Plan Review Details - Permit 05110247
Plan Review Stops For Permit 05110247
Review Stop AD ADDRESSING
Rev No 1 Status N Date 2006-04-15 Cont ID  
Sent By rbrown Date 2006-04-15 Time 11:55 Rev Time 0.00
Received By rbrown Date 2006-04-15 Time 11:55 Sent To  
Notes
2006-04-15 00:00:00ADDRESS CORRECTED TO 350 S. AUSTRALIAN
 AVE.CREATED AS AN EXTENSION TO THE
 PCN.
  
2006-01-25 00:00:00NEEDS , AS PLANS AND APPLICATION FOR
 PHASE II IS SHOWN AS 350 S AUSTRALIAN,
 HOWEVER, SYSTEM INDICATES 300. EXTENSION
 NEEDED FOR SAME PCN?

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-12-17 Cont ID  
Sent By rbrown Date 2006-12-17 Time 18:32 Rev Time 0.00
Received By rbrown Date 2006-12-17 Time 15:21 Sent To  
Notes
2006-12-17 15:28:55BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 4/22/06:
  
 1) WORKING DRAWING REVIEW ONLY.NO PERMIT CAN BE
 ISSUED UNTIL THE PERMIT APPLICATION AND FEES ARE
 SUBMITTED.
  
 2) INFORMATIVE:
 A NOTICE OF COMMENCEMENT SHALL BE RECORDED, COUNTY
 IMPACT FEES PAID AND A SIGNED THRESHOLD INSPECTION
 AGREEMENT SUBMITTED BEFORE A PERMIT CAN BE ISSUED.
  
 3) FBC 13-103.1.2THIS COMMENT HAS NOT BEEN PROPERLY
 ADDRESSED.IT IS NOTED THAT THE NAME AND LICENSE
 NUMBER OF EACH DESIGN PROFESSIONAL HAS BEEN ADDED TO
 THE ENERGY CODE COMPLIANCE FORM, BUT THE SIGNATURES AND
 DATES REQUIRED TO CERTIFY CODE COMPLIANCE HAVE NOT BEEN
 INCLUDED.BEFORE A BUILDING PERMIT CAN BE ISSUED, THE
 'CERTIFICATION' BOX ON SHEET 2 OF THE SUBMITTED ENERGY
 CODE COMPLIANCE FORMS SHALL BE SIGNED AND DATED BY THE
 'PREPARER' AND THE BUILDING OWNER, THE OWNER'S
 ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNATED
 BY THE OWNER. ALSO, SHEET 1 SHOULD BE COMPLETED WITH
 THE PERMIT NUMBER (05110247).
  
 19) FBC 1606.1TRANSFORMER VAULT DOOR 117A.SUBMITTAL
 OF PRODUCT APPROVAL NOA# 02-0222.06 (FL2198.3) FOR A
 6070 DOUBLE DOOR IS NOTED BUT SHEETS 1 AND 2 OF 11 BOTH
 STATE MAXIMUM POSITIVE AND NEGATIVE DESIGN PRESSURES OF
 +60 PSF AND -60 PSF FOR THE PROPOSED DOOR.THE
 PRESSURES REQUIRED BY THE SUBMITTED RWDI WIND LOAD
 STUDY REPORT FOR THE SOUTH ELEVATION OF THE PHASE II
 BUILDING ARE +65 PSF AND -65 PSF.SUBMIT AN
 ALTERNATIVE PRODUCT APPROVAL.
  
 21) FBC 1606.1HORIZONTAL SLIDER WINDOW W2, W4, W6,
 W6.1.THE RESPONSE IS NOTED AS STATING THAT A CUT DOWN
 EFCO CORP. SERIES 3014 SLIDING GLASS DOOR WILL BE USED
 FOR W2 AND W6 WHERE THE REQUIRED DESIGN PRESSURE IS 95
 PSF, AND AN EFCO CORP. SERIES 3500 HORIZONTAL SLIDING
 WINDOW WILL BE USED FOR W2, W4, W6, W6.1 WHERE THE
 REQUIRED DESIGN PRESSURE IS LESS THAN 95 PSF.NO
 PRODUCT APPROVAL WAS SUBMITTED FOR EFCO CORP. SERIES
 3014 SLIDING GLASS DOOR AND ONLY ONE COPY OF THE
 PRODUCT APPROVAL (ONE COPY ATTACHED TO THE COMMENT
 RESPONSE LETTER) FOR EFCO CORP. SERIES 3500 HORIZONTAL
 SLIDING WINDOW WERE SUBMITTED.SUBMIT THREE COPIES OF
 THE PRODUCT APPROVALS INCLUDING THE FLORIDA STATEWIDE
 PRODUCT APPROVAL COVER SHEET (FL####).FOR EASE OF
 REFERENCE A COPY OF THE FLORIDA STATEWIDE PRODUCT
 APPROVAL COVER SHEET FOR EFCO CORP. SERIES 3500
 HORIZONTAL SLIDING WINDOW HAS BEEN INSERTED INTO THE
 COMMENT RESPONSE LETTER ATTACHMENT PACKET FOR YOUR
 USE.
  
 22) INFORMATIVE:
 FBC 1606.1PRODUCT APPROVAL SUBMITTAL. ALL THREE
 COPIES OF THE SUBMITTED DOCUMENT BINDERS INCLUDE SOME
 INCOMPLETE PRODUCT APPROVAL DOCUMENTS.PLEASE REVIEW
 THE BINDERS TO ENSURE THAT A PRODUCT APPROVAL HAS BEEN
 SUBMITTED FOR EACH TYPE OF PRODUCT THAT IS TO BE
 INSTALLED.PLAN REVIEW WILL ONLY ENSURE THAT THE
 BINDERS INCLUDE PRODUCT APPROVALS TO COVER THE WORST
 CASE.FOR, EXAMPLE IF ONLY A LARGE MISSILE IMPACT
 PRODUCT APPROVAL IS SUBMITTED, THAT WOULD MEET PLAN
 REVIEW REQUIREMENTS BUT IT WOULD MEAN THAT PRODUCT
 WOULD HAVE TO BE USED EVEN WHERE LARGE MISSILE IMPACT
 RATING IS NOT REQUIRED.REMOVE, FROM EACH BINDER, ALL
 PRODUCT APPROVAL DOCUMENTS WHICH ARE NO LONGER
 APPLICABLE DUE TO THE SUBSTITUTIONS MADE.ALSO, WHERE
 MULTIPLE OPTIONS ARE COVERED BY A PRODUCT APPROVAL, THE
 APPROPRIATE PAGES OF THE PRODUCT APPROVAL SHALL BE
 MARKED TO SHOW WHICH PRODUCT OPTIONS/SIZES ARE PROPOSED
 SO THAT THE APPLICABLE DESIGN PRESSURE RATING CAN BE
 DETERMINED.
  
 23) -PROVISO-
 WINDOW WALLS: THE WINDOW SHOP DRAWING SUBMITTAL SHALL
 INCLUDE A STRUCTURAL MULLION.THE MULLION MUST BE
 CAPABLE OF SPANNING HORIZONTALLY ACROSS THE ENTIRE
 WIDTH OF THE OPENING FOR THOSE WINDOWS THAT EXCEED THE
 MAXIMUM HEIGHT STATED IN THE SUBMITTED MIAMI WALL
 SYSTEMS INC. FIXED WINDOW LARGE MISSILE IMPACT SERIES
 101 AND SMALL MISSILE IMPACT SERIES 101
 PRODUCT APPROVAL NOA'S 03-0415.18 AND 05-0420.01.
  
 24) -PROVISO-
 SLIDING GLASS DOORS:THE WINDOW/DOOR SUBCONTRACTOR
 SHALL PROVIDE RATIONAL ANALYSIS FROM A FLORIDA
 REGISTERED ENGINEER TO JUSTIFY THE USE OF THE PROPOSED
 SLIDING GLASS DOOR IN SIZES THAT EXCEED THE MAXIMUM IN
 THE SUBMITTED EFCO CORP. SERIES S-3005 SLIDING GLASS
 DOOR PRODUCT APPROVAL NOA 02-0722.02, AND MIAMI WALL
 SYSTEMS INC. SERIES 100 SLIDING GLASS DOOR PRODUCT
 APPROVAL NOA'S 04-0908.02 AND 01-1108.03.
 NOTE: MISSILE IMPACT RATING FOR THESE LARGER SIZES
 CANNOT BE JUSTIFIED BY RATIONAL ANALYSIS.MISSILE
 IMPACT TEST RESULTS MUST BE SUBMITTED.
  
 25) -PROVISO-
 HORIZONTAL SLIDER WINDOWS: IT IS NOTED THAT 'CUT-DOWN'
 SLIDING GLASS DOORS WILL BE USED FOR THOSE HORIZONTAL
 SLIDER WINDOWS WHICH EXCEED 6'-6" WIDE X 6'-0" HIGH
 (FOR EXAMPLE W2, W2.1, W3, W3.1, W3.2(SLIDER?), W3.P,
 W4, W4.1, W5, W5.1, W5.P, W6, W6.1).
  
 26) -PROVISO-
 FIXED WINDOWS:THE WINDOW SHOP DRAWING SUBMITTAL SHALL
 INCLUDE A STRUCTURAL MULLION.THE MULLION MUST BE
 CAPABLE OF SPANNING HORIZONTALLY ACROSS THE ENTIRE
 WIDTH OF THE OPENING FOR THOSE WINDOWS THAT EXCEED THE
 6'-0" MAXIMUM HEIGHT STATED IN THE SUBMITTED MIAMI WALL
 SYSTEMS INC. SERIES 122 ALUMINUM FIXED WINDOW PRODUCT
 APPROVAL NOA 04-0322.09.
  
 28) STOREFRONT WINDOWS.PLEASE NOTE THAT THE SUBMITTED
 EFCO CORP. SERIES 5600 ALUMINUM CURTAIN WALL PRODUCT
 APPROVAL NOA# 02-0304.01 (FL 1561.1) IS RATED FOR SMALL
 MISSILE IMPACT ONLY.IT CAN ONLY BE USED IN LOCATIONS
 HIGHER THAN 30 FEET ABOVE GRADE.PLEASE NOTE THAT
 SHEET A6-61 REFERS TO THE FIRST FLOOR STOREFRONT AS SF1
 AND THE ROOF (LANTERN) STOREFRONT AS SF2 WHICH IS
 CONSISTENT WITH THE BUILDING ELEVATIONS.THE
 EXCEPTIONS ARE SHEETS A4-06 AND A4-11 SHOULD BE REVISED
 AS THEY REFER TO THE ROOF LANTERN STOREFRONT AS SF1.
  
 29) TO EXPEDITE REVIEW OF A RESUBMITTAL WHICH REQUIRES
 NEW PLANS IN ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW SHEETS
 INSERTED.ONE COPY OF EACH OLD SHEET SHOULD BE
 STAPLED/CLIPPED TO THE REMAINING OLD SHEETS, TO FORM A
 SET OF 'OLD/VOID SHEETS', FOR COMPARISON OF REVISIONS
 WHEN REVIEWING THE RESUBMITTED PLANS.
  
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE:
 (561) 805 6652ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-04-22 Cont ID  
Sent By rbrown Date 2006-04-22 Time 14:46 Rev Time 0.00
Received By rbrown Date 2006-04-15 Time 13:25 Sent To  
Notes
2006-04-15 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) WORKING DRAWING REVIEW ONLY.NO
 PERMIT CAN BE ISSUED UNTIL THE PERMIT
 APPLICATION AND FEES ARE SUBMITTED.
  
 2) INFORMATIVE:
 A NOTICE OF COMMENCEMENT SHALL BE
 RECORDED, COUNTY IMPACT FEES PAID AND A
 SIGNED THRESHOLD INSPECTION AGREEMENT
 SUBMITTED BEFORE A PERMIT CAN BE ISSUED.
  
 3) FBC 13-103.1.1.1ONLY THE
 MECHANICAL SYSTEM DESIGNER'S NAME AND
 LICENSE NUMBER ARE CURRENTLY INCLUDED ON
 SHEET 2 OF THE ENERGY CODE COMPLIANCE
 FORM.ALL OF THE PROFESSIONALS
 RESPONSIBLE FOR THE DESIGN OF THE
 BUILDING SHELL AND THE ELECTRICAL,
 LIGHTING, MECHANICAL AND PLUMBING
 SYSTEMS SHALL EACH SIGN THE ENERGY CODE
 COMPLIANCE FORM, IN THE SPACE PROVIDED,
 TO CERTIFY COMPLIANCE.
 ALSO, SHEET 1 SHOULD BE COMPLETED WITH
 THE CORRECT PROJECT ADDRESS (350 S
 AUSTRALIAN AVE), ZIP CODE (33401) AND
 PERMIT NUMBER (05110247).
  
 4) 471.023 F.S.STRUCTURAL PLANS.ADD
 THE CERTIFICATE OF AUTHORIZATION NUMBER
 (EB 25930) FOR ECHELON ENGINEERING, LLC
 TO EACH SHEET.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ENGINEER
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING
 ENGINEERING SERVICES, SHALL INCLUDE THE
 CERTIFICATE OF AUTHORIZATION NUMBER. ADD
 THE NUMBER TO EACH SHEET.THIS MAY BE
 ADDED BY HAND.
  
 5) FBC* 104.2.1SHEET CD-02, 2ND - 5TH
 FLOORS, EXITING PLAN.THERE ARE TWO
 DOOR WIDTH NOTES BELOW THE PLAN WHICH
 POINT TO EXITING VIA THE BALCONY OF UNIT
 E2 AT THE NORTH-WEST CORNER OF THE
 BUILDING.THE NOTES ARE NOT APPLICABLE
 TO THE 2ND - 5TH CONFIGURATION.REMOVE
 THE NOTES.
  
 6) FBC* 104.2.1SHEET A1-01, GROUND
 FLOOR PLAN.THE LOCATION OF THE
 ENTRANCE DOOR TO UNIT F1 IS NOT SHOWN
  
 7) FBC* 704.1SHEETS A1-01 AND A1.01B,
 GROUND FLOOR PLAN.THERE IS NO LINE
 TYPE SHOWN ON THE PARTITION LEGEND TO
 SHOW THE FIRE RESISTANCE RATING OF THE
 TRANSFORMER VAULT.
  
 8) FBC* 704.1SHEET A1-01A, GROUND
 FLOOR PLAN.THERE IS NO LINE TYPE
 DIFFERENCE ON THE PLAN OR THE PARTITION
 LEGEND TO DIFFERENTIATE BETWEEN 1 HOUR
 AND 2 HOUR RATED WALLS.
  
 9) RECOMMENDATION:SHEETS A1-01 TO
 A1-17, FLOOR PLANS. FOR CLARITY AT THE
 FIRE RATED WALL LOCATIONS, PLEASE
 CONSIDER CONTINUING THE RELEVANT LINE
 TYPE (SEE PARTITION LEGEND) THROUGH ANY
 ASSOCIATED CONCRETE WALL, COLUMN,
 SHEARWALL ETC SHOWN ON THE PLANS. ALSO,
 THE LINE TYPE FOR THE EXPANSION JOINT,
 ACROSS THE PARKING DECK, ON SHEETS A1-02
 AND A1-04 SHOULD BE CHANGED FOR CLARITY.
  
 10) FBC* 104.2.1SHEET A1-02, 2ND, 3RD,
 5TH FLOOR PLAN.THERE APPEARS TO BE A
 SECTION OF WALL MISSING ALONG GRID A AT
 GRID 25.
  
 11) FBC* 104.2.1FLOOR PLANS.THERE
 APPEARS TO BE NO SPOT LEVELS SHOWN ON
 THE PLANS.IN PARTICULAR, ADD SPOT
 LEVELS TO SHEETS A1-06, A1-17 AND A1-18
 WHICH ARE THE 6TH FLOOR, MAIN ROOF AND
 UPPER ROOF PLANS, RESPECTIVELY.
  
 12) FBC 1608.2.2SHEETS A4-10, A6-20
 AND A7-20.THE GUARDRAIL SHALL BE
 DESIGNED AND CONSTRUCTED FOR A
 CONCENTRATED LOAD OF 200 LB APPLIED IN
 ANY DIRECTION AT THE TOP OF THE
 GUARDRAIL, A CONCENTRATED HORIZONTAL
 LOAD OF 200 LB APPLIED ON A 1 SQ FT AREA
 AT ANY POINT, AND A LINE LOAD OF 50 PLF
 APPLIED HORIZONTALLY AT THE REQUIRED
 GUARDRAIL HEIGHT WITH A SIMULTANEOUS
 LINE LOAD OF 100 PLF APPLIED VERTICALLY
 DOWNWARD ON THE TOP OF THE GUARDRAIL.
 THESE LOADS SHALL NOT BE APPLIED
 SIMULTANEOUSLY (UNLESS NOTED ABOVE) BUT
 SHALL BE APPLIED INDIVIDUALLY TO PRODUCE
 MAXIMUM STRESS IN EACH OF THE COMPONENTS
 OR SUPPORTS.ANNOTATE THE PLANS TO
 ENSURE THIS REQUIREMENT IS MET.
  
 13) FBC 1606.1SHEET A6-20, DETAIL 9.
 THE ATTACHMENT OF THE STUCCO CORNICE
 FRAMING SHALL BE SPECIFIED ON THE DETAIL
 OR A NOTE ADDED TO STATE THAT THE
 FRAMING AND ATTACHMENT DETAILS WILL BE
 SUBMITTED ON SPECIALIST SHOP DRAWINGS
 AFTER FIRST BEING REVIEWED BY THE
 DESIGNER OF RECORD.ANNOTATE THE DETAIL
  
 14) FBC 1015.2SHEET A6-20, DETAIL 11.
 THE EFFECTIVE HEIGHT OF THE GUARDRAIL IS
 REDUCED BY THE PRESENCE OF THE CONCRETE
 UPTURNED BEAM WHICH FORMS A LEDGE ON THE
 INSIDE FACE OF THE GUARDRAIL.TO
 PREVENT BUILDING OCCUPANTS FROM STANDING
 ON THIS LEDGE, EITHER PROVIDE A 45
 DEGREE CHAMFER ON THE INSIDE EDGE OF THE
 CONCRETE UPSTAND OR PROVIDE SOME OTHER
 MEANS TO DISCOURAGE CLIMBING.
  
 15) FBC 1608.2.1SHEET A7-20,THE
 HANDRAIL SHALL BE DESIGNED AND
 CONSTRUCTED FOR A CONCENTRATED LOAD OF
 200 LB AND A LINE LOAD OF 50 PLF.THESE
 LOADS SHALL NOT BE APPLIED
 SIMULTANEOUSLY BUT SHALL BE APPLIED
 INDIVIDUALLY AT ANY POINT, AND IN ANY
 DIRECTION, TO PRODUCE MAXIMUM STRESS IN
 EACH OF THE COMPONENTS OR SUPPORTS.
 AMEND/ANNOTATE THE PLANS TO ENSURE THIS
 REQUIREMENT IS MET.
  
 16) FBC 1601.1SHEET L7-04, PAVILION.
 ADD A PAVILION FOOTING DETAIL.
  
 17) FBC 1606.1PRODUCT APPROVALS
 GENERALLY.MANY OF THE SUBMITTED
 PRODUCT APPROVALS INCLUDE MORE THAN ONE
 OPTION WITH DIFFERENT DESIGN PRESSURE
 RATINGS (WIND PRESSURE IN PSF).MARK
 THE PRODUCT APPROVAL TO SHOW WHICH
 OPTION (DESIGN PRESSURE RATING) IS
 APPLICABLE.PLEASE DO NOT USE
 HIGHLIGHTER PEN BECAUSE IT DOES NOT SHOW
 UP WHEN THE DOCUMENTS ARE SCANNED FOR
 ARCHIVING AT THE END OF THE PROJECT.
  
 18) FBC 1504.1ROOF COVERING. SUBMITTAL
 OF MANUFACTURER'S PRODUCT DATA IS NOTED
 BUT NO OTHER DOCUMENTATION WAS INCLUDED.
 SUBMIT PRODUCT APPROVAL(S) FOR THE
 PROPOSED ROOF SYSTEM(S).
  
 19) FBC 1606.1TRANSFORMER VAULT DOOR
 117A.THE DOOR SCHEDULE, SHEET A8-10,
 SPECIFIES A PAIR OF 3070 HOLLOW METAL
 DOORS.NO PRODUCT APPROVAL WAS
 SUBMITTED FOR A PAIR OF 3070 HOLLOW
 METAL DOORS.THE SUBMITTED CURRIES
 COMPANY COMMERCISL STEEL DOOR PRODUCT
 APPROVAL IS FOR A SINGLE 3070 DOOR.
  
 20) FBC 1606.1SLIDING GLASS DOOR S1.
 ACCORDING TO THE SUBMITTED RWDI WIND
 LOAD STUDY REPORT, THERE ARE LOCATIONS
 ON THE NORTH AND SOUTH ELEVATION WHERE
 THIS DOOR WILL BE SUBJECT TO NEGATIVE
 WIND PRESSURE OF -115 PSF.DRAWING
 SHEET 1 OF THE SUBMITTED MIAMI WALL
 SYSTEMS INC SERIES 100 ALUMINUM SLIDING
 GLASS DOOR PRODUCT APPROVAL NOA#
 04-0908.02, STATES THAT THE MAXIMUM
 DESIGN PRESSURE RATING FOR THE WINDOW IS
 100 PSF.PROVIDE RATIONAL ANALYSIS TO
 JUSTIFY THIS OR PROVIDE AN ALTERNATIVE
 PRODUCT APPROVAL.
  
 21) FBC 1606.1HORIZONTAL SLIDER WINDOW
 W2, W4, W6, W6.1.ACCORDING TO THE
 SUBMITTED RWDI WIND LOAD STUDY REPORT,
 THERE ARE LOCATIONS WHERE THESE WINDOWS
 WILL BE SUBJECT TO A POSITIVE AND/OR
 NEGATIVE WIND PRESSURE OF 95 PSF.
 DRAWING SHEET 1 OF THE SUBMITTED MIAMI
 WALL SYSTEMS INC SERIES 106 ALUMINUM
 HORIZONTAL SLIDER WINDOW PRODUCT
 APPROVAL NOA# 04-1122.02, STATES THAT
 THE MAXIMUM DESIGN PRESSURE RATING FOR
 THE WINDOW IS 90 PSF.PROVIDE RATIONAL
 ANALYSIS TO JUSTIFY THIS OR PROVIDE AN
 ALTERNATIVE PRODUCT APPROVAL.
  
 22) INFORMATIVE:
 FBC 1606.1PRODUCT APPROVAL SUBMITTAL.
 ALL THREE COPIES OF THE SUBMITTED
 DOCUMENT BINDERS INCLUDE SOME INCOMPLETE
 PRODUCT APPROVAL DOCUMENTS.PLEASE
 REVIEW THE BINDERS TO ENSURE THAT A
 PRODUCT APPROVAL HAS BEEN SUBMITTED FOR
 EACH TYPE OF PRODUCT THAT IS TO BE
 INSTALLED.PLAN REVIEW WILL ONLY ENSURE
 THAT THE BINDERS INCLUDE PRODUCT
 APPROVALS TO COVER THE WORST CASE.FOR,
 EXAMPLE IF ONLY A LARGE MISSILE IMPACT
 PRODUCT APPROVAL IS SUBMITTED, THAT
 WOULD MEET PLAN REVIEW REQUIREMENTS BUT
 IT WOULD MEAN THAT PRODUCT WOULD HAVE TO
 BE USED EVEN WHERE LARGE MISSILE IMPACT
 RATING IS NOT REQUIRED.
  
 23) -PROVISO-
 WINDOW WALLS: THE WINDOW SHOP DRAWING
 SUBMITTAL SHALL INCLUDE A STRUCTURAL
 MULLION.THE MULLION MUST BE CAPABLE OF
 SPANNING HORIZONTALLY ACROSS THE ENTIRE
 WIDTH OF THE OPENING FOR THOSE WINDOWS
 THAT EXCEED THE MAXIMUM HEIGHT STATED IN
 THE SUBMITTED MIAMI WALL SYSTEMS INC.
 FIXED WINDOW LARGE MISSILE IMPACT SERIES
 101 AND SMALL MISSILE IMPACT SERIES 101
 PRODUCT APPROVAL NOA'S 03-0415.18 AND
 05-0420.01.
  
 24) -PROVISO-
 SLIDING GLASS DOORS:THE WINDOW/DOOR
 SUBCONTRACTOR SHALL PROVIDE RATIONAL
 ANALYSIS FROM A FLORIDA REGISTERED
 ENGINEER TO JUSTIFY THE USE OF THE
 PROPOSED SLIDING GLASS DOOR IN SIZES
 THAT EXCEED THE MAXIMUM IN THE SUBMITTED
 MIAMI WALL SYSTEMS INC. SERIES 100
 SLIDING GLASS DOOR PRODUCT APPROVAL
 NOA'S 04-0908.02 AND 01-1108.03.
 NOTE: MISSILE IMPACT RATING FOR THESE
 LARGER SIZES CANNOT BE JUSTIFIED BY
 RATIONAL ANALYSIS.MISSILE IMPACT TEST
 RESULTS MUST BE SUBMITTED.
  
 25) -PROVISO-
 HORIZONTAL SLIDER WINDOWS: IT IS NOTED
 THAT 'CUT-DOWN' SLIDING GLASS DOORS WILL
 BE USED FOR THOSE HORIZONTAL SLIDER
 WINDOWS WHICH EXCEED 6'-6" WIDE X 6'-0"
 HIGH (FOR EXAMPLE W2, W2.1, W3, W3.1,
 W3.2(SLIDER?), W3.P, W4, W4.1, W5, W5.1,
 W5.P, W6, W6.1).
  
 26) -PROVISO-
 FIXED WINDOWS:THE WINDOW SHOP DRAWING
 SUBMITTAL SHALL INCLUDE A STRUCTURAL
 MULLION.THE MULLION MUST BE CAPABLE OF
 SPANNING HORIZONTALLY ACROSS THE ENTIRE
 WIDTH OF THE OPENING FOR THOSE WINDOWS
 THAT EXCEED THE 6'-0" MAXIMUM HEIGHT
 STATED IN THE SUBMITTED MIAMI WALL
 SYSTEMS INC. SERIES 122 ALUMINUM FIXED
 WINDOW PRODUCT APPROVAL NOA 04-0322.09.
  
 27) TO EXPEDITE REVIEW OF A RESUBMITTAL
 WHICH REQUIRES NEW PLANS IN ORDER TO
 ADDRESS THE ABOVE COMMENTS, THE OLD
 SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHOULD BE STAPLED/CLIPPED TO THE
 REMAINING OLD SHEETS, TO FORM A SET OF
 'OLD/VOID SHEETS', FOR COMPARISON OF
 REVISIONS WHEN REVIEWING THE RESUBMITTED
 PLANS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6652ROBERT BROWN
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-11-05 Cont ID  
Sent By dpalmer Date 2006-11-05 Time 16:34 Rev Time 0.00
Received By dpalmer Date 2006-08-20 Time 14:24 Sent To  
Notes
2006-11-05 16:34:06**** THE EDGE PHASE II ** 17 STORY **
  
 ********** UNSAT 2ND REVIEW ***************
  
 ** PLEASE KNOW PLANS ARE NOT COMPLETE AT THIS TIME FOR
 CODE COMPLIANCE.
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH NEW COMMENTS BASED ON
 PLANS SUBMITTED.
 ** PLEASE SEE NOTE BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH NEW NOTES ADDED TO THE BOTTOM OF
 THE REVIEW.
  
  
 1) NOTE: OK.
  
 2) NOTE:NO, PLEASE SEE TITLE BLOCKS FOR
 MECHANICAL/PLUMBING COMPANY DOES NOT CONTAIN THE
 CORRECT LICENSURE INFORMATION AS REQUIRED. PLEASE ALSO
 KNOW IT IS KNOWN TO THIS OFFICE THAT CEASE AND DESIST
 LETTERS WERE SENT TO THE COMPANY AND ENGINEERS AS SHOWN
 ON RECORD. PLEASE SEE NEW PLANS WERE SUBMITTED EVEN
 AFTER THIS WAS ISSUED BY THE STATE FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS. PLEASE KNOW THAT ONE COMPLETE
 SET OF PLANS WILL BE FORWARDED TO THE BOARD AS
 REQUESTED BY THE STATE ONCE ALL REVIEWS ARE COMPLETED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING LICENSE INFORMATION REQUIRED ON
 TITLE BLOCKS FOR CONSULTING ENGINEERING FIRM AS
 REQUIRED UNDER FLORIDA STATUES 471.023, FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002.
 PLEASE SEE COMPANIES AS LISTED ARE PROVIDING
 ENGINEERING SERVICES" AND NO
 CERTIFICATE OF AUTHORIZATION NUMBER COULD BE LOCATED ON
 STATE WEBSITE OF DEPARTMENT OF BUSINESS AND
 PROFESSIONAL REGULATION. (DBPR).
 PLEASE KNOW AS REQUIRED BY THE SAID FLORIDA STATUES AND
 LICENSING UNDER FS
 468 FOR THIS OFFICE, ONE SET OF MEP PLANS ARE BEING
 RETAINED AND SHALL BE FORWARDED TO THE FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS FOR REVIEW OF SAID REQUIREMENTS.
 WE HAVE CONSULTED WITH THE FBPE'S ON THE ABOVE. PLEASE
 CONTACT MR. JERRY ONGLEY AND MR. DOUGLAS SUNSHINE IF
 THERE ARE ANY QUESTIONS.
 ** PLEASE KNOW, THESE REQUIREMENTS ARE ALSO FOR THE
 OTHER CONSULTING COMPANIES AS LISTED ON SAID TITLE
 BLOCKS.
  
 3) NOTE:NO, PLEASE SUBMIT ALL AS PREVIOUS REQUESTED.
 PLEASE SEE REVIEW OF CODE COMPLAINT ITEMS CAN NOT BE
 VERIFIED AS THERE HAVE BEEN CHANGES SINCE PHASE ONE
 PLANS PER RESPONSE AND REVIEW OF THESE DO NOT
 CORRELATE.110.3, 90.7, NFPA-20 ETC.
 FBC ADMIN SECTION 104.2.1
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE SPECS SUBMITTED FOR FIRE PUMP CONTAIN THE
 TITLE AND THE RESPONSIBLE ENGINEER AS STEVEN FELLER OF
 FELLER ENGINEERING. STEVEN FELLER AND FELLER
 ENGINEERING ARE THE CONSULTING ENGINEERS OF PHASE-ONE.
 PLEASE CORRECT ALL SUBMITTALS FOR FIRE PUMP, FIRE PUMP
 CONTROLLER ETC.
  
 4) NOTE: NO, RESPONSE MENTIONS THIS PROJECT IS UNDER
 THE 2001 FBC WHICH WAS NOT THE REQUEST. PLEASE LIST THE
 FOLLOWING CODES ON PLANS RELEVANT TO DESIGN AS THE
 FOLLOWING CODES ARE IN EFFECT FOR THIS PROJECT UNDER
 THE 2001 FBC.
  
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE BE SURE PLANS REFERENCE ALL CURRENT CODE IN
 EFFECT FOR THIS PROJECT. PLEASE KNOW WE ARE CURRENTLY
 UNDER THE 2003 NFPA-101, 2002 NFPA-72 AND 2002 NFPA-70
 ETC.
  
 5) NOTE:NO, PLEASE SEE NOW DOORS ARE EVEN MISSING
 FROM ELECTRICAL FLOOR PLANS? PLEASE KNOW THE ENTRANCE
 LOCATION FOR ACCESS IS ALSO A MAIN CONCERN. RESPONSE
 SPEAKS OF EGRESS WHICH IS ALSO IMPORTANT, HOWEVER
 OBTAINING ACCESS TO THE MAIN ELECTRICAL ROOM IS MOST
 IMPORTANT IF THE FIRE DEPT PERSONNEL IS IN NEED OF
 SHUTTING DOWN POWER.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE KNOW, ENTRANCE TO MAIN ELECTRICAL ROOM SHALL BE
 DETERMINED BY THIS OFFICE AND FIRE MARSHAL'S OFFICE FOR
 ACCESSIBILITY. PLANS INDICATE ACCESS GRANTED THROUGH
 GARAGE AREA AND TRAVEL DISTANCE IN BLDG MAY REQUIRED A
 MORE ACCESSIBLE MEANS TO MAIN ELECTRICAL ROOM.
 ** PLEASE SEE POSSIBLE FIRE REVIEW COMMENTS.
  
 6) NOTE: NO, PLEASE SEE NOTE ABOVE AS DOORS ARE NOT
 SHOWN ON LAYER AS PRINTED FOR FIRST FLR.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 110.26 FOR MIN DOOR(S) REQUIRED FOR MAIN
 ELECTRICAL ROOM. PLEASE SEE ONE MAIN/EQUIPMENT LOCATED
 DIRECTLY IN-FRONT OF THE EGRESS PATH/DOOR. PLEASE SEE
 PANIC HARDWARE SHALL BE REQUIRED AND DOORS MUST OPEN IN
 THE DIRECTION OF TRAVEL. PLEASE PROVIDE A NOTE ON PLANS
 FOR THIS.
 A NOTE ON E4.00 STATES "DOOR NEEDS TO BE RELOCATED",
 HOWEVER THIS WAS NOT DONE AND IS SHOWN THE SAME IN
 A-SHEETS AND E-SHEETS.
 PLEASE ADD NOTE(S) TO PLANS FOR ALL CLEARANCES PER
 110.26 SHALL BE MET.
 4.00 ETC
  
 7) NOTE: OK.
  
 8) NOTE: NO, SAME NOTE, A BATTERY BACK UP FIXTURE IN
 STAIRS WILL BE REQUIRED MIN AT EVERY OTHER LANDING.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE NFPA-72 WHICH REQUIRES BATTERY BACK UP
 FIXTURES IN STAIR TOWERS AND OTHER AREAS WHERE EM LTS
 ARE REQUIRED FOR MIN EGRESS PATHS.
 PLEASE SEE 7.9.2.2 WHICH STATES NO SINGLE MEANS OF OVER
 CURRENT PROTECTION OR SWITCHING ETC SHALL LEAVE ANY
 EGRESS PATHS IN TOTAL DARKNESS AS SHOWN ON PLANS.
 PLEASE KNOW AS REQUIRED BY THE AHJ AND THE FIRE
 MARSHAL'S OFFICE A BATTERY BACK-UP FIXTURE OF SOME SORT
 WILL BE REQUIRED FOR THESE EGRESS PATHS TO ALLEVIATE
 THE ABOVE.
  
 9) NOTE: NO/YES, PLEASE PROVIDE THE STAIRS SEPARATELY;
 THE CALCULATIONS SEEM TO FIGURE IN ALL OTHER AREAS. THE
 STAIR MINIMUM LIGHTING LEVELS ARE THE MOST IMPORTANT.
  
 ** PREVIOUS REVIEW NOTE **PLEASE PROVIDE COMPLETE
 PHOTO-METRICS FORALL STAIR-TOWERS AND EGRESS PATHS.
 PLEASE SEE LS 101 7.8.1.3 WHICH REQUIRES A MINIMUM OF
 10FT/CANDLES (108 LUX) FOR STAIR TOWERS UNDER NORMAL
 CONDITIONS AND A MIN OF 1FT/CD UNDER EMERGENCY
 CONDITIONS.
 7.9.2.2
  
 10) NOTE: OK, HOWEVER PLEASE KNOW FIXTURE TYPE FOR
 STAIR TOWERS WILL BE REVISED.
  
 11) NOTE: OK.
  
 12) NOTE: NO, COULD NOT LOCATE IN PACKAGE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT A LETTER FROM THE
 FLORIDA POWER AND LIGHT REPRESENTATIVE ON THE
 ACCEPTANCE OF FPL VAULT AS SHOWN.
  
 13) NOTE:NO, PLEASE SEE THERE ARE STILL SOME COMMON
 AREAS WHICH ARE MISSING CIRCUITING AND SOME MINOR
 CIRCUITS IN UNITS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE COMPLETE PLANS WITH ALL CIRCUITING AND CORRELATE
 WITH SUBMITTED PANEL SCHEDULES. REVIEW FOR CODE
 COMPLIANCE CAN NOT BE DONE AT THIS TIME.
 PLEASE BE SURE TO SEE 210.52B1,210.52D,210.11C3 ETC.
  
 14) NOTE:NO, PLEASE SEE SOME HEAT STRIP UNITS ARE NOT
 INDICATING THIS. PLEASE SEE SOME OF THESE ARE SHOWN
 ABOVE THE NORMAL?
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 424.3B WHICH REQUIRES OCP FOR AHU/HEAT TO BE
 SIZED AT A MIN OF 125%. PLEASE SEE SOME OCP AS
 INDICATED WILL NEED TO BE ADJUSTED.
 ** PLEASE BE SURE TO ADJUST AND CONDUCTOR SIZES AS
 NEEDED. PER 310.16,240.4 ETC
  
 15) NOTE: OK.
  
 16) NOTE: OK, HOWEVER SEE NEW NOTES WITH RESPECT TO
 PANEL SCHEDULES NOW THAT ROOMS AND AREAS ARE SHOWN.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PLACE ALL AREA AND ROOM DESIGNATIONS ON PLANS.
 PLEASE SEE PREVIOUS COMMENTS WITH RESPECT TO COMPLIANCE
 WITH CIRCUITING.
  
 17) NOTE: OK.
  
 18) NOTE: NO,/ OK, PLEASE SEE THE DETECTORS ARE NOW
 SHOWN HOWEVER AS THESE ACT ON A INDIVIDUAL UNIT BASIS,
 PLEASE SEE NFPA-72 DEFINITIONS AS SMOKE DETECTORS DO
 ONLY THAT, DETECT. PLEASE ADJUST NOTES TO READ AS SMOKE
 ALARMS AS THESE ARE DEVICES WHICH ACTUALLY DETECT AND
 SOUND AN ALARM WHICH IS WHAT IS BEING STATED IN THE
 NOTES.
 PLEASE ALSO SEE 11.8.3. AS INSTALLATION ALSO INCLUDES
 ANY DEVICES WITHIN 20FT OF COOKING APPLIANCES WHICH
 REQUIRE A DIFFERENT TYPE OF DEVICE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE NFPA-72 11.8.3.5, 11.5.1.1 FOR SMOKE
 DETECTORS REQUIRED INSIDE AND OUTSIDE ALL SLEEPING
 RMS.
 PLEASE SEE UNIT D1, PLEASE ALSO SEE OTHER UNITS WHERE
 SD'S DO NOT APPEAR TO BE "OUTSIDE" SLEEPING AREAS OR
 CORRIDORS. PLEASE SEE A DOOR SEPARATES BEDRM HALLWAYS
 FROMLIVING/COMMON AREA OF UNIT. THIS SEEMS TO SHOW
 NO SD COVERAGE FOR AREAS OUTSIDE BEDROOMS. PLEASE FIRE
 REVIEW COMMENTS.
 ** PLEASE PLACE NOTE ON PLANS WITH REFERENCE TO THE MIN
 PLACEMENT REQUIREMENTS OF ABOVE NFPA. PLEASE SEE THAT
 SD'S ARE LOCATED A MIN OF 3' FROM BATH, KITCHEN DOORS,
 3' FROM SUPPLY REGISTERS, ETC: WITH EXCEPTIONS AS
 LISTED FOR LOCATIONS WITHIN 20' OF COOKING APPLIANCES.
 ** PLEASE SEE SPECS/LISTING FROM SD MANUFACTURE AS MANY
 REQUIRED SD'S TO BE FURTHER THAN LISTED ABOVE AND MOST
 REQUIRED SD'S TO BE 5' FROM THE RETURN AIR GRILLE.
 ** PLEASE KNOW, ANY CEILING HEIGHT VARIATIONS MAY
 CHANGE LOCATION OF SD'S, AS THEY ARE REQUIRED TO BE
 LOCATED WITHIN 12" OF THE HIGHEST POINT OF A FLAT
 CEILING.
  
 19) NOTE: OK.
  
 20) NOTE: OK, SEEM TO BE OK..
  
 21) NOTE: OK.
  
 22) NOTE: OK, HOWEVER SEE NOTE FOR FIRST FLR AREA IN
 NEW NOTE.
  
 23) NOTE:NO, PLEASE SEE 3RD FLOOR. ALSO SEE OTHER
 NOTES.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CORRELATE ELECTRICAL ROOMS AND RISER DIAGRAM.
 PLEASE SEE E4.0 SHOWS ELECTRICAL RM ON EVERY FLR,
 HOWEVER RISER DOES NOT.
 PLEASE SEE OTHER COMMENTS WITH RESPECT TO ELECTRICAL
 RMS.
 215.5
  
 24) NOTE: OK.
  
 25) NOTE: NO, PLEASE SEE ONE STILL SHOWN AS 2500A'S AND
 THE OTHER 3200A'S.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CORRELATE MAIN ELECTRICAL ROOM EQUIPMENT WITH
 RISER DIAGRAM. PLEASE SEE ONE SHOWS 3000A MAIN, THE
 OTHER 4000A, PLEASE SEE ELECTRICAL PANELS SHOWN ON 4.00
 ALSO DO NOT CORRELATE WITH RISER.
 PLEASE SEE MANY OF THESE ITEMS/LOCATIONS WERE REDLINED
 ON ONE SET.
  
 26) NOTE: NO, SEE 3RD FLR.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE METER CENTERS ON ELECTRICAL ROOMS SHOWN ON
 E4.00 DO NOT CORRESPOND TO THE METER CENTERS ON 5.02
  
 27) NOTE: OK.
  
 28) NOTE: OK.
  
 29) NOTE:NO, PLEASE SEE LETTER RESPONSE MENTIONS THIS
 IS IN PHASE ONE PLANS, HOWEVER THIS BUILDING OF PHASE
 II IS BEING DONE UNDER ITS OWN RECORD AND SHALL
 INDICATE ALL INFORMATION PERTINENT TO THE DESIGN, LIFE
 SAFETY OF CONDUCTORS OVER CURRENT PROTECTION ETC.
 PLEASE SEE RESPONSE LETTER MENTIONS OCP IS AT 800A'S?,
 HOWEVER PLEASE SEE THE FEEDERS AS SHOWN ON THIS RISER
 ONLY INDICATE CONDUCTORS RATED FOR 680A'S. PLEASE SEE
 240.4B, AND 240.6. AS THE FEEDERS ARE ONLY RATED AT
 680A'S AND THE LOAD ITSELF SHOWN IS 708A'S, PLEASE MAKE
 NEEDED ADJUSTMENTS WITH THE CONDUCTORS AS SHOWN.
 310.16, 110.14
 PLEASE STILL BE SURE TO CORRELATE ALL WITH THE PHASE I
 ENGINEERING DESIGN TEAM.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE OCP LOCATED AT GENERATOR WHICH IS PART
 OF THE PHASE 1 HIGH-RISE BLDG.
 PLEASE SEE EQUIPMENT SPECS INDICATE THE
 GEN AT 1000KW.
 215.5
  
 30) NOTE: OK, HOWEVER NOTES FOR SIGNAGE NOT SHOWN.
 PLEASE ALSO SEE RISER SHOWS EDPH2 AND MCB, YET EDPH2 IS
 BEING SHOWN AS MLO ON PANEL SCHEDULE.
 PLEASE SEE NEW NOTES WITH RESPECT TO THE LOCATION OF
 SUCH EQUIPMENT.
  
 ** PREVIOUS REVIEW NOTE **]
 PLEASE PROVIDE A MEANS OF DISCONNECT FOR THE FEEDERS
 COMING FROM
 GEN.225.31-225.39
 PLEASE SEE A MAIN CIRCUIT BRKR LOCATED IN EDPH2 WOULD
 BE ACCEPTABLE.
 SHALL ALSO REQUIRE SIGNAGE.
 230.2E,700.8 ETC.
  
 31) NOTE:NO, PLEASE SEE PLANS AND CIRCUITS IN THIS
 BUILDING STILL INDICATE ELECTRICAL BEING IN THIS
 BUILDING FROM A PANEL IN THE PHASE I BUILDING WHICH IS
 NOT AND WILL NOT BE PERMITTED. THESE ARE SEPARATE
 BUILDINGS AND NO ELECTRICAL IN THIS PHASE II BLDG MAY
 BE FED FROM THE PHASE II.
 PLEASE SEE FBC DEFINITIONS OF BUILDINGS, WHICH WOULD
 REQUIRE A FIREWALL, PLEASE SEE FIREWALL DEFINITION.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PANEL "GH" AS SHOWN ON RISER WHICH IS SHOWN
 FROM ANOTHER BLDG AND ANOTHER SERVICE, MAY NOT BE
 LOCATED IN THIS BLDG.230.3
 *****PLEASE KNOW AS CONDITION SET FORTH BY THE DESIGN
 TEAM ON PHASE ONE, A COMPLETE SEPARATION OF ALL
 ELECTRICAL SYSTEMS WILL TAKE PLACE AND A COMPLETE 4 HR
 SEPARATION WILL BE PROVIDED BETWEEN PARKING GARAGE AND
 PHASE II HIGH RISER BLDG. PLANS DO NOT SEEM TO
 CORRELATE WITH THIS. PLEASE KNOW, GARAGE IS NOW SHOWING
 ELECTRICAL DEVICES/SYSTEMS FED FROM TWO SEPARATE
 SERVICES WHICH WILL NOT BE PERMIT. A DEFINITIVE
 SEPARATION WILL BE PROVIDED AND CROSSING OVER OF
 SYSTEMS WILL NOT BE ACCEPTABLE.
 230.2, 230.3 ETC, 90.4
  
 32) NOTE: OK.
  
 33) NOTE: OK.
  
 34) NOTE: NO/, PLEASE SEE RISER OF THE 3/0 SHALL EXTEND
 THROUGH OUT BUILDING.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE A COMPLETE GROUNDING ELECTRODE RISER IN
 BLDG AND PROVIDE THIS LINE DIAGRAM ON ELECTRICAL RISER.
 THIS SHOULD INCLUDE ALL GROUNDING FOR
 TRANSFORMER(S)/SEPARATELY DERIVED SYSTEMS.250.58
  
 35) NOTE: OK.
  
 36) NOTE:NO, THE LOADS SHOWN AS CONNECTED LOADS ON
 PANELS ARE NOT THE LOAD CALCULATIONS NEEDED FOR ALL
 MAINS AND BUILDING SERVICES AS SHOWN.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE NO LOAD CALCULATIONS WERE SUBMITTED FOR
 MAINS, SERVICES, METER CENTERS ETC. MC1?
 PLEASE SEE SOME CONNECTED LOADS DO NOT INDICATE LOADS
 AND HOW THEY WERE DERIVED?
 PLEASE KNOW VERIFICATION OF CODE COMPLIANCE FOR SERVICE
 SIZES, FEEDERS,
 SEC'S ETC CAN NOT BE VERIFIED OR REVIEWED AT THIS
 TIME.
 310.16.240.4, 220, 215.5
 PLEASE BE SURE ALL CONTINUOUS LOADS ARE SHOWN AND
 FIGURED AT 125%,
 215.3, 230.42 ETC.
  
 37) NOTE: NO, NOT SUBMITTED, PLEASE KNOW THIS IS
 REQUIRED AT THIS TIME IF PERMIT IS GOING TO BE ISSUED.
 PLEASE KNOW, ANY MANUFACTURE CAN BE CHOSEN WHICH MEETS
 THE SIZES AND LISTINGS AS NEEDED. PLEASE KNOW AT ANY
 TIME AT A LATER DATE THIS MAY BE REVISED.
 90.7, 110.3
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE VERIFY AND SUBMIT SPECS FOR BUS-DUCT AS LOCAL
 AMENDMENT DOES NOT PERMIT ALUM AS THE EQUIPMENT
 GROUNDING METHOD. 250.62 SEE PREVIOUS NOTES.
  
 38) NOTE: NO, SAME NOTE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE SPEC BOOKS SUBMITTED ARE FOR EQUIPMENT AND
 SPEC BOOK FOR JOB-SITE WAS NOT SUBMITTED AT THIS TIME.
 PLEASE SEE SOME OF THE ABOVE COMMENTS WHICH MAY AFFECT
 PAGES IN THE JOB-SITE SPEC BOOKS. THESE SHOULD BE
 REVIEWED AND MAKE ANY CHANGES AS NEEDED.
  
 39) NOTE: OK, THE MAINS HAVE NOW BEEN DECREASED FROM
 1000A?S DOWN TO 800A?S; HOWEVER AS LOAD CALCULATIONS
 HAVE NOT YET BEEN SUBMITTED FOR ALL, THIS IS YET TO BE
 VERIFIED FULLY.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 230.95, 240.13 WHICH REQUIRES GROUND FAULT
 PROTECTION FOR SYSTEMS WITH A VOLTAGE MORE THEN 150V TO
 GROUND AND OVER 1000A'S.
 PLEASE SEE "MSBH2.
  
 40) NOTE: OK, 4-POLE SHOWN..
  
 41) NOTE:NO, NOT VERIFIED AT THIS TIME. RESPONSE
 MENTIONS PART OF PHASE I WHICH IS KNOW, HOWEVER AS THIS
 STATES THE FIRE PUMP IS NOW DIESEL AND THE SPECS
 SUBMITTED ARE FOR AN ELECTRICAL FIRE PUMP, SOME
 COORDINATION NEEDS TO TAKE PLACE WITH THE DESIGN TEAM
 FROM PHASE I AND PLEASE KNOW AT THIS TIME CODE
 COMPLIANCE WITH NFPA-20 FOR MINIMUM FUEL CONSUMPTION IF
 INDEED DIESEL CAN NOT BE CONFIRMED.
 90.7, 110.3, NFPA-20, CHAPTERS 6, 7 AND 8, AT THIS TIME
 THERE ARE TOO MANY SECTIONS TO LIST WHEN INFORMATION
 PROVIDED DOES NOT CORRELATE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING FIRE PUMP AND EQUIPMENT NOT
 INDICATED ON RISER DIAGRAM.
 PLEASE SEE 695.4B1 FOR OCP REQUIRED FOR LOCKED ROTOR.
 PLEASE ALSO SEE NFPA-20 FOR ELECTRICAL REQUIREMENTS FOR
 MEANS-OF DISCONNECT LOCATION ETC. PLEASE SEE SPECS
 SUBMITTED APPEAR TO SHOW THIS, HOWEVER NONE OF THESE
 ITEMS ARE SHOWN ON RISER. UNABLE TO VERIFY CODE
 COMPLIANCE FOR FIRE PUMP, FIRE PUMP CONTROLLER,
 FEEDERS, SEC'S ETC.
 ** PLEASE SEE SPECS WHICH CONTAIN THE TITLE FROM STEVEN
 FELLER'S OFFICE INDICATE THE PUMP AS 277/480V, 125HP.
 215.5
  
 42) NOTE: NO, PLEASE SEE RISER AND SCHEDULE STILL DO
 NOT CORRELATE.
 PLEASE SEE "ERL2", PLEASE SEE RISER 45KVA AND PANEL
 SHOWS 30 ETC.
 PLEASE SEE THE MAXIMUM OCP FOR THE 112 KVA TRANSFORMERS
 SHALL BE SIZED PER 450.3. (125%). PLEASE SEE ONLY IF
 MEETING ALL THE EXCEPTIONS, OCP CAN BE HIGHER THAN
 125%
 **PLEASE ALSO SEE NEW NOTES DUE TO PLANS AND CHANGES
 AND PANEL SCHEDULES SUBMITTED.
  
  
 **PLEASE CORRELATE ALL TRANSFORMERS WITH SCHEDULE(S).
 PLEASE SEE 112.5?, 150? KVA
 PLEASE ALSO CONFIRM KVA AS MAX OCP FOR TRANSFORMER MAY
 NOT EXCEED 125% AS 450.3
 TABLES.
  
 43) NOTE: OK.
  
 44) NOTE: NO, PLEASE ONE OF THE PREVIOUS NOTES ABOVE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE THE COMPLETE GROUNDING ELECTRODE
 SYSTEMS DETAIL PER
 250.50, 250.104, 250.64,,,
  
 45) NOTE: OK, HOWEVER SEE NOTES AS NOTES ABOVE WITH
 RESPECT TO THE MLO AND MCB BEING DIFFERENT ON PANEL AND
 RISER.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE EDPH2 IS SHOWN AS
 1000A'S ON PANEL SCHEDULES AND SHOWN AS 800A ON RISER??
 PLEASE CORRELATE.
 215.5
  
 46 NOTE: OK, AS MSBE HAS NOW CHANGED TO 800A?S.
  
 47)NOTE: OK, HOWEVER PLEASE KNOW, IF THIS INFORMATION
 IS NOT SUBMITTED, SEPARATE PERMITS PLANS AND FEES WILL
 BE REQUIRED BEFORE ANY SITE LIGHTING MAY BE INSTALLED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PANEL "SL" IS SHOWN AS HAVING "SITE
 LIGHTING" HOWEVER, SITE LIGHTING COULD NOT BE LOCATED
 ON ELECTRICAL PLANS?
 IF SITE LIGHTING CONTAINS LT POLES, PLEASE SUBMIT WIND
 LOAD CALCULATIONS FOR FBC 140MPH. THESE WILL BE
 REVIEWED BY A STRUCTURAL REVIEWER. ** PLEASE BE SHOULD
 POLE CONTAIN FIXTURES FOR CALCULATION PURPOSES.
  
 48) NOTE: OK.
  
 49) NOTE:NO, PLEASE SEE RISER SHOWS SOME ITEMS WHICH
 ARE STILL NOT LISTED ON PANELS SCHEDULES. PLEASE SEE
 4EH2 TO 4EL2, MISSING ON PANEL SCHEDULE AND MISSING
 TRANSFORMER INFORMATION ETC. CAN NOT BE VERIFIED AT
 THIS TIME.
  
 ** PREVIOUS REVIEW NOTE ** PLEASE LABEL ALL
 TRANSFORMERS ON RISER AS INDICATED ON PANEL SCHEDULES.
 215.5, 450, ETC
  
 50) NOTE: OK.
  
 51) NOTE:NO, PLEASE SEE NOTES WERE NOTED, HOWEVER
 PLEASE PROVIDE THE DETAIL FOR TYPICAL.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE A DISCONNECT DETAIL INCLUDING SIZE ETC
 FOR ROOF TOP UNITS. THIS MAY BE A "TYPICAL" DETAIL FOR
 EACH SIZE IF NOT ALL THE SAME.
 215.5, 440.11
  
 52) NOTE: OK.
  
 53) NOTE: NO, RESPONSE MENTIONS DEVICES HEIGHTS SHOWN
 ON E0.00, HOWEVER THE HEIGHTS ON DEVICES ARE NOT THE
 ONLY REQUIREMENTS FOR ELECTRICAL DEVICES. PLEASE LIST
 NOTE AS PREVIOUSLY REQUESTED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FAIR HOUSING ACT
 REGULATIONS, 24 CFR 100.205 WITH RESPECT TO THE
 LOCATIONS OF "ALL" ELECTRICAL DEVICES, CONTROLS.
 A NOTE IS LOCATED ON "GEN NOTES" WHICH MENTIONS THE
 HEIGHTS FOR RECEPTS AND SWITCHES, HOWEVER THIS SHOULD
 REFLECT
 FHAR ETC AS NOTED ABOVE.
  
 54) NOTE:NO? PLEASE KNOW AS THE PHASING OF THIS
 PROJECT ANDHOW THIS IS BEING DONE AND HOW THE PLANS
 HAVE BEEN SUBMITTED SHOWING PARTS OF PHASE II BEING FED
 FROM PHASE I IS UNCLEAR.
 THE EGRESS PATH SEEMS TO HAVE BEEN SHOWN, HOWEVER AS
 THE BUILDING OF EACH PHASE IS NOT CLEAR, UNABLE TO
 REVIEW FOR ACTUAL INSTALLATION.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THE AMENITY DECK DETAILS COULD NOT BE
 LOCATED IN SETS.
 PLEASE SEE E2.06 WHICH ONLY SEEMS TO INDICATE A PARTIAL
 AREA SHOWN.
 PLEASE SEE NO ELECTRICAL SHOWN FOR LIGHTING ETC?
 PLEASE SEE LS 101 7.8 AND 7.9 WHICH REQUIRE MEANS OF
 EGRESS LIGHTING TO THE PUBLIC RIGHT OF WAY; THIS WOULD
 INCLUDE EMERGENCY LIGHTING AS REQUIRED.
 PLANS NOW SHOW A SEPARATE PHASE LINE, AS GARAGE WAS TO
 BE BUILT WITH PHASE ONE BLDG AND DID NOT SHOW GARAGE
 WITH PHASE LINE DOWN THE CENTER OF THE GARAGE.
  
  
 ** NEW NOTES 2ND REVIEW ***
 NOTES ARE BASED ON REVISIONS MADE TO PLANS AND
 INFORMATION NOW SUBMITTED. PLEASE SEE ALSO NEW NOTES
 WHICH WERE NOT COMMENTED ON THE PREVIOUS REVIEW #63 AND
 64 AS THIS WAS NOT PART OF THE ELECTRICAL REVIEW.
  
 55) NOTE: PLEASE SEE MSBH2 IS MISSING
 CONDUCTORS/FEEDERS FOR H-2 AND SL1.
 310.16, 240.4,215.5 ETC
  
 56)NOTE: PLEASE SEE MSBH2 PANEL SCHEDULE FOR OCP
 DEVICES FOR EACH PANEL BEING SERVED DOES NOT CORRELATE
 WITH THE OCP DEVICES SHOWN ON RISER. PLEASE ALSO
 CORRELATE CONDUCTORS/FEEDERS.
 408.4, 310.16, 240.4
  
 57) NOTE: PLEASE SEE FEEDERS ON THE SECONDARY SIDE FOR
 RL2 SHOW #6'S WHICH TERMINATE IN 100A OCP. PLEASE SEE
 240.21C, 408.16, 310.16 ETC,
 PLEASE SEE THE LOAD ON THIS PANEL EXCEEDS THAT OF THE
 RATING OF THE #6'S IN EITHER CASE.
  
 58) NOTE: PLEASE SEE PANEL SCHEDULE FOR MSBH2 WHICH
 SHOWS 400A OCP FEEDING PANEL H2 WHICH IS ONLY RATED AT
 225A'S? PLEASE SEE CONDUCTORS ON PANEL SCHEDULE ARE
 MISSING HOWEVER SHOWN ON RISER.
 240.4, 408, ETC
  
 59) NOTE: PLEASE SEE RISER SHOWS FPL SERVICE
 TRANSFORMER BEING 120/208V , YET THIS IS BEING SHOWN
 FEEDING 277/480V SYSTEMS??
  
 60) NOTE: PLEASE SEE PANEL SCHEDULES FOR UNITS INDICATE
 A 1-POLE BREAKER FEEDING EACH OF THE DISHWASHER AND
 DISPOSAL RECEPTACLE, HOWEVER PLEASE SEE 210.4B AS THIS
 WOULD BE REQUIRED TO BE A 2-POLE BRKR IF FEEDING A
 DEVICE ON SAME YOKE.
  
 61) NOTE: PLEASE SEE FBC 2001 CHAPTER 13, THE ENERGY
 CALCULATIONS SUBMITTED ARE NOT SIGNED, DATED OR SEALED
 BY THE RESPONSIBLE DESIGN PROFESSIONAL.
 FS 471.025, FAC 61G15-23.002
  
 62) NOTE: PLEASE SEE FIRE SPRINKLER SHEETS ARE BEING
 SEALED WITH A SEAL AND STAMP WHICH IS NOT PERMITTED
 (RUBBER STAMP) AND SEAL WHICH IS NO LONGER VALID WITH
 THE STATE. PLEASE SEE RULING IN THE FAC 61G15-23.001
 WHICH REQUIRED ALL ENGINEERS TO OBTAIN THEIR NEW SEALS
 WITH THE WORDING OF "LICENSE" AND "CERTIFICATE" WAS NOT
 LONGER PERMITTED. THIS RULE WAS PAST IN 2/04, HOWEVER
 AN EXTENSION WAS GRANTED TO 12/31/05 ONLY.
  
 63) NOTE: PLEASE SEE FPL VAULT IS SHOWING A STROBE
 DEVICE FROM THE BUILDINGS FA SYSTEM WHICH IS NOT
 PERMITTED. NO EQUIPMENT OR ELECTRICAL DEVICES OF ANY
 KIND ARE PERMITTED IN THE FPL VAULT.
  
 64) NOTE:PLEASE SEE ALL AUDIBLE AND VISUAL DEVICES
 FOR FA SYSTEMS ARE REQUIRED TO MEET FBC 2001,
 11-4.28.1, PLEASE LIST AND SHOW COMPLIANCE FOR
 11-4.28.2 AND 11-4.28.3(4). PLEASE SEE THERE ARE MANY
 LOCATIONS FOR MIN CANDELAS DO NOT SEEM TO HAVE BEEN
 MET.
  
 65) NOTE: PLEASE SEE E2.01, PLEASE SEE AREAS AND WALL
 OUTSIDE UNIT A3, WHICH DO NOT SEEM TO BE COMPLETE?
 PLEASE CLARIFY HOW ACCESS TO THE FIRE COMMAND ROOM WILL
 TAKE PLACE, COULD NOT LOCATE ANY DOORS ON THIS SHEET
 FOR THIS??
  
 66) NOTE: PLEASE BE SURE TO GO BACK AND CHECK ALL
 KITCHEN COUNTER SPACES PER 210.52C1, E-2, G1A, ETC.
  
 67) NOTE: PLEASE SEE NOW THAT ROOM AND AREA
 DESIGNATIONS ARE PLACES ON PLANS, PLEASE REVISE PANEL
 SCHEDULES FOR UNITS TO CORRELATE WITH THESE ROOMS AND
 AREAS. INSTEAD OF GEN LTS, GEN RECEPTS, IT WOULD
 MENTION: BEDRM, #2 LTS, MASTER BDRM RECEPTS ETC.
 408.4.
  
 68) NOTE: PLEASE SEE NFPA-110 7.2.2.1. TRANSFER
 SWITCHES SHALL BE PERMITTED TO BE INSTALLED IN THE
 NORMAL ELECTRICAL SERVICE ROOM WHERE TWICE THE
 CLEARANCE REQUIRED BY ARTICLE 110.26(A) OF NFPA 70,
 NATIONAL ELECTRICAL CODE, EXISTS BETWEEN EQUIPMENT
 ENCLOSURES.
 PLEASE ADJUST ROOM AS NEEDED AND REQUIRED.
  
  
  
 ** NOTE: PLEASE SEE MANY OF THE ABOVE ITEMS WERE
 REDLINED ON ONE SET FOR AREAS OF NOTES ABOVE.
  
 ** NOTE: PLEASE SEE POSSIBLE NOTES FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL PLANS AND
 DESIGN.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  
  
2006-11-05 11:30:44REVIEW IN PROGRESS
2006-08-23 00:00:00REVIEW STOPPED ON 8/23 , PLANS WILL GO
 INTO "F" STATUS ONCE REVIEW IS
 COMPLETED.
 NOTES WILL FOLLOW.
2006-08-22 00:00:00REVIEW IN PROGRESS
2006-08-20 00:00:00** ONE ROLL OF MEP, FP IN ELECTRICAL
 FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-02-02 Cont ID  
Sent By dpalmer Date 2006-02-02 Time 20:18 Rev Time 0.00
Received By dpalmer Date 2006-01-24 Time 19:03 Sent To  
Notes
2006-01-27 00:00:00**** THE EDGE PHASE II ** 17 STORY **
  
 ********** UNSAT ***************
  
 ** PLEASE KNOW, PLANS ARE NOT COMPLETE
 AND REVIEW BELOW IS BASED ON PLANS
 SUBMITTED.
 PLEASE ALSO KNOW, SINCE PLANS ARE NOT
 COMPLETE, THERE MAY OR MAY NOT BE
 FURTHER COMMENTS ON NEXT REVIEW.
  
  
 1)NOTE: PLEASE SEE ADDRESSING NEEDS TO
 BE ADDRESSED AS PERMIT APPLICATION
 MENTIONS 350 S AUST, PCN USED ON
 APPLICATION IS FORRR 300 S AUST.
 PLEASE ALSO SEE PLANS INDICATE 300 S
 AUSTRALIAN AVE.
 PLEASE BE SUREADDRESS IS CORRECTED
 WITH THE ADDRESSING DEPT AND ADJUST
 PLANS IF NEEDED.
  
 2)NOTE: PLEASE SEE MISSING LICENSE
 INFORMATION REQUIRED ON TITLE BLOCKS FOR CONSULTING
 ENGINEERING FIRM AS REQUIRED
 UNDER FLORIDA STATUES 471.023, FLORIDA ADMINISTRATIVE
 CODE 61G15-23.002.
 PLEASE SEE COMPANIES AS LISTED ARE
 PROVIDING ENGINEERING SERVICES" AND NO
 CERTIFICATE OF AUTHORIZATION NUMBER
 COULD BE LOCATED ON STATE WEBSITE OF
 DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION.
 (DBPR).
 PLEASE KNOW AS REQUIRED BY THESAID
 FLORIDA STATUES AND LICENSINGUNDER FS
 468 FOR THIS OFFICE, ONE SET OF MEP
 PLANS ARE BEING RETAINED AND SHALL BE
 FORWARDED TO THE FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS FOR REVIEW OF
 SAID REQUIREMENTS. WE HAVE CONSULTED
 WITH THEFBPE'S ON THE ABOVE. PLEASE
 CONTACT MR. JERRY ONGLEY AND MR. DOUGLAS
 SUNSHINE IF THERE ARE ANY QUESTIONS.
 ** PLEASE KNOW, THESE REQUIREMENTS ARE
 ALSOFOR THE OTHER CONSULTING COMPANIES
 AS LISTED ON SAID TITLE BLOCKS.
  
 3)NOTE: PLEASE SEE SPECS SUBMITTED FOR
 FIRE PUMP CONTAIN THE TITLE AND THE
 RESPONSIBLE ENGINEER AS STEVEN FELLER OF
 FELLER ENGINEERING. STEVEN FELLER AND
 FELLER ENGINEERING IS THE CONSULTING
 ENGINEERS OF PHASE-ONE.
 PLEASE CORRECT ALL SUBMITTALS FOR FIRE
 PUMP, FIRE PUMP CONTROLLER ETC.
  
 4)NOTE: PLEASE BE SURE PLANS REFERENCE
 ALL CURRENT CODE IN EFFECT FOR THIS
 PROJECT. PLEASE KNOW WE ARE CURRENTLY
 UNDER THE 2003 NFPA-101, 2002 NFPA-72
 AND 2002 NFPA-70 ETC.
  
 5)NOTE: PLEASE KNOW, ENTRANCE TO MAIN
 ELECTRICAL ROOM SHALL BE DETERMINED BY
 THIS OFFICE AND FIRE MARSHAL'S OFFICE
 FOR ACCESSIBILITY. PLANS INDICATE ACCESS
 GRANTED THROUGH GARAGE AREA AND TRAVEL
 DISTANCE IN BLDG MAY REQUIRED A MORE
 ACCESSIBLE MEANS TO MAIN ELECTRICAL
 ROOM.
 ** PLEASE SEE POSSIBLE FIRE REVIEW
 COMMENTS.
  
 6)NOTE: PLEASE SEE 110.26 FOR MIN
 DOOR(S) REQUIRED FOR MAIN ELECTRICAL
 ROOM. PLEASE SEE ONE MAIN/EQUIPMENT
 LOCATED DIRECTLY IN-FRONT OF THE EGRESS
 PATH/DOOR.
 PLEASE SEE PANIC HARDWARE SHALL BE
 REQUIRED AND DOORS MUST OPEN IN THE
 DIRECTION OF TRAVEL.PLEASE PROVIDE A
 NOTE ON PLANS FOR THIS.
 A NOTE ON E4.00 STATES "DOOR NEEDS TO BE RELOCATED" ,
 HOWEVER THIS WAS NOT DONE
 AND IS SHOWN THE SAME IN A-SHEETS AND
 E-SHEETS.
 PLEASE ADD NOTE(S) TO PLANS FOR ALL
 CLEARANCES PER 110.26 SHALL BE MET.
 4.00 ETC
  
 7)NOTE: PLEASE VERIFY WHERE LIGHTING IS
 FOR ELECTRICAL RMS ON FLRS
 2,5,6,7,10,16?
 215.5, LS1017.8,7.9 ETC
  
 8)NOTE: PLEASE SEENFPA-72 WHICH
 REQUIRES BATTERY BACK UP FIXTURES IN
 STAIR TOWERS AND OTHER AREAS WHERE EM
 LTS ARE REQUIRED FOR MIN EGRESS PATHS.
 PLEASE SEE 7.9.2.2 WHICH STATES NO
 SINGLE MEANS OF OVERCURRENT PROTECTION
 OR SWITCHING ETC SHALL LEAVE ANY EGRESS
 PATHS IN TOTAL DARKNESS AS SHOWN ON
 PLANS.
 PLEASE KNOW AS REQUIRED BY THE AHJ AND
 THE FIRE MARSHAL'S OFFICE A BATTERY
 BACK-UP FIXTURE OF SOME SORT WILL BE
 REQUIRED FOR THESE EGRESS PATHS TO
 ALLEVIATE THE ABOVE.
  
 9)NOTE: PLEASE PROVIDE COMPLETE
 PHOTO-METRICS FOR FOR ALL STAIR-TOWERS
 AND EGRESS PATHS. PLEASE SEE LS 101
 7.8.1.3 WHICH REQUIRES A MIN OF
 10FT/CANDLES (108 LUX) FOR STAIR TOWERS
 UNDER NORMAL CONDITIONS AND A MIN OF
 1FT/CD UNDER EMERGENCY CONDITIONS.
 7.9.2.2
  
 10)NOTE: PLEASE INDICATE BY SOME MEANS
 THE IDENTIFICATION OF ALL LIGHTING
 FIXTURES ON PLANS. PLEASE SEE LIGHTING
 IN STAIRS, TYPE OF FIXTURE COULD NOT BE
 FOUND AND CORRELATION TO THE SUBMITTED
 FIXTURE SCHEDULE COULD NOT BE DONE.
  
 11)NOTE: PLEASE PROVIDE A NOTE ON ROOF
 PLANS:
 " ALL PROPOSED LIGHTNING PROTECTION
 SYSTEMS SHALL MEET NFPA-780" OR WORDS TO
 THAT AFFECT.
 ** PLEASE KNOW, THERE ARE MANY "LIGHTING PREVENTION
 SYSTEMS" ON THE MARKET WHICH
 ARE NOT ACCEPTABLE IN THIS JURISDICTION
 OR BY NFPA.
  
 12)NOTE: PLEASE SUBMIT A LETTER FROM THE
 FLORIDA POWER AND LIGHT REPRESENTATIVE
 ON THE ACCEPTANCE OF FPL VAULT AS SHOWN.
  
 13)NOTE: PLEASE COMPLETE PLANS WITH ALL
 CIRCUITINGAND CORRELATE WITH SUBMITTED
 PANEL SCHEDULES. REVIEW FOR CODE
 COMPLIANCE CAN NOT BE DONE AT THIS TIME.
 PLEASE BE SURE TO SEE
 210.52B1,210.52D,210.11C3 ETC.
  
 14)NOTE: PLEASE SEE 424.3B WHICH
 REQUIRES OCP FOR AHU/HEAT TO BE SIZED AT
 A MIN OF 125%. PLEASE SEE SOME OCP AS
 INDICATED WILL NEED TO BE ADJUSTED.**
 PLEASE BE SURE TO ADJUST AND CONDUCTOR
 SIZES AS NEEDED. PER 310.16,240.4 ETC
  
 15)NOTE: PLEASE SEE 210.52D,210.11C3 FOR
 BATH RECEPTS. PLEASE SEE SOME UNITS ,
 B2, B1 ETC.
  
 16)NOTE: PLEASE PLACE ALL AREA AND ROOM DESIGNATIONS ON
 PLANS.
 PLEASE SEE PREVIOUS COMMENTS WITH
 RESPECT TO COMPLIANCE WITH CIRCUITING.
  
 17)NOTE: PLEASE INDICATE THE KITCHEN
 CIRCUITS AS SMALL APPLIANCE.
 210.52B
  
 18)NOTE: PLEASE SEE NFPA-72 11.8.3.5,
 11.5.1.1 FOR SMOKE DETECTORS REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPINGRMS.
 PLEASE SEE UNIT D1, PLEASE ALSO SEE
 OTHER UNITS WHERE SD'S DO NOT APPEAR TO
 BE "OUTSIDE" SLEEPING AREAS OR
 CORRIDORS. PLEASE SEE A DOOR SEPARATES
 BEDRM HALLWAYS FROM LIVING/COMMON AREA
 OF UNIT. THIS SEEMS TO SHOW NO SD
 COVERAGE FOR AREAS OUTSIDE BEDROOMS.
 PLEASE FIRE REVIEW COMMENTS.
 ** PLEASE PLACE NOTE ON PLANS WITH
 REFERENCE TO THE MIN PLACEMENT
 REQUIREMENTS OF ABOVE NFPA. PLEASE SEE
 THAT SD'S ARE LOCATED A MIN OF 3' FROM BATH,KITCHEN
 DOORS , 3' FROM SUPPLY
 REGISTERS , ETC :WITH EXCEPTIONS AS
 LISTED FOR LOCATIONS WITHIN 20' OF
 COOKING APPLIANCES.
 ** PLEASE SEE SPECS/LISTING FROM SD
 MANUFACTURE AS MANY REQUIRED SD'S TO BE
 FURTHER THAN LISTED ABOVE AND MOST
 REQUIRED SD'S TO BE 5' FROM THE RETURN
 AIR GRILLE.
 ** PLEASE KNOW, ANY CEILING HEIGHT
 VARIATIONS MAY CHANGE LOCATION OF SD'S,
 AS THEY ARE REQUIRED TO BE LOCATED
 WITHIN 12" OF THE HIGHEST POINT OF A
 FLAT CEILING.
  
 19)NOTE: PLEASE SHOW AND LABEL ALL
 PANELS, ELECTRICAL AND PANELS WHICH
 APPEAR TO BE LOW VOLTAGE?
 PLEASE KNOW, ANY PLUG-IN TYPE
 TRANSFORMERS MAY NOT BE LOCATED IN CLOSE
 PROXIMITY OF EASILY IGNITABLE MATERIALS
 IN CLOTHES CLOSETS.
 PLEASE KNOWIN MANY LOCAL JURISDICTIONS
 AS A RESULT OF THE HEATING OF THESE TYPE TRANSFORMER A
 FIRE HAS OCCURRED. IN THE
 INTEREST OF LIFE SAFETY AND PROPERTY
 PLEASE ADJUST LOCATIONS.
 110.26,240.24D, 408.7 ETC.
 PLEASE ALSO SEE UNIT(S) WHICH INDICATE A
 PANEL OF SOME SORT "INSIDE " THE BATHTUB
 LOCATION. PLEASE SEE 240.24 FOR
 PERMITTEDLOCATIONS OF PANELS.
 PLEASE SEE REDLINED PLANS.
 PLEASE SEE UNIT "G" FOR WHAT APPEARS TO
 BE TWO PANELS?
 PLEASE SEE D2, PLEASE SEE A1, PANEL NOT
 LOCATED ON WALL, SEE P3, P2 MISSING
 PANEL.
 PLEASE VERIFY ALL OF THE ABOVE AS MANY
 OF THESE HAVE BEEN REDLINED ON ONE SET
 OF PLANS.
  
 20)NOTE: PLEASE SEE 210.52 FOR MISSING
 RECEPTS FOR 2',6'AND 12 RULE. PLEASE SEE
 SOME MISSING FOR 2' OF WALL SPACE.
  
 21)NOTE: PLEASE SEE 210.52C2, 210.8A16
 FOR WHAT APPEARS TO BE SHOWN AS AN
 ISLAND KITCHEN. B2
  
 22)NOTE: PLEASE SEE SEE UNIT UNIT A-2
 LAYOUT OF WALLS AND DOORS.PLEASE SEE
 AREA WHERE THERE SEEMS TO BE A ROOM?
  
 23)NOTE: PLEASE CORRELATE ELECTRICAL
 ROOMS AND RISER DIAGRAM. PLEASE SEE E4.0
 SHOWS ELECTRICAL RM ON EVERY FLR,
 HOWEVER RISER DOES NOT.
 PLEASE SEE OTHER COMMENTS WITH RESPECT
 TO ELECTRICAL RMS.
 215.5
  
 24)NOTE: PLEASE PROVIDE A CURB DETAIL
 FOR FLR PENETRATIONS OF BUS-DUCT PER
 368.6 WHERE A VERTICAL RISER PENETRATES
 TWO OR MORE DRY FLOORS, A MINIMUM 100 MM
 (4 IN.) HIGH CURB SHALL BE INSTALLED
 AROUND ALL FLOOR OPENINGS FOR RISER
 BUSWAYS TO PREVENT LIQUIDS FROM ENTERING
 THE OPENING. THE CURB SHALL BE INSTALLED
 WITHIN 300 MM (12 IN.) OF THE FLOOR
 OPENING. ELECTRICAL EQUIPMENT SHALL BE
 LOCATED SO THAT IT WILL NOT BE DAMAGED
 BY LIQUIDS THAT ARE RETAINED BY THE
 CURB.
  
 25)NOTE: PLEASE CORRELATE MAIN
 ELECTRICAL ROOM EQUIPMENT WITH RISER
 DIAGRAM. PLEASE SEE ONE SHOWS 3000A
 MAIN, THEOTHER 4000A, PLEASE SEE
 ELECTRICAL PANELSSHOWN ON 4.00 ALSO DO
 NOT CORRELATE WITH RISER.
 PLEASE SEE MANY OF THESE ITEMS/LOCATIONS
 WERE REDLINED ON ONE SET.
  
 26)NOTE: PLEASE SEE METER CENTERS ON
 ELECTRICAL ROOMS SHOWN ON E4.00 DO NOT
 CORRESPOND TO THE METER CENTERS ON 5.02
 215.5
  
 27)NOTE: PLEASE SEE METER CENTER(S),
 PLEASE SEE THERE ARE MANY UNIT
 IDENTIFICATIONS WHICH DO NOT CORRELATE
 TO THE UNITS ON PLANS.
 PLEASE SEE UNITS TYPES ON RISER.
 215.5
  
 28)NOTE: PLEASE SEE RISER WHICH
 INDICATES THE ELEVATOR'S ELECTRICAL
 EQUIPMENT LOCATED ON FIRST FLR, HOWEVER
 PLEASE SEE PLANS FOR ROOF AS ELEVATOR
 EQUIPMENT ROOM IS SHOWN AT THAT
 LOCATION. PLEASE CORRELATE.
 215.5
  
 29)NOTE: PLEASE PROVIDE OCP LOCATED AT
 GENERATOR WHICH IS PART OF THE PHASE 1
 HIGH-RISE BLDG.
 PLEASE SEE EQUIPMENT SPECS INDICATE THE
 GEN AT 1000KW.
 215.5
  
 30)NOTE: PLEASE PROVIDE A MEANS OF
 DISCONNECT FOR THE FEEDERS COMING FROM
 GEN.225.31-225.39
 PLEASE SEE A MAIN CIRCUIT BRKR LOCATED
 IN EDPH2 WOULD BE ACCEPTABLE.
 SHALL ALSO REQUIRE SIGNAGE.
 230.2E,700.8 ETC.
  
 31)NOTE: PLEASE SEE PANEL "GH" AS SHOWN
 ON RISER WHICH IS SHOWN FROM ANOTHER
 BLDG AND ANOTHER SERVICE, MAY NOT BE
 LOCATED IN THIS BLDG.230.3
 *****PLEASE KNOW AS CONDITION SET FORTH
 BY THE DESIGN TEAM ON PHASE ONE, A
 COMPLETE SEPARATION OF ALL ELECTRICAL
 SYSTEMS WILL TAKE PLACE AND A COMPLETE 4
 HR SEPARATION WILL BE PROVIDED BETWEEN
 PARKING GARAGE AND PHASE II HIGH RISER
 BLDG. PLANS DO NOT SEEM TO CORRELATE
 WITH THIS. PLEASE KNOW, GARAGE IS NOW
 SHOWING ELECTRICAL DEVICES/SYSTEMS FED
 FROM TWO SEPARATE SERVICES WHICH WILL
 NOT BE PERMIT. A DEFINITIVE SEPARATION
 WILL BE PROVIDE AND CROSSING OVER OF
 SYSTEMS WILL NOT BE ACCEPTABLE.
 230.2,230.3 ETC, 90.4
  
 32)NOTE: PLEASE PLACE NOT ON PLANS AS NO
 EQUIPMENT GROUNDING CONDUCTORS MAY BE
 ALUMINUM, AND NO FEEDERS SMALLER THAN
 #2. PER CITY OF WEST PALM BEACH LOCAL
 AMENDMENTS TO THE 2001 FBC.250.62,310.2
  
 33)NOTE: PLEASE PLACE NOTE ON PLANS FOR
 COLOR CODING OF 277/480V SYSTEMS PER
 LOCAL AMENDMENTS, 215.2
 BROWN, PURPLE, YELLOW.
 ** PLEASE KNOW SPECIFIC COLOR CODING PER
 277/480V IS NOT PROVIDED IN THE NEC AND
 ONLY A "HIGH-LEG" SHALL HAVE "ORANGE" AS
 THE COLOR.
  
 34)NOTE: PLEASE PROVIDE A COMPLETE
 GROUNDING ELECTRODE RISER IN BLDG AND
 PROVIDE THIS LINE DIAGRAM ON ELECTRICAL
 RISER. THIS SHOULD INCLUDE ALL GROUNDING
 FOR TRANSFORMER(S)/SEPARATELY DERIVED SYSTEMS.250.58
  
 35)NOTE: PLEASE INDICATE THE ATTACHMENT
 FOR TRANSFORMERS AS SHOWN AS REQUIRED
 PER ABOVE NOTE #34 AND 250.30, 250.66
  
 36)NOTE: PLEASE SEE NO LOAD CALCULATIONS
 WERE SUBMITTED FOR MAINS, SERVICES,
 METER CENTERS ETC. MC1?
 PLEASE SEE SOME CONNECTED LOADS DO NOT
 INDICATE LOADS AND HOW THEY WERE
 DERIVED.?
 PLEASE KNOW VERIFICATION OF CODE
 COMPLIANCE FOR SERVICE SIZES, FEEDERS,
 SEC'S ETC CAN NOT BE VERIFIED OR
 REVIEWED AT THIS TIME.
 310.16.240.4,220, 215.5
 PLEASE BE SURE ALL CONTINUOUS LOADS ARE
 SHOWN AND FIGURED AT 125%,
 215.3,230.42 ETC.
  
 37)NOTE: PLEASE VERIFY AND SUBMIT SPECS
 FO BUS-DUCT AS LOCAL AMENDMENT DOES NOT
 PERMIT ALUM AS THE EQUIPMENT GROUNDING
 METHOD. 250.62 SEE PREVIOUS NOTES.
  
 38)NOTE: PLEASE SEE SPEC BOOKS SUBMITTED
 ARE FOR EQUIPMENT AND SPEC BOOK FOR
 JOB-SITE WAS NOT SUBMITTED AT THIS TIME.
 PLEASE SEE SOME OF THE ABOVE COMMENTS
 WHICH MAY AFFECT PAGES IN THE JOB-SITE
 SPEC BOOKS. THESE SHOULD BE REVIEWED AND
 MAKE ANY CHANGES AS NEEDED.
  
 39)NOTE: PLEASE SEE 230.95,240.13 WHICH
 REQUIRES GROUND FAULT PROTECTION FOR
 SYSTEMS WITH A VOLTAGE MORE THEN 150V TO
 GRND AND OVER 1000A'S.
 PLEASE SEE "MSBH2.
  
 40)NOTE: PLEASE VERIFY SIZING OF
 EMERGENCY DISTRIBUTION SYSTEM AS ONE
 SHEET SHOWS 800A ATS AND SPECS FOR ATS
 INDICATE THIS AS 1000A'S?
 PLEASE SEE NOTE BELOW AS PANEL
 SCHEDULES ALSO INDICATE 1000A'S.
 PLEASE KNOW, IF 1000A'S, GFP SENSING
 WILL BE REQUIRED ON SECONDARY SIDE,GFP
 WILL BE REQUIRED ON MAIN ALSO AS NOTED
 PER 240.13,230.95.
 PLEASE SEE 700.7D, 700.26, 701.9D
 PLEASE SEE TEXT TAKEN DIRECTLY FROM ASCO
 AS A 4-POLE ATS MAY BE REQUIRED FOR THE
 CORRECT COORDINATION OF ELECTRICAL
 SYSTEMS.
 "WHERE GROUND FAULTPROTECTION IS
 TRIGGERED BY THE CODE AND AN ALTERNATE
 POWER SUPPLY IS INCLUDED,SWITCHING OF
 THE NEUTRAL BECOMES NECESSARY. THE
 CIRCUIT SHOWN ABOVE ILLUSTRATESSUCH A CIRCUMSTANCE.
 THE SERVICE IS LARGER THAN
 1,000 AMPS. CONSEQUENTLY, GROUNDFAULT
 PROTECTION IS REQUIRED AT THE MAIN
 SERVICE DISCONNECT AT A MINIMUM. IF IT
 IS INSTALLED THERE AND THE GENERATOR
 NEUTRAL GROUNDING WAS THROUGH A SOLID
 CONNECTION TO THE MAIN SERVICE NEUTRAL,
 A GROUND FAULT WHEN THE GENERATOR IS
 FEEDING THE LOAD WILL CAUSE THE MAIN
 SERVICE DISCONNECT TO OPEN. THIS WILL
 NOTDISCONNECT THE ARCING FAULT FROM
 THE GENERATOR. COORDINATION IS THUS
 LOST."
 PLEASE VERIFY AS SYSTEM IN EXISTING BLDG
 ONE MAY BE A SEPARATELY DERIVED
 GENERATOR AND SEEING HOW BOTH BLDGS EM
 POWER IS COMING FROM THE SAME GENERATOR,
 A 4-POLE SWITCH MAY BE REQUIRED. PLEASE
 ALSO KNOW, BOTH OF THESE MAIN
 DISTRIBUTION SYSTEMS ARE COMING FROM TWO
 SEPARATE FPL VAULTS AND TRANSFORMERS.
  
 41)NOTE: PLEASE SEE MISSING FIRE PUMP
 AND EQUIPMENT NOT INDICATED ON RISER
 DIAGRAM.
 PLEASE SEE 695.4B1 FOR OCP REQUIRED FOR
 LOCKED ROTOR. PLEASE ALSO SEE NFPA-20
 FOR ELECTRICAL REQUIREMENTS FOR MEANS-OF
 DISCONNECT, LOCATION ETC. PLEASE SEE
 SPECS SUBMITTED APPEAR TO SHOW THIS ,
 HOWEVER NONE OF THESE ITEMS ARE SHOWN ON
 RISER. UNABLE TO VERIFY CODE COMPLIANCE
 FOR FIRE PUMP, FIRE PUMP CONTROLLER,
 FEEDERS, SEC'S ETC.
 ** PLEASE SEE SPECS WHICH CONTAIN THE
 TITLE FROM STEVEN FELLER'S OFFICE
 INDICATE THE PUMP AS 277/480V, 125HP.
 215.5
  
 42)NOTE: PLEASE CORRELATE ALL
 TRANSFORMERS WITH SCHEDULE(S). PLEASE
 SEE 112.5?, 150? KVA
 PLEASE ALSO CONFIRM KVA AS MAX OCP FOR
 TRANSFORMER MAY NOT EXCEED 125% AS 450.3
 TABLES.
 215.5
  
 43)NOTE: PLEASE COMPLETE BUS-DUCT RISER
 AND METER CENTERS AS PLANS ONLY INDICATE
 THESE THOUGH FLOOR (8).??
 PLEASE SEE MISSING METER CENTER / MAIN
 DISCONNECT ON 3RD FLR, HOWEVER ONE IS
 SHOWN ON 4.00 PLANS FOR ELECTRICAL RMS.
 ALSO NOTED ABOVE FOR CORRELATION OF ALL
 RMS WITH RISER.
 215.5
  
 44)NOTE: PLEASE PROVIDE THE COMPLETE
 GROUNDING ELECTRODE SYSTEMS DETAIL PER
 250.50, 250.104, 250.64,,,
  
 45)NOTE: PLEASE SEE EDPH2 IS SHOWN AS
 1000A'S ON PANEL SCHEDULES AND SHOWN AS
 800A ON RISER ?? PLEASE CORRELATE.
 215.5
  
 46)NOTE: PLEASE SEE "MSBE2" AS THIS IS
 ALSO SHOWN AS 1000A'S ON PANEL
 SCHEDULE(S), HOWEVER SHOWN AS 800A'S ON
 RISER. PLEASE VERIFY AS 1000A'S OR MORE
 277/480V WILL ALSO REQUIRE GFP ON EM
 MAIN.
 230.95,240.13 ETC
  
 47)NOTE: PLEASE SEE PANEL "SL" IS SHOWN
 AS HAVING "SITE LIGHTING" HOWEVER, SITE
 LIGHTING COULD NOT BE LOCATED ON
 ELECTRICAL PLANS?
 IF SITE LIGHTING CONTAINS LT POLES,
 PLEASE SUBMIT WIND LOAD CALCULATIONS
 FOR FBC 140MPH. THESE WILL BE REVIEWED
 BY A STRUCTURAL REVIEWER. ** PLEASE BE
 SHOULD POLE CONTAIN FIXTURES FOR
 CALCULATION PURPOSES.
  
 48)NOTE: PLEASE VERIFY OCP FOR LARGER
 A/C SYSTEMS SHOWN ON PANEL SCHEDULES,
 PLEASE SEE 424.3B AS NOTED ABOVE FOR MIN
 OCP OF 125%.ADJUST WHERE NEEDED.
 RTU#1, #2, #3. PLEASE ALSO ADJUST AWG AS
 NEEDED.310.16,240.4
  
 49)NOTE: PLEASE LABEL ALL TRANSFORMERS
 ON RISER AS INDICATED ON PANEL
 SCHEDULES.
 215.5
  
 50)NOTE: PLEASE VERIFY THE USE OF WHAT
 APPEARS TO BE TANDEM BRKRS IN PANELS IN
 THIS NEW CONSTRUCTION PROJECT??
 THIS IS ONLY A NOTE.
  
 51)NOTE: PLEASE PROVIDE A DISCONNECT
 DETAIL INCLUDING SIZE ETC FOR ROOF TOP
 UNITS. THIS MAY BE A "TYPICAL" DETAIL
 FOR EACH SIZE IF NOT ALL THE SAME.
 215.5,440.11
  
 52)NOTE: PLEASE SEE A BATTERY BACK UP LT
 FIXTURE WILL BE REQUIRED IN THE MAIN
 ELECTRICAL RM(S), PUMP RMS, FIRE COMMAND
 RM, ELEVATOR EQUIPMENT RMS.
 700.16,700.12E,
  
 53)NOTE: PLEASE SEE FAIR HOUSING ACT
 REGULATIONS, 24 CFR 100.205 WITH RESPECT
 TO THE LOCATIONS OF "ALL" ELECTRICAL
 DEVICES, CONTROLS.
 A NOTE IS LOCATED ON "GEN NOTES" WHICH
 MENTIONS THE HEIGHTS FO RECEPTS AND
 SWITCHES, HOWEVER THIS SHOULD REFLECT
 FHAR ETC AS NOTED ABOVE.
  
 54)NOTE: PLEASE SEE THE AMENITY DECK
 DETAILS COULD NOT BE LOCATED IN SETS.
 PLEASE SEE E2.06 WHICH ONLY SEEMS TO
 INDICATE A PARTIAL AREA SHOWN.
 PLEASE SEE NO ELECTRICAL SHOWN FOR
 LIGHTING ETC?
 PLEASE SEE LS 101 7.8 AND 7.9 WHICH
 REQUIRES MEANS OF EGRESS LIGHTING TO THE
 PUBLIC RIGHT OF WAY.; THIS WOULD INCLUDE
 EMERGENCY LIGHTING AS REQUIRED.
 PLANS NOW SHOW A SEPARATE PHASE LINE, AS
 GARAGE WAS TO BE BUILT WITH PHASE ONE
 BLDG AND DID NOT SHOW GARAGE WITH PHASE
 LINE DOWN THE CENTER OF THE GARAGE.
  
 ** NOTE: PLEASE SEE MANY OF THE ABOVE
 ITEMS WERE REDLINED ON ONE SET FOR AREAS
 OF NOTES ABOVE.
  
 ** NOTE: PLEASE SEE POSSIBLE NOTES FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS AND DESIGN.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW ONCE ALL REVIEWS ARE COMPLETED.
 IF THERE ARE NAY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  
  
  
  
2006-01-26 00:00:00IN PROGRESS
2006-01-25 00:00:00REVIEW STARTED, IN PROGRESS.
 PLANS REVIEW STOPPED. NOTES TO FOLLOW,
 AS REVIEW IS NOT COMPLETE.
2006-01-24 00:00:00 
  
 I ROLL OF MEP'S AND I SUBMITTAL BOOK IN
 ELECTRICAL FOR REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2006-03-10 Cont ID  
Sent By mamini Date 2006-03-10 Time 14:09 Rev Time 1.00
Received By mamini Date 2006-03-10 Time 14:09 Sent To  
Notes
2006-03-10 00:00:00PASSED:
  
 1. SEE PERMIT # 04110964 AND O4120334
 FOR UNDERGROUND UTILITIES AND SITE WORK.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-11-20 Cont ID  
Sent By mwennerg Date 2006-11-20 Time 14:19 Rev Time 0.00
Received By mwennerg Date 2006-11-20 Time 14:19 Sent To  
Notes
2006-11-20 14:48:57***DENIED***
  
 PLEASE NOTE THAT IN SOME CASES WHERE THE ENGINEER
 ACKNOWLEDGED WITH RESPONSE LETTER, IT WOULD HELP
 EXPEDITE THE PLAN REVIEW PROCESS IF THE SHEET NUMBER IS
 IDENTIFIED IN ADITION TO THE RESPONSE.
  
 COMMENT
  
 1) OK
  
 2) OK
  
 3) OK
  
 4) OK
  
 5) CD SHEETS STILL ILLUSTRATE (2) STAIRWELL #2. IS THIS
 CORRECT?
  
 6) PLEASE INDICATE SHEET NUMBER.
  
 7) OK
  
 8) OK
  
 9) OK
  
 10) OK
  
 11) PLEASE INDICATE SHEET NUMBER
  
 12) SHEET CD-10 STILL REFERENCES THE 1999 EDITION.
  
 13) PLEASE INDICATE SHEET NUMBER
  
 14) OK PLEASE INDICATE SHEET NUMBER
  
 15) OK
  
 16) OK
  
 17)
  
 18) NOT ADDRESSED IN RESPONSE LETTER.
  
 19) NOT ADDRESSED IN RESPONSE LETTER.
  
 20) OK
  
 21) OK
  
 22) OK
  
 23) OK
  
 24) OK
  
 25) OK
  
 26) OK
  
 27) OK
  
 28) OK
  
 29) OK
  
 30) OK
  
 31) OK
  
 32) A SMOKE CONTROL SYSTEM IS MENTIONED IN LETTER FROM
 ATLAS. PLEASE CLARIFY IF THIS IS REFERENCING STAIRWELL
 PRESSURIZATION?
  
 33) OK
  
 34) OK
  
 35) OK
  
 36) NOT PROVIDED OR UNABLE TO LOCATE.
  
 37) OK
  
 38) OK
  
 39) OK
  
 40)OK
  
 41)OK
  
 42) OK
  
 43) NOTE ADDED THAT SD HAVE BEEN ADDED TO SHEETS.
 PLEASE IDENTIFY SHEETS AS UNABLE TO LOCATE.
  
 44) OK
  
 45) OK
  
 46) DEVICE STILL NOT SHOWING INSIDE UNIT.
  
 47) OK PLEASE IDENTIFY SHEET NUMBER
  
 48) OK PLEASE IDENTIFY SHEET NUMBER
  
 49) OK
  
 50) PLEASE FOLLOW CRITERIA IN ACCORDANCE WITH NFPA 13,
 2002 REF: ELECTRICAL VAULTS.
  
 51) OK
  
 NEW COMMENTS:
  
 1) NFPA 101 AND NFPA 1 2003 EDITIONS TO BE REFERENCED.
 SHT CD-10
  
 2) NFPA 72, 2002 EDITION TO BE REFERENCED. SHT CD-10

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-03-01 Cont ID  
Sent By mwennerg Date 2006-03-01 Time 13:32 Rev Time 0.00
Received By mwennerg Date 2006-03-01 Time 13:32 Sent To  
Notes
2006-03-01 00:00:00******DENIED******
  
 1) FIRE HYDRANTS SHALL BE FULLY
 OPERATIONAL PRIOR TO, DURING AND AFTER
 CONSTRUCTION.
  
 2) CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
 3) PARKING GARAGE SHALL COMPLY WITH
 APPLICABLE BUILDING CODES, AND NFPA 88A.
  
  
 4) KNOX BOXES ARE REQUIRED TO BE
 INSTALLED WITH APPROPRIATE KEYS PRIOR TO
 FINAL INSPECTION.
  
 5) ARE STAIRWELLS NUMBERED CORRECTLY ON
 CD SHTS?
  
 6) NFPA 101, AND NFPA 1, 2003 EDITIONS
 SHALL BE REFERENCED AFTER JAN. 1, 2005.
  
 7) ALL REQUIREMENTS FOR HIGHRISE
 BUILDINGS SHALL BE MET, AND BE IN
 COMPLIANCE WITH NFPA 101, CHAPTER 11.
  
 8) PLEASE INDICATE ON PLANS THAT ALL
 WALKING SURFACES SHOWN ON SHT CD-03 ARE
 SLIP RESISTANT.
  
 9) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENT FOR HANDRAILS AND GUARDS.
  
 10) MAXIMUM TRAVEL DISTANCE SHALL NOT
 EXCEED 250' IN ACCORDANCE WITH NFPA 101,
 SECTION 30.2.6.4.
  
 11) NFPA 72, 2002 EDITION TO BE
 REFERENCED.
  
 12) NFPA 13, 2002 EDITION SHALL BE
 REFERENCED.
  
 13) TEMPORARY STANDPIPES ARE REQUIRED
 WHEN THE BUILDING REACHES 3 STORIES OR
 30' IN HEIGHT.
  
 14) AT LEAST (2) FIRE DEPARTMENT
 CONNECTIONS ARE REQUIRED ON HIGHRISE
 BUILDINGS. OK ON FIRE SPRINKLER SITE
 PLAN.
  
 15) LOCKING KNOX BOX CAPS REQUIRED ON
 ALL FIRE DEPARTMENT CONNECTIONS.
  
 16) DUCT SMOKE DETECTORS REQUIRED ON
 SUPPLY SIDE OF AIR SYSTEM WITH
 CAPABILITY GREATER THAN 2000 CFM.
  
 17) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL.
  
 18) FIRE ALARM SYSTEM TO BE UL CERTIFIED
 FOR CENTRAL STATION SERVICE.
  
 19) UL CERTIFICATION SHALL BE PROVIDED
 PRIOR TO OR AT THE TIME OF FIRE ALARM
 FINAL INSPECTION.
  
 20) ACCESS ROADS SHALL BE A MINIMUM OF
 20' IN UNOBSTRUCTED WIDTH IN ACCORDANCE
 WITH NFPA 1, CHAPTER 18.
  
 21) AN ADDRESS IS REQUIRED ON BUILDING
 AND SHALL BE A MINIMUM OF 3" IN HEIGHT
 AND CONTRASTING WITH TO THE BACKGROUND.
  
 22) FIRE EXTINGUISHER CABINET ONLY SHOWN
 (1) LOCATION ON FL #1. PLEASE SHOW ALL
 LOCATIONS IN BUILDING.
  
 23) PLEASE INDICATE WHICH AELEVATORS ARE
 SRTETCHER ACCESSIBLE.
  
 24) TACTILE SIGNAGE IS REQUIRED AT
 STAIRWELLS, INDICATING FLOOR NUMBER,
 TOP, BOTTOM AND ROOF ACCESS.
  
 25) NO STORAGE ALLOWED IN ELECTRICAL,
 MECHANICAL OR FIRE COOMAND ROOMS.
  
 26) NO COMBUSTIBLE STORAGE ABOVE
 CEILINGS IF USED AS RETURN AIR PLENUM.
  
 27) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION OF WALLS AND CEILINGS,
 CLASS A,B OR C.
  
 28) HANDRAILS ARE REQUIRED ON BOTH SIDES
 OF STAIRS.
  
 29) STAIRS TO COMPLY WITH APPLICABLE
 BUILDING CODES, AND NFPA 101, CHAPTER 7.
  
  
 30) EXIT STAIRS ARE TO BE KEPT UP WITH
 CONSTRUCTION.
  
 31) ALL SHAFTS LARGE ENOUGH FOR PERSONS
 TO FALL INTO MUST BE MARKED SHAFTWAY
 WITH 6" HIGH LETTERS.
  
 32) THE ANTICIPATED STACK EFFECT NOTE
 WORDING SHALL BE ADDED TO THE MECHANICAL
 PLANS.
  
 33) NO CUTTING OR WELDING OPERATIONS TO
 OCCUR WITHOUT APPROVAL OF THE BUREAU OF
 FIRE PREVENTION AND COMPLIANCE WITH NFPA
 51B.
  
 34) ELEVATORS TO COMPLY WITH ASME/ANSI
 17.1.
  
 35) ELEVATOR LOBBIES SHALL HAVE WARNING
 SIGNS.
  
 36) PLEASE PROVIDE MANUFACTURER SPEC
 SHEETS FOR CO DETECTORS IN PARKING
 GARAGE.
  
 37) SMOKE DETECTORS SHALL BE LOCATED AT
 LEAST 3' FROM HVAC DIFFUSERS.
  
 38) MORE EXIT SIGNS APPEAR TO BE NEEDED
 IN LOBBY AND SURROUNDING AREA.
  
 39) EXITS SIGNS TO BE MOUNTED AT
 DISTANCES NOT TO EXCEED 100' AND MAKE
 EXITING CLEAR AND OBVIOUS.
  
 40) EMERGENCY LIGHTING FACILITIES ARE
 REQUIRED IN ROOMS AND AREAS WHERE
 ARTIFICIAL LIGHTING IS NOT ADEQUATE.
  
 41) ARE EXIT LIGHTS AND EMERGENCY
 LIGHTING FACILITIES MISSING IN THE
 PARKING GARAGE?
  
 42) WHERE ARE THE EXIT SIGNS LOCATED AT
 STAIRS #1&2 LEADING PERSONS I REGARDS TO
 EXITING?
  
 43) SOME CORRIDOR SMOKE DETECTORS APPEAR
 TO BE MISSING FROM ALL SHTS. PLEASE SHOW
 ALL LOCATIONS.
  
 44) FIRE ALARM SYSTEM TO MEET
 SURVIVABILITY REQUIREMENTS OF NFPA 72.
  
 45) FIRE ALARM SYSTEM TO BE CLASS A,
 STYLE D OR FULLY ADDRESSABLE.
  
 46) FIRE ALARM AUDIBLE DEVICE IS MISSING
 IN UNIT B1C ON SHT E.7.01.
  
 47) STANDPIPES CONNECTIONS SHALL BE 2
 1/2" TO 1 1/2" REDUCER WITH CHAINS.
  
 48) IN ADDITION TO ELECTRONIC
 SUPERVISION, CHAIN AND LOCK IS REQUIRED
 ON DOUBLE CHECK DETECTOR ASSEMBLY.
  
 49) PLEASE PROVIDE FURTHER INFORMATION,
 AND MANUFACTURER SPEC SHEETS FOR FIRE
 PUMP.
  
 50) FIRE SPRINKLERS ARE SHOWN IN
 TRANSFORMER VAULT? IS THAT INTENDED OR
 WILL THEY BE ELLIMINATED?
  
 51) PLEASE SHOW LOCATION AND DETAILS FOR
 DOUBLE CHECK DETECTOR ASSEMBLY. NOT
 SHOWN ON FIRE PROTECTION SITE PLAN.
  
 52) DO THE DOOR SWING AT THE ELECTRICAL
 ROOM AND TRASH CHUTE OBSTRUCT THE
 CORRIDOR BY GREATER THAN 1/2 THE WIDTH?
  
 53) SMOKE EVACUATION IS MENTIONED.
 PLEASE PROVIDE FURTHER INFORMATION.
  
 54) SMOKE MANAGEMENT PANELS WHERE
 PROVIDED SHALL PROVIDE A GRAPHIC
 REPRESENTATION OF THE BUILDING. HOA
 SWITCHES WITH NO OVERLAY OF THE BUILDING
 WILL NOT BE ACCEPTABLE.
  
 55) ARE THERE ANY ADA SPEAKER/STROBE
 DEVICES PLANNED FOR ANY LIVING UNITS?
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLANS REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-10-04 Cont ID  
Sent By kstevens Date 2006-10-04 Time 11:45 Rev Time 0.00
Received By kstevens Date 2006-09-13 Time 18:57 Sent To  
Notes
2006-10-04 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 FROM THE PLUMBING REVIEW:
  
  
 1. THE FOLLOWING INFORMATION IS
 REQUIRED FOR THE GAS APPLICATION:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGHTS PER FBC-2004
 FUEL GAS.
 ***RESPONSE NOTED, BUT CORRESPONDING
 LENGTHS NOT SHOWN. FBC-2001 FUEL GAS.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 ***RESPONSE NOTED, BUT INFORMATION SHALL
 BE LOCATED AT RISER WITH REQUIRED INFO.
 SECTION 104.2.1.
  
 C. TYPE OF GAS, (LP OR NATURAL).
 ***RESPONSE NOTED, INFORMATION REQUIRED
 ON PLANS WITH RISER.
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 ***RESPONSE NOTED, BUT TOTAL BTU LOAD OF
 SYSTEM NOT SHOWN. INFORMATION REQUIRED
 ON PLANS WITH RISER.
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ***NO RESPONSE NOT ADDRESSED.
  
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. IF
 2 PSI INDICATE LOCATION OF REGULATORS
 AND SUBMIT MANUF. SPECIFICATION SHEETS
 FOR REGULATORS INDICATING MODEL. IF
 VENTED REGULATORS, INDICATE MATERIAL FOR
 VENTS AND SHOW ROUTING OF PIPING.
 ***NO RESPONSE, NOT ADDRESSED.
  
 I. SUBMIT MANUFACTURE SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ***NO RESPONSE, NOT ADDRESSED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-20 Cont ID  
Sent By adarroug Date 2006-07-20 Time 10:58 Rev Time 0.00
Received By adarroug Date 2006-07-20 Time 10:58 Sent To  
Notes
2006-08-07 00:00:00WAITING FOR "COMM" BD
 TO "COMM" BD#10/PLANS ON RACK-10 ROLLS/3
 BINDERS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-04-22 Cont ID  
Sent By rbrown Date 2006-04-22 Time 14:47 Rev Time 0.00
Received By rbrown Date 2005-11-10 Time 07:50 Sent To  
Notes
2006-04-11 00:00:00COMM BD #36
  
  
2006-01-11 00:00:0012/29/05 PER MR JANOWSKI, PLANS ARE TO
 BE PLACED ON "HOLD" AND NOT TO BE
 REVIEWED UNTIL NEW REVISED PLANS ARE
 BROUGHT IN. SEE ROBERT BROWN OR DEWEY
 PALMER.
2005-12-05 00:00:00TO "COMM" BD#36/PLANS ON RACK/ 6 ROLLS
2005-11-10 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-10-10 Cont ID  
Sent By rregueir Date 2006-10-10 Time 17:30 Rev Time 0.00
Received By rregueir Date   Time   Sent To  
Notes
2006-10-04 00:00:00-----------------DENIED-----------------
 NOTE:THESE COMMENTS ARE NUMBERED FOR
 CONTINUITY WITH PREVIOUS PLAN REVIEW
 COMMENTS AND RESPONSES.
  
 FBC 2001
 FBC,M 2001
  
 1. OK
  
 2. PG.A8-10 RESIDENTIAL DOOR SCHEDULE:
 MECHANICAL CLOSET DOORS INDICATES WOOD
 DOORS WITH INTUMESCENT PAINT. ABSENT A
 LISTING FROM AN APPROVED TESTING AGENCY
 SHOWING THIS ASSEMBLY TO BE
 NON-COMBUSTIBLE, IT MUST BE SUBMITTED
 UNDER FBC 103.7.1 ALTERNATE MATERIALS
 AND METHODS.
  
 3. PG.M2-00 EF1 & EF2, PLEASE INDICATE
 WHETHER THESE FANS ARE TO RUN CONTINUOUS
 OR BE THERMOSTATICALLY CONTROLLED. WILL
 THEY WORK IN ANY WAY IN CONJUNCTION WITH
 GEF1 OR CO SENSORS?
  
 4. OK
  
 5. OK
  
 6. PG.M2-01 NO LONGER SHOWS A CONDENSER
 LOCATED INDOORS. HOWEVER, STORAGE ROOMS
 X47 AND X48 DO NOT SHOW WHAT EQUIPMENT
 IS TO BE USED. IF THEY ARE SPLIT SYSTEMS
 THERE IS NO LOCATION OF CONDENSERS SHOWN
 ON PLAN.
  
 7. PG.M3-00 UNIT 'D1' SHOWS A 30X12
 RAFG. IS THIS A TRANSFER GRILL THROUGH A
 WALL OR IS IT GOING INTO A PLENUM
 CEILING?PER 601.4 A TRANSFER GRILL
 WOULD REQUIRE A MINIMUM OF 450 SQ.IN.
 SINCE IT IS RETUNING 900 CFM. IF THERE
 IS A CEILING PLENUM, THERE CAN BE NO
 EXHAUST DUCTS UNDER POSITIVE PRESSURE IN
 THE PLENUM PER 601.3.
  
 8. OK
  
 9. PLEASE PROVIDE DETAIL/SPECS FOR TYPE
 OF DRYER VENT HOOD (WALL CAP) TO BE
 USED. TYPE OF WALL CAP MAY IMPACT
 ALLOWABLE DRYER DUCT LENGTH PER DRYER
 MANUFACTURER'S INSTALLATION INSTRUCTIONS.
  
 10. SUBMITTAL DATA FOR GOODMAN
 RESIDENTIAL A/C EQUIPMENT ONLY SHOWS
 COPPER LINE SIZES UP TO A LENGTH OF 35'.
 PROVIDE DOCUMENTATION SIGNED AND SEALED
 BY A GOODMAN ENGINEER (NOT A SALESMAN)
 AFFIRMING SUITABILITY OF SPECIFIED
 EQUIPMENT FOR COPPER LINE LENGTH AND
 VERTICAL DISTANCE BETWEEN AIR HANDLERS
 AND CONDENSING UNITS. PROPER COPPER LINE
 SIZES FOR THIS APPLICATION ARE ALSO
 REQUIRED.
  
 11. OK
  
 12. PG.M4-00 FBC 412.5 SMOKE CONTROL
 REQUIRES REMOVAL OF THE PRODUCTS OF
 COMBUSTION (SMOKE) VIA NATURAL OR
 MECHANICAL VENTILLATION. PLEASE CLARIFY
 HOW SMOKE IS TO BE REMOVED FROM EFFECTED
 AREAS. THE SYSTEM DESCRIBED ON THIS PAGE
 DOES NOT APPEAR TO BE RELATED IN ANY WAY
 TO MEETING THE REQUIREMENTS OF FBC
 412.5.
  
 13. OK
  
 14. OK
  
 15. PG.M5-01 DETAIL #11 STILL SHOWS DUCT
 SMOKE DETECTOR IN R/A PLENUM. DUCT SMOKE
 DETECTORS ARE TO BE INSTALLED IN SUPPLY DUCTS
 PER FBC,M 606.2.1.
  
 PLEASE NOTE: THIS REFERS TO DETAIL #11, NOT DETAIL #4.
  
 16. OK
  
 17. OK
  
 18. OK
  
 19. PG.M2-00 AHU 1 SHOWS 16X14 SUPPLY AND
 10" ROUND O/A DUCTS PENETRATING RATED WALLS. IT
 IS NOT CLEAR ON PLANS IF AHU 1 O/A INTAKE
 COMPLIES WITH FBC,M 401.5.1 INTAKE OPENINGS.
 ITS PROXIMITY TO A PARKING SPACE INDICATES IT IS
 IN THE PARKING GARAGE, WHICH IS A PROHIBITED LOCATION.
  
 20. PG.M2-00 AHU 1 DOES NOT SHOW ANY
 RETURN AIR FROM LOBBY OR MAIL ROOM AREAS.
  
 21. PG.M2-00 6" ROUND SUPPLY TO MAIL ROOM
 SHOWS A FIRE DAMPER IN-LINE.HOW WILL FIRE
 DAMPER ACCESS BE PROVIDED IN FLEXIBLE DUCT?
  
 22. PG.M2-00 AHU 2 DOES NOT SHOW ANY
 RETURN AIR FROM SUNDRIES SHOP.
  
 23. PG.M3-00 - M3-02 UNITS C,D1,D2,D3,
 E,F,G,P1,P2,P3 SHOW TRANSFER GRILLS LOW ON
 ONE SIDE OF WALL AND HIGH ON OTHER SIDE. IS
 THE INTENTION TO USE THE STUD WALL CAVITY TO
 CONVEY RETURN AIR FROM BEDROOMS? IF SO,
 PLEASE PROVIDE DETAIL SHOWING COMPLIANCE
 WITH BOTH FBC,M 602.3(5) AND FBC CH.13
 SECTION 610.1.ABC.3.6.
  
 24. PG.M4-00 NO INFORMATION IS PROVIDED
 AS TO TYPE OF DUCT TO BE USED IN SHAFTS OR
 THE REQUIRED THICKNESS/R-VALUE OF DUCT
 INSULATION. ENSURE DIMENSIONS OF SHAFTS ARE
 LARGE ENOUGH TO ACCOMODATE DUCT INSULATION
 DIMENSIONS WITH SUPPORTS AND STANDING
 SEAMS AT DUCT JOINTS.
  
 25. PG.M4-00 RTU SYSTEMS 1,2,3 SHOW
 24X24 DIFFUSERS IN CORRIDORS. WHAT SIZE
 NECKS AND DUCT CONNECTIONS ARE NEEDED
 TO ACHIEVE DESIRED CFM?
  
 26. PG.M4-00 PLEASE GIVE DETAILS AS TO HOW
 DESIGN CFM IS TO BE ACHIEVED DURING
 CORRIDOR PRESSURIZATION MODE. EXAMPLE:
 RTU 1 IS RATED FOR 8,600 CFM. IF ALL SMOKE
 DAMPERS EXCEPT TWO (FLOOR ABOVE AND FLOOR
 BELOW) ARE CLOSED, WILL FAN SPEED BE ADJUSTED
 TO PROVIDE CFM CALLED FOR ON PLAN DURING THIS
 MODE? WILL CORRIDOR DUCT BE CONSTRUCTED SO
 AS TO WITHSTAND THE ADDITIONAL
 VOLUME/PRESSURE?
  
 27. PG.M4-00 RTU SYSTEMS 2,3 SHOW ONE
 24X24 DIFFUSER ON EACH FLOOR BUT THERE IS A
 NOTE AT THE LOCATION WHICH SAYS "(QTY 2)".
 PLEASE CLARIFY.
  
 28. PG.M4-01 RD-1 AND RD-2 REMOVE FIRE
 DAMPERS FROM THESE LOCATIONS AS A CLOSED
 FIRE DAMPER BLADE WILL ADVERSELY EFFECT THE
 PERFORMANCE OF THE STAIRWELL PRESSURIZATION
 SYSTEM.
  
 29. PG.M4-01 SPF-1 AND SPF-2 REQUIRE DUCT
 SMOKE DETECTORS PER FBC,M 606.2.1 AS
 THEY EXCEED 2,000 CFM.
  
 30. PG.M5-00 PLEASE PROVIDE ALL RELEVANT SUB-
 MITTAL DATA FOR EXHAUST FANS AND RTUS.
  
 31. PG.M5-01 DETAIL 4 AND 9, PLEASE PROVIDE
 DETAILS FOR ATTACHING CURBS, STANDS, DUCTS AND
 EQUIPMENT ON ROOF PER FBC,M 301.13.NOTE:
 THE CITY OF WEST PALM BEACH IS IN THE 140 MPH
 ZONE PER FBC 1606.
  
 32. PG.M5-01 ALL FIR OR FIRE/SMOKE DAMPERS ARE
 TO BE UL 555 LISTED AND INSTALLED PER MANUFACTURER'S
 INSTALLATION INSTRUCTIONS PER FBC,M 607.1.2.
  
 REVIEW BY: RONALD J REGUEIRO
 561-805-6734
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-02-13 Cont ID  
Sent By pkrauss Date 2006-02-13 Time 08:07 Rev Time 0.00
Received By pkrauss Date 2006-02-13 Time 08:07 Sent To  
Notes
2006-02-13 00:00:00DENIED:2001 FLORIDA BUILDING CODE
  
 1.PLAN SHEET A6-70 DETAIL 5 & 8
 MECHANICAL EQUIPMENT RACK DETAIL,
 DETAILS DO NOT INDICATE THE ATTACHMENT
 TO THE STRUCTURE.PLEASE SHOW
 COMPLIANCE WITH 2001 FMC 301.13 &
 CHAPTER 16 OF THE 2001 FBC.
  
 2.PLAN SHEET A8-10 RESIDENTIAL DOOR
 SCHEDULE, THE MECHANICAL CLOSET
 REFERENCES NOTE #9 WHICH STATES THE
 INTERIOR OF THE CLOSET DOOR & FRAME WILL
 BE PAINTED WITH INTUMESCENT PAINT.IS
 THE INTENT OF THE PAINT TO CLASSIFY THE
 DOOR AS "NON-COMBUSTIBLE"?WILL THE
 DOOR BE NON-COMBUSTIBLE WITHOUT THE
 PAINT?
  
 3.PLAN SHEET M2-00 THE OUTSIDE AIR TO
 THE MAIN ELECTRICAL ROOM IS SUPPLIED
 FROM THE GARAGE & LOADING AREA?PLEASE
 CLARIFY.PLAN SHEET A9-01 INDICATES A 1
 HR SEPARATION.PER 2001 FMC 401.5.1,
 INTAKE OPENINGS SHALL BE LOCATED A
 MINIMUM OF 10 FT FROM HAZARDOUS OR
 NOXIOUS CONTAMINANT SUCH AS PARKING LOTS
 AND LOADING DOCKS.
  
 4.PLAN SHEET M2-00 INDICATES A 32" X
 12" LOUVER BETWEEN THE PUMP ROOM & THE
 DOMESTIC PUMP ROOM. PLAN SHEET A9-01
 INDICATES A 1 HR SEPARATION BETWEEN
 THESE ROOMS.PLEASE CLARIFY.THIS ALSO
 EFFECTS THE EXHAUST FROM THE PUMP ROOM &
 THE MAIN ELECTRICAL ROOM.
  
 5.PLAN SHEET M2-00 EXHAUST DUCT FROM
 MENS ROOM PENETRATES 1 HR SEPARATION TO
 THE FIRE COMMAND ROOM.SHOW COMPLIANCE
 WITH 2001 FMC 607.1.3 (3) ITEMS 1
 THROUGH 4.
  
 6.PLAN SHEET M2-01 AHU & CONDENSOR
 LOCATED IN THE GARAGE.PLEASE PROVIDE
 MANUFACTURERS SUBMITTAL/INSTALLATION
 DATA, FOR INSTALLATION OF THE CONDENSER
 LOCATED INDOORS.
  
 7.PLAN SHEET M3-00 THROUGH M3-02, PER
 2001 FMC 601.4 RETURN AIR REQUIRED FROM
 ROOMS SEPARATED FROM THE CENTRAL RETURN
 BY DOORS.TRANSFER GRILLES OR JUMPERS
 SHALL BE SIZED IN ACCORDANCE WITH 2001
 FMC 601.4 EXCEPTION 1 THROUGH 3.
  
 8.PLEASE INDICATE MATERIAL OF DRYER
 DUCT.SHOW COMPLIANCE WITH 2001 FMC
 504.2. & 504.4.
  
 9.PLAN SHEET M3-00 THROUGH M3-02,
 DRYER EXHAUST APPEARS TO EXCEED THE
 MANUFACTURERS REQUIREMENTS WITH THE
 OFFSETS.PLEASE CLARIFY.
  
 10.PLEASE PROVIDE MANUFACTURER
 SUBMITTAL DATA FOR THE RESIDENTIAL A/C
 EQUIPMENT.PLEASE VERIFY MAXIMUM LENGTH
 OF REFRIGERANT LINES.INDICATE SIZING.
  
 11.REFRIGERANT LINES SHALL BE IN A
 VENTED SHAFT IN ACCORDANCE WITH ASHRAE
 15-92.
  
 12. PLAN SHEET M4-00 REFERENCES 2001 FBC
 412.5 FOR THE SMOKE CONTROL.PLEASE
 INDICATE WHICH METHOD WILL BE USED.
 412.5 HAS 3 PRESCRIPTIVE METHODS AND ONE
 ENGINEERED METHOD THAT IS REQUIRED TO
 DEMONSTRATE THE MITIGATION OR REMOVAL OF
 SMOKE.PLEASE CLARIFY.
  
 13. PLAN SHEET M5-00 APARTMENT DRYER
 DATA UNIT A3 IS INDICATED AS REQUIRING A
 BOOSTER FAN OR ARCHITECTURAL REDESIGN.
 PLEASE NOTE, BOOSTER FANS MUST BE
 SUBMITTED UNDER 103.7.1, ALTERNATE
 MATERIALS & METHODS.PLEASE PROVIDE ALL
 PERTINANT INFORMATION.PROVIDE LETTER
 FROM AN ENGINEER EMPLOYED BY THE
 MANUFACTURER STATING THE INSTALLATION OF
 A DRYER BOOSTER FAN WILL NOT VOID THE
 WARRANTY OF THE DRYER.
  
 14. ALL LIFE SAFETY ITEMS AS WELL AS THE
 GARAGE VENTILATION FANS AND CO SENSORS
 SHALL HAVE THE CAPABILITY TO OPERATE
 UNDER EMERGENCY POWER.
  
 15. PLAN SHEET M5-01 DETAIL 11 INDICATES
 DUCT SMOKE DETECTOR IN THE RETURN AIR
 PLENUM.PER 2001 FMC 606.2.1, SMOKE
 DETECTORS SHALL BE INSTALLED IN THE
 SUPPLY AIR DUCT.
  
 16. PLEASE CLARIFY CONDENSATE, PLAN
 SHEET P4-05 & P4-06 DOES NOT INDICATE
 WHERE THE CONDENSATE TERMINATES (STORM
 DRAIN OR SANITARY).PLEASE CLARIFY. PER
 CITY CODE SEC.90-125 PROHIBITIONS &
 LIMITATIONS OF DISCHARGE (5), CONDENSATE
 SHALL NOT DISCHARGE INTO SANITARY.
 CONDENSATE SHALL TERMINATEINTO THE
 STORM DRAIN SYSTEM.PLEASE NOTE,
 CONDENSATE PIPING IN THE AHU CLOSET
 SHALL BE N0N-COMBUSTIBLE (NO PVC) PER
 2001 FMC 602.2.1.
  
 17. TRASH CHUTE SHALL BE SPRINKLERED IN
 ACCORDANCE WITH 2001 FBC 705.2.4.6.
  
 18. PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS IN ACCORDANCE WITH TABLE
 403.3 FOR ALL AREAS (I.E. RESIDENCE &
 COMMON AREAS).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-10-03 Cont ID  
Sent By kstevens Date 2006-10-03 Time 09:27 Rev Time 0.00
Received By kstevens Date 2006-09-13 Time 09:27 Sent To  
Notes
2006-10-03 00:00:00*****BECAUSE OF THE SYSTEM LIMITIONS,
 THE SECOND REVIEW NOTES WILL BE SPLIT UP
 INTO TWO REVIEW STOPS. THE FOLLOWING IS
 THE COMMENTS FROM THE SECOND REVIEW.
  
 DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
 FHA- 98DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 CITY MUNICIPAL CODE WPB
  
 *************NEW COMMENTS**************
  
 1B. SHTS P2-00 & P2-01 NO CD/5 SHOWN.
 PLEASE CORRELATE RISER WITH FLOOR PLAN.
 SECTION 104.2.1.
  
 2B. SHT P2-02B NO SECONDARY DRAINS
 SHOWN. - NO DRAINAGE SHOWN IN THE TENNIS
 COURT AREA, NOR IN THE AMENITY DECK AREA
 AS REQUIRED IN SECTIONS 1101.2, 1107.1,
 1107.2 & 1107.3.
  
 3B. SHT P2-02B 3 DRAINS SHOWN ARE NOT
 REFLECTED ON THE RISER DIAGRAM. PLEASE
 CORRELATE DRAINS WITH RISER DIAGRAM.
 SECTION 104.2.1.
  
 4B. SHT P2-02B TOTAL AREA OF TERRACE
 LEVEL DOES NOT APPEAR TO BE SHOWN ON THE
 FLOOR PLAN. PLEASE CLARIFY. SECTION
 104.2.1.
  
 5B. TWO CD/5 RISERS SHOWN. PLEASE
 CLARIFY. SECTION 104.2.1.
  
 6B. SHT P4-00 RISER SV1 DOES NOT REFLECT
 THE FLOOR PLAN 1ST FLOOR UNDERGROUND.
 SV1 ON THE FLOOR PLAN FOR ONE RISER
 SHOWS AN OFFSET, BUT ANOTHER SV1 ON THE
 FLOOR PLAN DOES NOT SHOW AN OFFSET. THE
 RISER DOES NOT REFLECT THE FLOOR PLAN
 AFTER THE OFFSET. RISERS SHALL BE
 SPECIFIC TO THE FLOOR PLAN. DIFFERENT
 FLOOR PLANS REQUIRE DIFFERENT RISERS.
 SECTION 104.2.1.
  
 7B. SHT P4-00 RISER SV2 DOES NOT REFLECT
 THE FLOOR PLAN FOR THE 1ST FLOOR
 UNDERGROUND. CORRELATE RISER AND FLOOR
 PLAN. SECTION 104.2.1.
  
 8B. SHT P4-00 RISER SV3 DOES NOT REFLECT
 THE FLOOR PLAN. ALSO OFFSET ON ONE FLOOR
 PLAN RISER BUT NOT THE OTHER. OFFSET
 PIPING AND PIPING FOR 12 THRU 16 FLOORS
 DO NOT REFLECT THE FLOOR PLAN. CORRELATE
 RISER AND FLOOR PLAN. SECTION 104.2.1.
  
 9B. SHT P4-00 RISER SV4 DOES NOT REFLECT
 THE FLOOR PLAN. CORRELATE THE RISER AND
 FLOOR PLAN. SECTION 104.2.1.
  
 10B. SHT P4-00 SV5 DOES NOT REFLECT THE
 FLOOR PLAN. SOME ALSO SHOW TUBS WHILE
 THE OTHERS SHOW SHOWERS. OFFSET PIPING
 ONLY SHOWN ON THE FLOOR PLAN FOR ONE.
 PIPING AFTER THE OFFSET DOES NOT REFLECT
 THE FLOOR PLAN. CORRELATE RISER AND
 FLOOR PLANS. SECTION 104.2.1.
  
 11B. SHT P4-00 RISER SV6 2ND THRU 5TH
 FLOORS NOT PIPED THE SAME ON ALL FLOOR
 PLANS. 2 FLOOR PLANS RELFECT THE FLOOR
 PLAN, BUT THE OTHER DOES NOT. TYPICAL
 RISERS DO NOT WORK AS THE FLOOR PLANS
 ARE DIFFERENT. RISER SHALL REFLECT THE
 FLOOR PLAN. SECTION 104.2.1.
  
 12B. SHT P4-00A SV7 DOES NOT REFLECT THE
 OFFSET ON THE FLOOR PLAN, AND IS NOT
 SHOWN ON THE FIRST FIVE FLOORS.
 CORRELATE THE RISER AND THE FLOOR PLAN.
 SECTION 104.2.1.
  
 13B. SHT P4-00A TWO SV9 RISERS SHOWN.
 NEITHER INDICATE A FIRST FLOOR BATHROOM.
 ONE FLOOR PLAN SV9 SHOWS A BATHROOM.
 DOES NOT REFLECT THE FLOOR PLAN AT
 OFFSET. PLEASE CLARIFY. SECTION 104.2.1.
  
 14B. SHT P4-00A SV10 IS NOT INDICATED ON
 THE FLOOR PLAN OF SHT P2-00 AND DOES NOT
 REFLECT THE FLOOR PLAN AT THE OFFSET.
 PLEASE CORRELATE RISER AND FLOOR PLAN.
 SECTION 104.2.1.
  
 15B. SHT P4-00A SV12 OFFSET ON FLOOR
 PLAN NOT SHOWN ON THE RISER DIAGRAM.
 CORRELATE RISER AND FLOOR PLAN. SECTION
 104.2.1.
  
 16B. SHT P4-00B SV13 DOES NOT REFLECT
 THE FLOOR PLAN AT THE FIRST FLOOR
 UNDERGROUND, AND VENT NOT SHOWN ON THE
 11TH THRU 16TH FLOOR. FLOOR PLAN SHOWS
 ONE SV13 CONNECTING TO SHOWER DRAIN.
 CORRELATE RISER AND FLOOR PLAN. SECTION
 104.2.1.
  
 17B. SHT P4-00B SV14 DOES NOT REFLECT
 THE FLOOR PLAN 1ST FLOOR UNDERGROUND.
 ONE FLOOR PLAN SHOWS NO FIXTURES THRU
 THE FIRST FIVE FLOORS. DOES NOT REFLECT
 AT THE OFFSET, SHOWN AS SHOWERS ON FLOOR
 PLAN 11TH THRU 16TH FLOORS FOR ONE RISER
 AND NOT SHOWN AS VTR ON ONE RISER.
 PLEASE CORRELATE RISER AND FLOOR PLAN.
 SECTION 104.2.1.
  
 18B. SHT P4-00B SV15 DOES NOT REFLECT
 THE FLOOR PLAN 1ST FLOOR UNDERGROUND,
 AND ONE RISER SHOWN ON THE FLOOR PLAN
 INDICATES FIXTURES ON THE FIRST FLOOR.
 PLEASE CORRELATE RISER AND FLOOR PLAN.
 SECTION 104.2.1.
  
 19B. SHT P4-00B SV16 DOES NOT REFLECT
 THE FLOOR PLAN 1ST FLOOR UNDERGROUND.
 FLOOR PLANS ALSO SHOWS NO FIXTURES ON
 FIRST FLOOR. CORRELATE RISER WITH FLOOR
 PLANS. SECTION 104.2.1.
  
 20B. SHT P4-00B SV17 NOT FOUND ON THE
 FIRST FLOOR PIPING LAYOUT SHT P2-00.
 CORRELATE RISER AND FLOOR PLAN. SECTION
 104.2.1.
  
 21B. SHT P4-01 RISER P1 OFFSET VENTS
 REQUIRED. SECTIONS 915.2 & 915.3.
  
 22B. SHT P4-01 RISER P2 RISER SHOWS NO
 BRANCH LINE FOR 5TH FLOOR. DOES NOT
 REFLECT THE FLOOR PLAN. CORRELATE RISER
 AND FLOOR PLAN. SECTION 104.2.1.
  
 23B. SHT P4-01 RISER P3 REFLECTS ONE
 FLOOR PLAN BUT NOT THE OTHER. FLOOR
 PLANS ARE NOT TYPICAL. SEPARATE RISERS
 REQUIRED. SECTION 104.2.1.
  
 24B. SHT P4-01 RISER P4 CHANGES TO P15
 ONE FLOOR PLAN FOR ONE P4. PLEASE
 CORRELATE RISER AND FLOOR PLAN. SECTION
 104.2.1.
  
 25B. SHT P4-01 RISER P5 DOES NOT REFLECT
 THE FLOOR PLAN 1ST FLOOR. CORRELATE THE
 RISER AND THE FLOOR PLAN. SECTION
 104.2.1.
  
 26B. SHT P4-01 RISERS P7, (10), SOME
 DIFFER FROM OTHERS. SOME DO NOT SHOW
 FIXTURES ON THE FIRST FLOOR. RISER CAN
 NOT BE TYPICAL IF FLOOR PLAN IS NOT THE
 SAME. PLEASE CORRELATE RISERS TO FLOOR
 PLAN. SECTION 104.2.1.
  
 27B. SHT P4-01 RISER P8 ONE RISER STARTS
 ON THE 1ST FLOOR AND IS NOT SHOWN ON THE
 6TH FLOOR & OFFSET DOES NOT REFLECT THE
 FLOOR PLAN. CORRELATE RISER AND FLOOR
 PLANS. SECTION 104.2.1.
  
 28B. SHT P4-01 RISER P9 RISER DOES NOT
 REFLECT THE FLOOR PLAN ON ONE 1ST THRU
 5TH FLOORS NO FIXTURE BRANCH. NOT SHOWN
 ABOVE THE 5TH FLOOR AT ALL ON ONE FLOOR
 PLAN. CORRELATE RISER AND FLOOR PLANS.
 SECTION 104.2.1.
  
 29B. SHT P4-01A RISER P15 CHANGES TO P4
 ON SHT P2-01. PLEASE CORRELATE RISER AND
 FLOOR PLAN. SECTION 104.2.1.
  
 30B. SHT P4-01A RISER P17 DOES NOT
 REFLECT THE FLOOR PLAN AT THE FIRST
 FLOOR. CORRELATE RISER AND FLOOR PLAN.
 SECTION 104.2.1.
  
 31B. SHT P4-01B RISER P18 NOT INDICATED
 ON FLOORS 1 THRU 5. CORRELATE RISER AND
 FLOOR PLAN. SECTION 104.2.1.
  
 32B. SHT P4-01B RISER P20 OFFSET VENTS
 REQUIRED. SECTIONS 915.2 & 915.3.
  
 33B. SHT P4-02 RISER 11 DOES NOT REFLECT
 THE FLOOR PLAN 6TH FLOOR. OFFSET NOT
 SHOWN. CORRELATE RISER AND FLOOR PLAN.
 SECTION 104.2.1.
  
 34B. SHT 4-02 RISER 1/2 DOES NOT REFLECT
 THE FLOOR PLAN 1ST & 2ND FLOORS.
 CORRELATE RISER AND FLOOR PLAN. SECTION
 104.2.1.
  
 35B. SHT P4-02 RISER CONNECTIONS TO THE
 MAIN FOR RISERS 9/10 & 11 DO NOT REFLECT
 THE FLOOR PLAN. CORRELATE THE RISER AND
 THE FLOOR PLAN. SECTION 104.2.1.
  
 36B. SHT P4-02 RISER CONNECTIONS TO MAIN
 FOR RISERS 17, 18/19, & 20/21 DO NOT
 REFLECT THE FLOOR PLAN. PLEASE CORRELATE
 RISERS AND FLOOR PLAN. SECTION 104.2.1.
  
 37B. SHT P4-03 RISER 18/19 DOES NOT
 REFLECT THE FLOOR PLAN. PLEASE CORRELATE
 THE FLOOR PLAN AND RISERS. SECTION
 104.2.1.
  
 38B. SHT P4-03 RISER 20 DOES NOT REFLECT
 THE FLOOR PLAN 7TH THRU 10TH FLOORS.
 OFFSET NOT SHOWN. CORRELATE RISER AND
 FLOOR PLAN. SECTION 104.2.1.
  
 39B. SHT P4-03 RISER 20/21 DOES NOT
 REFLECT THE FLOOR PLAN 1ST THRU 6TH
 FLOORS. CORRELATE RISER AND FLOOR PLAN.
 SECTION 104.2.1.
  
 40B. SHT P4-04 RD4 RISER DOES NOT
 REFLECT THE FLOOR PLAN. OFFSETS NOT
 SHOWN. CORRELATE THE RISER WITH THE
 FLOOR PLAN. SECTION 104.2.1.
  
 41B. SHT P4-04 RD6 RISER DOES NOT
 REFLECT THE FLOOR PLAN. OFFSET NOT
 SHOWN. CORRELATE THE RISER AND THE FLOOR
 PLAN. SECTION 104.2.1.
  
 42B. SHT P4-04 RD16 RISER DOES NOT
 REFLECT THE FLOOR PLAN. OFFSET NOT
 SHOWN. CORRELATE THE RISER AND THE FLOOR
 PLAN. SECTION 104.2.1.
  
 43B. SHT P4-05 CD RISER #5 DOES NOT
 REFLECT THE FLOOR PLAN 11TH FLOOR AND
 ABOVE. CORRELATE RISER AND FLOOR PLANS.
 SECTION 104.2.1.
  
 44B. SHT P4-05 CD RISER #2 DOES NOT
 REFLECT THE FLOOR PLAN AT THE 11TH
 FLOOR. OFFSET NOT SHOWN. CORRELATE RISER
 WITH FLOOR PLAN. SECTION 104.2.1.
  
 45B. SHEETS FOR ALL FLOOR PLANS. KEYED
 NOTES ARE NOT SHOWN ON ALL FLOOR PLANS.
 PLEASE CLARIFY. SECTION 104.2.1.
  
 46B. SHT PO-01 CODE REFERENCE TO
 IBC-2000 AND INTERNATIONAL ENERGY
 CONSERVATION CODE 2000 DO NOT APPLY.
 ADOPTED CODE IS THE FBC-2001 PLUMBING
 CODE ONLY. DELETE OTHER REFERENCES.
  
 47B. SHT PO-01 HORIZONTAL STORM DRAINAGE
 PIPING REFERENCES FBC-2004. ADOPTED CODE
 IS FBC-2001.
  
 48B. SHT P2-00 INDICATES SV19 RISER ON
 THE FLOOR PLAN. NO SV19 RISER SUBMITTED.
 PLEASE CLARIFY. SECTION 104.2.1.
  
 49B. SHT P2-00KEYED NOTE #1 HAS BEEN
 CHANGED TO NOTE #3 ON THE FLOOR PLAN AND
 NOTE #3 DOES NOT APPLY. PLEASE CORRELATE
 KEYED NOTES WITH INFORMATION INDICATED
 ON THE FLOOR PLAN. SECTION 104.2.1.
  
 50B. SHT P2-00 THE PIPE SIZE FOR THE
 STORM SYSTEM IS INCORRECT IN SOME
 PLACES. RECHECK ALL PIPE SIZES PER TABLE
 1106.3.
  
 51B. SHT P2-00 NOT ALL KEYED NOTES SHOWN
 ON THE FLOOR PLAN REFLECT THE FLOOR
 PLAN. (EXAMPLE, KEYED NOTE #2 ON THE
 FLOOR PLAN SHOWS A CONDENSATE LINE
 OFFSET, BUT THE KEYED NOTED IN THE INDEX
 STATES "4" STORM DOWN FROM TERACE
 ABOVE"). PLEASE CORRELATE KEYED NOTES
 WITH INFORMATION INDICATED ON THE FLOOR
 PLAN.
  
 52B. SHT P2-01 INDICATES 2ND THRU 5TH
 FLOORS. THERE ARE OFFSETS SHOWN ON THE
 FLOOR PLAN. ARE THESE OFFSETS TYPICAL
 FOR ALL FLOORS? IF NOT THEN FLOOR PLANS
 THAT ARE NOT TYPICAL SHALL BE SUBMITTED
 INDIVIDUALLY AND NOT SHOWN AS TYPICAL.
 (SEE KEYED NOTE #8, "ROUTE PIPING
 SUSPENDED FROM CEILING ON THIS LEVEL".
 LEVEL NOT INDICATED)PLEASE CLARIFY.
 SECTION 104.2.1.
  
 53B. SHT P2-01 SV9 SHOWN IN THE BLOCK
 WALL FOR STAIRWELL #1. PLEASE INDICATE
 HOW THE FIRE RATING WILL BE MAINTAINED
 FOR THE STAIRWELL. ALSO SHOW COMPLIANCE
 WITH SECTIONS 1907.3, 1907.4,
 1907.5(1)(3), AND 1907.3.6(3). SUBMIT A
 DETAIL.
 SECTION 104.2.3.
  
 54B. SHT P2-01 NOT ALL KEYED NOTES SHOWN
 ON THE FLOOR PLAN REFLECT THE FLOOR
 PLAN. (EXAMPLE, KEYED NOTE #2 STATES
 "OFFSET 2" SANITARY DRAIN" AND IS
 INDICATED ON A CONDENSATE LINE).
 CORRELATE KEYED NOTES AND FLOOR PLAN.
 SECTION 104.2.1.
  
 55B. SHT P2-01 SHEET APPEARS TO BE
 INCOMPLETE. SHOW A MATCH LINE AND
 INDICATE WHERE THE REST OF THE FLOOR
 PLAN CAN BE LOCATED, OR SUBMIT A SHEET
 THAT IS 100% COMPLETE. SECTION 104.2.1.
  
 56B. SHT P2-01 RD11 SHOWS AN OFFSET ON
 THE FLOOR PLAN THAT IS NOT REFLECTED ON
 THE RISER DIAGRAM. PLEASE CORRELATE THE
 RISER WITH THE FLOOR PLAN. SECTION
 104.2.1.
  
 57B. SHT P2-01 RISER 8, 9, 10 DOES NOT
 INDICATE WHERE THE RISER ROUTES DOWN TO
 THE FLOOR BELOW. PLEASE CLARIFY SECTION
 104.2.1.
  
 58B. SHT P2-01B RECHECK PIPE SIZING AS
 SOME SIZING IS INCORRECT. ALSO SOME AREA
 DRAINS ARE SHOWN AS PLANTER DRAINS AND
 SOME PLANTER DRAINS ARE SHOWN AS AREA
 DRAINS. CORRELATE RISER AND FLOOR PLAN.
 SECTION 104.2.1 AND TABLE 1106.3.
  
 59B. SHT P2-01B SHOW THE SF OF EACH
 DRAIN AND INDICATE SQUARE FOOTAGE AS IT
 ACCUMULATES IN THE SYSTEM. TABLE 1106.3.
  
 60B. SHT P2-02 CD5 SHOWN ON FLOOR PLAN
 WAS NOT SHOWN ON FLOORS 1 THRU 5.
 INDICATE WHERE CD5 TERMINATES. SECTION
 104.2.1.
  
 61B. SHT P2-02B THREE PLANTER DRAINS
 SHOWN ON THE FLOOR PLAN ARE NOT SHOWN
 ON THE RISER DIAGRAM. CORRELATE THE
 RISER AND THE FLOOR PLAN. SECTION
 104.2.1.
  
 62B. SHT P2-02B NO DRAINAGE IS SHOWN FOR
 THE AMENITY DECK AREA NOR FOR THE TENNIS
 COURT AREA AS REQUIRED BY SECTION
 1101.2. PLEASE CLARIFY.
  
 63B. SHT P2-02B SHOW THE LOCATION FOR
 ALL REQUIRED SECONDARY ROOF DRAINS, AND
 INDICATE THE SIZE. SECTIONS 1107.1,
 1107.2, & 1107.3.
  
 64B. SHT P2-03 IS FOR FLOORS 7 THRU 10.
 THERE ARE OFFSETS SHOWN ON THE FLOOR
 PLAN. ARE THESE OFFSETS FOR EACH FLOOR?
 IF NOT THE FLOORS CAN NOT BE TYPICAL,
 AND INDIVIDUAL SHEETS ARE REQUIRED FOR
 EACH FLOOR THAT IS NOT TYPICAL. SECTION
 104.2.1.
  
 65B. SHT P2-03 KEYED NOTES DO NOT
 REFLECT WHERE THEY ARE APPLIED ON THE
 FLOOR PLAN. CORRELATE KEYED NOTES AND
 THE FLOOR PLAN. SECTION 104.2.1.
  
 66B. P2-05 IS FOR SHEETS 12, 14 THRU 16.
 THERE ARE OFFSETS SHOWN ON THE FLOOR
 PLAN, AND VENTS CONNECTING TO EACH OTHER
 AND VENTING THRU THE ROOF. ARE THESE
 OFFSETS AND VENTS CONNECTING ON EACH
 FLOOR? SEPARATE SHEETS SHALL BE
 SUBMITTED FOR FLOOR PLANS THAT ARE NOT
 TYPICAL. SECTION 104.2.1.
  
 67B. SHT P2-06 NOT ALL VENTS ARE SHOWN
 AS THRU THE ROOF. SOME VENTS CONNECTING
 WITH OTHER VENTS AS SHOWN ON SHT P2-05
 DO NOT REFLECT WHAT IS SHOWN ON P2-06.
 CORRELATE ALL VENTS AS THEY COME THRU
 THE ROOF WITH THE FLOOR BELOW. ALL VENTS
 SHALL BE SHOWN AS VTR. SECTION 104.2.1.
  
 68B. SUBMIT WATER RISER DIAGRAMS FOR ALL
 UNITS, (SHOWN ON SHTS P3-00 THRU P3-03),
 SHOWING ALL PIPE SIZES, VALVES, AND
 WATER HAMMER ARRESTORS, (REQUIRED BY
 SECTION 604.9). WATER HAMMER ARRESTORS
 SHALL BE LOCATED NEAR THE FIXTURE, IN AN
 "EFFECTIVE RANGE", (NOT IN THE CEILING),
 PER PDI-WH 201 AND MANUF. INSTALLATION
 INSTRUCTIONS. SECTION 104.3.1.1.
  
 69B. SHT P4-00B RISER SV13 DOES NOT
 REFLECT THE FLOOR PLAN. OFFSET NOT SHOWN
 ON THE FLOOR PLAN AT THE 11TH FLOOR.
 CORRELATE RISER AND FLOOR PLAN. SECTION
 104.2.1.
  
 70B. SHT P4-00B RISER SV17 IS NOT SHOWN
 ON THE FIRST FLOOR. CORRELATE RISER AND
 FLOOR PLAN. SECTION 104.2.1.
  
 71B. SHT P4-01A RISER P16 DOES NOT
 REFLECT THE FLOOR PLAN. OFFSET NOT SHOWN
 ON FLOOR PLAN. CORRELATE RISER AND FLOOR
 PLAN. SECTION 104.2.1.
  
 72B. SHT P4-03 SUBMIT WATER SUPPLY RISER
 ISOMETRIC RISER DIAGRAMS FOR TOILET
 ROOMS AND DRINKING FOUNTAIN. SECTION
 104.3.1.1. - WATER HAMMER ARRESTORS
 SHALL BE LOCATED IN AN "EFFECTIVE RANGE"
 NOT IN THE CEILING AS SHOWN. PDI-WH 201
 AND MANUF. INSTALLATION INSTRUCTIONS.
  
 73B. SHT P4-04 ROOF DRAIN STORM WATER
 RISER. RECHECK THE PIPE SIZING, AS SOME
 SIZES ARE INCORRECT PER TABLE 1106.3. -
 RD3 SQUARE FOOTAGE DOES NOT REFLECT SF
 SHOWN ON THE ROOF PLAN.- RD-11 IS SHOWN
 AS 6", BUT IS SHOWN AS 4" ON THE ROOF
 PLAN. CORRELATE RISER WITH FLOOR PLAN.
 - RECHECK ADDITION FROM 10" (18656SF)
 AND ALL DOWNSTREAM FIGURES. SECTION
 104.2.1.
  
 74B. SHT P4-04B SOME PIPE SIZING IS
 INCORRECT. ADDITION NEEDS TO BE CHECKED
 FROM 8" (5960SF) AND DOWNSTREAM. SOME
 AREA DRAINS ARE SHOWN AS PLANTER DRAINS
 AND SOME PLANTER DRAINS ARE SHOWN AS
 AREA DRAINS. CORRELATE RISER AND FLOOR
 PLAN. SECTION 104.2.1 AND TABLE 1106.3.
  
 75B. SHTS P4-05 & P4-06 THE CONDENSATE
 AND EMERGENCY PAN DRAIN LINE FOR THE
 WATER HEATER SHALL NOT BE COMBINED. PAN
 DRAIN SHALL BE SEPARATE. SECTION
 504.8.2.
  
 76B. SHT P4-06 CD18 DOES NOT REFLECT THE
 FLOOR PLAN ON THE 1ST FLOOR. CORRELATE
 RISER AND FLOOR PLAN. SECTION 104.2.1.
  
  
 77B. SHT P4-06 CD15 IS NOT SHOWN ON
 FLOORS 1 THRU 5. PLEASE INDICATE WHERE
 CD15 TERMINATES. SECTION 104.2.1.
  
 78B. SHT P6-00 INDICATES TWO SUPPLY
 LINES TO RISER W17. PLEASE CLARIFY.
 SECTION 104.2.1.
  
 79B. SUBMIT EMERGENCY PAN DRAIN LINE
 RISERS FOR THE WATER HEATERS. SHOW ALL
 PIPE SIZES, OFFSETS AND TERMINATION
 POINT. SECTION 104.3.1.1.
  
 80B. SUBMIT A HORIZONTAL ISOMETRIC RISER
 DIAGRAM FOR THE BUILDING SANITARY DRAIN.
 SHOW ALL PIPE SIZES, RISER CONNECTION
 LOCATION, IDENTIFY RISER, AND SHOW DFU'S
 AS THEY ACCUMULATE IN THE SYSTEM.
 SECTION 104.3.1.1.
  
 81B. SHT P2-05 KEYED NOTES ON FLOOR PLAN
 BUT NO "PLUMBING KEYED NOTES INDEX"
 SUBMITTED ON THE SHEET. SUBMIT KEYED
 NOTES FOR THIS SHEET, MAKING SURE THEY
 REFLECT THE KEYED NOTES SHOWN ON THE
 FLOOR PLAN. SECTION 104.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-10-04 Cont ID  
Sent By kstevens Date 2006-09-30 Time 07:27 Rev Time 0.00
Received By kstevens Date 2006-09-13 Time 18:57 Sent To  
Notes
2006-09-30 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 WPB CITY CODE
  
 FROM PREVIOUS REVIEW. COMMENT NUMBER TO
 REMAIN THE SAME.
  
 1. OK
 2. OK
 3. OK
 4. OK
  
 5. SHT CD-11 DETAIL #1 CLEAR FLOOR SPACE
 AT THE TOILET SHALL COMPLY WITH ONE OF 3
 SHOWN ON PAGE 7.43 FHA DESIGN MANUAL.
 ***RESPONSE NOTED, BUT BOTH DIMENSIONS
 SHALL BE SHOWN.
  
 6. SHT CD-11 RESIDENTIAL UNIT
 ACCESSIBLITY NOTES:
 #7 OK
 #8(II)(B)(V) CALLS FOR DETAIL 3/CD-4.
 NO DETAIL 3 FOUND THAT SHEET. CLARIFY.
 SECTION 106.1.1.
 ***RESPONSE NOTED, BUT IT NOW CALLS FOR
 DETAIL 3/CD-11. THIS DETAIL DOES NOT
 SHOW LAVS/VANITIES. SECTION 104.2.1.
  
 7. OK
  
 8. SHT CD-12 NOTES FOR W/C REFERENCE
 DETAIL 3/CD-03.DETAIL NOT FOUND.
 PLEASE CLARIFY. SECTION 106.1.1.
 ***RESPONSE NOTED, BUT IT ONLY SHOWS
 DIMENSION 5'6". BOTH DIMENSIONS SHALL BE
 SHOWN. PAGE 7.43.
  
 9.OK
 10. OK
 11. OK
 12. OK
 13. OK
 14. OK
 15. OK
  
 16. SHT A1-04 4TH FLOOR BALCONYS APPEAR
 TO HAVE A PARAPET WALL ON ALL THREE
 SIDES. SHT REFERENCES DETAIL 1/A6-05,
 BUT SHT A6-05 WAS NOT SUBMITTED. SHT
 ALSO REFERENCES DETAIL 11/A6.20 WHICH
 SHOWS 1-1/2" WEEP HOLES. DRAINAGE PER
 SECTIONS 1106 & 1107WILL BE REQUIRED
 FOR STORM WATER IF A PARAPET WALL IS ON
 ALL SIDES. PLEASE SUBMIT A DETAIL AND
 CLARIFY. SECTION 106.1.1.
 ***RESPONSE NOTED, BUT SCUPPERS SHALL BE
 A MINIMUM 4" HIGH. SECTION 1503.4.2. THE
 PEDESTRAIN TRAFFIC COATING IS INDICATED
 AS 4" HIGH UP THE WALL ON DETAIL
 11/A6.20. THIS APPEARS TO COVER THE
 SCUPPERS. PLEASE CLARIFY OR SUBMIT AN
 ELEVATION DETAIL OF THE SCUPPERS.
 SECTION 104.2.1.
  
 17. SHTS A3-20, A3-21 SHOW DIMENSIONS OF
 OPENINGS FOR EACH WATER CLOSET. MINIMUM
 33" OPENING REQUIRED. 18" OFF THE WALL
 TO THE CENTER OF THE FIXTURE, AND
 MINIMUM 15" TO THE NEXT FIXTURE. MINIMUM
 18" OFF ONE FIXTURE, AND 15" MINIMUM OFF
 THE OTHER FIXTURE. FHA DESIGN MANUAL
 PAGES 7.43, 7.44, 7.45, 7.46.
 ***RESPONSE NOTED, BUT DETAILS 7 & 9 SHT
 A3-20, (INDICATED AS 2ND DETAIL #5), AND
 DETAILS 3 & 4 SHT A3-21, THE 18" FROM
 THE CENTERLINE OF THE WATER CLOSET TO
 THE WILL IS AN ABSOLUTE MEASUREMENT, NOT
 A MINIMUM AS SHOWN. PAGE 6.5 FHA DESIGN
 MANUAL.
  
 18. N/A
 19. SHT A1-18 OVERFLOW SCUPPERS ARE
 REQUIRED FOR THE UPPER ROOF. SECTION
 1106.5. SHOW LOCATION AND INDICATE SIZE
 OF OVERFLOW SCUPPERS PER SECTION 1101.7,
 1107.3 AND TABLE 1106.7.
 ***RESPONSE NOTED, BUT OVERFLOW SCUPPERS
 ARE NOT INDICATED ON THE MECHANICAL ROOM
 OR STAIRWELL ROOFS. SECTIONS 1107.1,
 1107.2 & 1107.3.
  
 20. SHT AP1-06 SHOW THE LOCATION OF ALL
 SECONDARY ROOF DRAINS. SECTION 1107.
 ***RESPONSE NOTED, BUT THE SECONDARY
 DRAINS ARE REQUIRED AT THE 6TH FLOOR
 DECK AREA. PLEASE INDICATE THE LOCATION,
 SIZE AND SQUARE FOOTAGE DRAINED BY EACH
 SECONDARY DRAIN. SECTION 1107.1, 1107.2,
 AND 1107.3.
  
 21. SHT ID7-01 PER SECTION 1210.2 WALLS
 WITHIN 2' OF A WATER CLOSET SHALL BE
 NONABSORBENT UP TO 4'. PLANS INDICATE
 THAT ONLY THE WALL BEHIND THE WATER
 CLOSET HAS TILE. PLEASE INDICATE HOW THE
 VINAL WALL PAPER COMPLYS WITH THE NON-
 ABSORBENT REQUIREMENT.
 ***RESPONSE NOTED, BUT A SUBMITTAL FOR
 THE PRODUCT, WITH INSTALLATION
 INSTRUCTIONS, SHALL BE SUBMITTED FOR
 REVIEW AND APPROVAL. SECTION 104.2.1.2.
  
 22. SHT ID8-01 DETAILS 1 & 2 SHOW THE
 FOLLOWING ON THE DETAILS:
 11-4.16.2 CLEAR FLOOR SPACE (W/C) OK
 11-4.16.3 HEIGHT 9W/C) OK
  
 11-4.16.5 FLUSH CONTROLS (W/C) NOT
 ADDRESSED.
  
 11-4.16.6 DISPENSERS (W/C) OK
  
 11-4.19.2 HEIGHT & CLEARANCES (LAV)
 CLEARANCES NOT ADDRESSED.
  
 11-4.19.3 CLEAR FLOOR SPACE (LAV) OK
  
 11-4.19.5 FAUCETS (LAV) NOT ADDRESSED
  
 11-4.19.6 MIRRORS (LAV) OK
 11-4.22.3 5' TURNING AREA (TOILET ROOM)
 OK
 23. OK
  
 24. ALL PLUMBING SHEETS, ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME, ADDRESS,
 AND LICENSE NUMBER ON EACH SHEET, AND IF
 PRACTICING THROUGH A DULY AUTHORIZED
 ENGINEERING BUSINESS, ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME AND LICENSE
 NUMBER, AS WELL AS, THE NAME, ADDRESS,
 AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS ON EACH
 SHEET. FAC 61G15-23.002(2) & FS 471.2055
 ***RESPONSE NOTED, BUT LICENSE NUMBER IS
 NOT IS NOT INDCATED.
  
 25. OK
  
 26. SHT P0-01 PLUMBING FIXTURE SCHEDULE,
 SHOW ALL PIPE SIZES TO ALL WATER
 HEATERS. SECTION 106.1.1.
 ***RESPONSE NOTED, BUT EWH-3
 SPECIFICATION SHEET INDICATES 1-1/4"
 OPENING FOR THE HOT & COLD WATER.
 FIXTURE SCHEDULE INDICATES 1/2" COLD
 WATER SUPPLY. PLEASE CORRELATE SUPPLY
 SIZE PIPE FOR ALL HEATERS WITH MANUF.
 SPECIFICATION FOR PIPE SIZE CONNECTIONS.
 SECTION 104.2.1.
  
 27. N/A
 28. N/A
 29. OK
 30. OK
 31. OK
 32. OK
 33. OK
 34. OK
 35. OK
  
 36. SHT P2-00 NO KEYED NOTE FOR #5
 FOUND. SECTION 106.1.1.
 ***RESPONSE NOTED, BUT KEY NOTE #1 WAS
 CHANGED TO #3 ON THE FLOOR PLAN AND DOES
 NOT REFLECT THE INFORMATION INDICATED IN
 KEY NOTE. PLEASE CLARIFY SECTION
 104.2.1.
  
 37. SHT P2-00 RD-21, SV2, SV3, SV-4, P1.
 P2, P-3, CD-10 AND OTHER RISERS SHOWN ON
 SHT P2-01 BUT NOT SHOWN ON THIS SHEET.
 ALL RISERS START ON THE FIRST FLOOR AND
 ALL RISERS LOCATIONS SHALL BE SHOWN
 WHERE THEY START IN THE SYSTEM.
 ***RESPONSE NOTED, BUT MANY RISER
 NUMBERS CHANGE FROM FLOOR TO FLOOR ON
 THE FLOOR PLAN. SOME RISERS ARE NOT
 INDICIATED ON THE FIRST FLOOR, SOME
 RISER DESIGNATIONS HAVE NO RISER
 DIAGRAMS. SOME RISER START OFF AS ONE
 RISER NUMBER, CHANGE TO ANOTHER RISER
 NUMBER AND THEN CHANGE BACK TO THE
 ORIGINAL NUMBER. PLEASE CORRELATE ALL
 RISERS. SECTION 104.2.1.
  
 38. EACH SANITARY RISER DIAGRAM, BE IT A
 CONVENTIONAL SYSTEM OR A SOVENT SYSTEM
 RISER SHALL HAVE ITS OWN RISER
 DESIGNATION, SUCH AS P-1, P-2. P3 OR
 SV-1, SV-2, SV-3 ETC. SHOWING MULTIPLE
 RISERS WITH THE SAME RISER DESIGNATION
 IS CONFUSING BECAUSE, (FOR EXAMPLE), NOT
 ALL P-1 RISERS ARE THE SAME AS THE
 PIPING IS NOT ALWAYS THE SAME AND THE
 OFFSETS ARE NOT ALL THE SAME FOR EACH
 P-1. SEE FOR EXAMPLE THE WATER RISERS,
 THE CONDENSATE RISERS, OR THE STORM
 RISERS. SECTION 106.1.1.
 ***RESPONSE NOTED, BUT THE RISERS ARE
 STILL CONFUSING. ALL SANTARY RISERS
 SHOULD HAVE THERE OWN RISER NUMBER.
 EXAMPLE SANT. 1, SANT. 2, SANT. 3 ETC.
 EACH RISER CAN BE A TYPICAL OF A RISER
 TYPE FOR EXAMPLE SV-4 OR P-4, BUT EACH
 RISER WOULD BE ABLE TO BE LOCATED
 INDIVIDUALLY, AND WHEN A COMMENT IS MADE
 CONCERNING A SANT. RISER, IT WOULD BE
 EASY TO UNDERSTAND WHICH RISER IS BEING
 COMMENTED ON.SECTION 104.2.1.
  
  
 39. ALL SHEETS SHOWING PIPING ON FLOOR
 PLANS: SHOW ALL PIPING INCLUDING ARMS TO
 LAVS OR KITCHEN SINKS. SECTION 106.1.1.
 ***RESPONSE NOTED, BUT NO PIPING IS
 SHOWN FOR COMMON AREA TOILET ROOMS 104,
 & 105. SECTION 104.2.1.
  
 40. OK
  
 41. SHT P2-01 RISERS RD-6, RD-9, RD-12
 AND RD-13 HAVE BEEN OFFSET, BUT NO
 OFFSET PIPING IS SHOWN. PLEASE SHOW ALL
 OFFSET PIPING ON PLANS. SECTION 106.1.1.
 ***RESPONSE NOTED, BUT RD-6 RISER STILL
 DOES NOT REFLECT THE FLOOOR PLAN.
 SECTION 104.2.1.
  
 42. SEE COMMENT 38.
 43. SEE COMMENT 38
 44. SEE COMMENT 38
 45. SEE COMMENT 38
  
 46. SHT P2-02 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY DRAINS PER
 SECTIONS 1106 & 1107 AND ALL
 SUBSECTIONS. SHOW SQUARE FOOOTAGE BEING
 DRAINED AT EACH PRIMARY DRAIN AND SHOW
 1/2 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS ADDED IN CALCULATIONS AS WELL
 AS ANY AREAS FROM UPPER ROOFS ADDED TO
 THE DECK AREA.
 ***RESPONSE NOTED, BUT CALCULATIONS FOR
 PRIMARY ROOF DRAINS AND FOR AREA DRAINS
 FOR THE 6TH FLOOR TERRACE AREAS HAVE NOT
 BEEN SUBMITTED. TABLE 1106.3
  
 47. SHT P2-02 MANY AREA DRAINS ARE
 MISLABELED AS PLANTER DRAINS, MANY
 DRAINS ARE NOT LABELED, MANY LABELS SHOW
 NO DRAIN. PLEASE CLARIFY. SECTION
 106.1.1.
 ***RESPONSE NOTED, BUT SOME DRAINS ARE
 STILL MISLABELED. SECTION 104.2.1.
  
 48. OK
 49. SEE COMMENT 38
 50. SEE COMMENT 38
 51. SEE COMMENT 38
 52. SEE COMMENT 38
 53. SEE COMMENT 38
 54. SEE COMMENT 38
 55. SEE COMMENT 38
 56. SEE COMMENT 38
 57. SEE COMMENT 38
 58. SEE COMMENT 38
 59. SEE COMMENT 38
 60. SEE COMMENT 38
 61. SEE COMMENT 38
 62. SEE COMMENT 38
 63. SEE COMMENT 38
 64. SEE COMMENT 38
 65. SEE COMMENT 38
 66. OK
 67. SEE COMMENT 38
 68. SEE COMMENT 38
 69. SEE COMMENT 38
 70. SEE COMMENT 38
 71. SEE COMMENT 38
 72. SEE COMMENT 38
 73. OK
 74. OK
 75. OK
  
 76. SHT P2-06 THE VENTS THRU THE ROOF DO
 NOT REFLECT THE VENTS SHOWN ON SHT P2-05
 FOR LOCATION. PLEASE CORRELATE VENTS
 FROM FLOOR TO FLOOR. SECTION 106.1.1.
 ***RESPONSE NOTED, BUT SOME VENTS ARE
 NOT SHOWN OR DO NOT CONNECT TO OTHER
 VENTS AS SHOWN BELOW. SECTION 104.2.1.
  
 77. OK
 78. OK
 79. OK
 80. OK
 81. OK
 82. OK
 83. OK
 84. OK
 85. OK
  
 86. SHT P4-00 ALL SV RISERS DO NOT
 REFLECT THE FLOOR PLANS FOR THE FIRST
 FLOOR PIPING. SECTION 106.1.1.
 ***RESPONSE NOTED, BUT THE SOME RISERS
 DO NOT REFLECT THE FLOOR PLANS ON THE
 FIRST FLOOR, OR AT THE OFFSETS. SOME
 RISERS REFLECT THE FLOOR PLANS IN ONE
 INSTANCE, BUT THE FLOOR PLAN CHANGES FOR
 THE SAME RISER IN ANOTHER INSTANCE.
 RISER CAN NOT BE TYPICAL IF NOT EXACTLY
 THE SAME IN EACH CASE. SECTION 104.2.1.
  
 87. SHT P4-00 ALL SV RISERS DO NOT
 REFLECT THE FLOOR PLANS FOR THE 16TH
 FLOORS. NO VENT PIPING SHOWN FOR THE
 REVENTS SHOWN ON THE 16TH FLOOR. SECTION
 106.1.1.
 ***RESPONSE NOTED, BUT FOR EXAMPLE THE
 VENTS P1/P19/SV-13/SV-1 ARE CONNECTED
 TOGETHER ON THE FLOOR PLAN, BUT THE VTR
 ON THE ROOF PLAN DOES NOT SHOW THIS.
 SV-13 DOES NOT INDICATE CONNECTING TO
 SV-1. P19 OFFSET VENT BUT DOES NOT
 INDICATE TO WHICH VENT STACK. THIS IS
 EVEN MORE OF A PROBLEM WHEN THERE ARE
 MORE THAN ONE RISER FOR A RISER
 DESIGNATION. (SEE COMMENT 38).
  
 88.OK
  
 89. SHT P4-00 16TH FLOOR SHALL BE
 DIFFERENT FROM OTHER FLOOR ON ALL RISERS
 AS THE VENTING/REVENTING IS ONLY ON THIS
 FLOOR. SHOW ALL VENTING/REVENTING ON
 RISERS. (THIS IS REQUIRED FOR ALL VENTS
 INCLUDING SOVENT SYSTEM IF VENTS FROM
 OTHER STACKS ARE TYING INTO THEM.
 SECTION 106.1.1.
 ***RESPONSE NOTED, BUT SOME FLOORS ARE
 NOT TYPICAL AND INDIVIDUAL FLOORS FOR
 THE FLOORS THAT ARE NOT TYPICAL SHALL BE
 SUBMITTED SEPARATELY.
  
 90. OK
 91. OK
  
 92. SEE COMMENT 38
  
 93. SHT P4-00 SUBMIT A RISER DIAGRAM FOR
 EACH SANTITARY RISER DIAGRAM AND EACH
 SOVENT RISER DIAGRAM. COMMON RISERS WITH
 DIFFERENT FLOOR PLANS ARE NOT
 ACCEPTABLE. IF THE TUB AND LAV ARE ON
 THE OPPOSITE SIDE OF THE WATER CLOSET
 FROM ONE FLOOR PLAN TO THE OTHER, OR
 OFFSETS ARE DIFFERENT, OR ON DIFFERENT
 FLOOR PLANS, THEN SEPARATE RISER
 DIAGRAMS ARE REQUIRED. RISER DIAGRAMS
 SHALL REFLECT THE FLOOR PLAN FROM THEIR
 CONNECTION TO THE BUILDING DRAIN UP THRU
 THE ROOF FOR VENTING. BECAUSE THIS IS AN
 ENGINEERED SYSTEM, SEPARATE RISERS ARE
 REQUIRED, AND SEPARATE RISER
 DESIGNATIONS ARE REQUIRED. SOME RISERS
 CHANGE RISER NUMBERS FROM FLOOR TO FLOOR
 PLEASE CLARIFY. FLOOR PLANS SHOW REVENTS
 FROM OTHER RISERS TYING TOGETHER PRIOR
 TO VENTING THRU THE ROOF. THIS IS NOT
 REFLECTED ON ANY OF THE RISER DIAGRAMS.
 ***RESPONSE NOTED, BUT PROBLEM NOT
 ADDRESSED. SEE COMMENT 38.
  
 94. SUBMIT AN APPROVED DESIGN MANUAL FOR
 THE SOVENT SYSTEM. SUBMIT MANUFACTURE
 SPECIFICATIONS FOR AERATORS AND
 DEAERATORS FOR PRODUCT APPROVAL PER
 SECTIONS 303.1 & 303.4.
 ***COMMENT NOT ADDRESSED. NO RESPONSE.
  
  
 95. PLANS APPEAR TO BE INCOMPLETE AT
 THIS TIME, AS ALL THE SV RISERS ARE NOT
 SUBMITTED AS WELL AS THE BLDG DRAIN FOR
 OTHER SYSTEMS. OTHER COMMENTS MAY OR MAY
 NOT FOLLOW UPON SUBMITTAL OF REQUIRED
 INFORMATION AND INFORMATION NOT
 SUBMITTED AT THIS TIME. SECTIONS 106.1.1
 AND 106.3.5.1.3.
 ***RESPONSE NOTED, BUT PLANS DO NOT SEEM
 TO BE COMPLETE YET. (SEE NEW COMMENTS)
  
 96. SHT P4-01 ALL STACKS, RELIEF VENTS
 ARE REQUIRED PER SECTION 914.1 AND SHALL
 BE PROVIDED AT EACH 10TH INTERVAL
 BEGINNING WITH THE TOP FLOOR. SECTION
 914.1.
 ***RESPONSE NOTED, BUT THE STACKS WITH
 VENT STACKS REQUIRE RELIEF VENTS PER
 SECTION 914.1 HAS NOT BEEN ADDRESSED.
  
 97. OK
 98. OK
 99. OK
  
 100. SHT P4-02 RISERS W1, W2, W6, W8, &
 W10 FULL OPEN VALVES SHALL BE INSTALLED
 ON THE BASE OF EVERY WATER RISER PIPE.
 SECTION 606.1(3).
 ***RESPONSE NOTED, BUT W8 RISER STILL
 SHOWS NO VALVE.
  
 101. SHT P4-04 SUBMIT THE BUILDING STORM
 DRAIN IN AN ISOMETRIC RISER DIAGRAM THAT
 REFLECTS THE PIPING SHOWN ON THE
 UNDERGROUND PLUMBING PLAN SHT P2-00.
 SECTION 106.3.5.1.3. SHOW ALL PIPE SIZES
 AND SQUARE FOOTAGE AS IT ACCUMULATES IN
 THE SYSTEM. IDENTIFY ALL RISERS AS THEY
 CONNECT TO THE BUILDING DRAIN IN THE
 ISOMETRIC DIAGRAM OF THE BUILDING DRAIN.
 SHOW ALL OFFSETS IN THE STORM RISERS,
 AND INDICATE ALL PIPE SIZES.
 ***RESPONSE NOTED, BUT RISER NUMBER ARE
 NOT SHOWN TO IDENTIFY RISERS. (EXAMPLE
 RWL-1, RWL-2 ETC.). SECTION 104.2.1.
  
 102. SHTS P4-05 & P4-06 INDICATE
 MATERIAL FOR CONDENSATE SYSTEM. NO
 FLAMABLE MATERIAL IN THE AIR CONDITION
 ROOM IF IT IS USED AS A PLENUM. INDICATE
 METHOD OF VENTING THE CONDENSATE RISERS.
 VENTS CAN NOT TERMINATE IN THE WALLS OR
 IN A PLENUM.
 ***RESPONSE NOTED, BUT THE MATERIAL FOR
 THE CONDENSATE SYSTEM WAS NOT FOUND ON
 SHT P0-01. SECTION 104.2.1.
  
 103. SHTS P4-05 & P4-06 SUBMIT A
 BUILDING DRAIN CONDENSATE ISOMETRIC
 RISER DIAGRAM THAT REFLECTS THE
 UNDERGROUND PIPING ON SHT P2-00. SECTION
 106.3.5.1.3.
 ***RESPONSE NOTED, BUT THE HORIZONTAL
 BUILDING DRAIN FOR THE CONDENSATE IS
 REQUIRED BY SECTION 104.3.1.1. THE
 CONDENSATE AND THE WATER HEATER PAN
 DRAIN LINE CAN NOT BE COMBINED. SEPARATE
 DRAIN LINES AND SYSTEMS ARE REQUIRED.
 SECTION 504.8.2.
  
 104. SHT P5-00 DETAIL 05 WASHER BOX
 CONNECTION WATER HAMMER ARRESTORS ARE
 REQUIRED AT THE WASHER BOX PER 604.9.
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURES IN AN "EFFECTIVE
 RANGE" NOT IN THE CEILING. PDI-WH 201
 AND MANUF. INSTALLATION INSTRUCTIONS.
 ***RESPONSE NOTED, BUT WATER HAMMER
 ARRESTORS ARE NOT SHOWN. SECTION
 104.2.1.
  
 105. OK
 106. OK
  
 107. SHT P5-00 DETAIL 04 WATER HEATER
 SUBMIT EMERGENCY PAN DRAIN ISOMETRIC
 RISER DIAGRAM SHOWING ALL PIPE SIZES,
 MATERIAL, AND TERMINATION POINT. SECTION
 106.3.5.1.3.
 ***RESPONSE NOTED, BUT RESPONSE DID NOT
 ADDRESS COMMENT. SECTION 104.3.1.1.
  
 108. OK
  
 109. SHT P5-00 DETAIL 07 DOMESTIC WATER
 BOOSTER PUMP DETAIL: SUBMIT MANUF.
 SPECIFICATION SHEETS FOR PUMP. PUMP
 SHALL BE LISTED. SECTION 303.4.
 ***RESPONSE NOTED, BUT RESPONSE NEEDS TO
 BE CLARIFIED. SCHEDULED PUMP?
  
 110. OK
 111. OK
 112. OK
  
 113. ALL SETS OF PLANS AND ALL SHEETS IN
 EACH SET OF PLANS: IF THE DESIGN
 PROFESSIONAL IS AN ENGINEER, THEN HE OR
 SHE SHALL AFFIX HIS OR HER OFFICIAL
 SEAL, SIGNATURE AND DATE TO SAID
 DRAWINGS AS REQUIRED BY FLORIDA
 STATUTES. NO INITIALS. LEGAL SIGNATURE
 IS REQUIRED.
 ***RESPONSE NOTED, BUT INITIALS APPEAR
 TO BE SUBMITTED IN PLACE OF A SIGNATURE.
 IF THIS IS THE LEGAL SIGNATURE, PLEASE
 SUBMIT A SIGNED, SEALED, DATED,
 NOTORIZED LETTER INDICATING LEGAL
 SIGNATURE FOR OUR FILES. FAC
 61G15-23.002(2) AND FS
 471.025.
  
 114. SUBMIT WATER ISOMETRIC RISER
 DIAGRAMS FOR EACH UNIT SHOWING ALL PIPE
 SIZES, VALVES, AND WATER HAMMER
 ARRESTORS REQUIRED BY SECTION 604.9.
 SECTION 106.3.5.1.3.
 ***RESPONSE NOTED, BUT RESPONSE HAS
 NOTHING TO DO WITH COMMENT INFORMATION
 REQUESTED. SECTION 104.3.1.1.
  
 115. THE FOLLOWING INFORMATION IS
 REQUIRED FOR THE GAS APPLICATION:
  
 ***DUE TO THE FACT THAT THERE ARE NOT
 APPROVED GAS PLANS FROM PHASE I, THE
 INFORMATION IS STILL REQUIRED.***
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGHTS PER FBC-2004
 FUEL GAS.
 ***RESPONSE NOTED, BUT CORRESPONDING
 LENGTHS NOT SHOWN. FBC-2001 FUEL GAS.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 ***RESPONSE NOTED, BUT INFORMATION SHALL
 BE LOCATED AT RISER WITH REQUIRED INFO.
 SECTION 104.2.1.
  
 C. TYPE OF GAS, (LP OR NATURAL).
 ***RESPONSE NOTED, INFORMATION REQUIRED
 ON PLANS WITH RISER.
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 ***RESPONSE NOTED, BUT TOTAL BTU LOAD OF
 SYSTEM NOT SHOWN. INFORMATION REQUIRED
 ON PLANS WITH RISER.
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ***NO RESPONSE NOT ADDRESSED.
  
 F. NA
  
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. IF
 2 PSI INDICATE LOCATION OF REGULATORS
 AND SUBMIT MANUF. SPECIFICATION SHEETS
 FOR REGULATORS INDICATING MODEL. IF
 VENTED REGULATORS, INDICATE MATERIAL FOR
 VENTS AND SHOW ROUTING OF PIPING.
 ***NO RESPONSE, NOT ADDRESSED.
  
 H. NA
  
 I. SUBMIT MANUFACTURE SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ***NO RESPONSE, NOT ADDRESSED.
  
 J. N/A
 K. N/A
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE RESUBMIT RED LINED SET OF
 PLUMBING PLANS FROM FIRST REVIEW TO HELP
 TO EXPEDITE THE SECOND REVIEW.
 ***NO RESPONSE, NOT ADDRESSED ADDING
 MANY HOURS TO REVIEW. RED LINED SET OF
 PLUMBING PLANS TO BE RETAINED TO
 EXPEDITE NEXT REVIEW.
  
 END OF COMMENTS FROM FIRST REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-02-25 Cont ID  
Sent By kstevens Date 2006-02-25 Time 15:20 Rev Time 0.00
Received By kstevens Date 2006-02-22 Time 18:27 Sent To  
Notes
2006-02-25 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 WPB CITY CODE
  
 1. ALL "CS", "CD" AND ARCHITECTURAL
 SHEETS SHALL BE DATED WHEN THE SEAL AND
 SIGNATURE ARE AFFIXED TO THE DOCUMENT.
 FAC 61G1-16.003, 61G1-16.004(5) AND FS
 481.2055.
 2. SHT CD-10 APPLICABLE CODES INDICATE
 2001-FBC. CURRENT CODES IN EFFECT ARE
 FBC-2004 AND PLANS ARE TO BE DESIGNED
 PER THIS CODE. PLEASE INDICATE ON PLANS.
 3. SHT CD-10 SCUPPERS TO BE SIZED PER
 SECTIONS 1101.7, 1107.3 AND TABLE
 1106.7. PLEASE INDICATE THIS ON THE
 PLANS AND THE SIZING OF THE SCUPPERS CAN
 NOT BE DETERMINED WITH OUT REFERENCE TO
 THE DEFLECTION OF THE ROOF.
 4. SHT CD-11 BACKING FOR SHOWERS ARE TO
 BE PER PAGE 6.12 FHA DESIGN MANUAL. SHOW
 ALL 3 SIDES, (ELEVATIONS) OF THE SHOWER,
 AND BACKING SHALL BE SIDE TO SIDE EACH
 ELEVATION.
 5. SHT CD-11 DETAIL #1 CLEAR FLOOR SPACE
 AT THE TOILET SHALL COMPLY WITH ONE OF 3
 SHOWN ON PAGE 7.43 FHA DESIGN MANUAL.
 6. SHT CD-11 RESIDENTIAL UNIT
 ACCESSIBLITY NOTES:
 #7 CALLS FOR DETAIL 2/A-6.11. SHT
 A-6.11 HAS NOT BEEN SUBMITTED. CLARIFY.
 SECTION 106.1.1.
 #8(II)(B)(V) CALLS FOR DETAIL 3/CD-4.
 NO DETAIL 3 FOUND THAT SHEET. CLARIFY.
 SECTION 106.1.1.
 7. SHT CD-12 NOTES FOR BATHROOM
 REFERENCE DETAIL 4/CD-05. THIS SHEET HAS
 NOT BEEN SUBMITTED. PLEASE CLARIFY.
 SECTION 106.1.1.
 8. SHT CD-12 NOTES FOR W/C REFERENCE
 DETAIL 3/CD-03.DETAIL NOT FOUND.
 PLEASE CLARIFY. SECTION 106.1.1.
 9. SHT CD-12 DETAIL 2 UNIT TYPE A2,
 U-SHAPED KITCHEN REQUIRES A 5' TURNING
 AREA. SEE PAGE 7.9 FHA DESIGN MANUAL.
 10. SHT CD-13 DETAIL 2 UNIT TYPE D3,
 SHOWER CLEAR FLOOR SPACE SHALL BE
 PARALLEL AND FLUSH WITH THE CONTROL
 WALL. PAGE 7.56 FHA DESIGN MANUAL.
 11. SHT CD-14 DETAIL 5 UNIT TYPE P3, A
 U-SHAPED KITCHEN REQUIRES A 5' DIA.
 TURNING AREA. PAGE 7.9 FHA DESIGN
 MANUAL.
 12. SHT CD-14 UNIT TYPE P1 DETAIL 3 LAV
 WITH FORWARD APPROACH TO HAVE REMOVABLE
 BASE CABINET. PAGES 7.49, 7.50, AND 7.51
 FHA DESIGN MANUAL. SUBMIT A DETAIL.
 13. SHT CD-14 UNIT TYPE P1 DETAIL 3
 U-SHAPED KITCHEN REQUIRES A 5' DIAMETER
 TURNING AREA. PAGE 7.9 FHA DESIGN MAN.
 14. SHT CD-14 DETAIL 1 UNIT TYPE G1A
 SHOWER CLEAR FLOOR SPACE SHALL BE
 PARALLEL TO SHOWER AND FLUSH WITH THE
 CONTROL WALL. PAGE 7.56 FHA DESIGN MAN.
 15. SHTS CD-12, CD-13, CD-14 ALL UNITS,
 SPECIFICATION "A" OR "B" REQUIRED TO BE
 SHOWN ON EACH UNIT/BATHROOM. FHA DESIGN
 MANUAL PAGES 7.34, 7.35.
 16. SHT A1-04 4TH FLOOR BALCONYS APPEAR
 TO HAVE A PARAPET WALL ON ALL THREE
 SIDES. SHT REFERENCES DETAIL 1/A6-05,
 BUT SHT A6-05 WAS NOT SUBMITTED. SHT
 ALSO REFERENCES DETAIL 11/A6.20 WHICH
 SHOWS 1-1/2" WEEP HOLES. DRAINAGE PER
 SECTIONS 1106 & 1107WILL BE REQUIRED
 FOR STORM WATER IF A PARAPET WALL IS ON
 ALL SIDES. PLEASE SUBMIT A DETAIL AND
 CLARIFY. SECTION 106.1.1.
 17. SHTS A3-20, A3-21 SHOW DIMENSIONS OF
 OPENINGS FOR EACH WATER CLOSET. MINIMUM
 33" OPENING REQUIRED. 18" OFF THE WALL
 TO THE CENTER OF THE FIXTURE, AND
 MINIMUM 15" TO THE NEXT FIXTURE. MINIMUM
 18" OFF ONE FIXTURE, AND 15" MINIMUM OFF
 THE OTHER FIXTURE. FHA DESIGN MANUAL
 PAGES 7.43, 7.44, 7.45, 7.46.
 18. SHT A1-17 OVERFLOW SCUPPERS SHALL BE
 SIZED PER FBC-2004 PLUMBING SECTIONS
 1101.7, 1107.3 AND TABLE 1106.7. THE
 SIZING OF THE SCUPPERS CAN NOT BE
 DETERMINED WITH OUT REFERENCE TO THE
 DEFLECTION OF THE ROOF. PLEASE PROVIDE
 CALCULATION AND SHOW COMPLIANCE WITH
 ABOVE SECTIONS AND TABLE ON PLANS
 INDICATING THE SIZE OF THE SCUPPERS.
 19. SHT A1-18 OVERFLOW SCUPPERS ARE
 REQUIRED FOR THE UPPER ROOF. SECTION
 1106.5. SHOW LOCATION AND INDICATE SIZE
 OF OVERFLOW SCUPPERS PER SECTION 1101.7,
 1107.3 AND TABLE 1106.7.
 20. SHT AP1-06 SHOW THE LOCATION OF ALL
 SECONDARY ROOF DRAINS. SECTION 1107.
 21. SHT ID7-01 PER SECTION 1210.2 WALLS
 WITHIN 2' OF A WATER CLOSET SHALL BE
 NONABSORBENT UP TO 4'. PLANS INDICATE
 THAT ONLY THE WALL BEHIND THE WATER
 CLOSET HAS TILE. PLEASE INDICATE HOW THE
 VINAL WALL PAPER COMPLYS WITH THE NON-
 ABSORBENT REQUIREMENT.
 22. SHT ID8-01 DETAILS 1 & 2 SHOW THE
 FOLLOWING ON THE DETAILS:
 11-4.16.2 CLEAR FLOOR SPACE (W/C)
 11-4.16.3 HEIGHT 9W/C)
 11-4.16.5 FLUSH CONTROLS (W/C)
 11-4.16.6 DISPENSERS (W/C)
 11-4.19.2 HEIGHT & CLEARANCES (LAV)
 11-4.19.3 CLEAR FLOOR SPACE (LAV)
 11-4.19.5 FAUCETS (LAV)
 11-4.19.6 MIRRORS (LAV)
 11-4.22.3 5' TURNING AREA (TOILET ROOM)
 23. SHT ID10-01 FLOOR COVERING SCHEDULE
 DOES NOT INDICATE MEN'S OR WOMEN'S
 RESTROOMS. - WALL COVERING SCHEDULE
 (REMARK) INDICATE WHAT A "WET WALL" IS.
 - BASE SCHEDULE (WB-2) INDICATE HOW
 SEMI-GLOSS PAINT MEETS THE NONABSORBENT
 REQUIREMENT FOR MEN'S AND WOMEN'S TOILET
 ROOMS. SECTION 1210.2.
 24. ALL PLUMBING SHEETS, ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME, ADDRESS,
 AND LICENSE NUMBER ON EACH SHEET, AND IF
 PRACTICING THROUGH A DULY AUTHORIZED
 ENGINEERING BUSINESS, ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME AND LICENSE
 NUMBER, AS WELL AS, THE NAME, ADDRESS,
 AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS ON EACH
 SHEET. FAC 61G15-23.002(2) & FS 471.2055
 25. SHT P0-01 REFERENCES FBC-2001.
 ADOPTED CODE IS FBC-2004. PLEASE DESIGN
 PER FBC-2004 AND CHANGE REFERENCE.
 26. SHT P0-01 PLUMBING FIXTURE SCHEDULE,
 SHOW ALL PIPE SIZES TO ALL WATER
 HEATERS. SECTION 106.1.1.
 27. SHT P0-01 DOMESTIC WATER FIXTURE
 UNIT LOAD CALCS. REFER TO FBC-2001.
 PLEASE CALCULATE PER ADOPTED CODE WHICH
 IS FBC-2004.
 28. SHT P0-01 PLUMBING GENERAL NOTES
 REFERENCES UPC-2000. SHOULD REFERENCE
 FBC-2004.
 29. SHT P0-01 PLUMBING GENERAL NOTES
 UNDER PIPING & MATERIALS: UNABLE TO READ
 3RD SECTION, LINE 5, WORDS SUPERIMPOSED
 ON TOP OF EACH OTHER. SECTION 106.1.1.
 30. SHT P2-00 RAIN/STORM TO TRASH ROOM?
 PLEASE CLARIFY. SECTION 106.1.1.
 31 SHT P2-00 SV8 IS NOT CONNECTED TO THE
 BUILDING DRAIN. 106.1.1.
 32. SHT P2-00 CD-21 PIPED TO STORM?
 PLEASE CLARIFY. SECTION 106.1.1.
 33. SHT P2-00 SV2 IS NOT CONNECT TO THE
 BUILDING DRAIN. 106.1.1.
 34. SHT P2-00 CD-1 DESIGNATOR IS
 POINTING TO A SANITARY RISER. PLEASE
 CLARIFY. SECTION 106.1.1.
 35. SHT P2-00 RD-3 CONNECTING TO THE
 SANITARY SYSTEM. THIS IS NOT APPROVED
 PER CITY CODE SECTION 90-125(5).
 36. SHT P2-00 NO KEYED NOTE FOR #5
 FOUND. SECTION 106.1.1.
 37. SHT P2-00 RD-21, SV2, SV3, SV-4, P1.
 P2, P-3, CD-10 AND OTHER RISERS SHOWN ON
 SHT P2-01 BUT NOT SHOWN ON THIS SHEET.
 ALL RISERS START ON THE FIRST FLOOR AND
 ALL RISERS LOCATIONS SHALL BE SHOWN
 WHERE THEY START IN THE SYSTEM.
 38. EACH SANITARY RISER DIAGRAM, BE IT A
 CONVENTIONAL SYSTEM OR A SOVENT SYSTEM
 RISER SHALL HAVE ITS OWN RISER
 DESIGNATION, SUCH AS P-1, P-2. P3 OR
 SV-1, SV-2, SV-3 ETC. SHOWING MULTIPLE
 RISERS WITH THE SAME RISER DESIGNATION
 IS CONFUSING BECAUSE, (FOR EXAMPLE), NOT
 ALL P-1 RISERS ARE THE SAME AS THE
 PIPING IS NOT ALWAYS THE SAME AND THE
 OFFSETS ARE NOT ALL THE SAME FOR EACH
 P-1. SEE FOR EXAMPLE THE WATER RISERS,
 THE CONDENSATE RISERS, OR THE STORM
 RISERS. SECTION 106.1.1.
 39. ALL SHEETS SHOWING PIPING ON FLOOR
 PLANS: SHOW ALL PIPING INCLUDING ARMS TO
 LAVS OR KITCHEN SINKS. SECTION 106.1.1.
 40. ALL SHEETS RESEALED AND RESUBMITTED
 SHALL CONTAIN THE NEW TYPE SEAL REQUIRED
 AFTER DECEMBER 31 2005. SEE ATTACHED
 SHEET FROM THE FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS.
 41. SHT P2-01 RISERS RD-6, RD-9, RD-12
 AND RD-13 HAVE BEEN OFFSET, BUT NO
 OFFSET PIPING IS SHOWN. PLEASE SHOW ALL
 OFFSET PIPING ON PLANS. SECTION 106.1.1.
 42. SHT P2-01 19 RISERS SHOWN ON THIS
 SHEET WERE NOT SHOWN ON SHEET P2-00.
 PLEASE CLARIFY. SECTION 106.1.1.
 43. SHT P2-01 RISER P-1 IS SHOWN AS
 RISER P-3 ON SHT P2-00. PLEASE CORRELATE
 RISERS FROM FLOOR LEVEL TO FLOOR LEVEL.
 SECTION 106.1.1.
 44. SHT P2-02 24 RISERS SHOWN ON THIS
 SHEET WERE NOT SHOWN ON SHT P2-01.
 PLEASE CORRELATE RISERS FROM FLOOR TO
 FLOOR. SECTION 106.1.1.
 45. SHT P2-02 RISER P-4 IS SHOWN AS
 RISER P-3 ON SHT P2-01. PLEASE CORRELATE
 RISERS FROM FLOOR TO FLOOR. SECTION
 106.1.1.
 46. SHT P2-02 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY DRAINS PER
 SECTIONS 1106 & 1107 AND ALL
 SUBSECTIONS. SHOW SQUARE FOOOTAGE BEING
 DRAINED AT EACH PRIMARY DRAIN AND SHOW
 1/2 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS ADDED IN CALCULATIONS AS WELL
 AS ANY AREAS FROM UPPER ROOFS ADDED TO
 THE DECK AREA.
 47. SHT P2-02 MANY AREA DRAINS ARE
 MISLABELED AS PLANTER DRAINS, MANY
 DRAINS ARE NOT LABELED, MANY LABELS SHOW
 NO DRAIN. PLEASE CLARIFY. SECTION
 106.1.1.
 48. SHT P2-02 RISER CV-18 HAS BEEN
 OFFSET FROM SHEET P2-01, BUT NO OFFSET
 PIPING IS SHOWN ON THE FLOOR PLAN.
 PLEASE CORRELATE PIPING FROM FLOOR TO
 FLOOR. SECTION 106.1.1.
 49. SHT P2-03 RISERS P-4 & CD-19 SHOWN
 ON THIS SHEET WERE NOT SHOWN ON SHEET
 P2-02. PLEASE CORRELATE RISERS FROM
 FLOOR TO FLOOR. SECTION 106.1.1.
 50. SHT P2-03 RISER SV-19 SHOWN AS SV-3
 ON SHEET P2-02. CORRELATE RISERS FROM
 FLOOR TO FLOOR. SECTION 106.1.1.
 51. SHT P2-03 RISER P-6 SHOWN AS P-5 ON
 SHT P2-02. CORRELATE RISERS FROM FLOOR
 TO FLOOR. SECTION 106.1.1.
 52. SHT P2-03 RISER SV-1 SHOWN AS SV-7
 ON SHT P2-02. PLEASE CORRELATE RISERS
 FROM FLOOR TO FLOOR. SECTION 106.1.1.
 53. SHT P2-03 RISER CD-19 IS SHOWN AS
 CD-14 ON SHT P2-02. PLEASE CORRELATE
 RISERS FROM FLOOR TO FLOOR. SECTION
 106.1.1.
 54. SHT P2-03 RISER CD-4 SHOW AS CD-13
 ON SHT P2-02. PLEASE CORREATE RISERS
 FROM FLOOR TO FLOOR. SECTION 106.1.1.
 55. SHT P2-03 RISER CD-3 SHOWN AS CD-12
 ON SHT P2-02. PLEASE CORRELATE RISER
 FROM FLOOR TO FLOOR. SECTION 106.1.1.
 56. SHT P2-03 RISER CD-2 SHOWN AS CD-11
 ON SHT P2-02. PLEASE CORRELATE RISERS
 FROM FLOOR TO FLOOR. SECTION 106.1.1.
 57. SHT P2-03 RISER P-5 SHOWN AS P-6 ON
 SHT P2-02. PLEASE CORRELATE RISERS FROM
 FLOOR TO FLOOR. SECTION 106.1.1.
 58. SHT P2-03 RISER CV-13 SHOWN AS RISER
 CV-1 ON SHT P2-02. PLEASE CORRELATE
 RISERS FROM FLOOR TO FLOOR. SECTION
 106.1.1.
 59. SHT P2-03 RISERS P-4, P-5, RD5,
 SV-11, AND SV-15. PLANS INDICATE THESE
 RISERS HAVE BEEN OFFSET. NO PIPING FOR
 OFFSETS HAS BEEN SHOWN ON THE FLOOR
 PLAN. PLEASE SHOW ALL OFFSET PIPING ON
 THE FLOOR PLANS. RISER DIAGRAMS SHALL
 REFLECT ALL OFFSETS. SECTION 106.1.1.
 60. SHT P2-04 RISER P-6 SHOWN AS RISER
 P-5 ON SHT PD2.03. PLEASE CORRELATE
 RISERS FROM FLOOR TO FLOOR. SECTION
 106.1.1.
 61. SHT P2-04 RISERS P-9, (2 OF THEM),
 ARE NOT SHOWN ON SHT P2-03. PLEASE
 CORRELATE RISERS FROM FLOOR TO FLOOR.
 SECTION 106.1.1.
 62. SHT P2-04 RISER P-8 NOT SHOWN ON SHT
 P2-03. PLEASE CORRELATE RISERS FROM
 FLOOR TO FLOOR . SECTION 106.1.1.
 63. SHT P2-04 RISER P-? DOES NOT HAVE A
 RISER DESIGNATION NUMBER. PLEASE CLARIFY
 SECTION 106.1.1.
 64. SHT P2-04 RISERS SV-1, SV-7, SV-13,
 SV-14, & CD-2 HAVE BEEN OFFSET, BUT NO
 OFFSET PIPING IS SHOWN ON THE FLOOR
 PLAN. PLEASE SHOW ALL OFFSET PIPING ON
 THE FLOOR PLAN, AND RISER DIAGRAMS SHALL
 REFLECT THESE OFFSETS. SECTION 106.1.1.
 65. SHT P2-04 RISERS P-7, (TWO OF THEM),
 ARE NOT SHOWN ON SHT P2-03. PLEASE
 CORRELATE RISERS FROM FLOOR TO FLOOR.
 SECTION 106.1.1.
 66. SHT P2-04 RISER AND PIPING NOT SHOWN
 FOR BATHROOM GROUP IN UNIT P1. PLEASE
 SHOW RISER AND INDICATE RISER NUMBER,
 SHOW ALL PIPING. SECTION 106.1.1.
 67. SHT P2-05 RISER SV-1 SHOWN AS SV-3
 ON SHT P2-04. PLEASE CORRELEATE ALL
 RISERS FROM FLOOR TO FLOOR. SECTION
 106.1.1.
 68. SHT P2-05 RISER SV-9 SHOWN AS SV-1
 ON SHT P2-04. PLEASE CORRELATE RISERS
 FROM FLOOR TO FLOOR. SECTION 106.1.1.
 69. SHT P2-05 RISER SV-1 SHOWN AS SV-20
 ON SHT P2-04. PLEASE CORRELATE RISERS
 FROM FLOOR TO FLOOR. SECTION 106.1.1.
 70. SHT P2.05 RISER P-3 SHOWN AS P-4 ON
 SHT P2-04. PLEASE CORRELATE RISERS FROM
 FLOOR TO FLOOR. SECTION 106.1.1.
 71. SHT P2-05 RISER SV-4 IS SHOWN AS
 SV-1 ON SHT P2-04. PLEASE CORRELATE
 RISERS FROM FLOOR TO FLOOR. SECTION
 106.1.1.
 72. SHT P2-05 RISER SV-2 IS SHOWN AS
 SV-7 ON SHT P2-04. PLEASE CORRELATE
 RISERS FROM FLOOR TO FLOOR. SECTION
 106.1.1.
 73. SHT P2-05 NO PIPING OR RISER SHOWN
 FOR BATHROOM FIXTURES IN UNIT P1. PLEASE
 SHOW PIPING AND RISER. INDICATE RISER
 NUMBER. SECTION 106.1.1.
 74. SHT P2-05 SHEET TITLE DOES NOT
 INCLUDE 15TH FLOOR AS INDICATED IN THE
 MIDDLE OF THE SHEET AT THE BOTTOM.
 PLEASE CORRELATE SHEET TITLE WITH
 INFORMATION SHOWN ON SHEET. SECTION
 106.1.1.
 75. SHT P2-06 OVERFLOW SCUPPERS DO NOT
 REFLECT THE OVERFLOW SCUPPERS ON THE
 ARCHITECTURAL ON SHT A1-17. PLEASE
 CORRELATE THE SCUPPER AMOUNT AND
 LOCATIONS FOR THE ARCHITECTURAL AND
 PLUMBING SHEETS. ENGINEER SHALL INDICATE
 REQUIRED NUMBER OF SCUPPERS PER THE
 CALCULATIONS REQUIRED FOR SECONDARY ROOF
 DRAINS OR SCUPPERS ACCORDING TO SECTIONS
 1101.7, 1107.3 AND TABLE 1106.7.
 76. SHT P2-06 THE VENTS THRU THE ROOF DO
 NOT REFLECT THE VENTS SHOWN ON SHT P2-05
 FOR LOCATION. PLEASE CORRELATE VENTS
 FROM FLOOR TO FLOOR. SECTION 106.1.1.
 77. SHT P3-00 PLUMBING KEYED NOTES:
 NUMBER 9 REFERENCES SHT P0-04. THIS
 SHEET HAS NOT BEEN SUMBITTED. PLEASE
 CLARIFY. SECTION 106.1.1.
 78. SHT P3-00 DETAIL #4 REFERENCES UNIT
 B2B. THIS IS NOT SHOWN IN THE SHEET
 TITLE. PLEASE CORRELATE SHEET TITLE WITH
 INFORMATION ON DETAILS. SECTION 106.1.1.
 79. SHT P3-01 PLUMBING KEYED NOTES:
 NUMBER 9 REFERENCES SHT P0-04. THIS
 SHEET HAS NOT BEEN SUBMITTED. PLEASE
 CLARIFY. SECTION 106.1.1.
 80. SHT P3-01 DETAIL #4 PLEASE INDICATE
 THE KEYED NOTES NUMBERS FOR WATER DROPS
 AT THE TUB/SHOWER, LAV/WATER CLOSET
 PIPING. SECTION 106.1.1.
 81. SHT P3-02 PLUMBING KEYED NOTES:
 NUMBER 9 REFERENCES SHT P0-04. THIS
 SHEET HAS NOT BEEN SUBMITTED. PLEASE
 CLARIFY. SECTION 106.1.1.
 82. SHT P3-02 DETAIL #1 NO WATER RISER,
 (#8), IS SHOWN. PLEASE CLARIFY. SECTION
 106.1.1.
 83. SHT P3-02 DETAIL #2 HOT & COLD DROPS
 TO THE SHOWER HAVE BEEN MISLABLED.
 SECTION 106.1.1.
 84. SHT P3-03 PLUMBING KEYED NOTES:
 NUMBER 9 REFERENCES SHT P0-04. THIS
 SHEET HAS NOT BEEN SUBMITTED. PLEASE
 CLARIFY. SECTION 106.1.1.
 85. SHT P3-03 DETAIL #2 BOTH THE DROPS
 TO THE WATER HEATER AND TO THE TUB HAVE
 BEEN MISLABELED. PLEASE CLARIFY. SECTION
 106.1.1.
 86. SHT P4-00 ALL SV RISERS DO NOT
 REFLECT THE FLOOR PLANS FOR THE FIRST
 FLOOR PIPING. SECTION 106.1.1.
 87. SHT P4-00 ALL SV RISERS DO NOT
 REFLECT THE FLOOR PLANS FOR THE 16TH
 FLOORS. NO VENT PIPING SHOWN FOR THE
 REVENTS SHOWN ON THE 16TH FLOOR. SECTION
 106.1.1.
 88. SHT P4-00 SV-4 DOES NOT REFLECT THE
 FLOOR PLANS 2ND THRU 15TH FLOORS. THIS
 RISEER IS NOT SHOWN ON THE FIRST FLOOR.
 PLEASE CLARIFY. SECTION 106.1.1.
 89. SHT P4-00 16TH FLOOR SHALL BE
 DIFFERENT FROM OTHE FLOOR ON ALL RISERS
 AS THE VENTING/REVENTING IS ONLY ON THIS
 FLOOR. SHOW ALL VENTING/REVENTING ON
 RISERS. (THIS IS REQUIRED FOR ALL VENTS
 INCLUDING SOVENT SYSTEM IF VENTS FROM
 OTHER STACKS ARE TYING INTO THEM.
 SECTION 106.1.1.
 90. SHT P4-00 SV-5 DOES NOT REFLECT THE
 FLOOR PLANS FROM THE 2ND FLOOR THRU THE
 15TH FLOOR. OFFSET ON THE 11TH FLOOR IS
 NOT SHOWN ON THE 11TH FLOOR FLOOR PLAN.
 SECTION 106.1.1.
 91. SHT P4-00 SV-6 DOES NOT REFLECT THE
 FLOOR PLAN ON THE 11TH FLOOR. SECTION
 106.1.1.
 92. SHT P4-00 SV-7 DOES NOT REFLECT THE
 FLOOR PLAN ON THE 2ND FLOOR THRU THE
 11TH FLOOR. SECTION 106.1.1.
 93. SHT P4-00 SUBMIT A RISER DIAGRAM FOR
 EACH SANTITARY RISER DIAGRAM AND EACH
 SOVENT RISER DIAGRAM. COMMON RISERS WITH
 DIFFERENT FLOOR PLANS ARE NOT
 ACCEPTABLE. IF THE TUB AND LAV ARE ON
 THE OPPOSITE SIDE OF THE WATER CLOSET
 FROM ONE FLOOR PLAN TO THE OTHER, OR
 OFFSETS ARE DIFFERENT, OR ON DIFFERENT
 FLOOR PLANS, THEN SEPARATE RISER
 DIAGRAMS ARE REQUIRED. RISER DIAGRAMS
 SHALL REFLECT THE FLOOR PLAN FROM THEIR
 CONNECTION TO THE BUILDING DRAIN UP THRU
 THE ROOF FOR VENTING. BECAUSE THIS IS AN
 ENGINEERED SYSTEM, SEPARATE RISERS ARE
 REQUIRED, AND SEPARATE RISER
 DESIGNATIONS ARE REQUIRED. SOME RISERS
 CHANGE RISER NUMBERS FROM FLOOR TO FLOOR
 PLEASE CLARIFY. FLOOR PLANS SHOW REVENTS
 FROM OTHER RISERS TYING TOGETHER PRIOR
 TO VENTING THRU THE ROOF. THIS IS NOT
 REFLECTED ON ANY OF THE RISER DIAGRAMS.
 94. SUBMIT AN APPROVED DESIGN MANUAL FOR
 THE SOVENT SYSTEM. SUBMIT MANUFACTURE
 SPECIFICATIONS FOR AERATORS AND
 DEAERATORS FOR PRODUCT APPROVAL PER
 SECTIONS 303.1 & 303.4.
 95. PLANS APPEAR TO BE INCOMPLETE AT
 THIS TIME, AS ALL THE SV RISERS ARE NOT
 SUBMITTED AS WELL AS THE BLDG DRAIN FOR
 OTHER SYSTEMS. OTHER COMMENTS MAY OR MAY
 NOT FOLLOW UPON SUBMITTAL OF REQUIRED
 INFORMATION AND INFORMATION NOT
 SUBMITTED AT THIS TIME. SECTIONS 106.1.1
 AND 106.3.5.1.3.
 96. SHT P4-01 ALL STACKS, RELIEF VENTS
 ARE REQUIRED PER SECTION 914.1 AND SHALL
 BE PROVIDED AT EACH 10TH INTERVAL
 BEGINNING WITH THE TOP FLOOR. SECTION
 914.1.
 97. SHT P4-01 ALL STACKS, EVERY VENT
 STACK SHALL CONNECT TO THE BASE OF THE
 DRAINAGE STACK. PLEASE SHOW VENT STACK
 CONNECTION TO STACK. SECTION 903.4.
 98. SHT P4-01 ALL STACKS, NO 11TH FLOOR
 FIXTURES SHOWN ON THE RISER DIAGRAMS.
 CLARIFY. SECTION 106.1.1
 99. SHT P4-01 ALL STACKS, DRAINAGE STACK
 CAN NOT TERMINATE ABOVE THE 10TH FLOOR
 AND THEN START UP AGAIN BELOW THE 12TH
 FLOOR AS SHOWN ON THE RISER DIAGRAM.
 SECTION 106.1.1.
 100. SHT P4-02 RISERS W1, W2, W6, W8, &
 W10 FULL OPEN VALVES SHALL BE INSTALLED
 ON THE BASE OF EVERY WATER RISER PIPE.
 SECTION 606.1(3).
 101. SHT P4-04 SUBMIT THE BUILDING STORM
 DRAIN IN AN ISOMETRIC RISER DIAGRAM THAT
 REFLECTS THE PIPING SHOWN ON THE
 UNDERGROUND PLUMBING PLAN SHT P2-00.
 SECTION 106.3.5.1.3. SHOW ALL PIPE SIZES
 AND SQUARE FOOTAGE AS IT ACCUMULATES IN
 THE SYSTEM. IDENTIFY ALL RISERS AS THEY
 CONNECT TO THE BUILDING DRAIN IN THE
 ISOMETRIC DIAGRAM OF THE BUILDING DRAIN.
 SHOW ALL OFFSETS IN THE STORM RISERS,
 AND INDICATE ALL PIPE SIZES.
 102. SHTS P4-05 & P4-06 INDICATE
 MATERIAL FOR CONDENSATE SYSTEM. NO
 FLAMABLE MATERIAL IN THE AIR CONDITION
 ROOM IF IT IS USED AS A PLENUM. INDICATE
 METHOD OF VENTING THE CONDENSATE RISERS.
 VENTS CAN NOT TERMINATE IN THE WALLS OR
 IN A PLENUM.
 103. SHTS P4-05 & P4-06 SUBMIT A
 BUILDING DRAIN CONDENSATE ISOMETRIC
 RISER DIAGRAM THAT REFLECTS THE
 UNDERGROUND PIPING ON SHT P2-00. SECTION
 106.3.5.1.3.
 104. SHT P5-00 DETAIL 05 WASHER BOX
 CONNECTION WATER HAMMER ARRESTORS ARE
 REQUIRED AT THE WASHER BOX PER 604.9.
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURES IN AN "EFFECTIVE
 RANGE" NOT IN THE CEILING. PKI-WH 201
 AND MANUF. INSTALLATION INSTRUCTIONS.
 105. SHT P5-00 DETAIL 04 WATER HEATER
 CONNECTION DETAIL: A FULL OPEN VALVE IS
 REQUIRED ON THE SUPPLY PIPE TO EVERY
 WATER HEATER. SECTION 606.1(7).
 106. SHT P5-00 DETAIL 04 WATER HEATER:
 SUBMIT P&T RELIEF VALVE DISCHARGE PIPING
 RISER DIAGRAM SHOWING ALL PIPE SIZES,
 AND TERMINATION POINT. SECTION
 106.3.5.1.3. THE RELIEF VALVE DISCHARGE
 SHALL NOT HAVE ANY TRAPPED SECTIONS AND
 SHALL HAVEA VISIBLE AIR GAP OR AIR GAP
 FITTING LOCATED IN THE SAME ROOM AS THE
 WATER HEATER. INDICATE MATERIAL FOR P/T
 DISCHARGE PIPING.
 107. SHT P5-00 DETAIL 04 WATER HEATER
 SUBMIT EMERGENCY PAN DRAIN ISOMETRIC
 RISER DIAGRAM SHOWING ALL PIPE SIZES,
 MATERIAL, AND TERMINATION POINT. SECTION
 106.3.5.1.3.
 108. SHT P5-00 DETAIL 04 WATER HEATER:
 THERMAL EXPANSION CONTROL IS REQUIRED
 PER SECTION 607.13.2. PLEASE INDICATE
 METHOD FOR COMPLIANCE.
 109. SHT P5-00 DETAIL 07 DOMESTIC WATER
 BOOSTER PUMP DETAIL: SUBMIT MANUF.
 SPECIFICATION SHEETS FOR PUMP. PUMP
 SHALL BE LISTED. SECTION 303.4.
 110. SHT P6-00 SHOWS TWO RISER NUMBER 1
 AND TWO RISER NUMBER 11, AND NO RISERS
 NUMBER 9 & 12. PLEASE CLARIFY. SECTION
 106.1.1.
 111. SHT P6-01 NO RISER NUMBER 2. PLEASE
 CLARIFY. SECTION 106.1.1.
 112. SHT P6-03 RISER NUMBER 20
 MISLABELED AS RISER 19. PLEASE CORRELATE
 RISERS. SECTION 106.1.1.
 113. ALL SETS OF PLANS AND ALL SHEETS IN
 EACH SET OF PLANS: IF THE DESIGN
 PROFESSIONAL IS AN ENGINEER, THEN HE OR
 SHE SHALL AFFIX HIS OR HER OFFICIAL
 SEAL, SIGNATURE AND DATE TO SAID
 DRAWINGS AS REQUIRED BY FLORIDA
 STATUTES. NO INITIALS. LEAGAL
 SIGNATURE REQUIRED.
 114. SUBMIT WATER ISOMETRIC RISER
 DIAGRAMS FOR EACH UNIT SHOWING ALL PIPE
 SIZES, VALVES, AND WATER HAMMER
 ARRESTORS REQUIRED BY SECTION 604.9.
 SECTION 106.3.5.1.3.
 115. THE FOLLOWING INFORMATION IS
 REQUIRED FOR THE GAS APPLICATION:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGHTS PER FBC-2004
 FUEL GAS.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 F. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. IF
 2 PSI INDICATE LOCATION OF REGULATORS
 AND SUBMIT MANUF. SPECIFICATION SHEETS
 FOR REGULATORS INDICATING MODEL. IF
 VENTED REGULATORS, INDICATE MATERIAL FOR
 VENTS AND SHOW ROUTING OF PIPING.
 H. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
 I. SUBMIT MANUFACTURE SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 J. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 K. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE RESUBMIT RED LINED SET OF
 PLUMBING PLANS FROM FIRST REVIEW TO HELP
 TO EXPEDITE THE SECOND REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2006-09-05 Cont ID  
Sent By aaponte Date 2006-09-05 Time 09:57 Rev Time 0.00
Received By aaponte Date 2006-09-05 Time 09:57 Sent To  
Notes
2006-09-05 00:00:00NORTH ELEVATION DOES NOT REFLECT DOORS
 FOR SCOTER STORAGE ROOM. PLEASE UPDATE
 DRAWINGS.
 FIRST FLOOR UNITS SHALL BE RAISED 18
 INCHES ABOVE THE SIDEWALK LEVEL. PLEASE
 PROVIDE INFORMATION TO CONFIRM
 COMPLIANCE WITH REGULATION.
 TRAVEL LANES WITH PARKING STALLS SHALL
 BE MINIMUM 24 FEET WIDE. THE TRAVEL LANE
 ON THE NORTH SIDE OF GARAGE IS LESS THAN
 24 FEET.
 ON APPROVED PHASE I, STAIR FOR
 MECHANICAL SPACE ALONG AUSTRALIAN AVENUE
 IS SHOWN ENCROACHING THE SPECIAL
 LANDSCAPE TREATMENT AREA. PLEASE ADJUST
 OR PROCEED FOR DAC VARIANCE.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-04-19 Cont ID  
Sent By aaponte Date 2006-04-19 Time 14:30 Rev Time 0.00
Received By aaponte Date 2006-04-19 Time 09:18 Sent To  
Notes
2006-04-19 00:00:001. PLEASE PROVIDE A FULL SITE PLAN,
 INCLUDING PHASE I, WHICH INDICATES
 SIDEWALKS DIMENSIONS, LOCATION OF TREES,
 AND SITE LEVELS.
 2. SIDEWALKS SHALL BE MINIMUM 8 FEET IN
 WIDTH.
 3. 1ST FLOOR RESIDENTIAL USES SHALL BE
 RAISED 18 INCHES FROM THE SIDEWALK
 LEVEL.
 4. MAIN ENTRANCE ACCESS SHALL PROVIDE
 FOR 8 FEET SIDEWALK IN FRONT OF DOOR AND
 CONNECTED WITH SIDEWALK FROM STREET.
 5. PLEASE PROVIDE A TABLE INDICATING THE
 PARKING SPACES PROVIDED FOR THE WHOLE
 PROJECT.
 6. PLEASE PROVIDE FLOOR PLANS FOR ALL
 LEVELS WHICH INCLUDE PARKING. THESE
 FLOOR PLANS SHALL INCLUDE THE PHASE I,
 ALREADY APPROVED.