Plan Review Details - Permit 05110210
Plan Review Stops For Permit 05110210
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-11-18 Cont ID  
Sent By btrobaug Date 2005-11-18 Time 16:48 Rev Time 0.50
Received By btrobaug Date 2005-11-18 Time 16:48 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-11-17 Cont ID  
Sent By btrobaug Date 2005-11-17 Time 17:25 Rev Time 0.33
Received By btrobaug Date 2005-11-17 Time 16:52 Sent To PC
Notes
2005-11-17 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE INDICATE CONDUIT AND CONDUCTOR
 SIZE AND TYPE PER 310.15&16.
  
 2} GIVE THE AIC RATING FOR THE EQUIPMENT
 BEING INSTALLED PER 110.9&10.
  
 3} SIZE THE GROUNDING ELECTRODE
 CONDUCTOR PER 250.66, SHOW SAME ON THE
 PLAN.
  
 4} SUBMIT A FLOOR PLAN WITH LOCATION OF
 THE DEVICES AFFECTED BY THIS PERMIT,
 INDICATE THE ONES BEING ADDED AND THE
 ONES THAT ARE BEING REPLACED(IF ANY).
  
 5} THE CONTRACTOR MUST SIGN THE
 APPLICATION, AND PRINT NAME, SEE THE
 BACK OF THE FORM. IF THE CONTRACTOR
 CANNOT BE HERE PERSONNALLY, HE MAY HAVE
 THE SIGNATURE ON THE DOCUMENT NOTORIZED.
  
 IF THERE ARE ANY QUESTION SPLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-11-15 Cont ID  
Sent By adarroug Date 2005-11-15 Time 11:17 Rev Time 0.00
Received By adarroug Date 2005-11-15 Time 11:17 Sent To E
Notes
2005-11-15 00:00:00TO "E" BOX