BLDG
 SHALL BE 2% PER SECTION 704.1. - PER
 TABLE 1106.3THE MAXIMUM SQUARE FOOTAGE
 FOR 4" PIPE @ 4.5 PER INCH RANIFALL RATE
 IS 1600SF. L-10 & L-11 ADD UP TO 1646SF.
 5" HORIZONTAL PIPING REQUIRED. PLEASE
 CLARIFY.
 27. SHT P-13 WATER HEATER DETAIL STATES
 "SEE PROJECT DOCUMENTS AND SPECIFICTION
 FOR ADDITIONAL INFORMATION AND WORK
 REQUIRED FOR A CODE APPROVED AND
 ARCHITECT ACCEPTED INSTALLATION". ALSO
 STATESIN PIPING ARRANGEMENT AT WATER
 HEATERS (E) "REFER TO MANUFACTURE
 RECOMMENDATIONS AND CODE REQUIREMENTS
 FOR INSTALLATIONS AND LOCATIONS OF
 INTAKE AND EXHAUST VENT TERMINALS".
 THESE HAVE NOT BEEN SUBMITTED. SECTION
 106.1.1.
 28. SHT P-14 STORM ISOMETRIC DIAGRAM
 DOES NOT REFLECT THE PIPING SHOWING ON
 SHEET P-10. THE RISER TO L-10 & L-11 IS
 SHOWN AS 5" ON SHT P-10, BUT NO PIPE
 SIZE IS SHOWN ON RISER. - INDICATE THE
 PIPE SIZE AND SQUARE FOOTAGE DOWNSTREAM
 OF RISER L-5. - 2% SLOPE SHOWN
 DOWNSTREAM OF RISER L-2. (SEE COMMENT
 26) SECTION 106.1.1 AND TABLE 1106.3.
 29. SHT P-14 NOTES REFER TO PROJECT
 SPECIFICATIONS THAT WERE NOT SUBMITTED.
 PLEASE SUBMIT ALL REFERENCED
 SPECIFICATIONS. SECTION 106.1.1.
 30. SHT P-14 ICE MACHINE DETAIL.
 SEPARATE DRAIN LINES REQUIRED FOR THE
 ICE CUBER AND THE ICE BIN.
 31. SHT P-15 GREASE WASTE ISOMETRIC
 DIAGRAM DOES NOT REFLECT THE FLOOR PLAN.
 NO LINE TO THE CAN WASH IS SHOWN. P-5
 BEHIND THE ELECTRICAL ROOM IS SHOWN AS A
 FLOOR SINK ON THE FLOOR PLAN AND AS A
 FLOOR DRAIN ON THE RISER DIAGRAM.
 (SHOULD BE A FLOOR SINK ON BOTH) SECTION
 106.1.1. - UNDER GREASE WASTE DIAGRAM
 THE NOTESTATES "SEE KITCHEN DOCUMENTS,
 SPECIFICATIONS, AND DATA SHEETS FOR
 ADDITIONAL INFORMATION AND REQUIREMENTS
 OF PLUMBING WORK ETC.". THESE WERE NOT
 SUBMITTED.
 32. P-15 THE FOLLOWING INFORMATION IS
 REQUIRED FOR GAS PLAN APPROVAL:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES,-
 SPECIFICATIONS NOT SUBMITTED. INDICATE
 IF PIPING WILL BE SCREW PIPE OR WELDED
 PIPE.
 C. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC.
 402.4(2). NATURAL GAS SPECIFY .5 PSI OR
 2 PSI.
 E. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
 F. SUBMIT MANUFACTURE SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 G. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. BYPASS
 PIPING SHALL BE CONNECTED DOWNSTREAM OF
 THE EMERGENCY HOOD SHUT OFF VALVE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 RESUBMIT ONE SET OF ORIGINAL SHEETS FOR
 COMPARISON.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 6 Status P Date 2007-02-06 Cont ID  
Sent By jroach Date 2007-02-06 Time 22:28 Rev Time 0.00
Received By jroach Date 2007-02-06 Time 22:28 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 5 Status F Date 2007-01-17 Cont ID  
Sent By jroach Date 2007-01-17 Time 13:55 Rev Time 0.00
Received By jroach Date 2007-01-17 Time 13:53 Sent To  
Notes
2007-01-17 13:55:231/17/07 ***LANDSCAPE REVISIONS FAILED***
  
 1) MINOR PD AMENDMENT SHALL BE SUBMITTED AND APPROVED
 BY THE PLANNING DEPARTMENT PRIOR TO APPROVAL OF A
 BUILDING PERMIT.
  
 2) PROPOSED LANDSCAPE REVISIONS WILL NOT BE SUPPORTED
 BY THIS OFFICE BASED ON CONCERNS BY THE LANDSCAPE
 PLANNER AS WELL AS MYSELF.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 4 Status P Date 2006-11-20 Cont ID  
Sent By jroach Date 2006-11-20 Time 11:52 Rev Time 0.00
Received By jroach Date 2006-11-20 Time 11:52 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2006-05-25 Cont ID  
Sent By jroach Date 2006-05-25 Time 21:10 Rev Time 0.00
Received By jroach Date 2006-05-25 Time 21:10 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2006-04-01 Cont ID  
Sent By jroach Date 2006-04-01 Time 10:57 Rev Time 0.00
Received By jroach Date 2006-04-01 Time 10:57 Sent To  
Notes
2006-04-01 00:00:004/1/2006 ***FAILED***
  
 1) ALL PLANS NEED TO BE CONSISTENT!!!
 SOME INSTANCES ARE INDICATED IN THE
 FOLLOWING COMMENTS.
  
 2) LETTER OF APPROVAL FROM THE MASTER
 DEVELOPMENT SHALL BE INCLUDED IN THE
 PERMIT PACKAGE INDICATING ACCEPTANCE OF
 THE SITE PLAN, LANDSCAPE PLAN,
 ELEVATIONS, MATERIALS, COLORS, ETC.
  
 3) THE PAVING/GRADING PLAN DOES NOT
 MATCH THE SITE PLAN WITH RESPECT TO THE
 LOCATION OF THE BUILDING, THE ADDITONAL
 HC PARKING SPACE, ETC.
  
 4) THE LANDSCAPE PLANS DO NOT MATCH THE
 SITE PLAN WITH RESPECT TO THE LOCATION
 OF THE BUILDING, THE ADDITIONAL HC
 PARKING SPACE, THE SWIMMING POOL, THE
 REFLECTING POOL.
  
 5) THE WALLS/FENCES AROUND THE TWO POOLS
 ARE NOT SHOWN ON THE LANDSCAPE PLAN AND
 THE PROPOSED LANDSCAPING APPEARS TO
 INTERFERE WITH THEIR LOCATION.
  
 6) THE SCREENING OF THE POOL EQUIPMENT
 IS NOT SHOWN ON THE SITE OR LANDSCAPE
 PLANS...THE LOCATION OF THE POOL
 EQUIPMENT IS NOT EVEN SHOWN ON THE
 LANDSCAPE PLAN.
  
 7) THE LANDSCAPING AT THE NORTHEAST
 CORNER OF THE PROPERTY INTERFERES WITH
 THE EXISTING ASPHALT PATH THAT GOES
 AROUND THE BELLSOUTH EASEMENT...IS THE
 PATH BEING RELOCATED?IF SO, IS
 BELLSOUTH ACCEPTABLE OF THIS AND NO
 OTHER PLANS INDICATE IT BEING RELOCATED.
  
 8) ON SHEET SP.02, PROVIDE THE OUTLINE
 OF THE BUILDING.NO DETAIL WAS PROVIDED
 ON THE PROPOSED ALUMINUM FENCE AND THE
 LANDSCAPE PLAN DOES NOT MATCH THE
 PLANTING BEDS THAT ARE INDICATED HERE.
  
 9) ON SHEET SP.03, THE LABEL NEAR THE
 POOL INDICATES A FOUNTAIN FEATURE, BUT
 NONE IS SHOWN, SCREENING OF THE POOL
 EQUIPMENT IS NOT SHOWN, NO DETAIL OF THE
 PROPOSED BIKE RACK HAS BEEN PROVIDED,
 THE LANDSCAPE PLAN DOES NOT MATCH THE
 PLANTING BEDS THAT ARE INDICATED HERE.
  
 10) PROVIDE MORE DETAIL REGARDING THE
 CANOPIES THAT ARE INDICATED ON SHEETS
 SP.02 AND SP.03.THESE CANOPIES ALSO
 ARE NOT SHOWN ON THE ELEVATIONS.
  
 11) THE LOCATION OF THE KITCHEN EXHAUST
 FAN IS NOT CONSISTENT BETWEEN ALL
 ELEVATIONS NOR THE ROOF PLAN.
  
 12) PLEASE PROVIDE MORE DETAIL OF THE
 SCREENING OF THE KITCHEN EXHAUST FAN.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH,
 SENIOR PLANNER AT (561) 822-1435.
  
 -----------------
  
 THE FOLLOWING COMMENTS ARE FROM ALAN
 BARATTA, LANDSCAPE PLANNER....
  
 1) THE TREE PLANTING DIAGRAM NEEDS TO BE
 MODIFIED TO ACTUALLY SHOW A PLANTING
 HOLE 3 TIMES THE SIZE OF THE ROOT BALL,
 AS INDICATED IN THE VERBAGE.
  
 2) ADD A STATEMENT THAT THE TRUNK FLARE
 OR TOP ROOT WILL BE VISIBLE ON THE
 SURFACE.
  
 3) ADD A CONTAINER SPECIFIICATION THAT
 CONTAINER-GROWN TREES WILL BE CHECKED
 FOR CIRCLING ROOTS PRIOR TO PLANTING.
 IF FOUND, THE MATERIAL MUST BE REJECTED
 OF IF THE ROOTS ARE LESS THAN 1/3 THE
 TRUNK DIAMETER, THEY CAN BE CUT IN AN
 AREA WHERE THEY ARE GROWNING RADIALLY
 FROM THE TRUNK.
  
 4) ADD A COMMENT THAT ALL TREES SHALL
 HAVE THE BURLAP FOLDED BACK TO THE
 BOTTOM 1/3 OF THE ROOT BALL.
  
 5) METAL BASKETS SHALL BE REMOVED FROM
 THE 1/2 FO THE ROOT BALL.
  
 QUESTIONS/COMMENTS, CONTACT ALAN
 BARATTA, LANDSCAPE PLANNER AT (561)
 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-01-17 Cont ID  
Sent By jroach Date 2006-01-26 Time 15:51 Rev Time 0.00
Received By jroach Date 2006-01-26 Time 15:51 Sent To  
Notes
2006-01-26 00:00:001/26/2005 ***FAILED***
  
 1) THE WALL/FENCE AROUND THE POOL AND
 REFLECTING POOL IS NOT CONSISTENT
 AMONGST ALL PLANS.SHEET SP.01 SHOWS 6'
 BLOCK WALL.SECTION E ON SP.04 SHOWS 6'
 BLOCK WALL.LEGEND ON SP.02 AND SP.03
 INDICATE 5' ALUMINUM FENCE.NOTES ON
 SP.03 INDICATE 5' ALUMINUM FENCE AND 6'
 BLOCK WALL.PROVIDE MORE DETAILS ON
 PLANS AND MAKE THEM CONSISTENT.
  
 2)THE POOL EQUIPMENT IS NOT SHOWN ON
 THE LANDSCAPE PLANS.MAKE SURE ALL
 MECHANICAL EQUIPMENT IS SHOWN AND IS
 PROPERLY SCREENED.
  
 3) SIGNS SHALL BE REVIEWED UNDER A
 SEPARATE PERMIT.REMOVE FROM THE PLANS
 OR NOTE THAT IT WILL BE PERMITTED BY
 OTHERS.
  
 4) PER THE CONDITION OF SITE PLAN
 APPROVAL, THE LANDSCAPE BUFFER SHALL BE
 PROVIDED BETWEEN THE SIDEWALK AND THE
 WEST WALL/FENCE SURROUNDING THE
 REFLECTING POOL.
  
 5) LETTER OF APPROVAL FROM THE MASTER
 DEVELOPER INDICATING APPROVAL OF THE
 SITE PLAN, LANDSCAPE PLAN, ELEVATIONS,
 COLORS, MATERIALS, SIGNS, ETC. SHALL BE
 PROVIDED.
  
 6) PLEASE IDENTIFY AND CLARIFY THE 7'4
 3/4" TOWER THAT IS SHOWN ON THE SOUTH
 END OF THE PAVILLION.
  
 7) PLEASE EXPLORE ALTERNATIVES TO SHIELD
 THE KITCHEN EXHAUST ON TOP OF THE
 PAVILLION.
  
 8) THE LANDSCAPE PLANS DO NOT SHOW THE
 WALLS/FENCES AROUND THE POOL AND
 REFLECTING POOL.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT JOHN
 ROACH, PLANNER AT (561) 822-1435.
  
 COMMENTS FROM ALAN BARATTA, LANDSCAPE
 PLANNER...
  
 1) CHANGE THE EAST PALATKA HOLLY TO
 DAHOON HOLLY.
  
 2) THE TREE PLANTING DIAGRAM NEEDS TO
 SHOW A PLANTING HOLE 3 TIMES THE SIZE AS
 INDICATED IN THE VERBAGE.
  
 3) ADD A STATEMENT THAT THE TRUNK FLARE
 OR TOP ROOT WILL BE VISIBLE ON THE
 SURFACE.
  
 4) ADD TO THE CONTAINER SPECS THAT
 CONTAINER-GROWN TREES WILL BE CHECK FOR
 CIRCLING ROOTS PRIOR TO PLANTING.IF
 FOUND, THE MATERIAL MUST BE REJECTED OR
 IF THE ROOTS ARE LESS THAN 1/3 THE TRUNK
 DIAMETER, THEY CAN BE CUT IN AN AREA
 WHERE THEY ARE GROWING RADIALLY TO THE
 TRUNK.
  
 5) ADD A COMMENT THAT ALL TREES SHALL
 HAVE THE BURLAP FOLDED BACK TO THE
 BOTTOM 1/3 OF THE ROOT BALL.
  
 6) METAL BASKETS SHALL BE REMOVED FROM
 THE TOP 1/2 OF THE ROOT BALL.
  
 QUESTIONS/COMMENTS, CONTACT ALAN
 BARATTA, LANDSCAPE PLANNER AT (561)
 822-1435.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved