Plan Review Details - Permit 05110231
Plan Review Stops For Permit 05110231
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-01-13 Cont ID  
Sent By jleech Date 2006-01-13 Time 08:06 Rev Time 0.50
Received By jleech Date 2006-01-13 Time 08:06 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2005-12-09 Cont ID  
Sent By jleech Date 2005-12-09 Time 09:06 Rev Time 0.50
Received By jleech Date 2005-12-09 Time 09:06 Sent To B
Notes
2005-12-09 00:00:00DENIED;
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED
 3. TYPE OF GAS, (LP OR NATURAL)
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 6. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 7. GENORATOR SPECS CALL FOR 570 CU. FT.
 OF GAS NOT 450,000 BTU'S AS SHOWN ON
 PLAN.
 8.PLEASE USE THE GAS SIZING CHARTS FROM
 THE FBC-2004 FUEL GAS TABLE 402.4.().
 GAS PLAN REVIEW BY;
 JOHN LEECH
 805-6695
 .

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-11-21 Cont ID  
Sent By adarroug Date 2005-11-21 Time 11:32 Rev Time 0.00
Received By adarroug Date 2005-11-21 Time 11:32 Sent To E
Notes
2005-11-21 00:00:00TO "GEN-RES" "E"/W PERMIT#05110230

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-11-14 Cont ID  
Sent By adarroug Date 2005-11-14 Time 18:48 Rev Time 0.00
Received By adarroug Date 2005-11-14 Time 18:48 Sent To Z
Notes
2005-11-14 00:00:00TO "Z" BOX W/PERMIT#05110230

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-12-07 Cont ID  
Sent By tgordon Date 2005-12-07 Time 11:56 Rev Time 0.05
Received By tgordon Date 2005-12-07 Time 11:55 Sent To G
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved