Plan Review Details - Permit 05110258
Plan Review Stops For Permit 05110258
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2005-11-17 Cont ID  
Sent By jleech Date 2005-11-17 Time 09:27 Rev Time 0.00
Received By jleech Date 2005-11-17 Time 09:27 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2005-11-10 Cont ID  
Sent By mperson Date 2005-11-10 Time 14:20 Rev Time 2.00
Received By mperson Date 2005-11-10 Time 14:19 Sent To  
Notes
2005-11-10 00:00:00DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR GAS PERMIT:
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 2. TYPE OF GAS, (LP OR NATURAL)
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4)
 4. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 5. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 6. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 REVIEW BY
 MIKE PERSON
 (561) 805-6730
 (561) 653-2692 (FAX)
 E-MAIL [email protected]
  
 UNDER SUPERVISION OF KSTEVENS

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-11-16 Cont ID  
Sent By adarroug Date 2005-11-16 Time 14:24 Rev Time 0.00
Received By adarroug Date 2005-11-16 Time 14:24 Sent To P
Notes
2005-11-16 00:00:00TO "MPERSON" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-11-10 Cont ID  
Sent By adarroug Date 2005-11-10 Time 08:24 Rev Time 0.00
Received By adarroug Date 2005-11-10 Time 08:24 Sent To P
Notes
2005-11-10 00:00:00TO "MPERSON" DESK


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved