Plan Review Details - Permit 05110231
| Plan Review Stops For Permit 05110231 |
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2006-01-13 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-01-13 |
Time |
08:06 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2006-01-13 |
Time |
08:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2005-12-09 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2005-12-09 |
Time |
09:06 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2005-12-09 |
Time |
09:06 |
Sent To |
B |
|
| Notes |
| 2005-12-09 00:00:00 | DENIED; | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. | | | 2. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE BEING USED | | | 3. TYPE OF GAS, (LP OR NATURAL) | | | 4. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | | THRU 402.5.2 AND TABLES 402(1) THRU | | | 402(34). | | | 5. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES (A)(3). | | | 6. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | 7. GENORATOR SPECS CALL FOR 570 CU. FT. | | | OF GAS NOT 450,000 BTU'S AS SHOWN ON | | | PLAN. | | | 8.PLEASE USE THE GAS SIZING CHARTS FROM | | | THE FBC-2004 FUEL GAS TABLE 402.4.(). | | | GAS PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 | | | . |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-11-21 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-11-21 |
Time |
11:32 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-11-21 |
Time |
11:32 |
Sent To |
E |
|
| Notes |
| 2005-11-21 00:00:00 | TO "GEN-RES" "E"/W PERMIT#05110230 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-11-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-11-14 |
Time |
18:48 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-11-14 |
Time |
18:48 |
Sent To |
Z |
|
| Notes |
| 2005-11-14 00:00:00 | TO "Z" BOX W/PERMIT#05110230 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2005-12-07 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2005-12-07 |
Time |
11:56 |
Rev Time |
0.05 |
| Received By |
tgordon |
Date |
2005-12-07 |
Time |
11:55 |
Sent To |
G |
|
| Notes |
|
|
|
Account Summary | Usage Policy | Privacy Policy